GREENHECK AFL-601 Flush Mount Instructions

June 1, 2024
GREENHECK

Table of Contents

AFL-601
AMCA 540 and 550 Listed Hurricane Louver
FEMA Louver, Chevron Blade
Aluminum, Wind-Driven Rain
UL Classified R25119

AFL-601 Flush Mount

The AFL-601 is a UL Classified Wind-Storm Rated Assembly in accordance with FEMA Guidelines P-320 and P-361, and ICC 500 (2020 & 2023) to static and cyclical design pressures of positive/ negative 350 PSF and debris impact of a 15 lb sawn lumber 2×4  traveling at 100 MPH (6.8 kg at 44.7 m/s).

Options and Accessories

  • Head and Sill Mounting Configuration
  • Bird Screen
  • Cosmetic Front Flange
  • Extended Sill
  • Flange Frame
  • Insect Screen
  • Variety of Architectural Finishes

Standard Details and IOMs

AFL-601 Standard Details
[Flush Mount (IOM

486736)](https://content.greenheck.com/public/DAMProd/Original/10019/486736_AFL601FlushMount_iom.pdf)

Structural reinforcing members may be required to adequately support and install multiple louver sections within a large opening. Structural reinforcing members along with any associated installation hardware is not provided by Greenheck unless indicated  otherwise by Greenheck.

Standard Construction

Frame| Heavy gauge extruded 6005-T5 aluminum, 6 in. (152 mm) x 0.188 in. (5 mm) nominal wall thickness
---|---
Blades| Front: Chevron design, heavy gauge extruded 6005-T5 aluminum, 0.188 in. (5 mm) nominal wall thickness, positioned 45º on approximately 1.625 in. (41 mm) centers
Back: Vertical rain resistant style design, heavy gauge extruded 6005-T5 aluminum, 0.07 in. (2 mm)  nominal wall thickness, positioned on approximately 0.875 in. (22 mm) centers
Louver Depth| 6 in. (152 mm)
Finish| Mill
Mounting| Channel Frame Recessed/Flush
Mounting Angles| Continuous angles along the jambs, or head and sill, with mounting holes
Minimum Section Size| 12 in. W x 12 in. H
(305 mm W x 305 mm H)
Maximum Single Section Size| 48 in. W x 96 in. H
(1219 mm W x 2438 mm H)
Maximum Opening Width| Unlimited, larger openings may be configured of multiple louver panels without additional structural reinforcing when configured as head and sill mount
Approx. Weight| 15 PSF (0.7 kPa), integral lifting lugs included
Wind Load| +/-350 PSF (16.8 kPa) ASD

Performance Ratings

Greenheck Fan Corporation certifies that the AFL-601 recessed/flush frame louver shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the  requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to Water Penetration, Air Performance, and WindDriven Rain ratings.

https://l.ead.me/bd0hEe

Louvers were tested in accordance with AMCA Standard 500-L.

Performance of 48 in. x 48 in. (1219 mm x 1219 mm) Louver

Free Area
Area 6.97 sq. ft. (0.648 sq. m)
Percent 43.6%
Performance at Beginning Point of Water Penetration
Free Area Velocity above 1250 fpm (6.35 m/s)
Max Intake Volume 8713 cfm (4.11 m³/s)
Performance at 6,000 CFM (2.832 m³/s) Intake
Pressure Drop 0.327 in. wg (0.081 kPa)

Free Area Chart

Free Area Chart shows free area in square feet and square meters.

| Width
---|---
Height| Recessed/| 12| 18| 24| 30| 36| 42| 48
Flush Frame| | | | | | |
Actual Size| 0.30| 0.46| 0.61| 0.76| 0.91| 1.07| 1.22
12| 0.13| 0.24| 0.36| 0.48| 0.60| 0.72| 0.84
0.30| 0.01| 0.02| 0.03| 0.04| 0.06| 0.07| 0.08
18| 0.29| 0.52| 0.79| 1.06| 1.33| 1.60| 1.86
0.46| 0.03| 0.05| 0.07| 0.10| 0.12| 0.15| 0.17
24| 0.45| 0.79| 1.20| 1.61| 2.02| 2.42| 2.83
0.61| 0.04| 0.07| 0.11| 0.15| 0.19| 0.22| 0.26
30| 0.62| 1.10| 1.66| 2.22| 2.78| 3.35| 3.91
0.76| 0.06| 0.10| 0.15| 0.21| 0.26| 0.31| 0.36
36| 0.78| 1.39| 2.11| 2.82| 3.54| 4.25| 4.96
0.91| 0.07| 0.13| 0.20| 0.26| 0.33| 0.39| 0.46
42| 0.93| 1.67| 2.52| 3.37| 4.22| 5.08| 5.93
1.07| 0.09| 0.16| 0.23| 0.31| 0.39| 0.47| 0.55
48| 1.10| 1.96| 2.96| 3.96| 4.97| 5.97| 6.97
1.22| 0.10| 0.18| 0.27| 0.37| 0.46| 0.55| 0.65
54| 1.27| 2.26| 3.42| 4.58| 5.74| 6.90| 8.06
1.37| 0.12| 0.21| 0.32| 0.43| 0.53| 0.64| 0.75
60| 1.42| 2.54| 3.83| 5.13| 6.43| 7.73| 9.03
1.52| 0.13| 0.24| 0.36| 0.48| 0.60| 0.72| 0.84
66| 1.58| 2.82| 4.26| 5.70| 7.15| 8.59| 10.03
1.68| 0.15| 0.26| 0.40| 0.53| 0.66| 0.80| 0.93
72| 1.76| 3.13| 4.73| 6.34| 7.94| 9.54| 11.15
1.83| 0.16| 0.29| 0.44| 0.59| 0.74| 0.89| 1.04
78| 1.91| 3.41| 5.15| 6.90| 8.64| 10.38| 12.13
1.98| 0.18| 0.32| 0.48| 0.64| 0.80| 0.96| 1.13
84| 2.06| 3.68| 5.56| 7.45| 9.33| 11.22| 13.10
2.13| 0.19| 0.34| 0.52| 0.69| 0.87| 1.04| 1.22
90| 2.24| 3.99| 6.03| 8.08| 10.12| 12.17| 14.21
2.29| 0.21| 0.37| 0.56| 0.75| 0.94| 1.13| 1.32
96| 2.40| 4.28| 6.47| 8.66| 10.85| 13.04| 15.23
2.44| 0.22| 0.40| 0.60| 0.80| 1.01| 1.21| 1.41

Greenheck Fan Corporation certifies that the AFL-601 recessed/flush frame louver shown herein is approved to bear the AMCA Listing Label. The ratings shown are based on tests and procedures performed in accordance with AMCA Publications and comply  with the requirements of the AMCA Listing Label Program. The AMCA Listing Label applies to Wind Borne Debris Impact Resistant louvers rated for Enhanced Protection with a minimum blade span of less than 12 in. (305 mm) and a maximum unsupported  blade span of 48 in.
(1219 mm) and to High Velocity Wind-Driven Rain Resistant Louvers tested in the fully open position that permits airflow through the louver.

www.AMCA.org

Document Links
Louver Finishes & Colors
Louver Product Selection Guide
Louver Warranty Statement

Core Area Chart

Core Area Chart shows core area in square feet and square meters.

| Width
---|---
Height| Recessed/| 12| 18| 24| 30| 36| 42| 48
Flush Frame| | | | | | |
Actual Size| 0.30| 0.46| 0.61| 0.76| 0.91| 1.07| 1.22
12| 0.13| 0.80| 1.15| 1.49| 1.83| 2.18| 2.52
0.30| 0.01| 0.07| 0.11| 0.14| 0.17| 0.20| 0.23
12.5| 0.17| 0.85| 1.22| 1.58| 1.94| 2.31| 2.67
0.32| 0.02| 0.08| 0.11| 0.15| 0.18| 0.21| 0.25
18| 0.29| 1.39| 1.98| 2.57| 3.17| 3.76| 4.35
0.46| 0.03| 0.13| 0.18| 0.24| 0.29| 0.35| 0.40
24| 0.45| 1.97| 2.81| 3.66| 4.50| 5.34| 6.19
0.61| 0.04| 0.18| 0.26| 0.34| 0.42| 0.50| 0.58
30| 0.62| 2.55| 3.65| 4.74| 5.83| 6.93| 8.02
0.76| 0.06| 0.24| 0.34| 0.44| 0.54| 0.64| 0.75
36| 0.78| 3.14| 4.48| 5.82| 7.17| 8.51| 9.85
0.91| 0.07| 0.29| 0.42| 0.54| 0.67| 0.79| 0.92
42| 0.93| 3.72| 5.31| 6.91| 8.50| 10.09| 11.69
1.07| 0.09| 0.35| 0.49| 0.64| 0.79| 0.94| 1.09
48| 1.10| 4.30| 6.15| 7.99| 9.83| 11.68| 13.52
1.22| 0.10| 0.40| 0.57| 0.74| 0.91| 1.09| 1.26
54| 1.27| 4.89| 6.98| 9.07| 11.17| 13.26| 15.35
1.37| 0.12| 0.45| 0.65| 0.84| 1.04| 1.23| 1.43
60| 1.42| 5.47| 7.81| 10.16| 12.50| 14.84| 17.19
1.52| 0.13| 0.51| 0.73| 0.94| 1.16| 1.38| 1.60
66| 1.58| 6.05| 8.65| 11.24| 13.83| 16.43| 19.02
1.68| 0.15| 0.56| 0.80| 1.04| 1.28| 1.53| 1.77
72| 1.76| 6.64| 9.48| 12.32| 15.17| 18.01| 20.85
1.83| 0.16| 0.62| 0.88| 1.14| 1.41| 1.67| 1.94
78| 1.91| 7.22| 10.31| 13.41| 16.50| 19.59| 22.69
1.98| 0.18| 0.67| 0.96| 1.25| 1.53| 1.82| 2.11
84| 2.06| 7.80| 11.15| 14.49| 17.83| 21.18| 24.52
2.13| 0.19| 0.72| 1.04| 1.35| 1.66| 1.97| 2.28
90| 2.24| 8.39| 11.98| 15.57| 19.17| 22.76| 26.35
2.29| 0.21| 0.78| 1.11| 1.45| 1.78| 2.11| 2.45
96| 2.40| 8.97| 12.81| 16.66| 20.50| 24.34| 28.19
2.44| 0.22| 0.83| 1.19| 1.55| 1.90| 2.26| 2.62

Airflow Resistance
Standard Air – 0.075 lb/ft3 (1.2 kg/m³)
Test size 48 in. x 48 in. (1219 mm x 1219 mm)

GREENHECK AFL-601 Flush Mount - Free Area Chart

Model AFL-601 recessed/flush frame resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information. (Test Figure 5.5-6.5)

Water Penetration
Standard Air – 0.075 lb/ft3 (1.2 kg/m³)
Test size 48 in. x 48 in. (1219 mm x 1219 mm)Test duration of 15 min.

The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as  that velocity where the water penetration curve projects through 0.01 oz. (3 g) of water (penetration) per sq. ft. (m²) of louver free area. The beginning point of water penetration for Model AFL-601 recessed/flush frame is above 1250 fpm (6.35 m/s) free area  velocity. These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.

Wind-Driven Rain Performance

3 in./hr. (75 mm/hr.) Rainfall Rate &| 8 in./hr. (203 mm/hr.) Rainfall Rate & 50 mph (22.4 m/s) Wind Velocity
---|---
29 mph (13 m/s) Wind Velocity
Ventilation Air Core Velocity fpm  (m/s)| Ventilation Air
Free Area
Velocity
fpm (m/s)| Water
Penetration
Effectiveness
%| Water
Penetration
Classification| Ventilation Air
Core Velocity
fpm (m/s)| Ventilation Air
Free Area
Velocity
fpm (m/s)| Water
Penetration
Effectiveness
%| Water
Penetration
Classification
0 (0.0)| 0 (0.0)| 100.0| A| 0 (0.0)| 0 (0.0)| | A
98 (0.5)| 196 (1.0)| 100.0| A| 98 (0.5)| 196 (1.0)| | A
197 (1.0)| 394 (2.0)| 100.0| A| 197 (1.0)| 394 (2.0)| | A
295 (1.5)| 590 (3.0)| 100.0| A| 295 (1.5)| 590 (3.0)| | A
394 (2.0)| 789 (4.0)| 100.0| A| 394 (2.0)| 789 (4.0)| | A
492 (2.5)| 985 (5.0)| 100.0| A| 492 (2.5)| 985 (5.0)| | A
591 (3.0)| 1183 (6.0)| 100.0| A| 591 (3.0)| 1183 (6.0)| | A
689 (3.5)| 1379 (7.0)| 100.0| A| 689 (3.5)| 1379 (7.0)| | A
787 (4.0)| 1575 (8.0)| 100.0| A| 789 (4.0)| 1580 (8.0)| 99.9| A
886 (4.5)| 1773 (9.0)| 100.0| A| 883 (4.5)| 1766 (9.0)| 99.8| A
984 (5.0)| 1969 (10.0)| 100.0| A| 983 (5.0)| 1968 (10.0)| 99.5| A

Water penetration classification ratings are based on the amount of simulated rain that penetrates the louver during a specific rainfall rate, wind velocity, and intake velocity. Ratings are based on a 39.4 in. x 39.4 in. (1 m x 1 m) core size.

Wind-Driven Rain
Penetration Classes

Class| Effectiveness
A| 1 to 0.99
B| 0.989 to 0.95
C| 0.949 to 0.80
D| Below 0.80

P.O. Box 410 + Schofield, WI 54476-0410 + 715.359.6171
greenheck.com

Copyright © 2024 Greenheck Fan Corporation
AFL-601, April 2024
Greenheck Fan Corporation reserves the right
to make product changes without notice.