RICH SOLAR RS-H2424 Hybrid Off-Grid Inverter User Manual

August 8, 2024
RICH SOLAR

User Manual
2400WATT
HYBRID OFF-GRID INVERTER
RICH SOLAR RS H2424 Hybrid Off Grid Inverter
- MODEL :RS-H2424

ABOUT THIS MANUAL

Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.

SAFETY INSTRUCTIONS

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.

  2. CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
    Other types of batteries may burst, causing personal injury and damage.

  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
    Incorrect re-assembly may result in a risk of electric shock or fire.

  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
    Turning off the unit will not reduce this risk.

  5.  CAUTION – Only qualified personnel can install this device with battery.

  6. NEVER charge a frozen battery.

  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.

  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.

  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Pleaserefer to INSTALLATION section of this manual for the details.

  10. Fuses (3 pieces of 40A, 32VDC for 1KW, 4 pieces of 40A, 32VDC for 2KW and 1 piece of 200A, 58VDC for 2.4KW, 3KW, 4KW and 5KW) are provided as over-current protection for the battery supply.

  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.

  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.

  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

INTRODUCTION

This hybrid PV inverter can provide power to connected loads by utilizing PV power, utility power and battery power.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Overview

Depending on different power situations, this hybrid inverter is designed to generate continuous power from PV solar modules (solar panels), battery, and the utility. When MPP input voltage of PV modules is within acceptable range (see specification for the details), this inverter is able to generate power to feed the grid (utility) and charge battery. Galvanic isolation designed between PV/DC and AC output, so that user could connect any type of PV array to this Hybrid inverter. See Figure 1 for a simple diagram of a typical solar system with this hybrid inverter.

Product Overview

RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Product
Overview

NOTE: For parallel model installation and operation, please check separate parallel installation guide for the details.

1. LCD display
2. Status indicator
3. Charging indicator
4. Fault indicator
5. Function buttons
6. Power on/off switch
7. Grid connectors
8. AC output connectors (Load connection)| 9. PV connectors
10. Battery connectors
11. Circuit breaker
12. Parallel communication cable
13. Current sharing cable
14. Dry contact
15. RS-232 communication port
16. USB communication port
---|---

INSTALLATION

Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  • The unit x 1, User manual x 1, Communication cable x 1, Software CD x 1

Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.

Mounting the Unit
Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter - model

Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to useappropriate cable for battery connection. To reduce risk of injury, please use theproper recommended cable and terminal size as below.

Recommended battery cable and terminal size:

Model| Typical Amperage| Battery Capacity| Wire Size| Ring Terminal| Torque Value
---|---|---|---|---|---
Cable mm 2| Dimensions
D (mm)| L (mm)
1KW, 2KW, 2.4KW, 3KW, 4KW| 140A| 200AH| 1*2AWG| 38| 6.4| 39.2| *** 2~3 Nm
2
6AWG| 28| 6.4| 33.2
5KW| 180A| 600AH| 2*4AWG| 44| 10.5| 55| 10~12 Nm

Please follow below steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Ring
terminal1

WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires

Model Gauge Torque Value
1KW 16 AWG 0.5 ~ 0.6 Nm
2KW 14 AWG 0.8 ~ 1.0 Nm
2.4KW 10 AWG 1.4 ~ 1.6 Nm
3KW 12 AWG 1.2 ~ 1.6 Nm
4KW 10 AWG 1.4 ~ 1.6 Nm
5KW 10 AWG 1.4 ~ 1.6 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.

  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.

  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor ( ) first.
    →Ground (yellow-green)
    L →LINE (brown or black)
    N →Neutral (blue)
    WARNING:
    Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
    Be sure to connect PE protective conductor ( ) first.
    →Ground (yellow-green)
    L →LINE (brown or black)
    N →Neutral (blue)
    RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Ring
terminal2

  5. Make sure the wires are securely connected.

CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Model Typical Amperage Cable Size Torque
1KW, 2KW, 2.4KW, 3KW, 4KW 80A 6AWG 2.0~2.4Nm
5KW PV 1 60A 8AWG
PV 2 60A 8AWG 2.0~2.4Nm

PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.

Solar Charging Mode

INVERTER MODEL| 1KW| 2KW| 2.4KW| 3KW| 4KW| 5KW
Max. PV Array Open Circuit Voltage| 145Vdc
PV Array MPPT Voltage Range| 15~115Vdc| 30~115Vdc| 60~115Vdc
MPP Number| 1| 1| 1| 1| 1| 2

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input  connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector.
    Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Ring
termina3

Recommended PV module Configuration

PV Module Spec.
(reference)
– 250Wp
– Vmp: 30.7Vdc
– Imp: 8.15A
– Voc: 37.4Vdc
– Isc: 8.63A
– Cells: 60| Inverter Model| SOLAR INPUT 1| SOLAR INPUT 2| Q’ty of modules
---|---|---|---|---
 1KW| 2S2P| N/A| 4pcs
2S4P| N/A| 8pcs
3KW, 4KW| 2S8P| N/A| 16pcs
3S5P| N/A| 15pcs
5KW| 2S6P| 2S6P| 24pcs
3S4P| 3S4P| 24pcs

Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and follow on-screen instruction to install the monitoring software. For the detailed software operation, please check user manual of software inside of CD.
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be used to deliver signal to external device when battery voltage reaches warning level.

Unit Status Condition Dry contact port:
NC & C NO & C
Power Off Unit is off and no output is powered. Close
Power On Output is powered from Utility. Close
Output      is powered from Battery    or Solar. Program 01 set as SUB
Battery voltage < Low DC warning voltage Open Close

Battery voltage > Setting value in Program 21 or battery charging reaches floating stage| Close| Open
Program 01 is set as SBU| Battery voltage < Setting value in Program 20| Open| Close
Battery voltage > Setting value in Program 21 or battery charging reaches floating stage| Close| Open

OPERATION

Power ON/OFF

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
OPERATION

Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter - LCD
display

LED Indicator

LED Indicator Messages

AC/ INV

| Green| Solid On| Output is powered by utility in Line mode.
Flashing| Output is powered by battery or PV in battery mode.

CHG

| Green| Solid On| Battery is fully charged.
Flashing| Battery is charging.

FAULT

| Red| Solid On| Fault occurs in the inverter.
Flashing| Warning condition occurs in the inverter.

Function Keys

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

LCD Display Icons

RICH SOLAR RS H2424 Hybrid Off Grid Inverter - LCD Display
Icons

Icon Function

Input source information

AC

| Indicates the AC input

PV1

| Indicates the 1st PV panel input

PV2

| Indicates the 2nd PV panel input
Left digital display information
| Indicate input voltage, input frequency, battery voltage, PV1 voltage, PV2 voltage, charger current
Middle digital display information
| **** Indicates the setting programs.


| Indicates the warning and fault codes. Warning: Flashing with warning code Fault: display with fault code
Right digital display information
| Indicate the output voltage, output frequency, load percent, load VA, load W, PV1 charger power, PV2 charger power, DC discharging current.
Battery information


| Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% and charging status.


| Indicates the battery type: AGM, Flooded or User-defined battery.
Load information


| Indicates overload.


| Indicates the load level by 0-24%, 25-50%, 50-74%, and 75-100%.
0%~25%| 25%~50%| 50%~75%| 75%~100%
| | |
Mode operation information

| Indicates unit connects to the mains.


| Indicates unit connects to the 1st PV panel
RICH SOLAR RS H2424 Hybrid Off Grid Inverter - LCD Display
Icons17|
Indicates unit connects to the 2nd PV panel
| Indicates the solar charger is working
| Indicates the DC/AC inverter circuit is working.
Mute operation


| Indicates unit alarm is disabled.

LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to exit.

Program Description Selectable option
00 Exit setting mode Escape

01| Output source priority selection| | Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time.
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 20 or solar and battery is not sufficient.
02| AC input voltage range| | If selected, acceptable AC input voltage range will be within 90-280VAC for output voltage at 220/230/240Vac or 65-140VAC for output voltage at 101/110/120Vac.
---|---|---|---

| If selected, acceptable AC input voltage range will be within 170-280VAC for output voltage at 220/230/240Vac or 85-140VAC for output voltage at 101/110/120Vac.
03| Output voltage| 101Vac
| If selected, acceptable feed-in grid voltage range will be 89~111VAC.
110Vac
| If selected, acceptable feed-in grid voltage range will be 97~121VAC.
120Vac(Default)

| If selected, acceptable feed-in grid voltage range will be 106~132VAC.
220Vac

| If 220Vac, 230Vac or 240Vac is selected for output voltage, please also set up country customized regulations in program 34 to determine acceptable feed- in grid voltage and frequency range.
230V (Default)

240Vac

04| Output frequency| 50Hz (default)

| If choosing 101, 110 or 120Vac in program 03 and 50Hz is selected here, output frequency is 50Hz and acceptable feed-in grid frequency range will be 47.5~51.5Hz.
If choosing 220, 230 or 240Vac in program 03 and 50Hz is selected here, the output frequency is 50Hz.
60Hz

| If choosing 101, 110 or 120Vac in program 03 and 60Hz is selected here, output frequency is 60Hz and acceptable feed-in grid frequency range will be 57.5~61.5Hz.
If choosing 220, 230 or 240Vac in program 03 and 60Hz is selected here, the output frequency is 60Hz.
05| Solar supply priority| | Solar energy provides power to charge battery as first priority.
| | | Solar energy provides power to the loads as first priority.
---|---|---|---
06| Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode.| Bypass disable (default)

| Bypass enable

07| Auto restart when overload occurs| Restart disable (default)
| Restart enable

08| Auto restart when over temperature occurs| Restart disable (default)

| Restart enable

09| Solar or battery energy feed to grid configuration| | Solar or battery energy feed to grid disable.
| Solar or battery energy feed to grid enable.
10| Charger source priority: To configure charger source priority| If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below:
Solar first

| Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
Solar and Utility (default)

| Solar energy and utility will charge battery at the same time.
Only Solar

| Solar energy will be the only charger source no matter utility is available or not.
If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it’s available and sufficient.
11| Maximum charging current: To configure total charging current for solar and utility chargers.
(Max. charging current = utility charging current + solar charging current)| 60A (default)

| For 1KW~4KW models, setting range is from 10A to 140A.
For 5KW model, setting range is from 10A to 180A.
Increment of each click is 10A.
13| Maximum utility charging current| |
---|---|---|---
|
|
|
14| Battery type| |
| If “User-Defined” is selected, battery charge voltage and low DC cut-off voltage can be set up in program 17, 18 and 19.
17| Bulk charging voltage (C.V voltage)|
If self-defined is selected in program 14, this program can be set up. Setting range is from 12.0V to 15.3V for 12Vdc model, 24.0V to 30.6V for 24Vdc model and 48.0V to 58.4V for 48Vdc model. Only for 2.4KW model, setting range is from 24.0V to 29.2V. Increment of each click is 0.1V.
18| Floating charging voltage|
18| Floating charging voltage|
---|---|---

If self-defined is selected in program 14, this program can be set up. Setting range is from 12.0V to 15.3V for 12Vdc model, 24.0V to 30.6V for 24Vdc model and 48.0V to 58.4V for 48Vdc model. Only for 2.4KW model, setting range is from 24.0V to 29.2V. Increment of each click is 0.1V.
19| Low DC cut off battery voltage setting|
If self-defined is selected in program 14, this program can be set up. Setting range is from 10.2V to 12.0V for 12Vdc model, 20.4V to 24V for 24Vdc model and 40.8V to 48.0V for 48Vdc model. Only for 2.4KW model, setting range is from 20.0V to 24V. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
20| Battery stop discharging voltage when grid is available| Available options for 12V models:
|
|
| RICH SOLAR RS H2424 Hybrid Off Grid Inverter - LCD Display
Icons91
20| Battery stop discharging voltage when grid is available| |
---|---|---|---
Available options for 24V models:
|
|
|
|
Available options for 48V models:
|
|
|
|
21| Battery stop charging voltage when grid is available| Available options for 12V models:
|
21| Battery stop charging voltage when grid is available| |
---|---|---|---
|
|
|
|
Available options for 24V models:
|
|
|
|
|
|
21| Battery stop charging voltage when grid is available| Available options for 48V models:
---|---|---
|
|
|
|
|
|
22| Auto return to default display screen| Return to default display screen (default)

| If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute.
| If selected, the display screen will stay at latest screen user finally switches.
23| Backlight control| |
24| Alarm control| |
25| Beeps while primary source is interrupted| |
27| Record Fault code| |
---|---|---|---
28| AC output mode: This setting is only for the inverter in parallel operation. For the detailed setting, please check section 7 in parallel function chapter. *This setting is only available when the inverter is in standby mode (Switch off).| |
|
|
29| Reset PV energy storage| |
30| Start charging time for AC charger| The setting range of start charging time for AC charger is from 00:00 to 23:00, increment of each click is 1 hour.
31| Stop charging time for AC charger| The setting range of stop charging time for AC charger is from 00:00 to 23:00, increment of each click is 1 hour.
32| Scheduled time for AC output on| The setting range of scheduled Time for AC output on is from 00:00 to 23:00, increment of each click is 1 hour.
33| Scheduled time for AC output off| The setting range of scheduled Time for AC output off is from 00:00 to 23:00, increment of each click is 1 hour.
34| Set country customized regulations (This setting is only available for 1KW, 2KW, 3KW, 4KW and 5KW models)| | If selected, acceptable feed-in grid voltage range will be 195.5~253VAC.
Acceptable feed-in grid frequency range will be 49~51Hz.
34| Set country customized regulations (This setting is only available for 1KW, 2KW, 3KW, 4KW and 5KW models)| | If selected, acceptable feed-in grid voltage range will be 184~264.5VAC.
Acceptable feed-in grid frequency range will be 47.5~51.5Hz.
---|---|---|---
| If selected, acceptable feed-in grid voltage range will be 184~264.5VAC. Acceptable feed-in grid frequency range will be 57~62Hz.
95| Time setting – Minute|
96| Time setting – Hour|
97| Time setting– Day|
98| Time setting– Month|
99| Time setting – Year|

Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main board firmware version and SCC firmware version.

Select item LCD display
Input voltage and output voltage (Default Display Screen)
Input frequency and output frequency
Battery voltage and output voltage
Battery voltage and load percentage
Battery voltage and load in VA
--- ---
Battery voltage and load in Watt
PV1 voltage and PV1 charger power
PV2 voltage and PV2 charger power
Charger current and DC discharging current
PV energy generated today
--- ---
PV energy generated this month
PV energy generated this year
PV energy generated totally
Real date
Real time
Main board firmware version
--- ---
SCC firmware version

Operating Mode Description

Operating mode Behaviors LCD display

** Standby mode
Note:
Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output.
Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected.| **
No output power, solar or utility charger available|
**** Line mode| Output power from utility. Charger available|
---|---|---
Output power from utility. Charger available|
Battery mode| **** Output power from battery or PV|
| | ****
---|---|---


Fault mode
Note:
*Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.| **** No output, no charging.|

Warning Indicator

Warning Code| Warning Event|

Icon flashing

---|---|---
01| Fan locked|
03| Battery over charged|
04| Low battery|
07| Overload|

Faults Reference Code

Fault Code| Fault Event|

Icon on

---|---|---
01| Fan locked|
02| Over temperature|
03| Battery voltage is too high|
04| Battery voltage is too low|
05| Output short circuited|
06| Output voltage abnormal|
07| Over load time out|
08| Bus voltage is too high|
09| Bus soft start failed|
51| Over current or surge|
52| Bus voltage is too low|
53| Inverter soft start failed|


55| Over DC offset in AC output|


56| Battery disconnected|
57| Current sensor failed|


58| Output voltage is too low|


SPECIFICATIONS

MODEL 1KW 2KW 3KW 4KW 5KW 2.4KW
RATED OUPUT POWER 1000 W 2000 W 3000W 4000W 5000W 2400W

PV INPUT (DC)
Max. PV Power| 1000W| 2000W| 4000W| 4000W| 6000W| 2000W
Max. PV Array Open Circuit Voltage| 145 VDC| 145 VDC| 145 VDC| 145 VDC| 145 VDC| 145 VDC
MPPT Range @ Operating Voltage| 15 VDC~115 VDC| 30 VDC~115 VDC| 60 VDC~115 VDC| 30 VDC~115 VDC
Number of MPP Tracker| 1| 1| 1| 1| 2| 1
GRID-TIE OPERATION
GRID OUTPUT (AC)
Nominal Output Voltage| 220/230/240 VAC| 101/110/120 VAC
Feed-in Grid Voltage Range| 195.5~253 VAC @India regulation 184 ~ 264.5 VAC @Germany regulation 184~264.5VAC @ South America regulation| 89~111 VAC @
101 VAC output 97~121 VAC @
110 VAC output 106~132 VAC @
120 VAC output
Feed-in Grid Frequency Range| 49~51Hz @India regulation 47.5~51.5Hz @Germany regulation 57~62Hz @ South America regulation| 47.5~51.5Hz @ 50Hz
57.5~61.5Hz @ 60Hz
Nominal Output Current| 4.3A| 8.7A| 13A| 17.4A| ** 21.7A| 29.7A @ 101Vac
27.2A @ 110Vac
25.0A @ 120Vac
Power Factor Range| >0.99
Maximum Conversion Efficiency (DC/AC)| 90%| 85%
OFF-GRID, HYBRID OPERATION
GRID INPUT
Acceptable Input Voltage Range| 90 – 280 VAC or 170 – 280 VAC| 65 – 140 VAC or 85 – 140 VAC
Frequency Range| 50 Hz/60 Hz (Auto sensing)
Rating of AC Transfer Relay| 30A| 40A
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage| 220/230/240 VAC| 101/110/120 VAC
Output Waveform| Pure Sine Wave
Efficiency (DC to AC)| 93%| 90%
BATTERY & CHARGER
Nominal DC Voltage| 12 VDC| 24 VDC| 48 VDC| 48 VDC| 48 VDC| 24 VDC
Maximum Charging Current (from Grid)| 60A
Maximum Charging Current (from PV)| 80A| 80A| 80A| 80A| 120A| 80 A
Maximum Charging Current| 140A| 140A| 140A| 140A| 180A| 140 A
GENERAL|
Dimension, D X W X H (mm)| 440 x 300 x 100| 440 x 300 x 100| 120 x 295 x 468| 120 x 295 x 468| 190 x 295 x 483| 120 x 295 x 468
Net Weight (kgs)| 8| 8| 11| 11| 16| 11
INTERFACE
Parallel-able| N/A| N/A| Yes| Yes| Yes| Yes
External Safety Box (Optional)| Yes
Communication| USB or RS232/Dry-Contact
ENVIRONMENT**
Humidity| 0 ~ 90% RH (No condensing)
Operating Temperature| 0 to 50°C

TROUBLE SHOOTING

Problem| LCD/LED/Buzzer| Explanation / Possible cause| What to do
---|---|---|---
Unit shuts down automatically during startup process.| LCD/LEDs and buzzer will be active for 3 seconds and then complete off.| The battery voltage is too low (<1.91V/Cell)| 1.  Re-charge battery.
2.  Replace battery.
No response after power on.| No indication.| 1.  The battery voltage is far too low. (<1.4V/Cell)
2.  Battery polarity is connected reversed.| 1.   Check if batteries and the wiring are connected well.
2.   Re-charge battery.
3.   Replace battery.
Mains exist but the unit works in battery mode.| Input voltage is displayed as 0 on the LCD and green LED is flashing.| Input protector is tripped| Check if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing.| Insufficient quality of AC power. (Shore or Generator)| 1.   Check if AC wires are too thin and/or too long.
2.   Check if generator (if applied) is working well or if input voltage range setting is correct. (UPSàAppliance)
Green LED is flashing.| Set “Solar First” as the priority of output source.| Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.| LCD display and LEDs are flashing| Battery is disconnected.| Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.| Fault code 07| Overload error. The inverter is overload 110% and time is up.| Reduce the connected load by switching off some equipment.
Fault code 05| Output short circuited.| Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 120°C. (Only available for 1-3KVA models.)| Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02| Internal temperature of inverter component is over 100°C.
Fault code 03| Battery is over-charged.| Return to repair center.
The battery voltage is too high.| Check if spec and quantity of batteries are meet requirements.
Fault code 01| Fan fault| Replace the fan.
Fault code 06/58| Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)| 1.   Reduce the connected load.
2.   Return to repair center
Fault code 08/09/53/57| Internal components failed.| Return to repair center.
Fault code 51| Over current or surge.| Restart the unit, if the error happens again, please return to repair center.
Fault code 52| Bus voltage is too low.
Fault code 55| Output voltage is unbalanced.
**** Fault code 56| Battery is not connected well or fuse is burnt.| If the battery is connected well, please return to repair center.

PARALLEL FUNCTION (only for 2.4KW/3KW/4KW/5KW models)

  1. Introduction
    This inverter can be used in parallel with two different operation modes.
    1. Parallel operation in single phase with up to 9 units. The supported maximum output power is 45KW.
    2. Maximum nine units work together to support three-phase equipment for 3KW- 5KW models or support two-phase equipment for 2.4KW model. In three-phase application, seven units support one phase maximum. The supported maximum output power is 45KW and one phase can be up to 35KW/35KVA. In two-phase application, eight units support one phase maximum. The supported maximum output is 21.6KW and one phase can be up to 19.2KW.
    NOTE: If this unit is bundled with share current cable and parallel cable, this inverter is default supported parallel operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following instruction from professional technical personnel in local dealer.

  2. Package Contents
    In parallel kit, you will find the following items in the package:
    RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Package
Contents

  3. Parallel board installation
    Step 1: Remove wire cover by unscrewing all screws.
    Step 2: Remove communication board by unscrewing two screws as below chart.
    Step 3: Remove two screws as below chart and remove 2-pin and 14-pin cables. Take out the board under the communication board.
    Step 4 : Remove two screws as below chart to take out cover of parallel communication.
    RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Package
Contents4 Step 5: Install new parallel board with 2 screws tightly.
    Step 6: Re-connect 2-pin and 14-pin to original position.
    RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Package
Contents7 Step 7: Put communication board back to the unit.
    Step 8 : Put wire cover back to the unit. Now the inverter is providing parallel operation function.

  4. Mounting the Unit
    When installing multiple units, please follow below chart.
    RICH SOLAR RS H2424 Hybrid Off Grid Inverter - Mounting the
Unit NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx.
    50 cm above and below the unit. Be sure to install each unit in the same level.

  5. Wiring Connection
    The cable size of each inverter is shown as below:
    Recommended battery cable and terminal size for each inverter: Model| Wire Size| Ring Terminal| Torque value
    ---|---|---|---
    Cable mm²| Dimensions
    D (mm)| L (mm)
    2.4KW/3KW/ 4KW| 14AWG| 22| 6.4| 33.2| 2~ 3 Nm
    2
    6AWG| 14| 6.4| 29.2
    5KW| 2 * 4AWG| 44| 10.5| 50| 10~ 12 Nm

WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between inverter and battery to cause parallel inverters not working.
Recommended AC input and output cable size for each inverter:

Model AWG no. Torque
2.4KW 10 AWG 1.4~1.6Nm
3KW 12 AWG 1.4~1.6Nm
4KW 8 AWG 1.4~1.6Nm
5KW 1 x 8 AWG 1.4~1.6Nm

You need to connect the cables of each inverter together. Take the battery cables for example: You need to use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X” indicates the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of battery or AC input. The recommended mounted location of the breakers is shown in the figures in 5-1 and 5-2.
Recommended breaker specification of battery for each inverter:

Model 1 unit*
2.4KW 125A/30VDC
3KW 80A/60VDC
4KW 100A/60VDC
5KW 125A/60VDC

*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:

Model 2 units 3 units 4 units 5 units 6 units 7 units 8 units 9 units
2.4KW 80A/120VAC 120A/120VAC 160A/120VAC 200A/120VAC 240A/120VAC
280A/120CAC 320A/120VAC 360A/120VAC
3KW 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC
280A/230CAC 320A/230VAC 360A/230VAC
4KW 100A/230VAC 150A/230VAC 200A/230VAC 250A/230VAC 300A/230VAC
400A/230VAC 450A/230VAC 500A/230VAC
5KW 100A/230VAC 150A/230VAC 200A/230VAC 250A/230VAC 300A/230VAC
400A/230VAC 450A/230VAC 500A/230VAC

Note1 : Also, you can use 40A breaker for 2.4KW/3KW and 50A for 4KW/5KW for only 1 unit and install one breaker at its AC input in each inverter.
Note2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units
Recommended battery capacity

Inverter parallel numbers 2 3 4 5 6 7 8 9
Battery Capacity for 2.4KW/3KW/4KW 400AH 600AH 800AH 1000AH 1200AH
1400AH 1600AH 1800AH
Battery Capacity for 5KW 1200AH 1800AH 2400AH 3000AH 3600AH 4200AH
4800AH 5400AH

WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.
5-1. Parallel Operation in Single phase
Two inverters in parallel:
RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal1RICH SOLAR RS H2424 Hybrid
Off Grid Inverter -Ring terminal2RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal3RICH SOLAR RS H2424 Hybrid Off
Grid Inverter - LCD Display Icons254 5-2. Support 2-phase equipment (only for 2.4KW model)
Two inverters in each phase:
Power Connection

Two inverters in one phases and one inverter for the remaining phase:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal6

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal7

Four inverters in one phase and one inverter for the other two phases:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal8

Note: It’s up to customer’s demand to pick 4 inverters on any phase.
P1: L1-phase, P2: L2-phase, P3: L3-phase.
Communication Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal9

Three inverters in one phase, two inverters in second phase and one inverter for the third phase:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal10

Communication Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal11

Three inverters in one phase and only one inverter for the remaining two phases:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal12

Two inverters in two phases and only one inverter for the remaining phase:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal13

Communication Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal14

Two inverters in one phase and only one inverter for the remaining phases:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal15

One inverter in each phase:
Power Connection

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -Ring
terminal16

WARNING: Do not connect the current sharing cable between the inverters which are in different phases.
Otherwise, it may damage the inverters.
6. PV Connection
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.

7. LCD Setting and Display
Setting Program:

Program Description Selectable option
**** When the unit is operated alone, please select “SIG” in program
  1. | | | When the units are used in parallel with single phase, please select “PAL” in program 28. Please refer to 5-1 for detailed information.
    28| AC output mode *This setting is only available when the inverter is in standby mode (Switch off).| | When the units are operated in 2-phase application, please choose “2PX” to define each inverter.
    It’s required to have at least 2 inverters (one inverter in each phase) or maximum 9 inverters to support two-phase equipment. Please refer to 5-2 for detailed information. Please select “2P1” in program 28 for the inverters connected to L1 phase and “2P2” in program 28 for the inverters connected to L2 phase

    | When the units are operated in 3-phase application, please choose “3PX” to define each inverter.
    It is required to have at least 3 inverters or maximum 9 inverters to support
    three-phase equipment. It’s required to have at least one inverter in each phase or it’s up to four inverters in one phase. Please refers to 5-3 for detailed information.
    Please select “3P1” in program 28 for the inverters connected to L1 phase, “3P2” in program 28 for the inverters connected to L2 phase and “3P3” in program 28 for the inverters connected to L3 phase.


| | L3 phase: | Be sure to connect share current cable to units which are on the same phase.
Do NOT connect share current cable between units on different phases.
| | | Besides, power saving function will be automatically disabled.
30| **** PV judge condition (Only apply for setting “Solar first” in program 1: Output source priority)|


| When “ONE” is selected, as long as one of inverters has been connected to PV modules and PV input is normal, parallel or 3-phase system will continue working according to rule of “solar first” setting.
For example, two units are connected in parallel and set “SOL” in output source priority. If one of two units has connected to PV modules and PV input is normal, the parallel system will provide power to loads from solar or battery power. If both of them are not sufficient, the system will provide power to loads from utility.
| | **** All of Inverters:| When “ALL” is selected, parallel or 3-phase system will continue working according to rule of “solar first” setting only when all of inverters are connected to PV modules.
For example, two units are connected in parallel and set “SOL” in output source priority. When selecting “ALL” in program 30, it’s necessary to have all inverters connected to PV modules and PV input is normal to allow the system to provide power to loads from solar and battery power. Otherwise, the system will provide power to loads from utility.
---|---|---|---

Fault code display:

Fault Code| Fault Event|

Icon on

---|---|---
60| Power feedback protection|
71| Firmware version inconsistent|
72| Current sharing fault|
80| CAN fault|
81| Host loss|
82| Synchronization loss|
83| Battery voltage detected different|
84| AC input voltage and frequency detected different|
85| AC output current unbalance|
86| AC output mode setting is different|

8. Commissioning
Parallel in single phase
Step 1: Check the following requirements before commissioning:

  • Correct wire connection
  • Ensure all breakers in Line wires of load side are off and each Neutral wires of each unit are connected together.

Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.
Step 3: Turn on each unit.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Commissioning

NOTE: Master and slave units are randomly defined.
Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility at the same time. If not, it will display fault 82 in following-order inverters. However, these inverters will automatically restart. If detecting AC connection, they will work normally.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Commissioning1

Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6 : Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.

Support two-phase equipment
Step 1 : Check the following requirements before commissioning:

  • Correct wire connection
  • Ensure all breakers in Line wires of load side are off and each Neutral wires of each unit are connected together.

Step 2 : Turn on all units and configure LCD program 28 as P1 and P2 sequentially. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.
Step 3: Turn on all units sequentially.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Commissioning52

Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and two phases are matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not work in line mode.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Commissioning2 Step 5: If there is no more fault alarm, the system to support 2-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.
Support three-phase equipment
Step 1 : Check the following requirements before commissioning:

  • Correct wire connection
  • Ensure all breakers in Line wires of load side are off and each Neutral wires of each unit are connected together.

Step 2 : Turn on all units and configure LCD program 28 as P1, P2 and P3 sequentially. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.
Step 3: Turn on all units sequentially.
RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Commissioning3 Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not work in line mode.

RICH SOLAR RS H2424 Hybrid Off Grid Inverter -
Commissioning4

Step 5 : If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.
Note 1: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole system in operation first.
Note 2: Transfer time for this operation exists. Power interruption may happen to critical devices, which cannot bear transfer time.

9. Trouble shooting

Situation Solution
Fault Code Fault Event Description
**** 60 **** Current feedback into the inverter is detected.

the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, make sure the sharing are connected in all inverters.
For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases.
4. If the problem remains, please contact your installer.
71| The firmware version of each inverter is not the same.| 1. Update all inverter firmware to the same version.
2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, please contact your instraller to provide the firmware to update.
3.  After updating, if the problem still remains, please contact your installer.
72| The output current of each inverter is different.| 1.  Check if sharing cables are connected well and restart the inverter.
2.  If the problem remains, please contact your installer.
80| CAN data loss| 1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
81| Host data loss
82| Synchronization data loss
83| The battery voltage of each inverter is not the same.| 1. Make sure all inverters share same groups of batteries together.
2.  Remove all loads and disconnect AC input and PV input. Then, check battery voltage of all inverters. If the values from all inverters are close, please check if all battery cables are the same length and same material type. Otherwise, please contact your installer to provide SOP to calibrate battery voltage of each inverter.
3.  If the problem still remains, please contact your installer.
84| AC input voltage and frequency are detected different.| 1.Check the utility wiring conncetion and restart the inverter.
2.  Make sure utility starts up at same time. If there are breakers installed between utility and inverters, please be sure all breakers can be turned on AC input at same time.
3. If the problem remains, please contact your installer.
85| AC output current unbalance| 1.Restart the inverter.
2.  Remove some excessive loads and re-check load information from LCD of inverters. If the values are different, please check if AC input and output cables are in the same length and material type.
3.  If the problem remains, please contact your installer.
86| **** AC output mode setting is different.| 1. Switch off the inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2, 3P3 or 2P1, 2P2 is set on #28.
For supporting two-phase system, make sure no “PAL” or 3P1, 3P2, 3P3 is set on

28.

For supporting three-phase system, make sure no “PAL” or 2P1, 2P2 is set on

28.

3.  If the problem remains, please contact your installer.

1-800-831-9889
www.richsolar.com
support@richsolar.com
5550 Jurupa St, Ontario, CA 91761

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals