RICH SOLAR RS-H2424 Hybrid Off-Grid Inverter User Manual
- August 8, 2024
- RICH SOLAR
Table of Contents
User Manual
2400WATT
HYBRID OFF-GRID INVERTER MODEL :RS-H2424
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
-
Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
-
CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage. -
Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire. -
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk. -
CAUTION – Only qualified personnel can install this device with battery.
-
NEVER charge a frozen battery.
-
For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.
-
Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
-
Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Pleaserefer to INSTALLATION section of this manual for the details.
-
Fuses (3 pieces of 40A, 32VDC for 1KW, 4 pieces of 40A, 32VDC for 2KW and 1 piece of 200A, 58VDC for 2.4KW, 3KW, 4KW and 5KW) are provided as over-current protection for the battery supply.
-
GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
-
NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
-
Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
INTRODUCTION
This hybrid PV inverter can provide power to connected loads by utilizing PV power, utility power and battery power.
Depending on different power situations, this hybrid inverter is designed to generate continuous power from PV solar modules (solar panels), battery, and the utility. When MPP input voltage of PV modules is within acceptable range (see specification for the details), this inverter is able to generate power to feed the grid (utility) and charge battery. Galvanic isolation designed between PV/DC and AC output, so that user could connect any type of PV array to this Hybrid inverter. See Figure 1 for a simple diagram of a typical solar system with this hybrid inverter.
Product Overview
NOTE: For parallel model installation and operation, please check separate parallel installation guide for the details.
1. LCD display
2. Status indicator
3. Charging indicator
4. Fault indicator
5. Function buttons
6. Power on/off switch
7. Grid connectors
8. AC output connectors (Load connection)| 9. PV connectors
10. Battery connectors
11. Circuit breaker
12. Parallel communication cable
13. Current sharing cable
14. Dry contact
15. RS-232 communication port
16. USB communication port
---|---
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. You should have received the following items inside of
package:
- The unit x 1, User manual x 1, Communication cable x 1, Software CD x 1
Preparation
Before connecting all wirings, please take off bottom cover by removing two
screws as shown below.
Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws. It’s recommended to use M4 or M5
screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested
to install a separate DC over-current protector or disconnect device between
battery and inverter. It may not be requested to have a disconnect device in
some applications, however, it’s still requested to have over-current
protection installed. Please refer to typical amperage in below table as
required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
useappropriate cable for battery connection. To reduce risk of injury, please
use theproper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model| Typical Amperage| Battery Capacity| Wire Size|
Ring Terminal| Torque Value
---|---|---|---|---|---
Cable mm 2| Dimensions
D (mm)| L (mm)
1KW, 2KW, 2.4KW, 3KW, 4KW| 140A| 200AH| 1*2AWG| 38| 6.4| 39.2|
*** 2~3 Nm
26AWG| 28| 6.4| 33.2
5KW| 180A| 600AH| 2*4AWG| 44| 10.5| 55| 10~12 Nm
Please follow below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in
series.
CAUTION!! Do not place anything between the flat part of the inverter
terminal and the ring terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before
terminals are connected tightly.
CAUTION!! Before making the final DC connection or closing DC
breaker/disconnector, be sure positive (+) must be connected to positive (+)
and negative (-) must be connected to negative (-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a
separate AC breaker between inverter and AC input power source. This will
ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings.
Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for AC input connection. To reduce risk of injury,
please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model | Gauge | Torque Value |
---|---|---|
1KW | 16 AWG | 0.5 ~ 0.6 Nm |
2KW | 14 AWG | 0.8 ~ 1.0 Nm |
2.4KW | 10 AWG | 1.4 ~ 1.6 Nm |
3KW | 12 AWG | 1.2 ~ 1.6 Nm |
4KW | 10 AWG | 1.4 ~ 1.6 Nm |
5KW | 10 AWG | 1.4 ~ 1.6 Nm |
Please follow below steps to implement AC input/output connection:
-
Before making AC input/output connection, be sure to open DC protector or disconnector first.
-
Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
-
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor ( ) first.
→Ground (yellow-green)
L →LINE (brown or black)
N →Neutral (blue)
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit. -
Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor ( ) first.
→Ground (yellow-green)
L →LINE (brown or black)
N →Neutral (blue)
-
Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are
connected reversely, it may cause utility short-circuited when these inverters
are worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3
minutes to restart because it’s required to have enough time to balance
refrigerant gas inside of circuits. If a power shortage occurs and recovers in
a short time, it will cause damage to your connected appliances. To prevent
this kind of damage, please check manufacturer of air conditioner if it’s
equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your
appliance but sometimes it still causes internal damage to the air
conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC
circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to
use appropriate cable for PV module connection. To reduce risk of injury,
please use the proper recommended cable size as below.
Model | Typical Amperage | Cable Size | Torque |
---|---|---|---|
1KW, 2KW, 2.4KW, 3KW, 4KW | 80A | 6AWG | 2.0~2.4Nm |
5KW | PV 1 | 60A | 8AWG |
PV 2 | 60A | 8AWG | 2.0~2.4Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode
INVERTER MODEL| 1KW| 2KW| 2.4KW| 3KW| 4KW|
5KW
Max. PV Array Open Circuit Voltage| 145Vdc
PV Array MPPT Voltage Range| 15~115Vdc| 30~115Vdc| 60~115Vdc
MPP Number| 1| 1| 1| 1| 1| 2
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector.
Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
Recommended PV module Configuration
PV Module Spec.
(reference)
– 250Wp
– Vmp: 30.7Vdc
– Imp: 8.15A
– Voc: 37.4Vdc
– Isc: 8.63A
– Cells: 60| Inverter Model| SOLAR INPUT 1| SOLAR INPUT 2| Q’ty of modules
---|---|---|---|---
1KW| 2S2P| N/A| 4pcs
2S4P| N/A| 8pcs
3KW, 4KW| 2S8P| N/A| 16pcs
3S5P| N/A| 15pcs
5KW| 2S6P| 2S6P| 24pcs
3S4P| 3S4P| 24pcs
Communication Connection
Please use supplied communication cable to connect to inverter and PC. Insert
bundled CD into a computer and follow on-screen instruction to install the
monitoring software. For the detailed software operation, please check user
manual of software inside of CD.
Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be
used to deliver signal to external device when battery voltage reaches warning
level.
Unit Status | Condition | Dry contact port: |
---|---|---|
NC & C | NO & C | |
Power Off | Unit is off and no output is powered. | Close |
Power On | Output is powered from Utility. | Close |
Output is powered from Battery or Solar. | Program 01 set as SUB | |
Battery voltage < Low DC warning voltage | Open | Close |
Battery voltage > Setting value in Program 21 or battery charging reaches
floating stage| Close| Open
Program 01 is set as SBU| Battery voltage < Setting value in Program 20| Open|
Close
Battery voltage > Setting value in Program 21 or battery charging reaches
floating stage| Close| Open
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected
well, simply press On/Off switch (located on the button of the case) to turn
on the unit.
Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel
of the inverter. It includes three indicators, four function keys and a LCD
display, indicating the operating status and input/output power information.
LED Indicator
LED Indicator | Messages |
---|
AC/ INV
| Green| Solid On| Output is powered by utility in Line mode.
Flashing| Output is powered by battery or PV in battery mode.
CHG
| Green| Solid On| Battery is fully charged.
Flashing| Battery is charging.
FAULT
| Red| Solid On| Fault occurs in the inverter.
Flashing| Warning condition occurs in the inverter.
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Icons
Icon | Function |
---|
Input source information
AC
| Indicates the AC input
PV1
| Indicates the 1st PV panel input
PV2
| Indicates the 2nd PV panel input
Left digital display information
| Indicate input voltage, input frequency, battery voltage, PV1 voltage, PV2
voltage, charger current
Middle digital display information
| **** Indicates the setting programs.
| Indicates the warning and fault codes. Warning: Flashing with warning code
Fault: display with fault code
Right digital display information
| Indicate the output voltage, output frequency, load percent, load VA, load
W, PV1 charger power, PV2 charger power, DC discharging current.
Battery information
| Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% and charging status.
| Indicates the battery type: AGM, Flooded or User-defined battery.
Load information
| Indicates overload.
| Indicates the load level by 0-24%, 25-50%, 50-74%, and 75-100%.
0%~25%| 25%~50%| 50%~75%| 75%~100%
| | |
Mode operation information
| Indicates unit connects to the mains.
| Indicates unit connects to the 1st PV panel
| Indicates unit
connects to the 2nd PV panel
| Indicates the solar charger is working
| Indicates the DC/AC inverter circuit is working.
Mute operation
| Indicates unit alarm is disabled.
LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter
setting mode. Press “UP” or “DOWN” button to select setting programs. And
then, press “ENTER” button to confirm the selection or ESC button to exit.
Program | Description | Selectable option |
---|---|---|
00 | Exit setting mode | Escape |
01| Output source priority selection| | Solar energy provides power to the
loads as first priority.
If solar energy is not sufficient to power all connected loads, Utility energy
will supply power to the loads at the same time.
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy
will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either
low-level warning voltage or the setting point in program 20 or solar and
battery is not sufficient.
02| AC input voltage range| | If selected, acceptable AC input voltage range
will be within 90-280VAC for output voltage at 220/230/240Vac or 65-140VAC for
output voltage at 101/110/120Vac.
---|---|---|---
| If selected, acceptable AC input voltage range will be within 170-280VAC for
output voltage at 220/230/240Vac or 85-140VAC for output voltage at
101/110/120Vac.
03| Output voltage| 101Vac
| If selected, acceptable feed-in grid voltage range will be 89~111VAC.
110Vac
| If selected, acceptable feed-in grid voltage range will be 97~121VAC.
120Vac(Default)
| If selected, acceptable feed-in grid voltage range will be 106~132VAC.
220Vac
| If 220Vac, 230Vac or 240Vac is selected for output voltage, please also set
up country customized regulations in program 34 to determine acceptable feed-
in grid voltage and frequency range.
230V (Default)
240Vac
04| Output frequency| 50Hz (default)
| If choosing 101, 110 or 120Vac in program 03 and 50Hz is selected here,
output frequency is 50Hz and acceptable feed-in grid frequency range will be
47.5~51.5Hz.
If choosing 220, 230 or 240Vac in program 03 and 50Hz is selected here, the
output frequency is 50Hz.
60Hz
| If choosing 101, 110 or 120Vac in program 03 and 60Hz is selected here,
output frequency is 60Hz and acceptable feed-in grid frequency range will be
57.5~61.5Hz.
If choosing 220, 230 or 240Vac in program 03 and 60Hz is selected here, the
output frequency is 60Hz.
05| Solar supply priority| | Solar energy provides power to charge battery as
first priority.
| | | Solar energy provides power to the loads as first priority.
---|---|---|---
06| Overload bypass: When enabled, the unit will transfer to line mode if
overload occurs in battery mode.| Bypass disable (default)
| Bypass enable
07| Auto restart when overload occurs| Restart disable (default)
| Restart enable
08| Auto restart when over temperature occurs| Restart disable (default)
| Restart enable
09| Solar or battery energy feed to grid configuration| | Solar or battery
energy feed to grid disable.
| Solar or battery energy feed to grid enable.
10| Charger source priority: To configure charger source priority| If this
inverter/charger is working in Line, Standby or Fault mode, charger source can
be programmed as below:
Solar first
| Solar energy will charge battery as first priority. Utility will charge
battery only when solar energy is not available.
Solar and Utility (default)
| Solar energy and utility will charge battery at the same time.
Only Solar
| Solar energy will be the only charger source no matter utility is available
or not.
If this inverter/charger is working in Battery mode or Power saving mode, only
solar energy can charge battery. Solar energy will charge battery if it’s
available and sufficient.
11| Maximum charging current: To configure total charging current for solar
and utility chargers.
(Max. charging current = utility charging current + solar charging current)|
60A (default)
| For 1KW~4KW models, setting range is from 10A to 140A.
For 5KW model, setting range is from 10A to 180A.
Increment of each click is 10A.
13| Maximum utility charging current| |
---|---|---|---
|
|
|
14| Battery type| |
| If “User-Defined” is selected, battery charge voltage and low DC cut-off
voltage can be set up in program 17, 18 and 19.
17| Bulk charging voltage (C.V voltage)|
If self-defined is selected in program 14, this program can be set up. Setting
range is from 12.0V to 15.3V for 12Vdc model, 24.0V to 30.6V for 24Vdc model
and 48.0V to 58.4V for 48Vdc model. Only for 2.4KW model, setting range is
from 24.0V to 29.2V. Increment of each click is 0.1V.
18| Floating charging voltage|
18| Floating charging voltage|
---|---|---
If self-defined is selected in program 14, this program can be set up. Setting
range is from 12.0V to 15.3V for 12Vdc model, 24.0V to 30.6V for 24Vdc model
and 48.0V to 58.4V for 48Vdc model. Only for 2.4KW model, setting range is
from 24.0V to 29.2V. Increment of each click is 0.1V.
19| Low DC cut off battery voltage setting|
If self-defined is selected in program 14, this program can be set up. Setting
range is from 10.2V to 12.0V for 12Vdc model, 20.4V to 24V for 24Vdc model and
40.8V to 48.0V for 48Vdc model. Only for 2.4KW model, setting range is from
20.0V to 24V. Increment of each click is 0.1V. Low DC cut-off voltage will be
fixed to setting value no matter what percentage of load is connected.
20| Battery stop discharging voltage when grid is available| Available options
for 12V models:
|
|
|
20| Battery stop discharging voltage when grid is available| |
---|---|---|---
Available options for 24V models:
|
|
|
|
Available options for 48V models:
|
|
|
|
21| Battery stop charging voltage when grid is available| Available options
for 12V models:
|
21| Battery stop charging voltage when grid is available| |
---|---|---|---
|
|
|
|
Available options for 24V models:
|
|
|
|
|
|
21| Battery stop charging voltage when grid is available| Available options
for 48V models:
---|---|---
|
|
|
|
|
|
22| Auto return to default display screen| Return to default display screen
(default)
| If selected, no matter how users switch display screen, it will
automatically return to default display screen (Input voltage /output voltage)
after no button is pressed for 1 minute.
| If selected, the display screen will stay at latest screen user finally
switches.
23| Backlight control| |
24| Alarm control| |
25| Beeps while primary source is interrupted| |
27| Record Fault code| |
---|---|---|---
28| AC output mode: This setting is only for the inverter in parallel
operation. For the detailed setting, please check section 7 in parallel
function chapter. *This setting is only available when the inverter is in
standby mode (Switch off).| |
|
|
29| Reset PV energy storage| |
30| Start charging time for AC charger| The setting range of start charging
time for AC charger is from 00:00 to 23:00, increment of each click is 1 hour.
31| Stop charging time for AC charger| The setting range of stop charging
time for AC charger is from 00:00 to 23:00, increment of each click is 1 hour.
32| Scheduled time for AC output on| The setting range of scheduled Time for
AC output on is from 00:00 to 23:00, increment of each click is 1 hour.
33| Scheduled time for AC output off| The setting range of scheduled Time for
AC output off is from 00:00 to 23:00, increment of each click is 1 hour.
34| Set country customized regulations (This setting is only available for
1KW, 2KW, 3KW, 4KW and 5KW models)| | If selected, acceptable feed-in grid
voltage range will be 195.5~253VAC.
Acceptable feed-in grid frequency range will be 49~51Hz.
34| Set country customized regulations (This setting is only available for
1KW, 2KW, 3KW, 4KW and 5KW models)| | If selected, acceptable feed-in grid
voltage range will be 184~264.5VAC.
Acceptable feed-in grid frequency range will be 47.5~51.5Hz.
---|---|---|---
| If selected, acceptable feed-in grid voltage range will be 184~264.5VAC.
Acceptable feed-in grid frequency range will be 57~62Hz.
95| Time setting – Minute|
96| Time setting – Hour|
97| Time setting– Day|
98| Time setting– Month|
99| Time setting – Year|
Display Setting
The LCD display information will be switched in turns by pressing “UP” or
“DOWN” key. The selectable information is switched as below order: input
voltage, input frequency, PV voltage, charging current, battery voltage,
output voltage, output frequency, load percentage, load in Watt, load in VA,
load in Watt, DC discharging current, main board firmware version and SCC
firmware version.
Select item | LCD display |
---|---|
Input voltage and output voltage (Default Display Screen) | |
Input frequency and output frequency | |
Battery voltage and output voltage | |
Battery voltage and load percentage | |
Battery voltage and load in VA | |
--- | --- |
Battery voltage and load in Watt | |
PV1 voltage and PV1 charger power | |
PV2 voltage and PV2 charger power | |
Charger current and DC discharging current | |
PV energy generated today | |
--- | --- |
PV energy generated this month | |
PV energy generated this year | |
PV energy generated totally | |
Real date | |
Real time | |
Main board firmware version | |
--- | --- |
SCC firmware version |
Operating Mode Description
Operating mode | Behaviors | LCD display |
---|
** Standby mode
Note:
Standby mode: The inverter is not turned on yet but at this time, the
inverter can charge battery without AC output.
Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected.| ** No output power, solar or utility charger available|
**** Line mode| Output power from utility. Charger available|
---|---|---
Output power from utility. Charger available|
Battery mode| **** Output power from battery or PV|
| | ****
---|---|---
Fault mode
Note:
*Fault mode: Errors are caused by inside circuit error or external reasons
such as over temperature, output short circuited and so on.| **** No output,
no charging.|
Warning Indicator
Warning Code| Warning Event|
Icon flashing
---|---|---
01| Fan locked|
03| Battery over charged|
04| Low battery|
07| Overload|
Faults Reference Code
Fault Code| Fault Event|
Icon on
---|---|---
01| Fan locked|
02| Over temperature|
03| Battery voltage is too high|
04| Battery voltage is too low|
05| Output short circuited|
06| Output voltage abnormal|
07| Over load time out|
08| Bus voltage is too high|
09| Bus soft start failed|
51| Over current or surge|
52| Bus voltage is too low|
53| Inverter soft start failed|
55| Over DC offset in AC output|
56| Battery disconnected|
57| Current sensor failed|
58| Output voltage is too low|
SPECIFICATIONS
MODEL | 1KW | 2KW | 3KW | 4KW | 5KW | 2.4KW |
---|---|---|---|---|---|---|
RATED OUPUT POWER | 1000 W | 2000 W | 3000W | 4000W | 5000W | 2400W |
PV INPUT (DC)
Max. PV Power| 1000W| 2000W| 4000W| 4000W| 6000W| 2000W
Max. PV Array Open Circuit Voltage| 145 VDC| 145 VDC| 145 VDC| 145 VDC| 145
VDC| 145 VDC
MPPT Range @ Operating Voltage| 15 VDC~115 VDC| 30 VDC~115 VDC| 60 VDC~115
VDC| 30 VDC~115 VDC
Number of MPP Tracker| 1| 1| 1| 1| 2| 1
GRID-TIE OPERATION
GRID OUTPUT (AC)
Nominal Output Voltage| 220/230/240 VAC| 101/110/120 VAC
Feed-in Grid Voltage Range| 195.5~253 VAC @India regulation 184 ~
264.5 VAC @Germany regulation 184~264.5VAC @ South America regulation| 89~111
VAC @
101 VAC output 97~121 VAC @
110 VAC output 106~132 VAC @
120 VAC output
Feed-in Grid Frequency Range| 49~51Hz @India regulation 47.5~51.5Hz
@Germany regulation 57~62Hz @ South America regulation| 47.5~51.5Hz @ 50Hz
57.5~61.5Hz @ 60Hz
Nominal Output Current| 4.3A| 8.7A| 13A| 17.4A|
** 21.7A| 29.7A @ 101Vac
27.2A @ 110Vac
25.0A @ 120Vac
Power Factor Range| >0.99
Maximum Conversion Efficiency (DC/AC)| 90%| 85%
OFF-GRID, HYBRID OPERATION
GRID INPUT
Acceptable Input Voltage Range| 90 – 280 VAC or 170 – 280 VAC| 65 – 140 VAC or
85 – 140 VAC
Frequency Range| 50 Hz/60 Hz (Auto sensing)
Rating of AC Transfer Relay| 30A| 40A
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage| 220/230/240 VAC| 101/110/120 VAC
Output Waveform| Pure Sine Wave
Efficiency (DC to AC)| 93%| 90%
BATTERY & CHARGER
Nominal DC Voltage| 12 VDC| 24 VDC| 48 VDC| 48 VDC| 48 VDC| 24 VDC
Maximum Charging Current (from Grid)| 60A
Maximum Charging Current (from PV)| 80A| 80A| 80A| 80A| 120A| 80 A
Maximum Charging Current| 140A| 140A| 140A| 140A| 180A| 140 A
GENERAL|
Dimension, D X W X H (mm)| 440 x 300 x 100| 440 x 300 x 100| 120 x 295 x 468|
120 x 295 x 468| 190 x 295 x 483| 120 x 295 x 468
Net Weight (kgs)| 8| 8| 11| 11| 16| 11
INTERFACE
Parallel-able| N/A| N/A| Yes| Yes| Yes| Yes
External Safety Box (Optional)| Yes
Communication| USB or RS232/Dry-Contact
ENVIRONMENT**
Humidity| 0 ~ 90% RH (No condensing)
Operating Temperature| 0 to 50°C
TROUBLE SHOOTING
Problem| LCD/LED/Buzzer| Explanation / Possible cause| What
to do
---|---|---|---
Unit shuts down automatically during startup process.| LCD/LEDs and buzzer
will be active for 3 seconds and then complete off.| The battery voltage
is too low (<1.91V/Cell)| 1. Re-charge battery.
2. Replace battery.
No response after power on.| No indication.| 1. The battery
voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.| 1. Check if batteries and the
wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Mains exist but the unit works in battery mode.| Input voltage is
displayed as 0 on the LCD and green LED is flashing.| Input protector is
tripped| Check if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing.| Insufficient quality of AC power. (Shore
or Generator)| 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range
setting is correct. (UPSàAppliance)
Green LED is flashing.| Set “Solar First” as the priority of output source.|
Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.|
LCD display and LEDs are flashing| Battery is disconnected.|
Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.| Fault code 07|
Overload error. The inverter is overload 110% and time is up.| Reduce the
connected load by switching off some equipment.
Fault code 05| Output short circuited.| Check if wiring is
connected well and remove abnormal load.
Temperature of internal converter component is over 120°C. (Only available for
1-3KVA models.)| Check whether the air flow of the unit is blocked or whether
the ambient temperature is too high.
Fault code 02| Internal temperature of inverter component is over 100°C.
Fault code 03| Battery is over-charged.| Return to repair center.
The battery voltage is too high.| Check if spec and quantity of
batteries are meet requirements.
Fault code 01| Fan fault| Replace the fan.
Fault code 06/58| Output abnormal (Inverter voltage below than 190Vac or
is higher than 260Vac)| 1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57| Internal components failed.| Return to repair center.
Fault code 51| Over current or surge.| Restart the unit, if the error happens
again, please return to repair center.
Fault code 52| Bus voltage is too low.
Fault code 55| Output voltage is unbalanced.
**** Fault code 56| Battery is not connected well or fuse is burnt.| If the
battery is connected well, please return to repair center.
PARALLEL FUNCTION (only for 2.4KW/3KW/4KW/5KW models)
-
Introduction
This inverter can be used in parallel with two different operation modes.
1. Parallel operation in single phase with up to 9 units. The supported maximum output power is 45KW.
2. Maximum nine units work together to support three-phase equipment for 3KW- 5KW models or support two-phase equipment for 2.4KW model. In three-phase application, seven units support one phase maximum. The supported maximum output power is 45KW and one phase can be up to 35KW/35KVA. In two-phase application, eight units support one phase maximum. The supported maximum output is 21.6KW and one phase can be up to 19.2KW.
NOTE: If this unit is bundled with share current cable and parallel cable, this inverter is default supported parallel operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following instruction from professional technical personnel in local dealer. -
Package Contents
In parallel kit, you will find the following items in the package:
-
Parallel board installation
Step 1: Remove wire cover by unscrewing all screws.
Step 2: Remove communication board by unscrewing two screws as below chart.
Step 3: Remove two screws as below chart and remove 2-pin and 14-pin cables. Take out the board under the communication board.
Step 4 : Remove two screws as below chart to take out cover of parallel communication.
Step 5: Install new parallel board with 2 screws tightly.
Step 6: Re-connect 2-pin and 14-pin to original position.
Step 7: Put communication board back to the unit.
Step 8 : Put wire cover back to the unit. Now the inverter is providing parallel operation function. -
Mounting the Unit
When installing multiple units, please follow below chart.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx.
50 cm above and below the unit. Be sure to install each unit in the same level. -
Wiring Connection
The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter: Model| Wire Size| Ring Terminal| Torque value
---|---|---|---
Cable mm²| Dimensions
D (mm)| L (mm)
2.4KW/3KW/ 4KW| 14AWG| 22| 6.4| 33.2| 2~ 3 Nm
26AWG| 14| 6.4| 29.2
5KW| 2 * 4AWG| 44| 10.5| 50| 10~ 12 Nm
WARNING: Be sure the length of all battery cables is the same. Otherwise,
there will be voltage difference between inverter and battery to cause
parallel inverters not working.
Recommended AC input and output cable size for each inverter:
Model | AWG no. | Torque |
---|---|---|
2.4KW | 10 AWG | 1.4~1.6Nm |
3KW | 12 AWG | 1.4~1.6Nm |
4KW | 8 AWG | 1.4~1.6Nm |
5KW | 1 x 8 AWG | 1.4~1.6Nm |
You need to connect the cables of each inverter together. Take the battery
cables for example: You need to use a connector or bus-bar as a joint to
connect the battery cables together, and then connect to the battery terminal.
The cable size used from joint to battery should be X times cable size in the
tables above. “X” indicates the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
CAUTION!! Please install the breaker at the battery and AC input side.
This will ensure the inverter can be securely disconnected during maintenance
and fully protected from over current of battery or AC input. The recommended
mounted location of the breakers is shown in the figures in 5-1 and 5-2.
Recommended breaker specification of battery for each inverter:
Model | 1 unit* |
---|---|
2.4KW | 125A/30VDC |
3KW | 80A/60VDC |
4KW | 100A/60VDC |
5KW | 125A/60VDC |
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:
Model | 2 units | 3 units | 4 units | 5 units | 6 units | 7 units | 8 units | 9 units |
---|---|---|---|---|---|---|---|---|
2.4KW | 80A/120VAC | 120A/120VAC | 160A/120VAC | 200A/120VAC | 240A/120VAC | |||
280A/120CAC | 320A/120VAC | 360A/120VAC | ||||||
3KW | 80A/230VAC | 120A/230VAC | 160A/230VAC | 200A/230VAC | 240A/230VAC | |||
280A/230CAC | 320A/230VAC | 360A/230VAC | ||||||
4KW | 100A/230VAC | 150A/230VAC | 200A/230VAC | 250A/230VAC | 300A/230VAC | |||
400A/230VAC | 450A/230VAC | 500A/230VAC | ||||||
5KW | 100A/230VAC | 150A/230VAC | 200A/230VAC | 250A/230VAC | 300A/230VAC | |||
400A/230VAC | 450A/230VAC | 500A/230VAC |
Note1 : Also, you can use 40A breaker for 2.4KW/3KW and 50A for 4KW/5KW
for only 1 unit and install one breaker at its AC input in each inverter.
Note2: Regarding three-phase system, you can use 4-pole breaker directly
and the rating of the breaker should be compatible with the phase current
limitation from the phase with maximum units
Recommended battery capacity
Inverter parallel numbers | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
---|---|---|---|---|---|---|---|---|
Battery Capacity for 2.4KW/3KW/4KW | 400AH | 600AH | 800AH | 1000AH | 1200AH | |||
1400AH | 1600AH | 1800AH | ||||||
Battery Capacity for 5KW | 1200AH | 1800AH | 2400AH | 3000AH | 3600AH | 4200AH | ||
4800AH | 5400AH |
WARNING! Be sure that all inverters will share the same battery bank.
Otherwise, the inverters will transfer to fault mode.
5-1. Parallel Operation in Single phase
Two inverters in parallel:
5-2. Support 2-phase equipment (only for 2.4KW
model)
Two inverters in each phase:
Power Connection
Two inverters in one phases and one inverter for the remaining phase:
Power Connection
Four inverters in one phase and one inverter for the other two phases:
Power Connection
Note: It’s up to customer’s demand to pick 4 inverters on any phase.
P1: L1-phase, P2: L2-phase, P3: L3-phase.
Communication Connection
Three inverters in one phase, two inverters in second phase and one inverter
for the third phase:
Power Connection
Communication Connection
Three inverters in one phase and only one inverter for the remaining two
phases:
Power Connection
Two inverters in two phases and only one inverter for the remaining phase:
Power Connection
Communication Connection
Two inverters in one phase and only one inverter for the remaining phases:
Power Connection
One inverter in each phase:
Power Connection
WARNING: Do not connect the current sharing cable between the inverters
which are in different phases.
Otherwise, it may damage the inverters.
6. PV Connection
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.
7. LCD Setting and Display
Setting Program:
Program | Description | Selectable option |
---|---|---|
**** | When the unit is operated alone, please select “SIG” in program |
- | | | When the units are used in parallel with single phase, please select
“PAL” in program 28. Please refer to 5-1 for detailed information.
28| AC output mode *This setting is only available when the inverter is in standby mode (Switch off).| | When the units are operated in 2-phase application, please choose “2PX” to define each inverter.
It’s required to have at least 2 inverters (one inverter in each phase) or maximum 9 inverters to support two-phase equipment. Please refer to 5-2 for detailed information. Please select “2P1” in program 28 for the inverters connected to L1 phase and “2P2” in program 28 for the inverters connected to L2 phase
| When the units are operated in 3-phase application, please choose “3PX” to define each inverter.
It is required to have at least 3 inverters or maximum 9 inverters to support
three-phase equipment. It’s required to have at least one inverter in each phase or it’s up to four inverters in one phase. Please refers to 5-3 for detailed information.
Please select “3P1” in program 28 for the inverters connected to L1 phase, “3P2” in program 28 for the inverters connected to L2 phase and “3P3” in program 28 for the inverters connected to L3 phase.
| | L3 phase: | Be sure to connect share current cable to units which
are on the same phase.
Do NOT connect share current cable between units on different phases.
| | | Besides, power saving function will be automatically disabled.
30| **** PV judge condition (Only apply for setting “Solar first” in
program 1: Output source priority)|
| When “ONE” is selected, as long as one of inverters has been connected to PV
modules and PV input is normal, parallel or 3-phase system will continue
working according to rule of “solar first” setting.
For example, two units are connected in parallel and set “SOL” in output
source priority. If one of two units has connected to PV modules and PV input
is normal, the parallel system will provide power to loads from solar or
battery power. If both of them are not sufficient, the system will provide
power to loads from utility.
| | **** All of Inverters:| When “ALL” is selected, parallel or 3-phase
system will continue working according to rule of “solar first” setting only
when all of inverters are connected to PV modules.
For example, two units are connected in parallel and set “SOL” in output
source priority. When selecting “ALL” in program 30, it’s necessary to have
all inverters connected to PV modules and PV input is normal to allow the
system to provide power to loads from solar and battery power. Otherwise, the
system will provide power to loads from utility.
---|---|---|---
Fault code display:
Fault Code| Fault Event|
Icon on
---|---|---
60| Power feedback protection|
71| Firmware version inconsistent|
72| Current sharing fault|
80| CAN fault|
81| Host loss|
82| Synchronization loss|
83| Battery voltage detected different|
84| AC input voltage and frequency detected different|
85| AC output current unbalance|
86| AC output mode setting is different|
8. Commissioning
Parallel in single phase
Step 1: Check the following requirements before commissioning:
- Correct wire connection
- Ensure all breakers in Line wires of load side are off and each Neutral wires of each unit are connected together.
Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each
unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program.
Otherwise, the setting can not be programmed.
Step 3: Turn on each unit.
NOTE: Master and slave units are randomly defined.
Step 4: Switch on all AC breakers of Line wires in AC input. It’s better
to have all inverters connect to utility at the same time. If not, it will
display fault 82 in following-order inverters. However, these inverters will
automatically restart. If detecting AC connection, they will work normally.
Step 5: If there is no more fault alarm, the parallel system is
completely installed.
Step 6 : Please switch on all breakers of Line wires in load side. This
system will start to provide power to the load.
Support two-phase equipment
Step 1 : Check the following requirements before commissioning:
- Correct wire connection
- Ensure all breakers in Line wires of load side are off and each Neutral wires of each unit are connected together.
Step 2 : Turn on all units and configure LCD program 28 as P1 and P2
sequentially. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program.
Otherwise, the setting can not be programmed.
Step 3: Turn on all units sequentially.
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and two phases are matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not work in line mode.
Step 5: If there is
no more fault alarm, the system to support 2-phase equipment is completely
installed.
Step 6: Please switch on all breakers of Line wires in load side. This
system will start to provide power to the load.
Support three-phase equipment
Step 1 : Check the following requirements before commissioning:
- Correct wire connection
- Ensure all breakers in Line wires of load side are off and each Neutral wires of each unit are connected together.
Step 2 : Turn on all units and configure LCD program 28 as P1, P2 and P3
sequentially. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program.
Otherwise, the setting can not be programmed.
Step 3: Turn on all units sequentially.
Step 4: Switch on
all AC breakers of Line wires in AC input. If AC connection is detected and
three phases are matched with unit setting, they will work normally.
Otherwise, the AC icon will flash and they will not work in line mode.
Step 5 : If there is no more fault alarm, the system to support 3-phase
equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This
system will start to provide power to the load.
Note 1: To avoid overload occurring, before turning on breakers in load
side, it’s better to have whole system in operation first.
Note 2: Transfer time for this operation exists. Power interruption may
happen to critical devices, which cannot bear transfer time.
9. Trouble shooting
Situation | Solution |
---|---|
Fault Code | Fault Event Description |
**** 60 | **** Current feedback into the inverter is detected. |
the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, make sure the sharing are connected
in all inverters.
For supporting three-phase system, make sure the sharing cables are connected
in the inverters in the same phase, and disconnected in the inverters in
different phases.
4. If the problem remains, please contact your installer.
71| The firmware version of each inverter is not the same.| 1.
Update all inverter firmware to the same version.
2. Check the version of each inverter via LCD setting and make sure the CPU
versions are same. If not, please contact your instraller to provide the
firmware to update.
3. After updating, if the problem still remains, please contact your
installer.
72| The output current of each inverter is different.| 1. Check if
sharing cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
80| CAN data loss| 1. Check if communication cables are connected well and
restart the inverter.
2. If the problem remains, please contact your installer.
81| Host data loss
82| Synchronization data loss
83| The battery voltage of each inverter is not the same.| 1.
Make sure all inverters share same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check battery
voltage of all inverters. If the values from all inverters are close, please
check if all battery cables are the same length and same material type.
Otherwise, please contact your installer to provide SOP to calibrate battery
voltage of each inverter.
3. If the problem still remains, please contact your installer.
84| AC input voltage and frequency are detected different.|
1.Check the utility wiring conncetion and restart the inverter.
2. Make sure utility starts up at same time. If there are breakers installed
between utility and inverters, please be sure all breakers can be turned on AC
input at same time.
3. If the problem remains, please contact your installer.
85| AC output current unbalance| 1.Restart the inverter.
2. Remove some excessive loads and re-check load information from LCD of
inverters. If the values are different, please check if AC input and output
cables are in the same length and material type.
3. If the problem remains, please contact your installer.
86| **** AC output mode setting is different.| 1. Switch off the
inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2, 3P3 or 2P1,
2P2 is set on #28.
For supporting two-phase system, make sure no “PAL” or 3P1, 3P2, 3P3 is set on
28.
For supporting three-phase system, make sure no “PAL” or 2P1, 2P2 is set on
28.
3. If the problem remains, please contact your installer.
1-800-831-9889
www.richsolar.com
support@richsolar.com
5550 Jurupa St, Ontario, CA 91761