BASENGREEN BR-WM-LV 5KWH Wall Mounted Battery Operation Manual
Preface
This manual will provide detailed product information and installation
instructions for users of the wall-mounted series products of SHENZHEN
BASENGREEN TECHNOLOGY CO.LTD (hereinafter referred to as BASENGREEN). Please
read this manual carefully, and put this manual in a place where you can
install, operate, and obtain it conveniently.
The safety precautions mentioned in the manual do not represent all the safety
matters that should be observed, but are only supplementary to the safety
precautions. When installing, operating, and maintaining equipment, local
safety regulations and norms should be followed. Only trained professionals
can install, operate and maintain equipment. Our company does not assume any
responsibility for losses caused by violation of general safety operation
requirements or violation of safety standards for the design, production, and
use of equipment. Installation and maintenance personnel must have high-
voltage and AC power operation skills. When installing, operating, and
maintaining equipment, they must not wear any conductive objects, such as
watches, bracelets, bracelets, and rings, and prevent moisture from entering
the equipment.
Safety Instructions
High Voltage Danger
The high-voltage power supply provides power for the operation of the equipment. Direct contact or indirect contact with high-voltage power supply through wet objects will cause fatal danger.
Use Professional Tools
Always use professional tools instead of personal tools when working with high
voltage and AC power
Anti-static
The static electricity generated by the human body will damage the electrostatic sensitive components on the board. Before touching the plug-in, circuit board or chip, make sure to take proper anti-static measures.
Operate Attention
The power must be cut off first before operation, do not hot-line work.
DC short circuit Danger
The power system provides a DC-regulated power supply, and a DC short circuit will damage the equipment and cause personal injury.
Label Explanation
The label contains the following information
Product Description
This product is a lithium iron phosphate battery (LFP LiFePO4) composed of 16 cells in series. Which is suitable for home energy storage systems. It can be customized according to customer needs to meet diverse application scenarios and provide stable power for various equipment of users.
Product Advantages
a. Built-in Battery Management System (BMS): Overcharge, over discharge,
overcurrent, temperature control, short circuit and other protection
functions.
b. Passive Balance Function: There is a voltage equalization function
during the charging.
c. High Cost Performance: High safety performance, long service life, stable
and reliable quality.
d. Expandable: Equipped with RS232/ RS485/ CAN bus ports, support up to
15 units in parallel.
e. Wide Working Temperature: -20℃ to 60℃, excellent high-temperature
discharge performance.
f. Convenient: Modular design, small size and lightweight, easy to
install and maintain.
Product Technical Parameters
Specification
Item | Specifications |
---|---|
Model | BR-WM-LV 5KWH |
Nominal Voltage | 51.2V |
Operating Voltage | 43.2V-57.6V |
Nominal Capacity | 100Ah |
Total Energy | 5120Wh |
Configuration | 2P16S |
Charging Cut-off Voltage | 58.4V |
Discharge Cut-off Voltage | 43.2V |
Operation Temperature | -20℃~60℃ |
Standard Charging Current (A) | 20A |
Max Continuous Charging Current (A) | 100A |
Max Continuous Discharge Current (A) | 100A |
Dimension(mm) | 615532187mm |
Net weight (KG) | 57KG |
Interface Overview
Position | Item | Description |
---|---|---|
1 | P+ | The positive terminal of the battery, can be connected to the positive |
pole of the inverter through a cable for DC output
2| P-| The negative terminal of the battery, can be connected to the negative
pole of the inverter through a cable for DC output
3| SOC| 4 indicators, indicating the remaining power status
4| Alarm| Indicating the abnormal state of the battery, if there is a low
voltage or over voltage, the alarm will sound
5| RUN| Indicating the normal operation status of the battery
6| ADD| Setting up battery parallel communication and inverter communication
7| RS485/CAN| RS485/CAN port for the inverter or the upper system
communication
8| RS485 B/C| RS485 port for parallel communication
9| RST| Manual-return switch button
10| Power switch| The switch for turn on/turn off the battery pack
11| LCD Screen| Display battery voltage, SOC, temperature, etc
Battery Management System (BMS)
Overcharge Protection
When the voltage of any single cell or whole battery pack is higher than the set value during the charging, and the duration reaches the limited time, the system enters the over charging protection state automatically, the charging MOS is turned off at the same time, and the battery cannot be charged. After the voltage of each cell and the whole battery pack drops below the cell overcharging recovery value, the over charging protection state is released. It can also be released by discharging to return to normal state.
Over discharge Protection
When the voltage of any single cell or whole battery pack is lower than the set value during discharging, and the duration reaches the limited time, the system enters the over discharge protection state, the discharge MOS is turned off, and the battery cannot be discharged. After the over discharge protection of the battery pack occurs, it can be released by charging the battery pack.
Over Temperature Protection
When the NTC detects the temperature of the battery cell surface is higher than the setting value of over temperature protection during charging and discharging, the management system enters the over temperature protection state, the charging or discharging MOS is turned off, and the battery pack cannot be charged or discharged in this state.
Low Temperature Protection
When the NTC detects that the temperature of the cell surface is lower than the setting value of low temperature protection during charging and discharging, the management system enters the low temperature protection state, the charging or discharging MOS is turned off, and the battery pack cannot be charged or discharged in this state.
Installation and configuration
Packing
a. After receiving the battery, open the box to check the battery surface
if get any broken, crack,s or other bad phenomena; if get that, please do not
install, and need to contact the supplier, and wait for the supplier’s reply
before proceeding to the next step.
b. Please ensure that the following items are included in the packaging:
-
Battery*1
-
Mounting Bracket*1
-
Expansion bolts*8
-
M812mm combination screws2
-
Inverter communication cable*1
-
Parallel communication cable*1
-
Upper system communication cable*1
Recommended Tools
Before installing the battery pack, the user needs to have the tools as following list:
Picture | Item | Description |
---|---|---|
Level | Make sure the bracket is properly installed | |
Hammer Drill | Drill holes on the wall | |
Impact Wrench Set | Locking expansion bolts | |
Electric Screwdriver | Wiring | |
Hammer | Hanging the bracket | |
Crimping Tool | Crimping tool for RJ45 terminal | |
Crimping Plier | Crimping tool for insulated electric connectors |
Notice for Installation
a. The wall for installation should be a solid brick or cement wall with
a strong load-bearing capacity, and the thickness of the wall should not be
less than 100mm.
b. In indoor installation, it needs to leave enough space to be installed
and operated easily and pay attention to ventilation. Do not place flammable
materials around the battery.
c. In outdoor installation, it needs to be surrounded by protective
measures, and make a rain protection.
Installation Procedure
a. Mark the drilling position using the wall mounting plate, and level
using a spirit level.
b. Place the wall mounting plate close to the wall firmly, mark the
drilling position, and remove the wall mounting plate.
c. Drill holes in the wall using the driller. The hole diameter is 12mm
and the depth is 60mm.
d. Fix the M8 Expansion bolts, tightening torque: 20N.m
e. Lift the battery parallel to the ground, and hang the battery module
on the bracket as shown in the following figure:
Connection
Precautions Before Connecting The Inverter
a. Use a multi-meter to measure whether connection of the positive and
negative cables are conducting, and check whether that connections are loose.
b. The battery should be switched off before wiring to ensure that there
is no DC output from the battery.
c. Connect positive terminals of the battery and the inverter with red
power cable, and then connect negative terminals of both sides with black
power cable.
d. Connect both communication ports of the battery(RS485A/CAN) and the
inverter(BMS port) with the communication cable, BMS ports of inverter have
different definitions for some brands, please check the inverter manual.
Communication cable connection Pin definition is as follows:
PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|---|
Define | RS485-B | RS485-A | GND | CAN-H | CAN-L | GND | NC | NC |
Precautions Before Connecting The Inverter with The Battery Pack in Parallel
a. Use a multi-meter to measure whether connection of the positive and
negative cables are conducting, and check whether that connections are loose.
b. The battery should be switched off before wiring to ensure that there is no
DC output from the battery.
c. Lock the parallel cable wires to the positive terminal of the battery
pack first, then connect another end to the negative terminal.
d. Parallel communication cable to the RS485 port of the battery pack.
e. Connect positive terminals of the battery and the inverter with red
power cable, and then connect negative terminals of both sides with black
power cable. f. Connect both communication ports of the battery(RS485A/CAN)
and the inverter(BMS port) with the communication cable, BMS ports of inverter
have different definitions for some brands, please check the inverter manual.
Parallel communication cable connection Pin definition is as follows:
PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|---|
Define | RS485-B | RS485-A | GND | NC | NC | GND | RS485-B | RS485-A |
Battery & Inverter Connection
Connect the positive and negative cables of the battery to the positive and negative terminals of the DC input of the inverter, insert the RJ45 crystal plug at one end of the distributed inverter communication cable to the RS485 of the battery, and connect the other end to the BMS terminal of the inverter according to the defined line voltage, and then connect the battery to the inverter.
Dip Code Switch Definition and Setting
ADD switch is a 8-bit DIP switch to manually distribute the communication
address of parallel batteries.
The BMS will only recognize the DIP address once it is reset, so please reset
the BMS when the DIP address is changed (the BMS must be reset in the standby
state). When the DIP address is 0, the battery is configured as the stand-
alone working mode; when the DIP address is 1, the BMS is configured as the
master working mode; when the DIP address is 2 to 6, the BMS is configured as
the slave working mode.
Please refer to the table below to set the DIP switch for parallel connection
of different batteries.
4-bit
Battery pack| Master| Slave 2| Slave 3| Slave 4|
Slave 5| Slave 6
1| | | | | |
2| | | | | |
3| | | | | |
4| | | | | |
5| | | | | |
6| | | | | |
8-bit
Battery pack| Master1| Slave 2| Slave 3| Slave 4|
Slave 5| Slave 6
1| | | | | |
2| | | | | |
3| | | | | |
4| | | | | |
5| | | | | |
6| | | | | |
Operation
Check Before Power on
a. Check all positive, negative cables and communication lines are
connected correctly and safely.
b. Check the battery is firmly installed, easy to operate and maintain,
and check ventilation.
c. Insulate the unused ports.
Power on
a. Turn on the switch on the battery.
b. The green running LED is normal on(Check the status of the LED
indicators)
c. If it is failed to switch on the battery system, check if all the
electrical connection is correct.
d. If the electrical connection is correct, but the battery system is
still unable to switch on, contact our after-sale service within 48 hours
LED Indicator Status
Status | Charging | Discharge |
---|---|---|
Capacity Indicator | L1 | L2 |
Battery Level | 0~25% | Flash |
25~50% | Light | Flash |
50~75% | Light | Light |
≥75% | Light | Light |
Normal Status Indicator | Light | Flash |
Flashing Definition
Item | Light | OFF |
---|---|---|
Flash 1 | 0.25 s | 3.75 s |
Flash 2 | 0.5 s | 0.5 s |
Flash 3 | 0.5 s | 1.5 s |
LED Flashing Faulty
Status| Normal/warning/ protection| RUN| ALM| Battery
capacity LED| Specification
---|---|---|---|---|---
| | | | | |
Power off| Sleep| OFF| OFF| ALL OFF|
Stand by| Normal| Light| OFF| ALL OFF|
Charging| Normal| Light| OFF| Display according to the actual SOC|
Over Current Alarm| Light| Flash 2|
Over Voltage Protection| Flash 1| OFF| ALL OFF|
Over temperature /Over Current Protection| Flash 1| Flash 1| ALL OFF|
Discharge| Normal| Flash 3| OFF| Display according to the actual SOC|
Alarm| Flash 3| Flash 3|
Temperature/ Over Current /Short circuit Protection| OFF| Light| ALL OFF| Cut-
off Discharge
Low Voltage Protection| OFF| OFF| ALL OFF| Cut-off Discharge
Operation of Upper System
BASEN 48V battery pack supports to connect with our upper system to monitor the status of the battery and modify the communication protocol, please contact our sales representative or visit our website to get the latest upper system software.
Log in
a. The upper system communication cable connects to the RS485 port on the
battery and then to the USB port on the PC/Laptop
b. Download and open the upper system software
c. Modify the language
d. Updated the status of battery automatically
Notice: If it is failed to connect to the upper system, check if all the connection is correct. If the connection is correct, but the upper system is still unable to work, please contact our after-sale service
Operation of The Communication Protocol Switch
Connect to the upper system and follow the path:
INFO—Parallel Group Display—CAN Type/RS485 Type—Read—Choose the protocol—Set
Communication Compatible List
Storage
a. External terminals of the battery pack are insulated and protected.
b. If the battery pack is stored for a long period of time without use,
it is recommended that it be charged 30%-60%, and it is prohibited to store it
completely uncharged.
c. Batteries that have been in storage for more than 3 months should be
recharged for 2-3 hours at 0.2C~0.3C.
d. Batteries should be stored in a dry, clean, ventilated, non-corrosive
gas environment, away from sources of ignition, to avoid exposure to the sun.
e. Do not store or put in high temperatures over 60°C for a long period
of time, otherwise, it will cause function deterioration and life span
reduction.
Warning
To prevent possible battery leakage, heat generation, and explosion, please observe the following warning:
a. It is strictly forbidden to immerse the battery in seawater or water.
When not in use, it should be placed in a cool and dry environment;
b. It is strictly forbidden to reverse the positive and negative poles to
use the battery;
c. It is forbidden to use metal to directly connect the positive and
negative electrodes of the battery to a short circuit;
d. It is forbidden to transport or store batteries together with metals,
such as hairpins, necklaces, etc;
e. It is forbidden to knock or throw, step on the battery, etc.;
f. It is forbidden to directly weld the battery and pierce the battery
with nails or other sharp objects.
Attention!
a. It is forbidden to use or place the battery under high temperatures
(in the hot sun or in a very hot car), otherwise, it may cause the battery to
overheat, catch fire or fail to function, and shorten its life; the
recommended temperature for long-term battery storage is 10-45°C;
b. It is forbidden to throw batteries into fires or heaters to prevent
fire, explosion, and environmental pollution. Scrapped batteries should be
returned to the supplier or battery recycling point for disposal;
c. Do not use it in places with strong static electricity and strong
magnetic fields, otherwise it will easily damage the battery safety protection
device and bring unsafe hidden dangers;
d. If the battery leaks and the electrolyte enters the eyes, do not rub
it. Immediately rinse the eyes with clean water and send them to the hospital
for treatment, otherwise, the eyes will be hurt. If the battery emits and
odor, heats up, discolors, deforms, or has any abnormality during use,
storage, or charging, immediately remove the battery from the device or
charger and stop using it;
e. It is forbidden to insert the positive and negative poles of the
battery directly into the power socket, and a special charger for lithium-ion
batteries must be used;
f. Check the battery voltage and connectors before installation, and use
it only after everything is normal;
g. The battery is stored in half power. If the battery has not been used
for three months, it needs to be recharged once;
h. If the electrode is dirty, it should be wiped with a dry cloth before
use. Otherwise, it may cause poor contact and function failure;