GREENHECK XG-TH Single Duct Vav Atu Instruction Manual

July 30, 2024
GREENHECK

GREENHECK XG-TH Single Duct Vav Atu

Product Information

Specifications:

  • Model: XG-TH, XG-TL, XG-BP
  • Type: Single Duct VAV Terminals
  • Document: 1041402
  • Product Type: Single Duct VAV ATU

Product Usage Instructions

  1. Safety Information:
    Only qualified personnel should install the unit. Be aware of general safety precautions to prevent hazards.

  2. Installation:
    Follow these steps for proper installation of the Single Duct VAV Terminals:

  3. Ensure qualified personnel are handling the installation.

  4. Ground the unit securely.

  5. Verify compatibility of the power source with the equipment.

  6. Transport, store, install, and operate the equipment only in its designated environment.

  7. Troubleshooting:
    If you encounter any issues with the product, refer to the troubleshooting section in the manual for guidance on resolving common problems.

FAQ:

Q: What should I do if I find shipping damage on the Single Duct Air Terminals?
A: If any shipping damage is found, report it immediately to the delivery carrier.

Installation, Operation, and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate, or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.

General Safety Information

Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. If more information is needed, contact a licensed professional engineer before moving forward.

  1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Association (NFPA), and the Canadian Electrical Code (CEC), where applicable.
  2. The unit must be securely and adequately grounded.
  3. Verify that the power source is compatible with the equipment.
  4. Electrical equipment should be transported, stored, installed, and operated only in the environment for which it is designed.

DANGER
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.

WARNING
Always disconnect power before working on or near a unit. Use appropriate lockout tagout procedures to prevent accidental power-ups.

NOTICE:
This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

Receiving Inspection and Hanging/Installation Requirements

  • Before removing the shipping materials, visually inspect the packing materials. There should be a black plastic strip wrapped in the clear plastic stretch wrap. If this black plastic strip is missing, the shipment may have been repacked by the shipper and you should make a note of this on the shipping documents and inform the delivering carrier. If any damage or other concerns are present, make a note of this on the shipping documents and inform the delivery carrier.
  • After unpacking the Single Duct Air Terminals, check for shipping damage. If any shipping damage is found, report it immediately to the delivery carrier.
  • Always store the product in a clean dry location before installation.
  • Units with controls are not recommended for use in ambient temperatures greater than 95ºF. For protection of controls, do not store in temperatures above 135ºF.

General Model Number Code

The model number code provides basic identification of the unit.

Installation

CAUTION: HAZARD OF EQUIPMENT DAMAGE
Do not use the flow sensor, connecting tubing, or damper shaft as a lift point. Damage to the components may result.

NOTICE:
The unit is not recommended for installation above 2,000 m.

Unless local building codes require hangers, the smaller size basic Single Duct Air Terminals may be light enough to be supported by the ductwork itself. However, when accessory components such as controls, hot water reheat coils, sound attenuators, or electric reheat are included, the single duct terminal should be supported directly with straps screwed into the side of the terminal. (See Figure 1)

Alternate trapeze hangers or the method prescribed for the rectangular duct on the job specification may be used. (See Figure 2)

Single Duct Air Terminals may also be suspended with factory-supplied and field-installed hanger brackets and field-supplied and installed hanger rods. (See Figure 3)

Single Duct Terminal Units are not designed nor suitable for outdoor use. In advance of start-up, verify all electrical connections are tight and that the correct voltage is supplied to the Single Duct Terminal Unit per the rated voltage listed on the unit label. If factory-supplied controls are present, review all wiring diagrams to ensure complete working knowledge.

IMPORTANT
If equipped with pneumatic controls, the orientation of the Single Duct Air Terminal unit is critical. The pneumatic controls must be mounted right side up. The Single Duct Terminal must be level within + or – 10 degrees of horizontal, both parallel to the airflow and at the right angle of airflow. The control side of the single-duct terminal is labeled with an arrow indicating up. Unless otherwise noted, most electric, analog electronic, and digital controls are not position sensitive and may be installed in any orientation.

MINIMUM CLEARANCE FOR ACCESS
Single Duct Air Terminals require sufficient space to allow servicing of the controls and electric reheat power hookup (if applicable). Horizontal clearance requirements are dependent upon access panel dimensions which are indicated on the appropriate submittal. For control panel access, a minimum of 18” is recommended. See the appropriate submittal for the control panel location.

CAUTION
These clearance recommendations are not meant to preclude NEC requirements or local building codes that may be applicable, which are the responsibility of the installing contractor.

CONNECTING DUCT WORK

NOTICE:
Do not insert duct work inside the inlet collar of the Single Duct Air Terminal. The inlet duct should be installed according to SMACNA guidelines.

  1. Slip each inlet duct over the inlet collar of the Single Duct Air Terminal.
  2. Fasten and seal the connection by the method prescribed by the job specification.
  3. The diameter of the inlet duct in inches must be equal to the listed size of the Single Duct Air Terminal; e.g., a duct that measures 8 inches must be fitted to a size 8-inch Single Duct Air Terminal. The inlet tube of the Single Duct Air Terminal is manufactured 1/8” smaller than the listed size to fit inside the duct.
  4. If an inlet airflow sensor is installed, it is recommended the installer provide a minimum of 3 duct diameters of the straight duct at the Single Duct Air Terminal inlet.
  5. The outlet end of the Single Duct Air Terminal is designed for use with slip and drive duct connections (flanged outlets optional).
  6. A rectangular duct the size of the Air Terminal outlet should be attached. (Refer to the submittal for the correct size.)

FIELD ELECTRICAL WIRING

DANGER
High high-voltage electrical supply is needed for this equipment. The control cabinet contains live electrical parts. Contacting these parts with power applied may cause serious injury or even death. This work should only be performed by a qualified electrician.

  • All field wiring must comply with local building codes and NEC. (ANSI/NFPA 70).
  • When applicable, electrical control and piping diagrams are attached to the inside of the control enclosure cover of the Single Duct Air Terminal.
  • Use copper-only conductors with insulation rated 75ºC.
  • The Single Duct Air Terminal must be properly grounded per NEC 424-14 and 250.
  • Always check product labels for voltage and current data to determine the proper wire size and over-current protection.
  • The control panel cover must be closed or in place before applying electric power to the Single Duct  Air Terminal.
  • These recommendations are not meant to preclude NEC requirements or other applicable local building codes and are the sole responsibility of the installing contractor.

NOTICE:
If the unit is not ordered with an internal disconnecting device then a disconnection device that shall disconnect all phases must be provided by the customer and incorporated in the fixed wiring.

SINGLE DUCT AIR TERMINALS WITH ELECTRICAL REHEAT

WARNING
Single Duct Air Terminals must not be operated without downstream ductwork in place. Failure to have downstream ductwork installed will expose the line voltages and high temperature present in the operating heater elements. Contact with these heater elements may cause serious injury or death.

  • Before installation always inspect the electric heating coils for damage.
  • All electric reheat is balanced by kW per stage.
  • The installing electrician should rotate the electric reheat stages by phase to balance the building’s electrical load.
  • The “UP” arrow orientation must be followed to prevent nuisance tripping or overheating which will cause damage to the electric heater and or building.

SINGLE DUCT AIR TERMINALS WITH HOT WATER COILS

CAUTION:

HAZARD OF EQUIPMENT DAMAGE
The copper tubing should not be used as lift points. Always inspect the hot water coils for damage before installing the Single Duct Air Terminal.

  • The hot water coil casing must be field insulated.
  • The hot water coils do not have drip pans and are not suitable for use as cooling coils.
  • The hot water coil maximum water operating temperature is 195°F.
  • The hot water coils are leak tested to 300 psi, with a minimum burst pressure of 2000 psi at ambient temperature.

CONTROLS

NOTICE:
Single Duct Air Terminals with digital controls, if factory programmed, incorporate specific communication addresses. Installing the Single Duct Air Terminal in a different location than noted on the Single Duct Air Terminal label and building plans may result in excessive start-up labor and is the sole responsibility of the contractor. For information on controls provided by other manufacturers and installed on the Air Terminals, contact the local branch or dealer.

INLET FLOW SENSOR
Single Duct Air Terminals are shipped with factory-installed (where applicable) pressure differential inlet flow sensors in the primary inlet. See Figure 4 for the calibration curve and K factors. Bypass Air Terminals offer an optional downstream flow sensor for field installation a minimum of 3 feet downstream of
box discharge.

Troubleshooting

Investigating Noise Complaints

  • Noise from a Single Duct Air Terminal can be due to a variety of conditions and can be difficult to eliminate.
  • The first step is to isolate the type, source, and direction.
  • Generally, noise heard at the air outlet is considered a discharge type.
  • Noise heard through the ceiling is considered radiated noise.
  • For detailed information concerning noise transmission in buildings, refer to AHRI Standard 885- 2008, “Procedure for estimating occupied space sound levels in the application of air terminals and air outlets”.

Discharge Noise

  • This is usually caused by high static pressure or little to no internal duct lining downstream of the Air Terminal.
  • It can sometimes be caused by the air outlet itself.
  • Air outlet-generated sounds can be reduced by reducing flow or increasing an outlet size.
  • Reducing static pressure, and flow or adding additional downstream attenuation materials will reduce discharge sounds from the Air Terminal.

Radiated Noise

  • Radiated noise is most commonly associated with Fan Powered Terminals.

Electric Duct Heater

CAUTION

  • Use extreme care if testing the electric heater with power on.
  • The control cabinet contains live electrical parts. Contacting these parts with the power applied may cause serious injury or death.
  • This unit should be serviced by a licensed electrician or a similarly qualified electrical service technician.

If the electric heater does not operate:

  • Check the electric power in the unit and verify the input power agrees with the label data.
  • Verify the Air Terminal is installed properly (according to the airflow orientation).
  • Review the wiring diagram attached to the inside of the control enclosure cover to verify the field wiring is correct with proper gauge wire, overcurrent protection and properly grounded.

If the electric heater cycles on and off:

  • Verify the airflow is uniformly distributed across the face of the heater elements.
  • Check for obstructions in the duct or insufficient airflow. (70 cfm per kW required)

If conditioned space fails to warm up:

  • Verify the electric heater controls and thermostat are compatible and wired properly.
  • Relocate the room thermostat if it is located in a position that is too warm.

If condition space overheats:

  • Verify the electric heater controls and room thermostat are compatible and wired properly.
  • Relocate the room thermostat if it is located in a position that is too cold.
  • Verify the air distribution to the space is appropriate for the required thermal load.

Specific Electric Heater Troubleshooting Procedures:

PROBLEM: Heater Does Not Energize


Cause|

Solution

Power not properly connected to the heater| 1. With a voltmeter, check the power wiring terminals to ensure the proper voltage is available to the heater element side of the power terminal block or to the field side of the disconnect switch, power fusing, or circuit breaker.

2. If proper voltage is not present, check the terminal studs for proper wiring and check the power source for power.

Disconnect switch, toggle switch or circuit breaker are set to OFF position| 1. Set the disconnect switch, toggle switch, or circuit breaker to the ON position.
Power fuses are blown or the circuit breaker is tripped| 1. Replace fuse(s) with the same type and amperage as those provided with the heater from the manufacturer or reset the circuit breaker by first setting the circuit breaker to the OFF position and then resetting it to the ON position.

2. With an ammeter, check the amp draw on the power lines.

3. For heaters with fusing, the amp draw should not exceed the fuse amperage.

4. Amp draw should not exceed the circuit breaker rated value.

5. If the amp draw is excessive, check the power supply as described above for power voltage.

6. If fuses blow or circuit breaker trips again, check for a short.

7. If no short is present and the power supply wiring/voltage is correct, contact the factory for further assistance.

The manual reset safety switch has tripped| 1. Push the reset safety button on the back of the safety reset. The manual safety reset is located inside the control enclosure cover near the bottom of the heater element header.
The airflow/static switch is not engaging| 1. Jump out the airflow/static switch by connecting the lead attached to the normally open terminal to the normally closed terminal.

2. If the heater starts operating, two conditions could exist.

A. The airflow/static switch may be defective.

B. There is insufficient airflow to make the switch.

3. To verify available static pressure, disconnect the pneumatic tubing from the HI side of the airflow/static switch and connect to a Magnehelic gauge.

4. Available static pressure should be 0.05 in. wg +/- 0.03 in. wg to be safe.

5. If available static pressure is in a dead band, between the two ranges, the airflow/static switch will not engage and could cause chattering of the contacts. Some methods must be devised to increase the available static pressure.

6. If sufficient static pressure is available, check to ensure the pneumatic tubing is connected to the correct port (HI) on the airflow/static switch.

The Automatic Safety Reset Switch is bad| 1. Allow the duct temperature to cool down below 90ºF.

2. If the heater still does not energize, jump out the automatic safety reset switch.

3. If the heater now energizes, contact the factory for a replacement automatic safety reset switch.

---|---
Manual Safety Reset Switch is bad| 1. Allow the duct temperature to cool down below 90ºF.

2. If the heater still does not energize, perform the following:

A.   On heaters with the manual safety reset switch connected to the backup contact circuit, jump out the manual safety reset switch.

B.   If the backup contactor now engages, contact the factory for a replacement manual safety reset switch.

C.   If the backup contactor fails to engage, there is a problem with the backup contactor holding coil.

D.   Use an ohmmeter to check the continuity of the holding coil on the backup contactor.

E.   If bad, contact the factory for a replacement backup contractor.

Insufficient airflow across the electric heating elements| 1. The minimum allowable airflow across the heating elements is 70 cfm/kW.

2. Unless this recommended minimum airflow is met, the leaving air temperature of the heater will be greater than the safety reset switch limits. This will cause nuisance tripping of the safety reset switch.

3. Reset the minimum airflow across the heating elements during a call for heat at 70 cfm/kW.

WARNING
On all troubleshooting that requires working inside the heater casing, disconnect the power first! Jumpers used for diagnostic purposes should be removed before returning the heater to normal operation.

Figure 4 – Multi-Quadrant Averaging Flow Sensor

MODEL INLET SIZE K FACTOR

XG-TH, XG-FCI, XG-FCQ

XG-FVI, XG-DD XG-DH, XG-BP XG-RT, XG-RA XG-TL (4 to 10)

XG-FCl C2 (4 to 8)

XG-FVL C2 (4 to 8)

| 04 Rnd| 300
05 Rnd| 375
06 Rnd| 540
07 Rnd| 760
08 Rnd| 990
09 Rnd| 1250
10 Rnd| 1640
12 Rnd| 2350
14 Rnd| 3250
16 Rnd| 4100
XG-TL (12)| 12 Flat Oval| 2270
XG- TL (14) & XG-FVL C6| 14 Flat Oval| 2850
XG- TL (16)| 16 Flat Oval| 3550
XG-FVL C4| 14×8 Rect| 2450
XG-FCl C4| 16×8 Rect| 2770
XG-FCI, XG-FCQ, & XG-FVI C7| 18×16 Rect| 6200
XG-TH 20| 20×16 Rect| 6430
XG-TH 24| 24×16 Rect| 7270

Note:
K-factor is the calibration flow constant at 1 in. wg delta P.

Our Commitment

  • As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
  • Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.

Contact Information

Copyright 2023 © Greenheck Fan Corporation.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals