SIEMENS PXC4.E16 Desigo Automation Stations Owner’s Manual

August 5, 2024
SIEMENS

SIEMENS PXC4.E16 Desigo Automation Stations

Specifications

  • Model: Desigo Automation Station PXC4.E16
  • Primary Use : Control of primary plants in HVAC and building control systems
  • Programming Interface: Graphical, freely programmable
  • Communication: BACnet/IP (BTL certified), BACnet Secure Connect, WLAN interface
  • Inputs/Outputs: 16 total (12 universal inputs/outputs, 4 relay outputs)
  • Power: AC or DC 24V
  • Mounting: Standard rails or wall mount

Product Usage Instructions

Installation:

  1. Mount the automation station on standard rails or a wall using appropriate fixtures.
  2. Connect the power supply (AC or DC 24V) to the station.
  3. If extending via I/O modules, connect them to the station as needed.

Programming:
The Desigo Automation Station is programmed using a graphical interface. Follow these steps:

  1. Access the programming interface either locally or via WLAN.
  2. Create and configure control logic for HVAC and building systems.
  3. Set up alarm, scheduling, and access protection functions as required.

Integration:
To integrate external devices and systems, follow these steps:

  1. Integrate data points and subsystems via Modbus RTU and/or Modbus TCP.
  2. Connect wired M-bus meters via RS485 level-converter.
  3. Connect KNX PL-Link devices for room control.

FAQ

  • What is the primary use of the Desigo Automation Station PXC4.E16?
    The primary use of this automation station is for the control of primary plants in HVAC and building control systems.

  • What communication protocols are supported by the automation station?
    The automation station supports BACnet/IP, BACnet Secure Connect, and WLAN interface for communication.

  • How many inputs/outputs does the PXC4.E16 have?
    The PXC4.E16 has a total of 16 inputs/outputs, including 12 universal inputs/outputs and 4 relay outputs.

For the control of primary plants

  • Compact automation station for HVAC and building control systems, freely programmable using graphical programming interface
  • BACnet/IP communication (BTL certified)
  • BACnet Secure Connect communication
  • 2-port Ethernet switch for low-cost cabling
  • 16 inputs/outputs: 12 universal inputs/outputs, 4 relay outputs Extendable via I/O modules TXM…
  • KNX PL-Link bus to connect RDG2..KN room thermostats, sensors, and operator units (including bus power)
  • Integration of M-bus energy meters via RS485 level-converter
  • Integration of Modbus data points via RTU and / or TCP
  • WLAN interface for engineering and commissioning
  • Operating voltage AC or DC 24 V
  • Mounted on standard rails or on the wall
  • Plug-in screw terminal blocks

Functions

Optimized, flexible automation station for HVAC and building automation and control systems

  • System functions (alarming, scheduling, trending, access protection with individually definable user profiles and categories)
  • Integrates data points and/or subsystems via Modbus RTU and/or Modbus TCP
  • Integration of wired M-bus meters via RS485 level-converter:
    • Offline and/or online engineering with ABT Site. No additional M-bus tool required
    • Primary and/or secondary device addressing
  • The following functions are available with KNX PL-Link bus:
    • Communication with RDG2..KN room thermostats, sensors, and operator units
    • Plug-and-play connection of Siemens field devices with KNX PL-Link
  • Engineering and commissioning with the ABT Site Tool using graphical function charts
  • Freely programmable. All function blocks, available in libraries, can be graphically connected.
  • BTL tested BACnet communication on IP (BACnet/IP or BACnet/SC), in compliance with the BACnet standard including B-BC profile (Rev. 1.16)
  • IT security including HTTPS, IEC-62443 4-2 (Security Level 2*), and BACnet Secure Connect
  • BACnet Secure Connect support as BACnet/SC node
  • Generic operation via embedded web interface
  • Cloud connectivity for remote access
  • 2-port Ethernet switch for low-cost cabling
  • WLAN interface for engineering and commissioning
  • Operating voltage AC 24 V or DC 24 V
  • Direct connection of field devices
  • DIN rail or screw mounting
  • Plug-in screw terminal blocks
  • For details about network and physical setup, refer to the Desigo Cybersecurity Guidelines.

Type summary

PXC4.E16 variants 1) PXC4.E16S PXC4.E16
Order number S55375-C108 S55375-C100
Number of inputs and outputs (Onboard) 16 16
Number of universal inputs and outputs (UIO) 12 12
Number of relay outputs (DO) 4 4
Number of inputs and outputs (Onboard + TXM) up to 40 up to 40

Number of integration data points

(M-bus + Modbus TCP + Modbus RTU)

| 0| up to 40
Total number TXM-I/Os and integration DPs| 40| 80 2)
Number of KNX PL-Link devices| 0| up to 64 2)
Number of configurable field level networks per RS485 (either for Modbus RTU or M-bus level converters with maximum of 250 meters each)| 0| 1
Number of M-bus meters wired via level converters (RS485) 3)| 0| up to 250
Number of BACnet/SC nodes connected to PXC4.E16/PXC4.E16S acting as hub| 0

(node only)

| 0

(node only)

  1. For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435.
  2. KNX PL-Link data points do not count as integration points. For KNX PL-Link, only the limits on BACnet objects are considered.
  3. The limitation is given by the maximum number of integration data points and maximum number of BACnet objects.

Onboard inputs and outputs

UIO| Universal inputs and outputs support the following signal types:

●       Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (375, 385), NTC 10k (Type II / Beta (0-50 °C) = 3892 K), NTC 100k

●       Resistance sensors 1000 Ohm, 2500 Ohm, 1000…1175 Ohm (for setpoint shift)

●       Voltage input analog DC 0…10 V

●       Current measurement analog DC 0…20 mA or 4…20 mA, (inputs U1, U2, U7, U8)

●       Binary potential-free contacts for signaling functions

●       Counter to 25 Hz (electronic switch to 100 Hz)

●       Analog outputs DC 0…10 V

---|---
DO| Relay outputs for binary controls, changeover contact (NO, NC, pulse)

Equipment combinations

TXM I/O modules

Description Type 1) Data sheet
Digital input module 8 or 16 I/O points TXM1.8D, TXM1.16D CM2N8172
Universal module without / with local operation and LCD TXM1.8U, TXM1.8U-ML

CM2N8173
Super universal module without / with local operation and LCD| TXM1.8X, TXM1 .8X-ML| CM2N8174
Relay module without / with local operation| TXM1.6R, TXM1.6R-M| CM2N8175
Resistance measuring module (for Pt100 4-wire)| TXM1.8P| CM2N8176
Triac module| TXM1.8T| CM2N8179
Digital input and relay module| TXM1.4D3R| CM2N8188
Power module| TXS1.12F10| CM2N8183
Bus connection module| TXS1.EF10| CM2N8183
Island bus extension module| TXA1.IBE| CM2N8184

Module series B and higher. In following use cases only series D can be used (available as of 2012):
I/O bus communication mode “Event”

KNX PL-Link devices

Description Type Data sheet
Wall-mounted temperature sensor QMX3.P30 CM2N1602
Wall-mounted temperature and humidity sensor QMX3.P40
Wall-mounted temperature, humidity, and CO2 sensor QMX3.P70
Wall-mounted temperature sensor and room operator unit QMX3.P34
Wall-mounted temperature and humidity sensor and room operator unit QMX3.P44
Wall-mounted temperature, humidity, and CO2 sensor and room operator unit

QMX3.P74
Wall-mounted temperature sensor and room operator unit| QMX2.P33| A6V10733768
Wall-mounted temperature and humidity sensor and room operator unit| QMX2.P43
Flush-mounted room sensors base and front modules:

●       Base module for temperature and / or humidity measurement 1)

●       Base module for CO2 measurement 1)

●       Front module for base module without sensor

●       Front module for base module with temperature sensor

●       Front module for base module with humidity and temperature sensor

●       Front module for base module with humidity, temperature sensor, and CO2 indicator LED

| ****

●       AQR2570

●       AQR2576

●       AQR2530NNW

●       AQR2532NNW

●       AQR2535NNW

●       AQR2535NNWQ

| CE1N1411
Passive infrared presence detector| UP 258D12| A6V10489489
Presence detector WIDE with temperature sensor| UP 258D31| A6V11894530
Presence detector WIDE with temperature and humidity sensor| UP 258D41
Presence detector WIDE with temperature, humidity, and CO2 sensor| UP 258D51
Presence detector WIDE with temperature sensor and ultrasound| UP 258D61
Room thermostat with temperature and humidity sensor| RDG200KN RDG260KN| A6V11545853
Room thermostat with temperature, humidity, and CO2 sensor| RDG204KN RDG264KN

Physical data points on the base module AQR257.. for use in HVAC functions:

  • 2 x Binary potential-free contacts (NO, NC)
  • 1 x Passive sensor NTC10K (Type II / Beta (0-50 °C) = 3892 K)
    For details see PXC4, PXC5 & PXC7 Planning overview A6V13054435 and data sheets.

Design Control Point

Description Type Data sheet
BACnet touch panels with integrated data storage and web server  

A6V11664137
functionality:| PXM30.E|
7.0 “| PXM40.E|
10.1 “| PXM50.E|
15.6 “|  |
TCP/IP client touch panels with data storage in web server PXG3.Wx00-2:|  | A6V11664139
7.0 “| PXM30-1|
10.1 “| PXM40-1|
15.6 “| PXM50-1|
BACnet/IP web server with standard functionality| PXG3.W100-2| A6V12304192
BACnet/IP web server with extended functionality| PXG3.W200-2|

System controller

Description Type Data sheet
System controller to integrate Modbus and MS/TP devices PXC5.E003

A6V11646020
 | PXC7| A6V12505052

Technical and mechanical design

The compact build allows for mounting the devices on a standard rail or a wall.

  1. Plastic housing
  2. Service button (identification in the network and WLAN on/off)
  3. LEDs for communication and state
  4. 2-port Ethernet switch with 2 LEDs per port for display purposes
  5. PXC4.E16: Plug-in terminal block with screw terminals KNX PL-Link
  6. Plug-in terminal block with screw terminals Power supply
  7. Plug-in terminal blocks with screw terminals Universal inputs/outputs, field device supply
  8. Connector for I/O modules TXM
  9. Plug-in terminal block with screw terminals Relay outputs
  10. PXC4.E16: Plug-in terminal block with screw terminals COM, M-bus, Modbus RTU
  11. PXC4.E16: DIP switch for bus termination and polarization COM
  12. Slider for mounting on DIN rails
  13. Eyelets for cable ties
  14. Holes for wall mounting
  15. Date / Series and Serial number
  16. QR code for default WLAN access Description see Technical data

LED displays

Product documentation

Related documents such as the environmental declarations, declarations of conformity, etc., can be downloaded from the following Internet address: www.siemens.com/bt/download

Notes

Safety
CAUTION

National safety regulations
Failure to comply with national safety regulations may result in personal injury and property damage.

  • Observe national provisions and comply with the appropriate safety regulations.

Mounting position and ambient temperature
The devices can be snapped onto standard rails or screwed onto a flat surface. Plug-in screw terminals connect power and interfaces.

Ambient temperature -5…50 °C (23…122 °F)| Ambient temperature -5…45 °C (23…113 °F)
---|---
●       Wall, horizontal

–    From left to right

–    From right to left

| ●       Overhead

●       Wall, vertically

–    From top to bottom

–    From bottom to top

●       On a horizontal surface

Installation

  • WARNING
    No internal line protection for supply lines to external consumers

    • Risk of fire and injury due to short-circuits
    • Adapt the line diameters as per local regulations to the rated value of the installed fuse.
  • WARNING
    The relay outputs may be connected to mains voltage
    Risk of electric shock! Incorrect installation of the device may lead to electric shock injuries when touching the device!

    • Install the device in a lockable cabinet or use terminal covers.
    • Do not install the device in locations where children are likely to be present.
    • Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.

Disposal
This symbol or any other national label indicate that the product, its packaging, and, where applicable, any batteries may not be disposed of as domestic waste. Delete all personal data and dispose of the item(s) at separate collection and recycling facilities in accordance with local and national legislation.
For additional details, refer to Siemens information on disposal.

Warranty

The application-specific technical data is guaranteed only in combination with the Siemens products listed in the ‘Device combinations’ section. If third- party products are used, any guarantee provided by Siemens will be invalidated.

Technical data

Power supply

Operating voltage (24 V~, ⏊, )| AC 24 V -15 / +20 % (PELV)

AC 24 V Class 2 (US) 48…63 Hz

---|---
Operating voltage DC 24 V (24 V≃, ⏊, )| DC 24 V -15 / +20 % (PELV)

DC 24 V Class 2 (US)

Functional ground (US) Functional earth| The terminal for the functional ground must be connected on the installation side with the building grounding system (PE).
Screw terminals for wire cross sections up to| Max. 2.5 mm2 (14 AWG)
Internal fusing| 4 A irreversible / non-replaceable
External supply line fusing (EU)| Non-renewable fuse max. 10 A slow-blow or

circuit breaker max. 13 A

Tripping characteristic B, C, D per EN 60898 or

Power supply with current limitation of max. 10 A

Protection| Reverse connection protection for DC 24 V

Power consumption (for transformer planning)

Operating voltage PXC4.E16S PXC4.E16
  AC 24 V DC 24 V
Full load 78 VA / 3.25 A 66 W / 2.75 A

Base load

PXC4.E16S: without loading by I/O modules TXM and field devices

PXC4.E16: without loading by I/O modules TXM, KNX PL-Link, and field devices

| 10 VA / 0.4 A| 6 W / 0.25 A| 10 VA / 0.4 A| 6 W / 0.25 A
Field device supply V+ (DC 24 V, 100 mA) (terminals 8 and 19)| 5 VA / 0.2 A| 3 W / 0.13 A| 5 VA / 0.2 A| 3 W / 0.13 A
Field device supply V≃ (terminals 18 and 29)| 48 VA / 2 A| 48 W / 2 A| 48 VA / 2 A| 48 W / 2 A
I/O modules TXM supply| 15 VA / 0.6 A| 8.5 W / 0.35 A| 15 VA / 0.6 A| 8.5 W / 0.35 A
KNX PL-Link supply|  |  | 4 VA / 0.17 A| 2.2 W / 0.09 A

Function data

Hardware information PXC4.E16, PXC4.E16S
Processor Texas Instruments AM335x, 300 MHz
Storage 128 MByte RAM

512 MByte Flash

Data backup in the event of power failure

Energy reserve (supercap) to support real-time clock (7 days).
Data available if stored to flash memory. Occurs every 5 minutes.

The interval of 5 minutes is only valid for change log but not for trending. In case of a power failure, trend log data can be lost up to 30 minutes.

Interfaces

Ethernet interface

Plug| 2 x RJ45, shielded
Interface type| 10Base-T / 100Base-TX, IEEE 802.3 compatible
Bit rate| 10/100 Mbps, autosensing
Protocol| BACnet/IP on UDP/IP, BACnet/SC on TCP/IP, and HTTPS on TCP/IP
Cabling (in-house cabling only), cable type| 10 Mbps: Min. CAT3, shielded cable is recommended 100 Mbps: Min. CAT5, shielded cable is recommended
Cable length| Max. 100 m (330 ft)
WLAN interface

Interface type| Wireless access point
Supported standards Frequency band WLAN channels

Maximum radio-frequency power

| IEEE 802.11b/g/n 2.4…2.462 GHz

1…11

16.4 dBm

Distance (unobstructed field)| Min. 5 m (16 ft)
Device pairing| Activation / deactivation with service button

Automatic switch off after 10 minutes if no WLAN-client is connected.

Optionally, for cyber security reasons, the WLAN can be permanently disabled via configuration.

Default SSID and WLAN password : Scan the QR code.

It will display something like WIFI:S:PXC4.E16_0000550;T:WPA;P: 1400052738 ;; Then SSID = PXC4.E16_0000550 and password = 1400052738

Determine manually: Use the information from the Date/Series/SN block It will display something like: Date/Series: 20190423A 0000550

S/N: 1400052738

SSID = _ and password = <S/N>

M-bus interface on COM interface (RS485)

Interface type| EIA-485, electrically isolated
Baud rate| 300, 600, 1200, 2400, 4800, 9600, 19200, 38400.

The maximum baud rate is depending on the configuration of M-bus S-devices (subordinate devices) and M-bus repeater.

Internal bus termination| 120 Ohm, switchable with DIP switch
Internal bus polarization| 270 Ohm pull-up/pull-down resistances, switchable with DIP switch
Cabling (in-house cabling only) Cable length| 3-wire cable, shielded cable recommended (shield must be connected to building earth in the mounting panel)

Max. 1000 m (3300 ft)

Protection| Short-circuit proof

Protection against faulty wiring with AC 24 V and DC 24 V

M-bus level converter including power supply (required)| Configuration examples (simple M-bus loads à 1.5 mA):

●       Up to 2 M-bus devices: STV Electronic, MPW-2 1

●       Up to 6 M-bus devices: STV Electronic, MPW-6 1

●       Up to 60 M-bus devices: Relay GmbH, PW60 1

1 For STV Electronic level converters, refer to https://www.stv- electronic.de/. For Relay GmbH level converters, refer to https://www.relay.de/.
The use of these products is a recommendation only. Siemens cannot guarantee functionality nor take over any warranty for third-party products. This information is subject to change without notice.

KNX PL-Link interface

Type| KNX TP1 PL-Link, galvanic isolation Baud rate: 9.6 kbps
Cabling (in-house cabling only)

Cable length

| 2-wire cable, 0.75 mm2 / AWG20 or 1 mm2 / AWG18

With internal supply: Max. 80 m (262 ft) With external supply: Max. 1000 m (3300 ft)

Internal bus power| Max. 50 mA

When using external bus power for KNX PL-Link, switch off the internal bus power via the ABT Site Tool.

I/O modules TXM bus interface

Nominal voltage| DC 24 V
Supply current for I/O modules TXM| Max. 300 mA
Connectable in parallel with DC 24 V power supply module TXS1.12F4| For details, see: TX-I/O- engineering and installation, CM110562
Protection| Short-circuit proof
TXM I/O module plug: No protection against faulty wiring with AC 24 V| No electric protection. Use cover
Field device supply (I/O module TXM)

AC 24 V output current (terminal V~ on the TXM module)| Max. 2 A, short- circuit proof 1)

If PXC4.E16 is powered by DC voltage, the field device supply on terminal V~ of the TXM modules is also DC voltage.

Sum of onboard V~ and TXM module V~ current is max. 2 A.

Field device supply (Onboard)

AC 24 V output current (terminal V≃)| Max. 2 A, short-circuit proof 1)

If PXC4.E16 is powered by DC voltage, the field device supply on terminal V≃ is also DC voltage.

DC 24 V output current (terminal V+)| Max. 100 mA, short-circuit proof, protected against incorrect wiring with AC 24 V

Sum of onboard V~ and TXM module V~ current is max. 2 A.

Screw terminals, plug-in

Cu-wire or Cu-strand with wire end sleeve| 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)

or 2 x 0.6 mm ∅ to 1.0 mm2 (22 to 18 AWG)

Cu-strand without wire end sleeve| 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)

or 2 x 0.6 mm ∅ to 1.5 mm2 (22 to 16 AWG)

Stripping length| 6…7.5 mm (0.24. 0.29 in)
Screwdriver| Slot screws, screwdriver size 1 with shaft ø = 3 mm
Max. tightening torque| 0.6 Nm (0.44 lb ft)

On PXC4.E16

Modbus RTU interface

Interface type| EIA-485, electrically isolated
Baud rate| 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,

57600, 76800, 115200 (depending on the configuration)

Internal bus termination| 120 Ohm, switchable with DIP switch
Internal bus polarization| 270 Ohm pull-up/pull-down resistances, switchable with DIP switch
Cabling (in-house cabling only) Cable length| 3-wire cable, shielded cable recommended (shield must be connected to building earth in the mounting panel)

Max. 1000 m (3300 ft)

Protection| Short-circuit proof

Protection against faulty wiring with AC 24 V and DC 24 V

Inputs

12 universal inputs / outputs U1…U12 with the following input functions (16-bit AD converter):

Temperature measurement, analog|
---|---
Type| Range (over range)| Resolution|
AI NTC10K (Type II / Beta (0-50 °C) = 3892 K)| -40…115 °C (-52.5…155 °C)| 10 mK (25 °C)|
 | -48…239 °F (-62.5…311 °F)| 0.018 °F|
AI NTC100K| -40…125 °C (-52.5…155 °C)|  |
 | -48…257 °F (-62.5…311 °F)|  |
AI PT1K 385 (EU) 1)| -50…600 °C (-52.5…610 °C)| 20 mK|
 | -58…1112 °F (-62.5…1130 °F)| 0.036 °F|
AI PT1K 375 (NA) 1)| -50…180 °C (-52.5…185 °C)| 10 mK|
-58…356 °F (-62.5…365 °F)| 0.018 °F|
AI (LG-)Ni1000 1)|
AI 2x (LG-)Ni1000 1)|  |  |

A fixed value of 1 Ω is calibrated to correct line resistance.

Resistance sensor, analog

Type| Range (over range)| Resolution
AI 1000 Ohm 1)| 0…1000 Ω (0…1050 Ω)| 0.1 Ω
AI 2500 Ohm 1)| 0…2500 Ω (0…2650 Ω)| 0.1 Ω
AI Pt1000 1)| 0…2500 Ω (0…2650 Ω)| 0.1 Ω
AI 1000-1175 Ohm 1) for setpoint shift| 1000…1175 Ω (900…1295 Ω)| 0.1 Ω

A fixed value of 1 Ω is calibrated to correct line resistance.

Voltage measurement, analog

Type| Range (over range)| Resolution
AI 0-10 V| 0…10 V (-1.5. 11.5 V)| 1 mV
AI 0-10 V standard| 0…100% (-10…110%)| 0.01%
Open connection: Negative voltage -1.5 V (line failure detection)
Current measurement, analog (only inputs U1, U2, U7, U8)

Type| Range (over range)| Resolution| Load
AI 4-20 mA| 4…20 mA (1.6. 22.4 mA)| 1 µA| 440 / 490 Ω
AI 0-20 mA| 0…20 mA (-3…23 mA)| 1 µA| 440 / 490 Ω
Digital input

Contact query voltage| 21.5…25 V
Contact query current| 1 mA; 6 mA initial current
Contact resistance for closed contacts| Max. 200 Ω
Contact resistance for open contacts| Min. 50 kΩ
Counter memory (counter inputs| 0…… 4.3 x 109 (32-bit counter)
 | Min. closing/operating time [ms] including bounces| Of which

Max. bounce time [ms]

| Max. counter frequency (symmetrical)
BI NO / BI NC| 60| 20|
BI Pulse NO| 30| 10|
CI Mech (25 Hz)| 20| 10| 25 Hz
CI El (100 Hz)| 5| 0| 100 Hz

Outputs

12 universal inputs / outputs U1…U12 with the following output functions (10-bit DA converter):

Voltage output, analog

Type| Range (over range)| Resolution| Output current
AO 0-10 V| 0…10 V (-0.05…10.6 V)| 1 mV| Max. 1 mA
AO 0-10 V| 0…100%| 0.01 %| Max. 1 mA
standard| 0% = 0 V, 100% = 10 V|  |
 | (-0.05. 10.6 V)|  |
Relay output (outputs DO1…DO4)

External supply line fusing

Non-renewable fuse Circuit breakers

|

Max. 10 A, slow

Max. 13 A, characteristic B, C, D as per EN 60898

Switching voltage AC/DC| Max. AC 250 V / DC 30 V Min. AC/DC 12 V
Current load AC| NO contact: Max. 4 A resistive, 3 A inductive (cos phi 0.6)

NC contact: max. 2 A resistive, 1.5 A inductive (cos phi 0.6)

Min. 1 mA at AC 250 V Min. 10 mA at AC 12 V

Current on make AC| NO contact: Max. 10 A (1 s) NC contact: Max. 3 A (1 s)
Current load DC| NO contact: Max. 3 A resistive at DC 30 V NC contact: Max. 1 A resistive at DC 30 V Min. 10 mA resistive at DC 12 V
Response / release time| 7 ms / 3 ms typical
Contact life at AC 250 V (reference values) At 0.3 A resistive

NO contact at 3 A resistive

NC contact at 2 A resistive

Reduction factor for inductive load (cos phi = 0.6)

|

5 x 105 switching cycles

1 x 105 switching cycles

1 x 105 switching cycles

0.6

Insulating strength between relay contacts and system electronics (reinforced insulation).| AC 3750 V, as per EN 60730-1

CAUTION
No overvoltage protection is used when switching inductive loads

  • Risk of heavy electromagnetic disturbances and lower contact life when no overvoltage protection is used when switching inductive loads.
  • When switching inductive loads (e.g. contactors or electric motors) it is strongly recommended to use suitable overvoltage protection devices to avoid heavy electromagnetic disturbances and to ensure the specified contact life.

Conformity

Ambient conditions and protection classification

Classification as per EN 60730 Automatic action

Control function Pollution degree

Overvoltage category

| ****

Type 1 Class A 2

III

Protection against electric shock| Suitable for use in protection class I or II systems
Protection degree of housing to EN 60529 Front parts in DIN cut-out

Terminal part

| ****

IP30 IP20

Climatic ambient conditions

●       Storage / Transport (packaged for transport) as per IEC EN 60721-3-1 / IEC EN 60721‑3‑2


●       Operation as per IEC/EN 60721-3-3

| ****

●       Class 1K22 / 2K12

Temperature -25…70 °C (-13…158 °F)

Air humidity 5…95 % (non-condensing)

●       Class 3K23

Operation in enclosed dry locations, having no temperature or humidity control

Temperature -5…50 °C (23…122 °F)

(for details see chapter Mounting)

Air humidity 5…95 % (non-condensing)

Mechanical ambient conditions

●       Transport per IEC/EN 60721-3-2

●       Operation as per IEC/EN 60721-3-3

| ****

●       Class 2M4

●       Class 3M11

Standards, directives, and approvals

Product standard| IEC/EN 60730-1
Product family standards| IEC/EN 63044-x
Electromagnetic compatibility (EMC)| For residential, commercial, and industrial environments
EU conformity (CE)| See CE declaration 1)
EAC conformity| Eurasian compliance
RCM conformity| See RCM declaration 1)
UL/cUL certification (US / Canada)| UL916, http://ul.com/database

UL94, housing material meets classification V-0 2)

CSA certification| C22.2, http://csagroup.org/services- industries/product- listing
FCC| CFR 47 Part 15C
BACnet| Profile: B-BC Revision: 1.16

Detailed information on BACnet certificates, BTL listings, and PICS can be found on the BACnet website (filtered for Siemens products)

AMEV profile (BACnet 2017)| AS-A / AS-B
KBOB profile (BACnet 2017)| AS-CH 3)
Environmental compatibility 1)| The product environmental declaration 1) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
OSHPD seismic certification| Product meets OSHPD Special Seismic Certification Preapproval (OSH-0217) under California Building Code 2022 (CBC 2022)4)

  • Documents can be downloaded at www.siemens.com/bt/download.
  • Material level
  • AS-CH pending
  • When installed within the following Siemens enclosures: PXA-ENC18, PXA-ENC19, or PXA-ENC34.

European Union conformity

Contact for regulatory topics: (EU) Siemens AG, Berliner Ring 23, DE-76437 Rastatt

FCC Statement

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation

FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland Ltd. could void user authority to operate the equipment. United States representative https://new.siemens.com/us/en/products/buildingtechnologies/home.html

Industry Canada statement
This device complies with ISED’s license-exempt RSSs. Operation is subject to the following two conditions:

  1. This device may not cause interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

Radiofrequency radiation exposure statement
This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20 cm between the radiator and your body.
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.

Housing

Color top / bottom 2003 Ti-Grey / 804 Black
Dimensions per DIN 43880, see Dimensions
Weight without / with packaging 483 g / 553 g

Connection terminals

Wiring lines for field devices

  • Wiring length max. 300 m (1,000 ft), CU wire or CU strand. Cross-section depending on the signal
  • 30 m (100 ft) applies for signal types AI NTC10K and AI NTC100K or 300 m (984 ft) with shielding
Examples of connection diagrams for universal inputs/outputs

Digital inputs

Count inputs:
Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in the same cable duct, must be shielded.

Analog inputs

Analog outputs

Dimensions