GREENHECK HCD Series Blade Seal Replacement Instructions

June 1, 2024
GREENHECK

GREENHECK HCD Series Blade Seal Replacement

GREENHECK-HCD-Series-Blade-Seal-Replacement PRODUCT

Product Specifications

  • Blade & Frame Material: Mill finish, Painted
  • Blade Seal Material: EPDM Silicone
  • Part Number Attachment: 480393, 464605, 480394, 480395
  • Adhesive: 3M #9469, 3M #4257
  • Temperature Range: -20°F (-29°C) to 400°F (204°C)

Product Usage Instructions

  1. Blade Seal Replacement or Installation:
    • Ensure the blade and frame are clean and dry before starting.
    • Handle the EPDM Silicone seal with care to avoid touching the adhesive.
    • Use a finger or roller to press the seal onto the blade firmly.
    • Avoid stretching the seal during installation to prevent it from popping off over time.

Our Commitment:
Greenheck reserves the right to change specifications without notice due to continuous improvement. For product warranties, refer to Greenheck.com on the specific product page or in the literature section at Greenheck.com/Resources/Library/Literature.
GFC Blade Seal Replacement for HCD, Rev. 3, September 2023

Frequently Asked Questions (FAQ):

  • Q: Can I use a different adhesive for attaching the blade seal?
    A: It is recommended to use the specified adhesives (3M #9469 or #4257) for attaching the blade seal for optimal performance and longevity.

  • Q: What should I do if the blade seal pops off after installation?
    A: If the blade seal pops off, carefully clean the surfaces, ensure they are dry, and reapply the seal following the installation instructions provided.

These instructions address either replacement or initial installation.

Silicone or EPDM Seal with Pressure Sensitive Adhesive

  • Open blades. Use a scraper to remove any existing seal or adhesive.
  • The surface must be free from dust, dirt, oil and moisture. Clean the blade edge with alcohol or similar solvents. Do not use mineral spirits or other petroleum-based solvents that leave a residue.
  • Install when the blade surface is at 70°F or above.
  • Cut seal material to exact blade length with release paper still on seal material.
  • A blade seal will need to be applied to the closure strip at the top of the frame. Apply the blade seal to the bottom of every blade tip when the blades are in the closed position.
  • Start at one end of the blade. Peel off 1-2 feet of release paper at a time and place the seal firmly onto the blade surface. Do NOT touch the adhesive. Use a finger or roller to press the seal to the blade. Do NOT stretch the seal as it will pop off in time

SPECIFICATION

Blade & Frame Material| Blade Seal Material| Blade Seal Part Number| Blade Attachment|

Adhesive

| Temperature °F (°C)
---|---|---|---|---|---
Minimum| Maximum

Mill finish

| EPDM| 480393| Adhesive| 3M #9469| -20 (-29)| 250 (121)
Silicone| 464605| Adhesive| 3M #9469| -60 (-51)| 400 (204)

Painted

| EPDM| 480394| Adhesive| 3M #4257| -20 (-29)| 250 (121)
Silicone| 480395| Adhesive| 3M #4257| -60 (-51)| 400 (204)

Our Commitment

  • As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
  • Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.

Phone : 715.359.6171
Fax : 715.355.2399
Parts : 800.355.5354
E-mail : [email protected]
Website : www.greenheck.com
GFC Blade Seal Replacement for HCD, Rev. 3, September 2023
Copyright © 2023 Greenheck Fan Corporation