TSI SUREFLOW Adaptive Offset Controller Instruction Manual
- July 28, 2024
- tsi
Table of Contents
- SUREFLOW Adaptive Offset Controller
- Product Information
- Specifications:
- Product Usage Instructions:
- Installation:
- User Basics:
- Technical Information:
- Q: What is the warranty coverage for the SureFlowTM Adaptive
- Q: Where can I find information on installation and proper
- Q: Can users perform calibration or maintenance on the
SUREFLOW Adaptive Offset Controller
“`html
Product Information
Specifications:
- Model: SureFlowTM Adaptive Offset Controller
- Models available: 8681, 8681-BAC
- Part Number: 1980476, Revision F July 2024
- Warranty: 90 days from the date of shipment for specified
parts
Product Usage Instructions:
Installation:
Ensure the SureFlow controller is properly installed following
the Installation Instructions provided.
User Basics:
This section provides an overview of the product, including its
purpose, operation details, and information on the Digital
Interface Module and Alarms. It is designed to give users a quick
understanding of the product functionality.
Technical Information:
For detailed technical specifications and information, refer to
Part Two of the manual. The manual primarily focuses on laboratory
spaces but is applicable to any room pressure application.
FAQ:
Q: What is the warranty coverage for the SureFlowTM Adaptive
Offset Controller?
A: The product is warranted for 90 days from the date of
shipment for specific parts. Refer to the warranty section in the
manual for detailed coverage information.
Q: Where can I find information on installation and proper
use?
A: Detailed installation instructions are provided in the user
manual. Ensure to follow the instructions carefully for proper
installation and usage of the SureFlow controller.
Q: Can users perform calibration or maintenance on the
product?
A: Calibration requirements should be followed as per the
manual. Users are advised to refer to the operator’s manual for
guidance on replacing consumables or performing recommended
cleaning. Opening the product by unauthorized personnel may void
the warranty.
“`
SureFlowTM Adaptive Offset Controller
Models 8681 8681-BAC
Operation and Service Manual
P/N 1980476, Revision F July 2024
www.tsi.com
Start Seeing the Benefits of Registering Today!
Thank you for your TSI® instrument purchase. Occasionally, TSI® releases
information on software updates, product enhancements and new products. By
registering your instrument, TSI® will be able to send this important
information to you.
http://register.tsi.com
As part of the registration process, you will be asked for your comments on
TSI products and services. TSI’s customer feedback program gives customers
like you a way to tell us how we are doing.
SureFlowTM Adaptive Offset Controller
Models 8681 8681-BAC
Operation and Service Manual
U.S. and Canada Sales & Customer Service:
800-680-1220/651-490-2860
Fax: 651-490-3824
Ship/Mail To: TSI Incorporated ATTN: Customer Service 500 Cardigan Road
Shoreview, MN 55126 USA
International Sales & Customer Service:
(001 651) 490-2860 Fax:
(001 651) 490-3824
E-Mail technical.services@tsi.com
Web Site www.tsi.com
www.tsi.com
Copyright – TSI Incorporated / 2010-2024 / All rights reserved.
Part number 1980476 Rev. F
Limitation of Warranty and Liability (effective May 2024) Seller warrants the
goods, excluding software, sold hereunder, under normal use and service as
described in the operator’s manual (version published at the time of sale), to
be free from defects in workmanship and material for the longer period of
either 24 months or the length of time specified in the operator’s
manual/warranty statement provided with the goods or made available
electronically (version published at the time of sale), from the date of
shipment to the customer. This warranty period is inclusive of any statutory
warranty. This limited warranty is subject to the following exclusions and
exceptions: a. Hot-wire or hot-film sensors used with research anemometers,
and certain other components when indicated
in specifications, are warranted for 90 days from the date of shipment;
b. Pumps are warranted for hours of operation as set forth in product or
operator’s manuals (versions published at the time of sale);
c. Parts repaired or replaced as a result of repair services are warranted to
be free from defects in workmanship and material, under normal use, for 90
days from the date of shipment;
d. Seller does not provide any warranty on finished goods manufactured by
others or on any fuses, batteries or other consumable materials. Only the
original manufacturer’s warranty applies;
e. This warranty does not cover calibration requirements, and Seller warrants
only that the goods are properly calibrated at the time of its manufacture.
Goods returned for calibration are not covered by this warranty;
f. This warranty is VOID if the goods are opened by anyone other than a
factory authorized service center with the one exception where requirements
set forth in the operator’s manual (version published at the time of sale)
allow an operator to replace consumables or perform recommended cleaning;
g. This warranty is VOID if the goods have been misused, neglected, subjected
to accidental or intentional damage, or is not properly installed, maintained,
or cleaned according to the requirements of the operator’s manual (version
published at the time of sale). Unless specifically authorized in a separate
writing by Seller, Seller makes no warranty with respect to, and shall have no
liability in connection with, goods which are incorporated into other products
or equipment, or which are modified by any person other than Seller;
h. New parts or components purchased are warranted to be free from defects in
workmanship and material, under normal use, for 90 days from the date of
shipment.
The foregoing is IN LIEU OF all other warranties and is subject to the
LIMITATIONS stated herein. NO OTHER EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR
PARTICULAR PURPOSE OR MERCHANTABILITY IS MADE. WITH RESPECT TO SELLER’S BREACH
OF THE IMPLIED WARRANTY AGAINST INFRINGEMENT, SAID WARRANTY IS LIMITED TO
CLAIMS OF DIRECT INFRINGEMENT AND EXCLUDES CLAIMS OF CONTRIBUTORY OR INDUCED
INFRINGEMENTS. BUYER’S EXCLUSIVE REMEDY SHALL BE THE RETURN OF THE PURCHASE
PRICE DISCOUNTED FOR REASONABLE WEAR AND TEAR OR AT SELLER’S OPTION
REPLACEMENT OF THE GOODS WITH NON-INFRINGING GOODS.
TO THE EXTENT PERMITTED BY LAW, THE EXCLUSIVE REMEDY OF THE USER OR BUYER, AND
THE LIMIT OF SELLER’S LIABILITY FOR ANY AND ALL LOSSES, INJURIES, OR DAMAGES
CONCERNING THE GOODS (INCLUDING CLAIMS BASED ON CONTRACT, NEGLIGENCE, TORT,
STRICT LIABILITY OR OTHERWISE) SHALL BE THE RETURN OF GOODS TO SELLER AND THE
REFUND OF THE PURCHASE PRICE, OR, AT THE OPTION OF SELLER, THE REPAIR OR
REPLACEMENT OF THE GOODS. IN THE CASE OF SOFTWARE, SELLER WILL REPAIR OR
REPLACE DEFECTIVE SOFTWARE OR IF UNABLE TO DO SO, WILL REFUND THE PURCHASE
PRICE OF THE SOFTWARE. IN NO EVENT SHALL SELLER BE LIABLE FOR LOST PROFITS OR
ANY SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES. SELLER SHALL NOT BE
RESPONSIBLE FOR INSTALLATION, DISMANTLING OR REINSTALLATION COSTS OR CHARGES.
No Action, regardless of form, may be brought against Seller more than 12
months after a cause of action has accrued. The goods returned under warranty
to Seller’s factory shall be at Buyer’s risk of loss, and will be returned, if
at all, at Seller’s risk of loss.
Buyer and all users are deemed to have accepted this LIMITATION OF WARRANTY
AND LIABILITY, which contains the complete and exclusive limited warranty of
Seller. This LIMITATION OF WARRANTY AND LIABILITY may not be amended, modified
or its terms waived, except by writing signed by an Officer of Seller.
ii
Service Policy Knowing that inoperative or defective instruments are as
detrimental to TSI as they are to our customers, our service policy is
designed to give prompt attention to any problems. If any malfunction is
discovered, please contact your nearest sales office or representative, or
call TSI’s Customer Service department at 1-800-6801220 (USA) or +001
651-490-2860 (International).
Trademarks TSI and the TSI logo are registered trademarks of TSI Incorporated
in the United States and may be protected under other country’s trademark
registrations. LonWorks is a registered trademark of Echelon® Corporation.
BACnet is a registered trademark of ASHRAE. Microsoft is a registered
trademark of Microsoft Corporation.
iii
CONTENTS
HOW TO USE THIS MANUAL …………………………………………………………………………………………. V PART ONE
………………………………………………………………………………………………………………………1
User Basics ………………………………………………………………………………………………1 The Instrument
………………………………………………………………………………………….1 Operator Panel
………………………………………………………………………………………….3
Alarms……………………………………………………………………………………………………… 5 Before Calling TSI®
Incorporated …………………………………………………………………7 PART
TWO………………………………………………………………………………………………………………………9 Technical Section
………………………………………………………………………………………9 Software
Programming……………………………………………………………………………….9 Menu and Menu
Items………………………………………………………………………………14 Setup / Checkout
……………………………………………………………………………………..47 Calibration
………………………………………………………………………………………………55 Maintenance and Repair
Parts…………………………………………………………………..59 APPENDIX
A………………………………………………………………………………………………………………….61 Specifications
………………………………………………………………………………………….61 APPENDIX
B………………………………………………………………………………………………………………….63 Network Communications
…………………………………………………………………………63 Modbus
Communications………………………………………………………………………….63 8681 BACnet® MS/TP Protocol
Implementation Conformance Statement ……….67 Model 8681-BAC BACnet® MS/TP
Object Set ……………………………………………..69 APPENDIX
C………………………………………………………………………………………………………………….71 Wiring Information
……………………………………………………………………………………71 APPENDIX
D………………………………………………………………………………………………………………….75 Access
Codes………………………………………………………………………………………….75
iv
How to Use This Manual
The SureFlowTM Operation and Service Manual is divided into two parts. Part
one describes how the SureFlowTM unit functions and how to interface with the
device. This section should be read by users, facilities staff, and anyone who
requires a basic understanding of how the SureFlowTM controller operates. Part
two describes the technical aspects of the product which includes operation,
calibration, configuration, and maintenance. Part two should be read by
personnel programming or maintaining the unit. TSI® recommends thoroughly
reading this manual before changing any software items.
NOTICE
This operation and service manual assumes proper SureFlow controller
installation. Refer to the Installation Instructions to determine if the
SureFlow controller has been properly installed.
v
(This page intentionally left blank)
iv
PART ONE
User Basics
Part one provides a brief but thorough overview of the SureFlowTM product by
maximizing information with minimal reading. These few pages explain the
purpose (the Instrument), and the operation (Useful User Information, Digital
Interface Module, Alarms) of the unit. Technical product information is
available in Part Two of the manual. The manual focuses on laboratory spaces;
however, the information is accurate for any room pressure application.
The Instrument
The SureFlowTM Adaptive Offset Controller (AOC) maintains laboratory pressure
and air balance. The AOC measures and controls all airflow into and out of the
laboratory, and measures the pressure differential. Proper laboratory pressure
differential provides safety by controlling airborne contaminants that can
adversely affect workers in the laboratory, people in the laboratory vicinity,
and experiments. For example, laboratories with fume hoods have negative room
pressure (air flowing into the room), to minimize exposure to people outside
the laboratory. The fume hood is the first level of containment, and the
laboratory space is the second level of containment.
Room pressure, or pressure differential, is created when one space (hallway)
is at a different pressure than an adjoining space (laboratory). The Adaptive
Offset Controller (AOC) creates a pressure differential by modulating supply
air into and exhaust air out of the laboratory (hallway space is a constant
volume system). The theory is that if more air is exhausted out than is
supplied, the laboratory will be negative compared to the hallway. A set
offset may not maintain an adequate pressure differential under all
conditions. The AOC compensates for the unknown pressure differential by
mounting a pressure differential sensor between the hallway and laboratory
that confirms correct pressure differential is being maintained. If pressure
is not being maintained, the AOC modulates the supply or exhaust air until
pressure is maintained.
Negative
Positive
Figure 1: Room Pressure
Negative room pressure is present when air flows from a hallway into the laboratory. If air flows from the laboratory into the hallway, the room is under positive pressure. Figure 1 gives a graphic example of positive and negative room pressure.
An example of negative pressure is a bathroom with an exhaust fan. When the fan is turned on, air is exhausted out of the bathroom creating a slight negative pressure when compared to the hallway. This pressure differential forces air to flow from the hallway into the bathroom.
User Basics
1
The SureFlowTM device informs the laboratory users when the laboratory is
under proper pressure, and provides alarms when the room pressure is
inadequate. If the room pressure is in the safe range, a green light is on. If
the pressure is inadequate, a red alarm light and audible alarm turn on.
The SureFlowTM controller consists of two pieces: a pressure sensor, and
Digital Interface Module (DIM) / Adaptive Offset Controller (AOC). The AOC is
internally part of the DIM module. The components are typically located as
follows; pressure sensor above the laboratory entrance, DIM / AOC is mounted
close to the entrance to the laboratory. The pressure sensor continuously
measures the room pressure and provides room pressure information to the DIM /
AOC. The DIM / AOC continuously reports the room pressure and activates the
alarms when necessary. The DIM / AOC controls the supply and exhaust dampers
to maintain the pressure differential. The DIM / AOC is a closed loop
controller that is continuously measuring, reporting, and controlling room
pressure.
Useful User Information The DIM has a green light and red light to indicate
room pressure status. The green light is on when the room has proper room
pressure. The red light comes on when an alarm condition exists.
Sliding the door panel to the right reveals a digital display and keypad
(Figure 2). The display shows detailed information about room pressure,
alarms, etc. The keypad allows you to test the device, put the device into
emergency mode, and program or change the device parameters.
Figure 2: Digital Interface Module (DIM)
SureFlowTM controller has two levels of user information:
1. SureFlow controller has a red light and green light to provide continuous
information on room pressure status.
2. SureFlow controller has a hidden operator panel providing detailed room
status information, self-testing capabilities, and access to the software
programming functions.
NOTICE
The unit provides continuous room pressure status through the red and green
light. The operator panel is normally closed unless further information on
room pressure status is needed, or software programming is required.
2
Part One
Operator Panel
The DIM in Figure 3 shows the location of the digital display, keypad and
lights. An explanation of the operator panel follows the figure.
Figure 3: SureFlowTM Operator Panel – Open
Green / Red Light
The green light is on when all the conditions for proper room pressure are
adequate. This light indicates the laboratory is operating safely. If any of
the room pressure conditions cannot be satisfied, the green light turns off
and the red alarm light turns on.
Operator Panel
A cover hides the operator panel. Sliding the door panel to the right exposes
the operator panel (Figure 2).
Digital Display
The alphanumeric digital display is a two-line display that indicates actual
room pressure (positive or negative), alarm status, menu options, and error
messages. In normal operation (green light is on), the display indicates
information about room pressure. If an alarm condition occurs, the display
changes from
STANDARD NORMAL
to read
STANDARD ALARM = *
- states type of alarm; low pressure, high pressure, flow
When programming the unit, the display changes and now shows menus, menu items, and current value of the item, depending on the specific programming function being performed.
NOTICE
The AOC system controls room pressure without a pressure sensor installed.
However, verification that room pressure is being maintained is not possible.
The display will not indicate room pressure or room pressure status when no
pressure sensor is installed. The alarms can be programmed to indicate when
low supply or exhaust flow is present.
User Basics
3
Keypad The keypad has six keys. The gray keys with black letters are user
information keys. In normal operation these keys are active. Additionally, the
red emergency key is active. The gray keys with blue characters are used to
program the unit. A thorough description of each key is given on the next two
pages.
User Keys – Gray with Black Letters The four keys with black letters provide
you information without changing the operation or the function of the unit.
TEST Key The TEST key initiates an instrument self-test. Pressing the TEST key
activates a scrolling sequence on the display that shows the product model
number, software version, and all setpoint and alarm values. The unit then
performs a self-test that tests the display, indicator lights, audible alarm,
and internal electronics to ensure they are operating properly. If a problem
with the unit exists, DATA ERROR is displayed. You should have qualified
personnel determine the problem with the unit.
RESET Key The RESET key performs three functions. 1) Resets the alarm light,
alarm contacts, and audible alarm when in a latched or non-automatic reset
mode. The DIM must return to the safe or normal range before the RESET key
will operate. 2) Resets the emergency function after the emergency key has
been pressed (see EMERGENCY key). 3) Clears any displayed error messages.
MUTE Key The MUTE key temporarily silences the audible alarm. The time the
alarm is temporarily silenced is programmable by you (see MUTE TIMEOUT). When
the mute period ends, the audible alarm turns back on if the alarm condition
is still present.
NOTICE
You can program the audible alarm to be permanently turned off (see AUDIBLE
ALM).
AUX Key The AUX key is active only in specialty applications and is not used
on the standard SureFlowTM controller. If the AUX key is used, a separate
manual supplement explains the AUX key function.
Programming Keys – Gray with Blue Characters The four keys with blue print are
used to program or configure the unit to fit a particular application.
WARNING
Pressing these keys changes how the unit functions, so please thoroughly
review the manual before changing menu items.
4
Part One
MENU Key The MENU key performs three functions. 1) Provides access to the
menus when in the normal operating mode. 2) When the unit is being programmed,
the MENU key acts as an escape key to remove you from an item or menu, without
saving data. 3) Returns the unit to the normal operating mode. The MENU key is
further described in the Software Programming section of this manual.
SELECT Key The SELECT key performs three functions. 1) Provides access to
specific menus. 2) Provides access to menu items. 3) Saves data. Pressing the
key when finished with a menu item saves the data, and exits you out of the
menu item.
/ Keys The/ keys are used to scroll through the menus, menu items, and through
the range of item values that can be selected. Depending on the item type the
values may be numerical, specific properties (on / off), or a bar graph.
Emergency Key – Red with Black Letters
EMERGENCY Key The red EMERGENCY key puts the controller into emergency mode.
If the room is under negative room pressure control, the emergency mode
maximizes the negative pressure. Conversely, if the room is under positive
room pressure control, the emergency mode maximizes the positive pressure.
Pressing the EMERGENCY key causes the display to flash “EMERGENCY”, the red
alarm light to flash on and off, and the audible alarm to beep intermittently.
To return to control mode press the EMERGENCY or RESET key.
Alarms
SureFlowTM controller has visual (red light) and audible alarms to inform you
of changing conditions. The alarm levels (setpoints) are determined by
administrative personnel, Industrial Hygienists, or the facilities group
depending on the organization.
The alarms, audible and visual, activate whenever the preset alarm level is
reached. Depending on the SureFlowTM controller items installed, programmed
alarms activate when room pressure is low or inadequate, when room pressure is
high or too great, or when the supply or general exhaust air flow is
insufficient. When the laboratory is operating safely, no alarms sound.
Example: The low alarm is programmed to activate when the room pressure
reaches 0.001 inches H2O. When the room pressure drops below 0.001 inches
H2O (gets closer to zero), the audible and visual alarms activate. The alarms
turn off (when set to unlatched) when the unit returns to the safe range which
is defined as negative pressure greater than 0.001 inches H2O.
Visual Alarm Operation The red light on the front of the unit indicates an
alarm condition. The red light is on for all alarm conditions, low alarms,
high alarms, and emergency. The light is on continuously in a low or high
alarm condition, and flashes in an emergency condition.
User Basics
5
Audible Alarm Operation- EMERGENCY key When the EMERGENCY key is pressed, the
audible alarm beeps intermittently until the EMERGENCY or RESET key is pressed
terminating the emergency alarm. The emergency alarm cannot be silenced by
pressing the MUTE key.
Audible Alarms – All Except Emergency The audible alarm is continuously on in
all low and high alarm conditions. The audible alarm can be temporarily
silenced by pressing the MUTE key. The alarm is silent for a period of time
(see MUTE TIMEOUT to program time period). When the time out period ends, the
audible alarm turns back on if the alarm condition is still present.
You can program the audible alarm to be permanently turned off (see AUDIBLE
ALM). The red alarm light still turns on in alarm conditions when audible
alarm is turned off. The audible and visual alarms can be programmed to either
automatically turn off when the unit returns to the safe range or to stay in
alarm until the RESET key is pressed (See ALARM RESET).
6
Part One
Before Calling TSI® Incorporated
This manual should answer most questions and resolve most problems you may
encounter. If you need assistance or further explanation, contact your local
TSI® representative or TSI®. TSI is
committed to providing high quality products backed by outstanding service.
Please have the following information available prior to contacting your authorized TSI
Manufacturer’s Representative or TSI Incorporated:
– Model number of unit*
8681- ____
– Software revision level*
– Facility where unit is installed
- First two items that scroll when TEST key is pressed
Due to the different SureFlowTM models available, the above information is needed to accurately answer your questions.
For the name of your local TSI representative or to talk to TSI service personnel, please call TSI Incorporated at:
U.S. and Canada Sales & Customer Service: 800-680-1220/651-490-2860 Fax: 651-490-3824
International Sales & Customer Service:
(001 651) 490-2860 Fax:
(001 651) 490-3824
Ship/Mail To: TSI Incorporated ATTN: Customer Service 500 Cardigan Road Shoreview, MN 55126 USA
E-Mail technical.services@tsi.com
Web Site www.tsi.com
User Basics
7
(This page intentionally left blank)
8
Part One
PART TWO
Technical Section
The AOC is ready to use after being properly installed. Please note that the
AOC is part of the DIM module and is not a separate component. Where AOC is
written, the overall control sequence is being discussed. When DIM is written,
the manual is referring to programming the unit or viewing what is on the
display. The pressure sensor is factory calibrated prior to shipping and
should not need adjustment. The flow stations need a zero point and/or a span
programmed prior to using them. The Digital Interface Module (DIM) is
programmed with a default configuration that can be easily modified to fit
your application.
The Technical section is separated into five parts that cover all aspects of
the unit. Each section is written as independently as possible to minimize
flipping back and forth through the manual for an answer.
The Software Programming section explains the programming keys on the DIM. In
addition, the programming sequence is described, which is the same regardless
of the menu item being changed. At the end of this section is an example of
how to program the DIM.
The Menu and Menu Item section lists all of the software items available to
program and change. The items are grouped by menu which means all setpoints
are in one menu, alarm items in another, etc. The menu items and all related
information are listed in table format and include menu item name, description
of menu item, range of programmable values, and how the unit shipped from the
factory (default values).
The Setup / Checkout section; explains the AOC controller theory of operation,
lists the menu items that need to be programmed for the system to operate,
provides a programming example, and provides information to confirm system is
operating correctly.
The Calibration section describes the required technique to compare the
pressure sensor reading to a thermal anemometer, and how to adjust the zero
and span to obtain an accurate calibration. This section also describes how to
zero a TSI® flow station transducer.
The Maintenance and Repair Parts section covers all routine maintenance of
equipment, along with a list of repair parts.
Software Programming
Programming the SureFlowTM controller is quick and easy if the programming
keys are understood and the proper key stroke procedure is followed. The
programming keys are defined first, followed by the required keystroke
procedure. At the end of this section is a programming example.
NOTICE
The unit is always operating while programming unit (except when checking the
control outputs). When a menu item value is changed, the new value takes
effect immediately after saving the change.
Technical Section
9
NOTICE
This section covers programming the instrument through the keypad and display.
If programming through RS-485 communications, use the host computer’s
procedure. The changes take place immediately upon “saving data.”
Programming Keys The four keys with blue characters (refer to Figure 4) are
used to program or configure the unit to fit your particular application.
Programming the instrument changes how the unit functions, so thoroughly
review the items to be changed.
Figure 4. Programming Keys
MENU Key The MENU key has three functions.
1. The MENU key is used to gain access to the menus when the unit is in the
normal operating mode. Pressing the key once exits the normal operating mode
and enters the programming mode. When the MENU key is first pressed, the first
two menus are listed.
2. When the unit is being programmed, the MENU key acts like an escape key.
When scrolling through the main menu, pressing the MENU key returns the unit
to standard operating mode. When scrolling through the items on a menu,
pressing the MENU key returns you to the list of menus. When changing data in
a menu item, pressing the MENU key escapes out of the item without saving
changes.
3. When programming is complete, pressing the MENU key returns the unit to
normal operating mode.
SELECT Key The SELECT key has three functions.
1. The SELECT key is used to gain access to specific menus. To access a menu,
scroll through the menus (using arrow keys) and place the flashing cursor on
the desired menu. Press the SELECT key to select the menu. The first line on
the display will now be the selected menu and the second line shows the first
menu item.
2. The SELECT key is used to gain access to specific menu items. To access a
menu item scroll through the menu items until item appears. Press the SELECT
key and the menu item now appears on the first line of the display and the
second line shows the item value.
10
Part Two
3. Pressing the SELECT key when finished changing an item saves the data and
exits back to the menu items. An audible tone (3 beeps) and visual display
(“saving data”) gives confirmation data is being saved.
/ Keys The / keys are used to scroll through the menus, menu items, and
through the range of item values that can be selected. Depending on the menu
item selected the value may be numerical, specific property (on / off), or a
bar graph.
NOTICE
When programming a menu item, continuously pressing the arrow key scrolls
through the values faster than if arrow key is pressed and released.
Keystroke Procedure The keystroke operation is consistent for all menus. The
sequence of keystrokes is the same regardless of the menu item being changed.
1. Press the MENU key to access the main menu. 2. Use the / keys to scroll
through the menu choices. The blinking cursor needs to be on
the first letter of the menu you want to access.
3. Press the SELECT key to access chosen menu.
4. The menu selected is now displayed on line one and the first menu item is
displayed on line 2. Use the / keys to scroll through the menu items. Scroll
through the menu items until desired item is displayed.
NOTICE
If “Enter Code” is flashing, the access code must be entered before you can
enter the menu. Access code is found in Appendix C. Appendix C may have been
removed from the manual for security reasons.
5. Press the SELECT key to access chosen item. The top line of display shows
menu item selected, while the second line shows current item value.
6. Use the / keys to change item value.
7. Save the new value by pressing the SELECT key (pressing the MENU key exits
out of menu function without saving data).
8. Press the MENU key to exit current menu, and return to main menu.
9. Press the MENU key again to return to normal instrument operation.
If more than one item is to be changed, skip steps 8 and 9 until all changes
are complete. If more items in the same menu are to be changed, scroll to them
after saving the data (step 7). If other menus need to be accessed, press the
MENU key once to access list of menus. The instrument is now at step 2 of the
keystroke sequence.
Technical Section
11
Programming Example
The following example demonstrates the keystroke sequence explained above. In
this example the high alarm setpoint is changed from -0.002 inches H2O to
-0.003 inches H2O.
Unit is in normal operation scrolling room pressure, flows, etc… Pressure is shown in this case.
PRESSURE -.00100 “H2O
Press the MENU key to gain access to the menus.
The first two (2) menu choices are displayed. SETPOINTS ALARM
Press the key once. Blinking cursor should be on A of Alarm. Press the SELECT
key to access the ALARM menu.
NOTICE Blinking cursor must be on A in Alarm.
Line 1 shows menu selected. ALARM Line 2 shows first menu item. LOW ALARM
Press the key once. HIGH ALARM is shown on display.
Menu selected ALARM Item name HIGH ALARM
Press the SELECT key to access the high alarm setpoint. The item name (HIGH
ALARM) is displayed on line 1, and the item’s current value is displayed on
line 2.
Item Name HIGH ALARM Current Value -.00200 “H2O
Press the key to change the high alarm setpoint to – 0.003 inches H2O.
HIGH ALARM – .00300 “H2O
12
Part Two
Press the SELECT key to save the new negative high alarm setpoint.
Three short beeps sound indicating that the data is being saved.
HIGH ALARM Saving Data
Immediately after the data is saved, the SureFlowTM controller returns to the menu level displaying the menu title on the top line of the display and the menu item on the bottom line (goes to step 4).
ALARM HIGH ALARM
WARNING
If the MENU key was pressed instead of the SELECT key, the new data would not
have been saved, and the SureFlowTM controller would have escaped back to the
menu level shown in step 3.
Press the MENU key once to return to the menu level:
Press the MENU key a second time to return to the normal operating level:
ALARM CONFIGURE
Unit is now back in normal PRESSURE operation -.00100 “H2O
Technical Section
13
Menu and Menu Items
The SureFlowTM controller is a very versatile device which can be configured
to meet your specific application. This section describes all of the menu
items available to program and change. Changing any item is accomplished by
using the keypad, or if communications are installed through the RS-485
Communications port. If you are unfamiliar with the keystroke procedure,
please see Software Programming for a detailed explanation. This section
provides the following information:
Complete list of menu and all menu items. Gives the menu or programming name.
Defines each menu item’s function; what it does, how it does it, etc. Gives
the range of values that can be programmed. Gives default item value (how it
shipped from factory).
The menus covered in this section are divided into groups of related items to
ease programming. As an example all setpoints are in one menu, alarm
information in another, etc. The manual follows the menus as programmed in the
controller. The menu items are always grouped by menu and then listed in menu
item order, not alphabetical order. Figure 5 shows a chart of all the Model
8681 controller menu items.
14
Part Two
SETPOINTS
SETPOINT VENT MIN SET COOLING FLOW UNOCCUPY SET MAX SUP SET MIN EXH SET TEMP
SETP UNOCC TEMP MIN OFFSET MAX OFFSET
ALARM
LOW ALARM HIGH ALARM MIN SUP ALM MAX EXH ALM ALARM RESET AUDIBLE ALM ALARM
DELAY ALARM RELAY MUTE TIMEOUT
CONFIGURE
UNITS EXH CONFIG NET ADDRESS MAC ADDRESS ACCESS CODES
CALIBRATION
TEMP CAL SENSOR SPAN ELEVATION
CONTROL
SPEED SENSITIVITY SUP CONT DIR EXH CONT DIR Kc VALUE Ti VALUE Kc OFFSET REHEAT
SIG TEMP DIR TEMP DB TEMP TR TEMP TI
SYSTEM FLOW
TOT SUP FLOW TOT EXH FLOW OFFSET VALUE SUP SETPOINT EXH SETPOINT
FLOW CHECK
SUP FLOW IN EXH FLOW IN HD1 FLOW IN HD2 FLOW IN**
DIAGNOSTICS
CONTROL SUP CONTROL EXH CONTROL TEMP SENSOR INPUT SENSOR STAT TEMP INPUT ALARM
RELAY RESET TO DEF
SUPPLY FLOW
EXHAUST FLOW
HOOD FLOW
SUP DCT AREA SUP FLO ZERO SUP LO SETP SUP HI SETP SUP LOW CAL SUP HIGH CAL FLO STA TYPE TOP VELOCITY RESET CAL
EXH DCT AREA EXH FLO ZERO EXH LO SETP EXH HI SETP EXH LOW CAL EXH HIGH CAL FLO STA TYPE TOP VELOCITY RESET CAL
HD1 DCT AREA HD2 DCT AREA HD1 FLO ZERO HD2 FLO ZERO MIN HD1 FLOW MIN HD2 FLOW HD1 LOW CAL HD1 HIGH CAL HD2 LOW CAL HD2 HIGH CAL ** FLO STA TYPE TOP VELOCITY RESET CAL
*MAC ADDRESS Menu Item only appears as a menu option for a Model 8681-BAC Adaptive Offset Controller which includes a BACnet® MSTP board. The Menu Item NET ADDRESS is deleted as a menu option on the Model 8681-BAC. **These menu items do not appear as options on the Model 8681-BAC.
Figure 5: Menu Items – Model 8681/8681-BAC Controller
Technical Section
15
Part Two
16
SETPOINTS MENU
SOFTWARE
MENU ITEM
NAME
PRESSURE
SETPOINT
SETPOINT
ITEM DESCRIPTION
The SETPOINT item sets the pressure control setpoint. The SureFlowTM
controller maintains this setpoint, negative or positive, under normal
operating conditions.
ITEM RANGE
0 to -0.19500 “H2O or 0 to +0.19500 H2O
Pressure differential is not maintained by direct pressure control; i.e. modulating dampers in response to pressure changes. The pressure signal is an AOC input that is used to calculate the required air flow offset value. The calculated offset value changes the supply (or exhaust) flow volume which changes the pressure differential. When the calculated offset value is between the MIN OFFSET and MAX OFFSET, room pressure control can be maintained. If the offset required to maintain pressure is less than the MIN OFFSET or greater the MAX OFFSET, pressure control will not be maintained.
VENTILATION MINIMUM SUPPLY FLOW SETPOINT
VENT MIN SET
The VENT MIN SET item sets the ventilation supply airflow setpoint. This item
provides a minimum supply airflow to meet the ventilation requirement, by
preventing the supply flow from going below the preset minimum flow.
The controller will not allow the supply air damper to be closed further than
the VENT MIN SET setpoint. If room pressure is not maintained at minimum
supply flow, the general exhaust damper modulates open until pressure setpoint
is reached (provided offset is between MIN OFFSET and MAX OFFSET).
0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the duct area in square
feet (ft2): square meters (m2).
DEFAULT VALUE
-0.00100” H2O
0
17
Technical Section
SETPOINTS MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
SPACE
COOLING The COOLING FLOW item sets the space cooling supply
COOLING
FLOW
airflow setpoint. This item defines a supply air flow
SUPPLY FLOW SETPOINT
intended to meet the space’s cooling requirements by allowing the supply flow to increase, gradually, to the
COOLING FLOW setpoint, from a minimum ventilation
rate, when the space temperature is too warm..
If room pressure is not maintained at minimum temperature flow, the general exhaust damper modulates open until pressure setpoint is reached (provided offset is between MIN OFFSET and MAX OFFSET).
ITEM RANGE 0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the duct area in square
feet (ft2): square meters (m2).
WIRING: This item requires 1000 platinum RTD to be wired to the TEMPERATURE input (DIM pins 23 and 24). The temperature sensor toggles the AOC between VENT MIN SET and COOLING FLOW.
UNOCCUPIED SUPPLY FLOW MINIMUM
UNOCCUPY SET
The UNOCCUPY SET item sets a minimum supply flow setpoint when the laboratory
is unoccupied (requires fewer air changes per hour). When UNOCCUPY SET is
active, the VENT MIN SET and COOLING FLOW setpoints are turned off, since only
one minimum supply setpoint can be enabled.
The controller will not allow the supply air damper to be closed further than
the UNOCCUPY SET setpoint. If room pressure is not maintained at minimum
supply flow, the general exhaust damper modulates open until pressure setpoint
is reached (provided required offset is between MIN OFFSET and MAX OFFSET).
0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the duct area in square
feet (ft2): square meters (m2).
WIRING: This item is enabled through RS 485 communication sends commands. When the UNOCCUPY SET menu item is enabled, VENT MIN SET and COOLING FLOW are disabled. Disabling UNOCCUPY SET and enables VENT MIN SET and COOLING FLOW.
DEFAULT VALUE 0
0
Part Two
18
SETPOINTS MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
MAXIMUM
MAX SUP
The MAX SUP SET item sets the maximum supply air
SUPPLY FLOW SET
flow into the laboratory. The controller will not allow the
SETPOINT
supply air damper to open further than the MAX SUP
SET flow setpoint.
NOTICE
The laboratory may not hold pressure setpoint when supply air is limited.
ITEM RANGE 0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the duct area in square
feet (ft2): square meters (m2).
MINIMUM EXHAUST FLOW SETPOINT
MIN EXH SET
SPACE
TEMP SETP
TEMPERATURE
SETPOINT
The MIN EXH SET item sets the minimum general exhaust air flow out of the
laboratory. The controller will not allow the general exhaust air damper to
close further than the MIN EXH SET flow setpoint.
NOTICE
This item requires a TSI® compatible flow station and control damper to be
mounted in the general exhaust duct.
The TEMP SETP item sets the temperature setpoint of the space. The SureFlowTM
controller maintains the temperature setpoint under normal operating
conditions.
0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the duct area in square
feet (ft2): square meters (m2).
50F to 85F.
WIRING: The 1000 platinum RTD temperature sensor is connected to the temp input (pins 23 & 24, DIM). The temperature sensor signal is continuously monitored by the AOC.
DEFAULT VALUE OFF
OFF
68F
19
Technical Section
SETPOINTS MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
UNOCCUPIED UNOCC
The UNOCC TEMP item sets the temperature setpoint of
SPACE
TEMP
TEMPERATURE
the space during unoccupied mode. The SureFlowTM controller maintains the temperature setpoint under
SETPOINT
unoccupied operating conditions.
WIRING: The 1000 platinum RTD temperature sensor is connected to the temp input (pins 23 & 24, DIM). The temperature sensor signal is continuously monitored by the AOC.
MINIMUM FLOW OFFSET
MIN OFFSET The MIN OFFSET item sets the minimum air flow offset between total exhaust flow (fume hood, general exhaust, other exhaust) and total supply flow.
MAXIMUM
MAX
FLOW OFFSET OFFSET
The MAX OFFSET item sets the maximum air flow offset between total exhaust flow (fume hood, general exhaust, other exhaust) and total supply flow.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
ITEM RANGE 50F to 85F.
– 10,000 to 10,000 CFM
– 10,000 to 10,000 CFM
DEFAULT VALUE 68F
0 0
Part Two
20
ALARM MENU
SOFTWARE
MENU ITEM
NAME
LOW
LOW ALARM
PRESSURE
ALARM
ITEM DESCRIPTION
The LOW ALARM item sets the low pressure alarm setpoint. A low alarm condition
is defined as when the room pressure falls below or goes in the opposite
direction of the LOW ALARM setpoint.
ITEM RANGE
OFF 0 to -0.19500 “H2O 0 to +0.19500 “H2O
HIGH PRESSURE ALARM
HIGH ALARM
The HIGH ALARM item sets the high pressure alarm setpoint. A high alarm condition is defined as when the room pressure rises above the HIGH ALARM setpoint.
OFF 0 to -0.19500 “H2O 0 to +0.19500 “H2O
MINIMUM SUPPLY FLOW ALARM
MIN SUP ALM
The MIN SUP ALM item sets the supply flow alarm setpoint. A minimum flow alarm
is defined as when the supply duct flow is less than the MIN SUP ALM setpoint.
NOTICE
Supply air duct size SUP DCT AREA (Supply Flow menu) must be entered before
MIN SUP ALM can be accessed. Actual total supply air flow is found in TOT SUP
FLOW menu item (system flow menu).
0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the supply duct area in
square feet (ft2 ): square meters (m2 ).
MAXIMUM EXHAUST FLOW ALARM
MAX EXH ALM
WIRING: This item is disabled when the UNOCCUPY SET is enabled [AUX key is
pressed, or the RS 485 communications sends a command].
The MAX EXH ALM item sets the general exhaust duct’s flow alarm setpoint. A
maximum flow alarm is defined as when the general exhaust duct flow is greater
than the MAX EXH ALM setpoint.
NOTICE
General exhaust air duct size EXH DCT AREA (Exhaust Flow menu) must be entered
before MAX EXH ALM can be accessed. Actual total exhaust air flow is found in
TOT EXH FLOW menu item (system flow menu).
0 to 30,000 CFM (0 to 14100 l/s)
Linear based flow stations 0 to TOP VELOCITY times the supply duct area in
square feet (ft2 ): square meters (m2 ).
DEFAULT VALUE OFF OFF OFF
OFF
21
Technical Section
ALARM MENU (continued)
SOFTWARE
MENU ITEM
NAME
ALARM RESET ALARM
RESET
ITEM DESCRIPTION
The ALARM RESET item selects how the alarms terminate after the unit returns
to control setpoint (pressure or flow). UNLATCHED (alarm follow) automatically
resets the alarms when the unit reaches control setpoint. LATCHED requires the
staff to press the RESET key after the unit returns to control setpoint. The
ALARM RESET affects the audible alarm, visual alarm, and relay output, which
means all are latched or unlatched.
AUDIBLE ALARM
AUDIBLE ALM
The AUDIBLE ALM item selects whether the audible alarm is turned ON or OFF. Selecting ON requires the staff to press the MUTE key to silence the audible alarm. Selecting OFF permanently mutes all audible alarms, except when the EMERGENCY key is pressed.
ALARM DELAY ALARM DELAY
The ALARM DELAY determines the length of time the alarm is delayed after an alarm condition has been detected. This delay affects the visual alarm, audible alarm, and relay outputs. An ALARM DELAY prevents nuisance alarms from people entering and leaving the laboratory.
ALARM RELAY ALARM RELAY
The ALARM RELAY item selects which alarms activate the relay contacts (pins 13, 14). Selecting PRESSURE triggers the relays when a pressure alarm is present. Selecting FLOW triggers the relays when a low flow condition exists. This item only affects the relay contacts, all audible and visual alarms are still active regardless of the ALARM RELAY status.
NOTICE
Pins 13, 14 -Alarm relay contacts; configurable for pressure or flow alarms.
ITEM RANGE LATCHED OR
UNLATCHED
ON or OFF
20 to 600 SECONDS
PRESSURE or FLOW
DEFAULT VALUE
UNLATCHED
ON 20 SECONDS
PRESSURE
22
ALARM MENU (continued)
SOFTWARE
MENU ITEM
NAME
MUTE
MUTE
TIMEOUT
TIMEOUT
ITEM DESCRIPTION
The MUTE TIMEOUT determines the length of time the audible alarm is silenced
after the MUTE key is pressed. This delay temporarily mutes the audible alarm.
END OF MENU
NOTICE
If the DIM is in alarm when MUTE TIMEOUT expires, the audible alarm turns on.
When the pressure returns to the safe range, the MUTE TIMEOUT is canceled. If
the room goes back into an alarm condition, the MUTE key must be pressed again
to mute the audible alarm.
The END OF MENU item informs you that the end of a menu has been reached. You
can either scroll back up the menu to make changes, or press the SELECT or
MENU key to exit out of the menu.
ITEM RANGE 5 to 30 MINUTES
DEFAULT VALUE
5 MINUTES
ALARM CONSTRAINTS There are a number of constraints built into the software
that prevent users from programming conflicting alarm information. These are
as follows:
1. The AOC does not allow the pressure alarms to be programmed within 20
ft/min (0.00028 in. H2O at 0.001 in. H2O) of the control setpoint.
Example: The control SETPOINT is set at -0.001 in. H2O. The LOW ALARM setpoint
cannot be set higher than -0.00072 in. H2O. Conversely, the HIGH ALARM
setpoint cannot be set lower than -0.00128 in. H2O.
2. The minimum flow alarms: MIN SUP ALM, MIN EXH ALM must be programmed to be
at least 50 CFM less than the minimum flow setpoint.
3. The pressure alarms: LOW ALARM, HIGH ALARM can be programmed for positive
or negative pressure. However, both the low and high alarm must be set either
positive or negative. The AOC does not allow one positive alarm and one
negative alarm.
4. Alarms DO NOT terminate until the pressure or flow slightly exceeds alarm
setpoint.
Part Two
Technical Section
5. The ALARM RESET item selects how the alarms terminates when controller returns to the safe range. The pressure and flow alarms all terminate the same; they are either latched or unlatched. If unlatched is selected, the alarms automatically turn off when the value slightly exceeds setpoint. If latched is selected, the alarms will not terminate until the controller returns to setpoint and the RESET key is pressed.
6. There is a programmable ALARM DELAY that determines how long to delay before activating the alarms. This delay affects all pressure and flow alarms.
7. The MUTE TIMEOUT item sets the length of time the audible alarm is off for all pressure and flow alarms.
8. The display can only show one alarm message. Therefore, the controller has an alarm priority system, with the highest priority alarm being displayed. If multiple alarms exist, the lower priority alarms will not display until after the highest priority alarm has been eliminated. The alarm priority is as follows: Pressure sensor – low alarm Pressure sensor – high alarm Low supply flow alarm Low exhaust flow alarm Data error
9. The low and high pressure alarms are absolute values. The chart below shows how the values must be programmed in order to operate correctly.
-0.2 inches H2O
0
+0.2 inches H2O
(maximum negative)
(maximum positive)
High Negative Alarm
Negative Setpoint
Low Negative Alarm
Zero
Low Positive Alarm
Positive Setpoint
High Positive Alarm
The value of each setpoint or alarm is unimportant (except for small dead band) in graph above. It is important to understand that the negative (positive) low alarm must be between zero (0) pressure and the negative (positive) setpoint, and that the high alarm is a greater negative (positive) value than setpoint.
23
24
CONFIGURE MENU
SOFTWARE
MENU ITEM
NAME
DISPLAYED
UNITS
UNITS
ITEM DESCRIPTION
The UNITS item selects the unit of measure that the DIM displays all values
(except calibration span). These units display for all menu items setpoints,
alarms, flows, etc.
GENERAL
EXH
EXHAUST DUCT CONFIG
CONFIGURATION
The EXH CONFIG menu item determines the exhaust configuration. If the general exhaust duct is separate from the total exhaust, select UNGANGED (left side of Figure 6). If the general exhaust duct is part of the total exhaust, select GANGED (right side of Figure 6). The correct configuration is required for the control algorithm to function correctly.
ITEM RANGE FT/MIN, m/s, in. H2O, Pa
GANGED or UNGANGED
DEFAULT VALUE “H2O
UNGANGED
Figure 6: Exhaust Configuration
NOTICES
The flow station input for a GANGED flow measurement is to be wired to the
applicable fume hood flow input; either HD 1 INPUT (terminals 11 & 12) or the
HD 2 INPUT (terminals 27 & 28).
A GANGED flow measurement configuration still requires a separate General
Exhaust flow measurement (right side of Figure 6).
Part Two
Technical Section
CONFIGURE MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
NETWORK
NET
The NET ADDRESS item is used to select the main
ADDRESS**
ADDRESS network address of the individual room pressure device.
Each unit on the network must have its own unique
address. The values range from 1-247. If RS-485
communications are being used, a unique NET
ADDRESS must be entered into the unit.
There is no priority between the RS-485 and keypad. The most recent signal by either RS-485 or keypad initiates a change.
RS-485 communications allows you access to all menu items except calibration and control items. The RS-485 network can initiate a change at any time.
MAC Address** MAC ADDRESS
MENU ACCESS ACCESS
CODES
CODES
NOTICE
The Model 8681 network protocol is Modbus®.
The MAC ADDRESS assigns the device an address on the MS/TP BACnet® network.
This address must be unique for each device on the BACnet® network. The ACCESS
CODES item selects whether an access code (pass code) is required to enter the
menu. The ACCESS CODES item prevents unauthorized access to a menu. If the
ACCESS CODES is ON, a code is required before the menu can be entered.
Conversely, if the ACCESS CODES is OFF, no code is required to enter the menu.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
ITEM RANGE 1 to 247
1 to 127 ON or OFF
DEFAULT VALUE 1
1 OFF
25
**The MAC ADDRESS Menu Item replaces the Network Address Menu Item on SureFlowTM controllers provided with the BACnet® MSTP board.
Part Two
26
CALIBRATION MENU
SOFTWARE
MENU ITEM
NAME
TEMPERATURE TEMP CAL
CALIBRATION
ITEM DESCRIPTION
The TEMP CAL is used to enter the actual space temperature. This adjustment
offsets the temperature sensor curve.
SENSOR SPAN SENSOR SPAN
The SENSOR SPAN item is used to match or calibrate the TSI® pressure sensor (velocity sensors) to the average room pressure velocity as measured by a portable air velocity meter.
NOTICE
The pressure sensor is factory calibrated. No initial adjustment should be
necessary.
ITEM RANGE 50°F to 85°F
NONE
ALTITUDE
ELEVATION
The ELEVATION item is used to enter the elevation of the building above sea level. This item has a range of 0 to 10,000 feet in 1,000 foot increments. The pressure value needs to be corrected due to changes in air density at different elevations.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
0 to 10,000 feet above sea level
DEFAULT VALUE 0
0
27
Technical Section
CONTROL MENU
SOFTWARE
MENU ITEM
NAME
SPEED
SPEED
ITEM DESCRIPTION
The SPEED item is used to select the control output speed (supply and general
exhaust). When this item is selected, a bar graph is shown on the display.
There are 10 bars, each one representing 10% of speed. Starting from the right
side (+ sign), 10 bars displayed indicates maximum speed. This is the fastest
the controller will operate. 1 bar is the slowest the controller will operate.
The more bars displayed, the faster the control output.
SENSITIVITY
SENSITIVITY
The SENSITIVITY item is used to select the integral dead band. The integral dead band determines when the controller uses integral control (slow control), and when the controller enters PID control (fast control). When this item is selected, a bar graph is shown on the display.
There are 10 bars total, with each one representing 50 CFM. Starting from the right side (+ sign), 10 bars displayed indicates no dead band so the controller is always in PID control mode. Each bar missing represents ±50 CFM of integral dead band. The less bars displayed, the larger the integral dead band. For example, with 8 bars displayed (2 bars missing) and an offset of 500 CFM, the integral dead band is between 400 and 600 CFM. When the measured offset is within this range, integral or slow control is used. However, when the flow offset falls below 400 CFM or rises above 600 CFM, PID control is enabled until the unit returns within the dead band.
The SENSITIVITY item has a unique feature that when zero bars are displayed, the unit never goes into PID control. The control output is always a slow control signal.
WARNING
When SENSITIVITY is set for 10 bars, the system is always in PID control,
which will probably cause an unstable system. It is recommended that
SENSITIVITY be set at 9 bars or less.
ITEM RANGE 1 to 10 bars
0 to 10 bars
DEFAULT VALUE 5 bars
5 bars
Part Two
28
CONTROL MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
SUPPLY DAMPER
SUP CONT DIR
The SUP CONT DIR item determines the control signal’s output direction. As an example, if the control system
CONTROL
closes the supply damper instead of opening the damper,
SIGNAL
this option reverses the control signal to now open the
DIRECTION
damper.
ITEM RANGE
DIRECT or REVERSE
EXHAUST DAMPER CONTROL SIGNAL DIRECTION
EXH CONT DIR
The EXH CONT DIR item determines the control signal’s output direction. As an example, if the control system closes the exhaust damper instead of opening the damper, this option reverses the control signal to now open the damper.
DIRECT or REVERSE
FLOW TRACKING CONTROL Kc VALUE & Ti VALUE
Kc VALUE Ti VALUE
WARNING
The Kc VALUE and Ti VALUE allow you to manually change the primary PID control
loop variables. DO NOT CHANGE THESE VALUES UNLESS YOU HAVE A THOROUGH
UNDERSTANDING OF PID CONTROL LOOPS. CONTACT TSI® FOR ASSISTANCE PRIOR TO
CHANGING ANY VALUES. Contact TSI® for assistance in determining your control
problem and for instructions on how to change a value. Incorrectly changing a
value results in poor or nonexistent control.
Kc = 0 to 1000 Ti = 0 to 1000
The range of values is very large. Poor control occurs if values are more than
twice or less than 1/2 the default value.
Suggestion: Before changing Kc or Ti, change the SPEED or adjust the SENSITIVITY to try to eliminate the problem.
The Kc VALUE item changes the gain control coefficient of the primary control loop (flow tracking loop). When this item is entered, a value for Kc is indicated on the display. If the AOC is not controlling correctly, the Kc gain control coefficient may need adjusting. Decreasing Kc slows the control system down, which increases stability. Increasing Kc will increase the control system which may cause system instability.
DEFAULT VALUE DIRECT
DIRECT
Kc = 80 Ti = 200
29
Technical Section
CONTROL MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
FLOW
Kc VALUE The Ti VALUE item changes the integral control
TRACKING
Ti VALUE
coefficient of the primary control loop (flow tracking loop).
CONTROL Kc
When this item is entered, a value for Ti is indicated on
VALUE &
the display. If the AOC is not controlling correctly, the unit
Ti VALUE
may have an inappropriate integral control coefficient.
(continued)
Increasing Ti slows the control system which increases
stability. Decreasing Ti increases the control system
speed which may cause system instability.
ITEM RANGE
ADAPTIVE OFFSET CONTROL Kc VALUE
Kc OFFSET
WARNING
The Kc OFFSET sets the pressure control PID variable. DO NOT CHANGE THIS VALUE
UNLESS YOU HAVE A THOROUGH UNDERSTANDING OF PID CONTROL LOOPS. CONTACT TSI®
FOR ASSISTANCE PRIOR TO CHANGING ANY VALUES. Contact TSI® for assistance in
determining your control problem and for instructions on how to change a
value. Incorrectly changing a value results in poor or nonexistent control.
Kc = 0 to 1000
The range of values is very large. Poor control occurs if values are more than
twice or less than 1/2 the default value.
The Kc OFFSET item changes the gain control coefficient of the secondary control loop (pressure control loop). The pressure control loop is very slow when compared to the primary flow control loop. This menu item should not be changed unless problems with the pressure control loop can be established (confirm problem is not with primary flow control loop).
When this item is entered, a value for Kc is indicated on the display. Decreasing Kc slows the pressure control loop down, while increasing Kc increases the pressure control loop speed.
TEMPERATURE REHEAT SIG The REHEAT SIG item switches the supply and exhaust
OUTPUT
control outputs from 0 to 10 VDC to 4 to 20 mA.
SIGNAL
0 to 10 VDC or 4 to 20 mA
DEFAULT VALUE Kc = 200
0 to 10 VDC
30
CONTROL MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
TEMPERATURE TEMP DIR CONTROL
The TEMP DIR item determines the control signal’s output direction. As an example: If the control system
DIRECTION
closes the reheat valve instead of opening this valve, this
option reverses the control signal to now open the valve.
TEMPERATURE TEMP DB SETPOINT DEAD BAND
The TEMP DB item determines the controller’s temperature control deadband,
which is defined as the
temperature range above and below the temperature setpoint (TEMP SETP or UNOCC
TEMP), where the controller will not take corrective action.
ITEM RANGE DIRECT OR REVERSE
0.0F to 1.0F
DEFAULT VALUE DIRECT
0.1F
If TEMP DB is set to 1.0°F, and the TEMP SETP is set to 70.0F, the controller will not take corrective action unless the space temperature is below 69.0°F or above 71.0°F.
Part Two
Technical Section
CONTROL MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
TEMPERATURE TEMP TR SETPOINT
The TEMP TR item determines the controller’s temperature control throttling range, which is defined as
THROTTLING
the temperature range for the controller to fully open and
RANGE
fully close the reheat valve.
ITEM RANGE 2.0°F to 20.0°F
DEFAULT VALUE
3.0°F
If TEMP TR is set to 3.0F, and the TEMP SETP is set to 70.0F, the reheat valve will be fully open when the space temperature is 67F. Similarly, the reheat valve will be fully closed when the space temperature is 73.0F.
31
Part Two
32
CONTROL MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
TEMPERATURE TEMP TI
WARNING
SETPONT INTEGRAL VALUE
The TEMP TI item provides you with the ability to manually change the temperature control PI integral control loop variable. DO NOT CHANGE THIS VALUE
UNLESS YOU HAVE A THOROUGH
UNDERSTANDING OF PI CONTROL LOOPS. CONTACT TSI® FOR ASSISTANCE PRIOR TO CHANGING ANY VALUES. Contact TSI® for
assistance in determining your control problem and for
instructions on how to change a value. Incorrectly
changing a value results in poor or nonexistent control.
Suggestion: Before changing TEMP TI adjust the TEMP DB or adjust the TEMP TR to try to eliminate the problem.
The TEMP TI item is used to read and change the integral control coefficient. When this item is entered, a value for TEMP TI is indicated on the display. If the SureFlowTM controller is not controlling correctly, the unit may have an inappropriate integral control coefficient. Increasing TEMP TI slows the control system which increases stability. Decreasing TEMP TI speeds up the control system which may cause system instability.
ITEM RANGE 1 to 10000 sec
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
DEFAULT VALUE
2400 sec
33
Technical Section
SYSTEM FLOW MENU
SOFTWARE
MENU ITEM
NAME
TOTAL SUPPLY TOT SUP
AIR FLOW
FLOW
ITEM DESCRIPTION
The TOT SUP FLOW menu item displays the current total measured supply flow
into the laboratory. This is a system information only menu item: no
programming is possible.
TOTAL EXHAUST AIR FLOW
TOT EXH FLOW
The TOT EXH FLOW menu item displays the current total measured exhaust flow out of the laboratory. This item calculates total exhaust by summing EXH FLOW IN and HD1 FLOW IN and HD2 FLOW IN. This is a system information only menu item: no programming is possible.
CONTROL
OFFSET
OFFSET VALUE VALUE
The OFFSET VALUE menu item displays the actual flow offset being used to control the laboratory. The OFFSET VALUE is calculated by the AOC control algorithm, which uses the MIN OFFSET, MAX OFFSET, and SETPOINT items to calculate required offset. This is a system information only menu item: no programming is possible.
SUPPLY FLOW SUP
SETPOINT
SETPOINT
(CALCULATED)
The SUP SETPOINT menu item displays the supply flow setpoint, which is calculated by the AOC control algorithm. The calculated SUP SETPOINT is a diagnostic item used to compare the actual TOT SUP FLOW to the calculated flow (they should match within 10%). This is a system information only menu item: no programming is possible.
ITEM RANGE NONE: Read only
value
NONE: Read only value
NONE: Read only value
NONE: Read only value
DEFAULT VALUE NONE
NONE
NONE
NONE
34
SYSTEM FLOW MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
GENERAL
EXH
The EXH SETPOINT menu item displays the general
EXHAUST
SETPOINT exhaust flow setpoint, which is calculated by the AOC
FLOW
control algorithm. The calculated EXH SETPOINT is a
SETPOINT
diagnostic item used to compare the actual EXH FLOW
(CALCULATED)
IN (from FLOW CHECK MENU) to the calculated flow.
This is a system information only menu item: no
programming is possible.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
ITEM RANGE
NONE: Read only value
DEFAULT VALUE
NONE
FLOW CHECK MENU
SOFTWARE
MENU ITEM
NAME
SUPPLY AIR
SUP FLOW
FLOW
IN
ITEM DESCRIPTION The SUP FLOW IN menu item displays the current supply air
flow. This item is a diagnostics tool used to compare the supply flow to a
traverse of the duct work. If flow error is greater than 10%, calibrate flow
station.
When a volt meter is hooked to the flow station output, a voltage should be
displayed. The exact voltage displayed is relatively unimportant. It is more
important that the voltage is changing which indicates the flow station is
working correctly.
ITEM RANGE
NONE: Read only value
DEFAULT VALUE
NONE
Part Two
35
Technical Section
FLOW CHECK MENU
SOFTWARE
MENU ITEM
NAME
GENERAL
EXH FLOW
EXHAUST
IN
FLOW
FUME HOOD EXHAUST FLOW
HD1 FLOW IN HD2 FLOW IN*
END OF MENU
ITEM DESCRIPTION The EXH FLOW IN menu item displays the current exhaust flow
from a general exhaust. This item is a diagnostics tool used to compare the
general exhaust flow to a traverse of the duct work. If flow error is greater
than 10%, calibrate flow station.
When a volt meter is hooked to the flow station output, a voltage should be
displayed. The exact voltage displayed is relatively unimportant. It is more
important that the voltage is changing which indicates the flow station is
working correctly.
The HD# FLOW IN menu item displays the current exhaust flow from a fume hood.
This item is a diagnostics tool to compare the hood flow reading to a traverse
of the duct work. If flow reading and traverse match within 10%, no change is
needed. If flow error is greater than 10%, calibrate flow station.
When a volt meter is hooked to the flow station output, a voltage should be
displayed. The exact voltage displayed is relatively unimportant. It is more
important that the voltage is changing which indicates the flow station is
working correctly.
The END OF MENU item informs you that the end of a menu has been reached. You
can either scroll back up the menu to make changes, or press the SELECT or
MENU key to exit out of the menu.
*These menu items do not appear on SureFlowTM controllers with BACnet® communications.
ITEM RANGE NONE: Read only
value
NONE: Read only value
DEFAULT VALUE NONE
NONE
36
DIAGNOSTICS MENU
SOFTWARE
MENU ITEM
NAME
SUPPLY AIR
CONTROL
CONTROL
SUP
OUTPUT
ITEM DESCRIPTION
The CONTROL SUP item manually changes the control output signal to the supply
air actuator/damper (or motor speed drive). When this item is entered, a
number between 0 and 100% is shown on the display indicating the control
output value. Pressing the / keys change the count on the display. Pressing
the key increases the displayed value, while pressing the key decreases the
displayed value. The supply air damper or VAV box should change (modulate) as
the number changes. A count of 50% should position the damper approximately
1/2 open. On units controlling variable frequency drives, fan speed should
increase or decrease as numbers change.
WARNING
The CONTROL SUP function overrides the AOC control signal. Adequate room
pressure WILL NOT be maintained while in this item.
EXHAUST AIR CONTROL OUTPUT
CONTROL EXH
The CONTROL EXH item manually changes the control output signal to the exhaust
air actuator/damper (or motor speed drive). When this item is entered, a
number between 0 and 100% is shown on the display indicating the control
output value. Pressing the / keys changes the count on the display. Pressing
the key increases the displayed value, while pressing the key decreases the
displayed value. The exhaust air damper or VAV box should change (modulate) as
the number changes. A count of 50% should position the damper approximately
1/2 open. On units controlling variable frequency drives, fan speed should
increase or decrease as numbers change.
WARNING
The CONTROL EXH function overrides the AOC control signal. Adequate room
pressure WILL NOT be maintained while in this item.
REHEAT VAVLE CONTROL
CONTROL
TEMP
OUTPUT
The CONTROL TEMP item manually changes the control output signal to the reheat
valve. When this item is entered, a number between 0 and 100% is shown on the
display indicating the control output value. Pressing the / keys changes the
count on the display. Pressing the key increases the displayed value, while
pressing the key decreases the displayed value. The reheat control valve
should modulate as the number changes. A count of 50% should position the
valve approximately 1/2 open.
WARNING
The CONTROL TEMP function overrides the AOC control signal. Adequate space
temperature WILL NOT be maintained while in this item.
Part Two
Technical Section
DIAGNOSTICS MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
PRESSURE
SENSOR
The SENSOR INPUT item verifies that the DIM is receiving a signal from the pressure sensor.
SENSOR
INPUT
When this item is entered, a voltage is indicated on the display. The exact voltage displayed is
SIGNAL CHECK
relatively unimportant. It is more important that the voltage is changing which indicates the sensor
is working correctly.
0 volts represents a negative pressure of -0.2 inches H2O. 5 volts represents 0 pressure
10 volts represents a positive pressure of +0.2 inches H2O.
PRESSURE SENSOR
COMMUNICATION CHECK
SENSOR STAT
The SENSOR STAT item verifies that the RS-485 communications between the
pressure sensor and DIM is working correctly. Pressure sensor error messages
do not display on DIM except when SENSOR STAT item is selected. This item
displays NORMAL if communications are established correctly. If problems
exist, one of four error messages display:
COMM ERROR – DIM cannot communicate with sensor. Check all wiring and pressure
sensor address. Address must be 1.
SENS ERROR – Problem with sensor bridge. Physical damage to pressure sensor or
sensor circuitry. Unit is not field repairable. Send to TSI® for repair.
CAL ERROR – Calibration data lost. Sensor must be returned to TSI® to be
calibrated.
DATA ERROR – Problem with EEPROM, field calibration, or analog output
calibration lost. Check all data programmed and confirm unit is function
correctly.
TEMPERATURE INPUT
TEMP INPUT
The TEMP INPUT item reads the input from the temperature sensor. When this item is entered, a temperature is indicated on the display. The exact temperature displayed is relatively unimportant. It is more important that the temperature changes indicating the temperature sensor is working correctly. The output range that can be read is resistance.
RELAY OUTPUT ALARM RELAY
The relay menu items are used to change the state of the relay contact. When
entered, the display indicates either OPEN or CLOSED. The / keys are used to
toggle the state of the relay. Pressing the key will OPEN the alarm contact.
Pressing the key will CLOSE the alarm contact.
When the contact is closed, the relay is in an alarm condition.
37
38
DIAGNOSTICS MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
RESET THE CONTROLLER TO FACTORY DEFAULT
RESET TO DEF
When this menu item is entered, the 8681 prompts you to verify that you want
to do this by indicating NO. Use the keys change the display to YES then press
the SELECT key to reset the controller to
its factory defaults. Pressing the MENU key before the SELECT key exits out of
the menu item.
SETTINGS
WARNING
If YES is selected, the Model 8681 resets all menu items to their factory default settings: The
controller will have to be reprogrammed and recalibrated after this operation is completed.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
Part Two
39
Technical Section
SUPPLY FLOW MENU
SOFTWARE
MENU ITEM
NAME
SUPPLY AIR
SUP DCT
DUCT SIZE
AREA
ITEM DESCRIPTION The SUP DCT AREA item inputs the supply air exhaust duct
size. The duct size is needed to compute the supply air flow into the
laboratory. This item requires a flow station to be mounted in each supply
duct.
If the DIM displays English units, area must be entered in square feet. If
metric units are displayed area must be entered in square meters.
ITEM RANGE 0 to 10 square feet (0 to 0.9500 square meters)
The DIM does not compute duct area. The area must be first calculated and then
entered into the unit.
SUPPLY FLOW SUP FLO STATION ZERO ZERO
The SUP FLO ZERO item establishes the flow station zero flow point. A zero or no flow point needs to be established in order to obtain a correct flow measurement output (see Calibration section).
NONE
All pressure based flow stations need to have a SUP FLO ZERO established on initial set up. Linear flow stations with a minimum output of 0 VDC do not need a SUP FLO ZERO.
SUPPLY FLOW LOW CALIBRATION SETTING
SUP LOW SETP
The SUP LOW SETP menu item sets the supply damper position for supply low flow calibration.
0 to 100% OPEN
SUPPLY FLOW HIGH CALIBRATION SETTING
SUP HIGH SETP
The SUP HIGH SETP menu item sets the supply damper position for the supply high flow calibration.
0 to 100% OPEN
DEFAULT VALUE 0
0% OPEN 100% OPEN
Part Two
40
SUPPLY FLOW MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
SUPPLY FLOW SUP LOW The SUP LOW CAL menu items display the currently
LOW
CAL
measured supply flow rate and the calibrated value for
CALIBRATION
that supply flow. The supply dampers move to the SUP
LOW SETP damper position for the low calibration.
The calibrated supply flow can be adjusted using the / keys to make it match a reference measurement.
Pressing the SELECT key saves the new calibration
data.
ITEM RANGE
SUPPLY FLOW HIGH CALIBRATION
SUP HIGH CAL
The SUP HIGH CAL menu items display the currently measured supply flow rate and the calibrated value for that supply flow. The supply dampers move to the SP HIGH SETP damper position for the high calibration. The calibrated supply flow can be adjusted using the / keys to make it match a reference measurement. Pressing the SELECT key saves the new calibration data.
FLOW STATION FLO STA
TYPE
TYPE
The FLO STA TYPE item is used to select the flow station input signal. PRESSURE is selected when TSI® flow stations with pressure transducers are installed. LINEAR is selected when a linear output flow station is installed. Typically a thermal anemometer based flow station.
PRESSURE or LINEAR
MAXIMUM
TOP
FLOW STATION VELOCITY
VELOCITY
The TOP VELOCITY item is used to input the maximum velocity of a linear flow station output. A TOP VELOCITY must be input for the linear flow station to operate.
0 to 5,000 FT/MIN (0 to 25.4 m/s)
NOTICE
This item is disabled if a pressure based flow station is installed.
DEFAULT VALUE
PRESSURE 0
41
Technical Section
SUPPLY FLOW MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
RESET
RESET CAL The RESET CAL menu item zeroes out the calibration
CALIBRATION
adjustments for the supply flow. When this menu item is
entered, the 8681 prompts you to verify that you want to
do this. Press the SELECT key to reset the calibrations,
and the MENU key to reject it.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
ITEM RANGE
DEFAULT VALUE
Part Two
42
EXHAUST FLOW MENU
SOFTWARE
MENU ITEM
NAME
GENERAL
EXH DCT
EXHAUST
AREA
DUCT SIZE
ITEM DESCRIPTION
The EXH DCT AREA item inputs the general exhaust duct size. The duct size is
needed to compute the total general exhaust flow out of the laboratory. This
item requires a flow station to be mounted in each general exhaust duct.
ITEM RANGE
0 to 10 square feet (0 to 0.9500 square meters)
If the DIM displays English units, area must be entered in square feet. If metric units are displayed, area must be entered in square meters.
The DIM does not compute duct area. The area must be first calculated and then entered into the unit.
EXHAUST
EXH FLO
FLOW STATION ZERO
ZERO
The EXH FLO ZERO item establishes the flow station zero flow point. A zero or no flow point needs to be established in order to obtain a correct flow measurement output (see Calibration section).
NONE
All pressure based flow stations need to have an EXH FLO ZERO established on initial set up. Linear flow stations with a minimum output of 0 VDC do not need a SUP FLO ZERO.
EXHAUST FLOW LOW CALIBRATION SETTING
EXH LOW SETP
The EXH LOW SETP menu item sets the general exhaust damper position for general exhaust low flow calibration.
0 to 100% OPEN
EXHAUST FLOW HIGH CALIBRATION SETTING
EXH HIGH SETP
The EXH HIGH SETP menu item sets the general exhaust damper position for the general exhaust high flow calibration.
0 to 100%
DEFAULT VALUE 0
0% OPEN 100% OPEN
43
Technical Section
EXHAUST FLOW MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
EXHAUST
EXH LOW The EXH LOW CAL menu items display the currently
FLOW LOW
CAL
measured general exhaust flow rate and the calibrated
CALIBRATION
value for that general exhaust flow. The exhaust
dampers move to the EXH LOW SETP damper position
for the low calibration. The calibrated general exhaust can be adjusted using the / keys to make it match a
reference measurement. Pressing the SELECT key
saves the new calibration data.
ITEM RANGE
EXHAUST FLOW HIGH CALIBRATION
EXH HIGH CAL
The EXH HIGH CAL menu items display the currently measured general exhaust
flow rate and the calibrated value for that general exhaust flow. The exhaust
dampers moves to the EXH HIGH SETP damper position for the high calibration.
The calibrated general exhaust flow can be adjusted using the / keys to make
it
match a reference measurement. Pressing the SELECT key saves the new
calibration data.
FLOW STATION FLO STA
TYPE
TYPE
The FLO STA TYPE item is used to select the flow station input signal. PRESSURE is selected when TSI® flow stations with pressure transducers are installed. LINEAR is selected when a linear output flow station is installed (0-5 VDC or 0-10 VDC): Typically a thermal anemometer based flow station.
PRESSURE or LINEAR
MAXIMUM
TOP
FLOW STATION VELOCITY
VELOCITY
The TOP VELOCITY item is used to input the maximum velocity of a linear flow
station output. A TOP VELOCITY must be input for the linear flow station to
operate.
NOTICE
This item is disabled if a pressure based flow station is installed.
0 to 5,000 FT/MIN (0 to 25.4 m/s)
DEFAULT VALUE
PRESSURE 0
Part Two
44
EXHAUST FLOW MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
RESET
RESET CAL The RESET CAL menu item zeroes out the calibration
CALIBRATION
adjustments for the general exhaust flow. When this
menu item is entered, the 8681 prompts you to verify that
you want to do this. Press the SELECT key to reset the
calibrations, and the MENU key to reject it.
ITEM RANGE
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
*These menu items do not appear on SureFlowTM controllers provided with BACnet® communications.
DEFAULT VALUE
45
Technical Section
HOOD FLOW MENU
SOFTWARE
MENU ITEM
NAME
FUME HOOD HD1 DCT
EXHAUST
AREA
DUCT SIZE
and
ITEM DESCRIPTION
The HD# DCT AREA item inputs the fume hood exhaust duct size. The duct size is
needed to compute the flow out of the fume hood. This item requires a flow
station to be mounted in each fume hood exhaust duct.
ITEM RANGE
0 to 10 square feet (0 to 0.9500 square meters)
HD2 DCT AREA*
If the DIM displays English units, area must be entered in square feet. If metric units are displayed area must be entered in square meters.
The DIM does not compute duct area. The area must be first calculated and then entered into the unit.
FUME HOOD FLOW STATION ZERO
HD1 FLO ZERO
and
HD2 FLOW ZERO*
The HD# FLO ZERO item establishes the flow station zero flow point. A zero or
no flow point needs to be established in order to obtain a correct flow
measurement output (see Calibration section).
All pressure based flow stations need to have a HD# FLO ZERO established on
initial set up. Linear flow stations with a minimum output of 0 to 5 VDC do
not need a HD# FLO ZERO.
NONE
MINIMUM HOOD # FLOWS
MIN HD1 FLOW
and
MIN HD2 FLOW*
The MIN HD# FLOW menu items adjust the minimum flow value for each fume hood input. Use this menu item if the fume hood flow measurements are too low when the sash is closed.
HOOD # LOW CALIBRATION POINTS
HD1 LOW CAL
and
HD2 LOW CAL*
The HD# LOW CAL menu items display the currently measured fume hood flow rate
and the calibrated value for that fume hood flow. The calibrated hood flow can
be adjusted using the / keys to make it match a
reference measurement. Pressing the SELECT key saves the new calibration data.
DEFAULT VALUE
0
Part Two
46
HOOD FLOW MENU (continued)
SOFTWARE
MENU ITEM
NAME
ITEM DESCRIPTION
HOOD # HIGH HD1 HIGH The HD# HIGH CAL menu items display the currently
CALIBRATION CAL
measured fume hood flow rate and the calibrated value
POINTS
and
HD2 HIGH CAL*
for that fume hood flow. The calibrated hood flow can be adjusted using the /
keys to make it match a
reference measurement. Pressing the SELECT key saves
the new calibration data.
ITEM RANGE
FLOW STATION FLO STA
TYPE
TYPE
The FLO STA TYPE item is used to select the flow station input signal. PRESSURE is selected when TSI® flow stations with pressure transducers are installed. LINEAR is selected when a linear output flow station is installed (0 to 5 VDC or 0 to 10 VDC): Typically a thermal anemometer based flow station.
PRESSURE or LINEAR
MAXIMUM
TOP
FLOW STATION VELOCITY
VELOCITY
The TOP VELOCITY item is used to input the maximum velocity of a linear flow station output. A TOP VELOCITY must be input for the linear flow station to operate.
0 to 5,000 FT/MIN (0 to 25.4 m/s)
NOTICE
This item is disabled if a pressure based flow station is installed.
RESET CALIBRATION
RESET CAL
The RESET CAL menu item zeroes out the calibration adjustments for the hood flow. When this menu item is entered, the 8681 prompts you to verify that you want to do this. Press the SELECT key to reset the calibrations and the MENU key to reject it.
END OF MENU
The END OF MENU item informs you that the end of a menu has been reached. You can either scroll back up the menu to make changes, or press the SELECT or MENU key to exit out of the menu.
*These menu items do not appear on SureFlowTM controllers provided with BACnet® communications.
DEFAULT VALUE
PRESSURE
0
Setup / Checkout
The AOC is easy to program and setup. This section covers the theory of
operation, required software programming, a programming example, and how to
verify (checkout) that the components are functioning correctly. The AOC uses
a unique control sequence that combines flow and pressure differential
measurements to maintain air balance and laboratory pressure, while
interfacing with a thermostat to maintain laboratory temperature. The overall
AOC control sequence seems quite complicated initially, but the Theory of
Operation section breaks the sequence down into sub-sequences which simplifies
the total system.
Theory of Operation The AOC control system requires the following measurement
inputs to function correctly:
General exhaust flow measured with a flow station (if general exhaust is
installed). Fume hood exhaust flow measured with a flow station. Supply air
flow measured with a flow station. Temperature measured with a thermostat (if
temperature is incorporated into sequence). Pressure differential with a TSI®
pressure sensor (if pressure is incorporated
into sequence).
Laboratory Air Balance Laboratory air balance is maintained by measuring the
fume hood exhaust (or other exhaust), subtracting an offset flow from the fume
hood total, and then setting the supply air damper(s) to maintain the offset
between supply air and fume hood exhaust. The general exhaust damper is
normally closed, except when room pressure cannot be maintained. This may
occur when the fume hood sashes are all down and the supply air is at a
minimum position. The general exhaust damper opens to maintain the required
offset and pressure differential.
Pressure Control The pressure differential signal is sent to the AOC
(assumption: laboratory is under negative pressure). If pressure is at
setpoint, the control algorithm does nothing. If pressure is not at setpoint,
the offset value is changed until pressure is maintained, or the minimum or
maximum offset value is reached. If the offset value:
increases, the supply air is reduced until one of three events occur: Pressure
setpoint is reached. The AOC maintains the new offset. The offset range is
exceeded. The offset will be at maximum attempting to reach
pressure setpoint. An alarm triggers to inform you pressure differential is
not being maintained. Supply air minimum is reached. The general exhaust
begins to open (was closed) to maintain pressure differential.
decreases, the supply air increases until one of three events occur: Pressure
setpoint is reached. The AOC maintains the new offset. The offset range is
exceeded. The offset will be at minimum attempting to reach
pressure setpoint. An alarm triggers to inform you pressure differential is
not being maintained. Supply air maximum is reached. The alarm triggers to
inform you pressure differential is not being maintained.
Technical Section
47
NOTICE
The pressure differential is a slow secondary control loop. The system
initially starts with a calculated offset value and then slowly adjusts the
offset value to maintain pressure differential.
Temperature Control
The Model 8681 receives a temperature input from a temperature sensor (1000
Platinum RTD). The Model 8681 controller maintains temperature control by: (1)
Controlling supply and general exhaust for ventilation and cooling (2)
Controlling the reheat coil for heating
The Model 8681 has three supply flow minimum setpoints. The ventilation
setpoint (VENT MIN SET) is the minimum flow volume required to meet
ventilation needs of the laboratory (ACPH). The temperature supply setpoint
(COOLING FLOW) is the theoretical minimum flow required to meet cooling flow
needs of the laboratory. The unoccupied setpoint (UNOCC SETP) is the minimum
flow required when the lab is not occupied. All of these setpoints are
configurable. If the Model 8681 is in the Unoccupied Mode, the controller will
control the supply air flow to the UNOCCUPY SET ventilation rate, the supply
flow will not be modulated for space cooling; space temperature control will
be maintained by modulating the reheat coil.
The Model 8681 continuously compares the temperature setpoint to the actual
space temperature. If setpoint is being maintained, no changes are made. If
setpoint is not being maintained, and the space temperature is rising, the
controller will first modulate the reheat valve closed. Once the reheat valve
is fully closed the controller begins a 3minute time period. If, after the
3-minute time period the reheat valve is still fully closed, the Model 86812
then gradually begins increasing the supply volume by 1 CFM/second up to the
COOLING FLOW setpoint.
The controller, when controlling supply flow for cooling, will not increase
the supply flow above the COOLING FLOW ventilation rate. If the space
temperature decreases below the setpoint, the controller first reduces the
supply volume. Once the supply volume reaches its minimum (VENT MIN SET), the
controller then starts a 3-minute time period. If, after 3 minutes the supply
flow is still at the VENT MIN SET flow rate, the controller begins modulating
the reheat coil open to meet the heating demand.
If the general exhaust is in the closed position and fume hood loads require
additional replacement air, the Model 8681 overrides ventilation or
temperature setpoints to modulate supply for pressurization control.
Temperature is then controlled by the reheat valve in this sequence.
The control output items in the DIAGNOSTICS menu shows a percentage value. If
control direction for a given output is set to DIRECT, the diagnostic value
will be percent OPEN. If control direction for a given output is set to
REVERSE, the diagnostic value will be percent CLOSED.
NOTICE
The greatest flow requirement dominates the supply flow. If hood replacement
air exceeds the ventilation or temperature flow minimums, the replacement air
requirement is maintained (minimums are ignored).
48
Part Two
In summary, understanding the AOC control algorithm is the key to getting the system functioning correctly. The AOC control algorithm functions as follows:
SUPPLY AIR = GENERAL EXHAUST + FUME HOOD EXHAUST – OFFSET
Supply air is at minimum position; unless additional replacement air is required (fume hood or general exhaust).
General exhaust is closed or at minimum position; except when supply air is at minimum position and pressure control cannot be maintained.
Independent control loop by fume hood controller maintains face velocity. Hood exhaust flow is monitored by AOC. The AOC does not control the fume hood.
Programmed by user. User programs minimum and maximum offset.
Required Software Programming
The following menu items must be programmed for the AOC to function. See Menu
and Menu Items section for information in individual menu items.
SUPPLY FLOW MENU SUP DCT AREA SUP FLO ZERO FLO STA TYPE TOP VELOCITY SUP LOW SETP SUP HIGH SETP SUP LOW CAL SUP HIGH CAL
EXHAUST FLOW MENU EXH DCT AREA EXH FLO ZERO FLO STA TYPE TOP VELOCITY EXH LOW SETP EXH HIGH SETP EXH LOW CAL EXH HIGH CAL
HOOD FLOW MENU HD1 DCT AREA HD2 DCT AREA HD1 FLO ZERO HD2 FLO ZERO FLO STA TYPE TOP VELOCITY HD1 LOW CAL HD1 HIGH CAL HD2 LOW CAL HD2 HIGH CAL
SETPOINT MENU MIN OFFSET MAX OFFSET
NOTICE If temperature or pressure control is being maintained by the AOC, the
following menu items must also be programmed: Temperature – The temperature
cooling and heating values: VENT MIN SET, TEMP MIN
SET, and TEMP SETP.
Pressure – The pressure differential value: SETPOINT
There are additional programmable software menu items to tailor the controller
to your specific application or increase flexibility. These menu items are not
required to be programmed for the AOC to operate.
Technical Section
49
Programming Example
The laboratory shown is Figure 7 is being initially setup. The required HVAC
information is below the figure.
Figure 7: Laboratory Setup Example
Laboratory Design
Laboratory size 5 foot fume hood
= 12′ x 14′ x 10′ (1,680 ft3). = 250 CFM min 1,000 CFM max
Flow offset
= 100 – 500 CFM*
Ventilation setpoint = 280 CFM* (ACPH = 10)
Supply Cooling Volume = 400 CFM*
Pressure differential = -0.001 in. H2O* Temperature setpoint = 72F
- Value supplied by laboratory designer.
Room Pressure Control System
(1) Model 8681 Adaptive Offset Control System mounted in the laboratory.
(2) A through-the-wall pressure sensor mounted between the corridor
(referenced space) and laboratory (controlled space).
(3) Damper, pressure dependent VAV box or venturi valve with actuator assembly
mounted in supply air duct(s).
(4) Damper, pressure dependent VAV box or venturi valve with actuator assembly
mounted in exhaust air duct.
(5) Flow station mounted in supply air duct. (Required for non-venturi valve
applications only).
(6) Flow station mounted in general exhaust air duct. (Required for non-
venturi valve applications only).
(7) Flow station mounted in fume hood exhaust duct. (Required for non-venturi
valve applications only).
50
Part Two
Temperature Control System
(1) Temperature Sensor (1000 RTD) mounted in the laboratory. (2) Reheat coil
mounted in supply air duct(s).
Fume Hood Control System (1) Independent SureFlowTM VAV Face Velocity Control system.
Based on the preceding information, and knowing duct sizes, the following required menu items can be programmed:
MENU ITEM
ITEM VALUE
DESCRIPTION
SUP DCT AREA EXH DCT AREA HD1 DCT AREA
1.0 ft2 (12″ x 12″) 0.55 ft2 (10 inch round) 0.78 ft2 (12 inch round)
Supply duct area General exhaust duct area Fume hood duct area
MIN OFFSET
100 CFM
Minimum offset.
MAX OFFSET
500 CFM
Maximum offset.
EXH CONFIG
UNGANGED (Default Value)
Additional menu items to program for temperature and pressure control.
VENT MIN SET COOLING FLOW
280 CFM 400 CFM
10 air changes per hour Required flow to cool laboratory.
TEMP SETP
72F
Laboratory temperature setpoint.
SETPOINT
0.001 in. H2O
Pressure differential setpoint.
Sequence Of Operation
Beginning scenario:
Laboratory is maintaining pressure control; -0.001 in. H2O. Temperature requirement is satisfied. Fume hood sashes are down, total hood exhaust is 250 CFM. Supply air is 280 CFM (maintain ventilation). General exhaust 130 CFM (calculated from below).
Fume hood + General exhaust – Offset = Supply air
250 +
?
– 100 = 280
The fume hood is opened so that the chemists can load experiments into the hood. The face velocity (100 ft/min) is maintained by modulating the fume hood dampers. The total fume hood flow is now 1,000 CFM.
Fume hood + General exhaust – Offset = Supply air
1,000 +
0
– 100 = 900
The supply air volume changes to 900 CFM (1,000 CFM hood exhaust – 100 CFM offset). The general exhaust is closed since no additional exhaust is needed for temperature or ventilation. However, the Digital Interface Module indicates the laboratory is now – 0.0002 in. H2O (not negative enough). The AOC algorithm slowly changes the offset until pressure control is maintained. In this case the offset changes to 200 CFM, which decreases the supply volume by 100 CFM. The additional offset maintains the pressure differential at – 0.001 in. H2O (setpoint).
Fume hood + General exhaust – Offset = Supply air
1,000 +
0
– 200 = 800
Technical Section
51
The hood is shut after the experiments are loaded so the initial conditions prevail.
Fume hood + General exhaust – Offset = Supply air
250
130 – 100 = 280
An oven is turned on and the laboratory is getting warm. The thermostat sends the AOC a signal to switch to temperature minimum (TEMP MIN SET). This increases the supply air to 400 CFM. The general exhaust air must also increase (damper opens) to maintain flow balance.
Fume hood + General exhaust – Offset = Supply air
250
250 – 100 = 400
The control loop continuously keeps the room balance, room pressure, and temperature control satisfied.
Checkout
The AOC controller should have the individual components checked prior to
attempting control of the laboratory. The checkout procedure outlined below
confirms all hardware is performing correctly. The checkout procedure is not
difficult and catches any hardware problems. The steps are as follows:
Confirm wiring is correct
The most common problem with installed hardware equipment is incorrect wiring.
This problem usually exists on initial installation, or when modifications to
the system take place. The wiring should be very closely checked to verify it
exactly matches the wiring diagram. Polarity must be observed for system to
operate correctly. The TSI® provided cables are all color coded to ensure
proper wiring. A wiring diagram is located in Appendix B of this manual.
Wiring associated with non TSI® components should be closely checked for
correct installation.
Confirming physical installation is correct
All of the hardware components need to be installed properly. Review the
installation instructions and verify components are installed properly at the
correct location. This can be easily confirmed when checking the wiring.
Verifying individual components
Verifying all TSI® components are operating correctly requires following a
simple procedure. The fastest procedure involves first checking the DIM, and
then confirming all component parts are functioning.
NOTICE These checks require power to the AOC and all components.
CHECK – DIM
Press TEST key to verify Digital Interface Module (DIM) electronics are
functioning correctly. At the end of the self test, the display shows SELF
TEST – PASSED if DIM electronics are good. If unit displays DATA ERROR at the
end of the test, the electronics may be corrupted. Check all software items to
determine cause of DATA ERROR.
52
Part Two
If SELF TEST – PASSED was displayed proceed to check individual components.
Enter Diagnostics and Flow Check Menu to check the following: Control output –
supply (if controlling supply air). Control output – exhaust (if controlling
exhaust air). Control output – reheat (if controlling reheat valve). Sensor
input (if pressure sensor is installed). Sensor status (if pressure sensor
installed). Temperature input. General exhaust flow station. Supply flow
station. Fume hood flow station.
The menu items are explained in detail in the Menu and Menu Items section of
the manual, so their function is not reviewed here. If the AOC system passes
each of the checks, the mechanical piece parts are all functioning correctly.
CHECK – Control output – supply
Enter CONTROL SUP menu item in diagnostics menu. A number between 0 and 255 is
displayed. Press the / keys until either 0 or 255 shows on the display. Note
the position of the supply air control damper. If display reads 0, press the
key until 255 is shown on display. If display reads 255, press key until 0 is
shown on display. Note the position of the supply air damper. The damper
should have rotated either 45 or 90 degrees depending on actuator installed.
CHECK – Control output – exhaust
Enter CONTROL EXH menu item in diagnostics menu. A number between 0 and 255 is
displayed. Press the / keys until either 0 or 255 shows on the display. Note
the position of the general exhaust control damper. If display reads 0, press
the key until 255 is shown on display. If display reads 255, press key until 0
is shown on display. Note the position of the general exhaust damper. The
damper should have rotated either 45 or 90 degrees depending on actuator
installed.
CHECK – Control output – temperature
Enter CONTROL TEMP menu item in diagnostics menu. A number between 0 and 255
is displayed. Press the / keys until either 0 or 255 shows on the display.
Note the position of the reheat valve. If display reads 0, press the key until
255 is shown on display. If display reads 255, press key until 0 is shown on
display. Note the position of the reheat valve. The valve should have rotated
either 45 or 90 degrees depending on actuator installed.
CHECK – Sensor input
Enter SENSOR INPUT menu item in diagnostics menu. A voltage between 0 and 10
volts DC is displayed. It is not important what the exact voltage is to pass
this test. Tape over the pressure sensor (slide pressure sensor door open) and
voltage should read approximately 5 volts (zero pressure). Remove tape and
blow on sensor. Displayed value should change. If voltage changes, the sensor
is functioning correctly. If voltage doesn’t change, proceed to CHECK – Sensor
status.
CHECK – Sensor status
Enter SENSOR STAT menu item in diagnostics menu. If NORMAL is displayed, the
unit passes test. If an error message is displayed, go to diagnostics menu
section of the manual, SENSOR STAT menu item for explanation of error message.
Technical Section
53
CHECK Temperature sensor input Enter TEMP INPUT menu item in diagnostics
menu. When this item is entered, a temperature, via a 1000 platinum RTD, is
indicated on the display. The exact temperature displayed is relatively
unimportant. It is more important that the temperature is changing which
indicates the sensor is working correctly.
CHECK – Flow station The Flow Check menu lists all the flow stations that can
be installed. Check each flow station menu item that has a flow station
attached. Enter FLOW IN menu item and the actual flow is displayed. If the
flow is correct, no changes need to be made. If flow is incorrect, adjust the
corresponding DCT AREA until actual flow matches flow station reading.
If unit passed all checks, the mechanical components are physically working.
54
Part Two
Calibration
The calibration section explains how to calibrate and set the elevation for
the AOC pressure sensor and how to zero a flow station.
NOTICE The pressure sensor is factory calibrated and normally does not need to
be adjusted. However, inaccurate readings may be detected if pressure sensor
is not installed correctly, or problems with the sensor exists. Before
calibrating, check that the sensor is installed correctly (usually only a
problem on initial set up). In addition, go into DIAGNOSTICS menu, SENSOR STAT
item. If NORMAL is displayed, calibration can be adjusted. If an error code is
displayed, eliminate error code and then verify pressure sensor needs
adjustment.
Adjusting the SureFlowTM pressure sensor calibration may be required to
eliminate errors due to convection currents, HVAC configuration, or equipment
used to make the measurement. TSI® recommends always taking the comparison
measurement in the exact same location (i.e., under the door, middle of door,
edge of door, etc.). A thermal air velocity meter is needed to make the
comparison measurement. Normally the velocity is checked at the crack under
the doorway, or the door is opened 1″ to allow alignment of the air velocity
probe making the measurement. If the crack under the door is not large enough,
use the 1″ open door technique.
All pressure transducer based flow stations and 1 to 5 VDC linear flow
stations must be zeroed upon initial system set up. Linear 0 to 5 VDC flow
stations do not require a zero flow to be established.
Calibrating Pressure Sensor Enter calibration menu (see Software Programming
if not familiar with key stroke procedure). Access code is turned on so enter
access code. All menu items described below are found in CALIBRATION menu.
Elevation The ELEVATION item eliminates pressure sensor error due to elevation
of building. (See ELEVATION item in Menu and Menu Items section for further
information).
Enter the ELEVATION menu item. Scroll through the elevation list and select
the one closest to the building’s elevation. Press the SELECT key to save the
data and exit back to the calibration menu.
Figure 8: Pressure Sensor Door Slid Open
Technical Section
55
Sensor span NOTICE
A smoke test and a comparison measurement by an air velocity meter are
required to calibrate the pressure sensor. The air velocity meter only gives a
velocity reading, so a smoke test must be performed to determine pressure
direction.
WARNING
The span can only be adjusted in the same pressure direction. Adjusting span
cannot cross zero pressure. Example: If unit displays +0.0001 and actual
pressure is -0.0001, DO NOT make any adjustments. Manually change the air
balance, close or open dampers, or open door slightly to get both unit and
actual pressure to read in same direction (both read either positive or
negative). This problem can only occur at very low pressures so slightly
changing the balance should eliminate the problem.
Perform a smoke test to determine pressure direction. 1. Select SENSOR SPAN
item. 2. Position thermal air velocity meter in door opening to obtain
velocity reading. Press
/ keys until pressure direction (+/-) and sensor span match thermal air
velocity meter, and smoke test. 3. Press SELECT key to save sensor span. 4.
Exit menu, calibration is complete.
Flow station pressure transducer zero NOTICE
Not required for linear flow stations with 0 to 5 VDC output.
Pressure based flow station
1. Disconnect tubing between pressure transducer and flow station. 2. Enter
menu item that corresponds to flow station: Hood flow, Exhaust Flow, or
Supply flow. 3. Select HD1 FLO ZERO or HD2 FLO ZERO to take a fume hood flow
station zero.
or 4. Select EXH FLO ZERO to take a general exhaust flow station zero.
or 5. Select SUP FLO ZERO to take a supply flow station zero. 6. Press SELECT
key. Flow zero procedure, which takes 10 seconds, is automatic. 7. Press
SELECT key to save data. 8. Connect tubing between pressure transducer and
flow station.
Linear flow station 1 to 5 VDC output
1. Remove flow station from duct, or cutoff flow in duct. Flow station must
have no flow going past the sensor.
2. Enter menu item that corresponds to flow station location: Hood flow,
Exhaust Flow, or Supply flow.
56
Part Two
3. Select HD1 FLO ZERO or HD2 FLO ZERO to take a fume hood flow station zero.
or
4. Select EXH FLO ZERO to take a general exhaust flow station zero. or
5. Select SUP FLO ZERO to take a supply flow station zero.
6. Press SELECT key. Flow zero procedure, which takes 10 seconds, is
automatic.
7. Press SELECT key to save data. 8. Install flow station back in duct.
2-Point Flow Calibration Supply and General Exhaust Flow Calibration: 1. Enter
menu that corresponds to flow calibration: Supply Flow, Exhaust Flow.
2. Select SUP LOW SETP to enter a supply flow low calibration setpoint. or
Select EXH LOW SETP to enter a general exhaust flow low calibration setpoint.
The DIM displays a value between 0% OPEN and 100% OPEN. Press the or keys to
adjust the value displayed (and the damper position). Using a voltmeter, read
the input voltage from the appropriate pressure transducer. When the voltmeter
reading is approximately 20% of the full flow reading (100% OPEN) press the
SELECT key to save the data. then Select SUP HIGH SETP to enter a supply flow
low calibration setpoint. or 3. Select EXH HIGH SETP to enter a general
exhaust flow low calibration setpoint. The DIM displays a value between 0%
OPEN and 100% OPEN. Press the or keys to adjust the value displayed (and the
damper position). Using a voltmeter, read the input voltage from the
appropriate pressure transducer. When the voltmeter reading is approximately
80% of the full flow reading (100% OPEN) press the SELECT key to save the
data. then Select SP LOW CAL to enter a supply flow low calibration value. or
Select EX LOW CAL to enter a general exhaust flow low calibration value. The
DIM displays two air flow values. Press the or keys to adjust the value
displayed on the right to match the actual measured airflow, which is obtained
with a duct traverse measurement or with a capture hood measurement.
4. Press SELECT key to save data. then Select SUP HIGH CAL to enter a supply
flow high calibration value. or
Technical Section
57
Select EXH HIGH CAL to enter a general exhaust flow high calibration value.
The DIM displays two airflow values. Press the or keys to adjust the value
displayed on the right to match the actual measured airflow, which is obtained
with a duct traverse measurement or with a capture hood measurement.
5. Press SELECT key to save data.
Hood Flow Calibration
1. Enter HOOD CAL menu. Raise the fume hood sash, of a previously calibrated
fume hood, from fully closed to an approximate height of 12”. Select the
corresponding HD# LOW CAL menu item.
2. The DIM displays two airflow values. Press the or keys to adjust the value
displayed on the right to match the actual airflow, which is obtained with a
duct traverse measurement or by calculating the volumetric flow. Calculated
volumetric flow can be determined by multiplying on the current sash open area
by the displayed face velocity.
3. Press SELECT key to save data.
then
Raise the fume hood sash above the low flow calibration, or to its sash stop
(approximately 18″). Select the corresponding HD# HIGH CAL menu item. The DIM
displays two airflow values. Press the or keys to adjust the value displayed
on the right to match the actual airflow, which is obtained with a duct
traverse measurement or by calculating the volumetric flow. Calculated
volumetric flow can be determined by multiplying on the current sash open area
by the displayed face velocity.
4. Press SELECT key to save data.
NOTICE
Insert number of flow calibration you are performing.
A low flow calibration must be performed before its associated high flow
calibration is performed. For example, in a laboratory that has two separate
supply flows, SUP LOW CAL must be completed before SUP HIGH CAL.
It is acceptable to complete all low flow calibrations before completing their
associated high flow calibrations. To continue with the previous example: HD1
LOW CAL and HD2 LOW CAL could both be completed before completing HD1 HIGH CAL
and HD2 HIGH CAL.
Fume hood face velocity calibration must be completed before beginning fume
hood flow calibration.
58
Part Two
Maintenance and Repair Parts
The Model 8681 SureFlowTM Adaptive Offset Controller requires minimal
maintenance. Periodic inspection of system components as well as an occasional
pressure sensor cleaning are all that are needed to ensure that the Model 8681
is operating properly.
System Component Inspection It is recommended that the pressure sensor be
periodically inspected for accumulation of contaminants. The frequency of
these inspections is dependent upon the quality of the air being drawn across
the sensor. Quite simply, if the air is dirty, the sensors require more
frequent inspection and cleaning.
Visually inspect the pressure sensor by sliding open the sensor housing door
(Figure 9). The air flow orifice should be free of obstructions. The small
ceramic coated sensors protruding from the orifice wall should be white and
free of accumulated debris.
Figure 9: Pressure Sensor Door Slid Open
Periodically inspect the other system components for proper performance and
physical signs of excessive wear.
Pressure Sensor Cleaning Accumulations of dust or dirt can be removed with a
dry soft-bristled brush (such as an artist’s brush). If necessary, water,
alcohol, acetone, or trichlorethane may be used as a solvent to remove other
contaminants.
Use extreme care when cleaning the velocity sensors. The ceramic sensor may
break if excessive pressure is applied, if sensor is scraped to remove
contaminants, or if the cleaning apparatus abruptly impacts the sensor.
WARNING
If you are using a liquid to clean the sensor, turn off power to the Model
8681. DO NOT use compressed air to clean the velocity sensors. DO NOT attempt
to scrape contaminants from the velocity sensors. The velocity sensors
are quite durable; however, scraping may cause mechanical damage and possibly
break the sensor. Mechanical damage due to scraping voids the pressure sensor
warranty.
Technical Section
59
Flow Station Inspection / Cleaning
The flow station can be inspected by removing mounting screws and visually
examining probe. Pressure based flow stations can be cleaned by blowing
compressed air into the low and high pressure taps (flow station does not need
to be removed from duct). Linear flow stations (thermal anemometer type) can
be cleaned with a dry soft-bristled brush (such as an artist’s brush). If
necessary, water, alcohol, acetone, or trichlorethane may be used as a solvent
to remove other contaminants.
Replacement Parts
All components of the room pressure controller are field replaceable. Contact
TSI® HVAC Control Products at
800-680-1220 (U.S. and Canada) or (001
651) 490-2860 (other countries) or your nearest TSI® Manufacturer’s
Representative for replacement part pricing and delivery.
Part Number 800776 or 868128
800326 800248 800414 800420 800199 800360
Description 8681 Digital Interface Module / Adaptive Offset Controller 8681-BAC Digital Interface Module / Adaptive Offset Controller Pressure Sensor Sensor Cable Transformer Cable Transformer Controller Output Cable Electric Actuator
60
Part Two
Appendix A
Specifications
Dim and AOC Module Display
Range ………………………………………………………… -0.20000 to +0.20000 inches H2O Accuracy
…………………………………………………….. ±10% of reading, ±0.00001 inches H2O
Resolution…………………………………………………… 5% of reading Display Update …………………………………………….
0.5 sec
Inputs type.
See Wiring Information Appendix C for
Flow Inputs …………………………………………………. 0 to 10 VDC . Temperature Input
……………………………………….. 1000 Platinum RTD
(TC: 385 /100C)
Outputs
Alarm Contact ……………………………………………… SPST (N.O.) Max current 2A Max voltage 220
VDC Maximum power 60 W Contacts close in alarm condition
Supply Control …………………………………………….. 0 to 10 VDC Exhaust Control
…………………………………………… 0 to 10 VDC Reheat Control ……………………………………………. 0 to 10 VDC or
4 to 20 mA RS-485……………………………………………………….. Modbus RTU BACnet®
MSTP……………………………………………. Model 8681-BAC only
General
Operating Temperature ………………………………… 32 to 120°F Input Power
………………………………………………… 24 VAC, 5 watts max Dim Dimensions ………………………………………….. 4.9
in. x 4.9 in. x 1.35 in. Dim Weight …………………………………………………. 0.7 lb.
Pressure Sensor
Temperature Compensation Range ……………….. 55 to 95°F Power
Dissipation………………………………………… 0.16 watts at 0 inches H2O,
0.20 watts at 0.00088 inches H2O Dimensions (DxH) ……………………………………….. 5.58 in. x
3.34 in. x 1.94 in. Weight………………………………………………………… 0.2 lb.
Damper/Actuator
Types of Actuator ………………………………………… Electric Input Power …………………………………………………
Electric: 24 VAC, 7.5 watts max. Control Signal Input …………………………………….. 0 volts
damper closed Time for 90° Rotation……………………………………. Electric: 1.5 seconds
61
(This page intentionally left blank)
62
Appendix A
Appendix B
Network Communications
Network communications are available on the Model 8681 and Model 8681-BAC. The
Model 8681 can communicate with a building management system through Modbus®
protocol. The Model 8681-BAC can communicate with a building management system
through BACnet® MSTP protocol. Please refer to the appropriate section below
for more detailed information.
Modbus Communications
Modbus communications are installed in the Model 8681 adaptive offset room
pressure controllers. This document provides the technical information needed
to communicate between the host DDC system and the Model 8681 units. This
document assumes the programmer is familiar with Modbus® protocol. Further
technical assistance is available from TSI® if your question is related to
TSI® interfacing to a DDC system. If you need further information regarding
Modbus programming in general, please contact:
Modicon Incorporated (a division of Schneider-Electric) One High Street North
Andover, MA 01845 Phone 800-468-5342
The Modbus® protocol utilizes the RTU format for data transfer and Error
Checking. Check the Modicon Modbus Protocol Reference Guide (PI-Mbus-300) for
more information on CRC generation and message structures.
The messages are sent at 9600 baud with 1 start bit, 8 data bits, and 2 stop
bits. Do not use the parity bit. The system is set up as a master slave
network. The TSI units act as slaves and respond to messages when their
correct address is polled.
Blocks of data can be written or read from each device. Using a block format
speeds up the time for the data transfer. The size of the blocks is limited to
20 bytes. This means the maximum message length that can be transferred is 20
bytes. The typical response time of the device is around 0.05 seconds with a
maximum of 0.1 seconds.
Unique to TSI® The list of variable addresses shown below skips some numbers
in the sequence due to internal Model 8681 functions. This information is not
useful to the DDC system and is therefore deleted. Skipping numbers in the
sequence will not cause any communication problems.
All variables are outputted in English units: ft/min, CFM, or inches H20. The
room pressure control setpoints and alarms are stored in ft/min. The DDC
system must convert the value to inches of water if that is desired. The
equation is given below.
Pressure in inches H2O = 6.210-8(Velocity in ft/min / .836)2
RAM Variables RAM variables use the Modbus command 04 Read Input Registers.
RAM variables are read only variables that correspond to what is shown on the
Digital Interface Module (DIM) display. TSI offers a number of different
models, so if a feature is not available on a unit, the variable is set to 0.
63
Variable Name Room Velocity Room Pressure
Variable Address 0 1
Space
2
Temperature
Supply Flow Rate 3
General Exhaust 4 Flow Rate
Hood #1 Flow
5
Rate
Hood #2 Flow
6
Rate
Total Exhaust
7
Flow Rate
Supply Flow
8
Setpoint
Minimum Supply 9
Flow Setpoint
General Exhaust 10
Flow Setpoint
Current Offset
11
Value
Status Index
12
Supply % Open 16 Exhaust % Open 17
Temperature % 18
Open
Current
19
Temperature
Setpoint
8681 RAM Variable List Information Provided to Master System Velocity of room
pressure Room pressure
Current temperature value
Integer DDC System Receives Displayed in ft/min. Displayed in inches H2O.
Host DDC system must divide value by 100,000 to report pressure correctly.
Displayed in F.
Flow (CFM) measured by the supply duct flow station Flow measured by flow station connected to general exhaust input Flow measured by flow station connected to hood input #1 Flow measured by flow station connected to hood input #2 Total exhaust out of laboratory
Displayed in CFM. Displayed in CFM.
Displayed in CFM. Displayed in CFM. Displayed in CFM.
Current supply setpoint
Displayed in CFM.
Minimum flow setpoint for ventilation. Current general exhaust setpoint Current offset value
Displayed in CFM. Displayed in CFM. Displayed in CFM.
Status of SureFlowTM device
Current supply damper position Current exhaust damper position Current
temperature control valve position Current temperature control setpoint
0 Normal 1 Alarm = Low Pressure 2 Alarm = High Pressure 3 Alarm = Max Exhaust
4 Alarm = Min Supply 5 Data Error 6 Emergency Mode 0 to 100% is displayed 0 to
100% is displayed
0 to 100% is displayed
Displayed in F.
64
Appendix B
EXAMPLE of 04 Read Input Registers function format. This example read variable addresses 0 and 1 (Velocity and Pressure from 8681).
Query Field Name Slave Address Function Starting Address Hi Starting Address Lo No. Of Points Hi No. Of Points Lo Error Check (CRC)
(Hex) 01 04 00 00 00 02 —
Response Field Name Slave Address Function Byte Count Data Hi Addr0 Data Lo Addr0 Data Hi Addr1 Data Lo Addr1 Error Check (CRC)
(Hex) 01 04 04 00 64 (100 ft/min) 00 59 (.00089 “H2O) —
XRAM Variables
These variables can be read using Modbus command 03 Read Holding Registers.
They can be
written to using Modbus command 16 Preset Multiple Regs. Many of these
variables are the same “menu items” that are configured from the SureFlowTM
controller keypad. The calibration and control items are not accessible from
the DDC system. This is for safety reasons, since each room is individually
setup for maximum performance. TSI® offers a number of different models, so if
a feature is not available on a unit, the variable is set to 0.
Variable Name Software Version
(read only) Control Device
(read only) Emergency Mode*
Variable Address 0
1
2
8681 XRAM Variable List Input Provided to Master System Current software
version
SureFlowTM Model
Emergency Mode Control
Occupancy Mode 3
Pressure Setpoint 4
Ventilation
5
Minimum Supply
Flow Setpoint
Cooling Flow
6
Setpoint
Unoccupied
7
Minimum Supply
Flow Setpoint
Maximum Supply 8
Flow Setpoint
Minimum Exhaust 9
Flow Setpoint
Occupancy mode device is in
Pressure control setpoint
Minimum supply flow control setpoint in normal mode
Minimum supply flow control setpoint in temperature mode Minimum supply flow
control setpoint in unoccupied mode
Maximum supply flow control setpoint Minimum exhaust flow control setpoint
Integer DDC System Receives 1.00 = 100
6 = 8681
0 Leave emergency mode 1 Enter emergency mode Value returns a 2 when read 0
Occupied 1 Unoccupied Displayed in feet per minute. Displayed in CFM.
Displayed in CFM.
Displayed in CFM.
Displayed in CFM.
Displayed in CFM.
Network/Modbus Communications
65
Variable Name Occupied Temperature Setpoint Minimum Offset Maximum Offset Low Alarm Setpoint
Variable Address 10
11 12 13
High Alarm Setpoint 14
Minimum Supply 15
Alarm
Maximum Exhaust 16
Alarm
Units
22
Unoccupied
75
Temperature
Setpoint
8681 XRAM Variable List Input Provided to Master System Occupied Mode Temperature setpoint
Integer DDC System Receives Displayed in F.
Minimum offset setpoint Maximum offset setpoint Low pressure alarm setpoint
High pressure alarm setpoint
Minimum supply flow alarm
Displayed in CFM. Displayed in CFM. Displayed in feet per minute. Displayed in feet per minute. Displayed in CFM.
Maximum general exhaust alarm Displayed in CFM.
Current pressure units displayed
Unoccupied Mode Temperature setpoint
0 Feet per minute 1 meters per second 2 inches of H2O 3 Pascal
Displayed in F.
EXAMPLE of 16 (10 Hex) Preset Multiple Regs function format: This example changes the setpoint to 100 ft/min.
Query Field Name Slave Address Function Starting Address Hi Starting Address Lo No. Of Registers Hi No. Of Registers Lo Data Value (High) Data Value (Low) Error Check (CRC)
(Hex) 01 10 00 04 00 01 00 64 —
Response Field Name Slave Address Function Starting Address Hi Starting Address Lo No. of Registers Hi No. of Registers Lo Error Check (CRC)
(Hex) 01 10 00 04 00 01 —
Example of 03 Read Holding Registers function format: This example reads the minimum ventilation setpoint and the minimum temperature setpoint.
Query Field Name Slave Address Function Starting Address Hi Starting Address Lo No. Of Registers Hi No. Of Registers Lo Error Check (CRC)
(Hex) 01 03 00 05 00 02 —
Response Field Name Slave Address Function Byte Count Data Hi Data Lo Data Hi Data Lo Error Check (CRC)
(Hex) 01 03 04 03 8E (1000 CFM) 04 B0 (1200 CFM) —
66
Appendix B
8681 BACnet® MS/TP Protocol Implementation Conformance Statement
Date: April 27, 2007 Vendor Name: TSI Incorporated Product Name: SureFlow Adaptive Offset Controller Product Model Number: 8681-BAC Applications Software Version: 1.0 Firmware Revision: 1.0 BACnet Protocol Revision: 2
Product Description:
TSI® SureFlowTM Room Pressure Controls are designed to maintain more exhaust
from a laboratory than is supplied to it. This negative air balance helps
ensure that chemical vapors
cannot diffuse outside the laboratory, complying with requirements in NFPA
45-2000 and
ANSI Z9.5-2003. The SureFlowTM controller Model 8681 also controls the
temperature of the laboratory space by modulating reheat and the supply air
volume. Optionally, a room pressure
sensor can be connected to the SureFlowTM Model 8681 controller to correct
long-term changes in the building dynamics. This model controller is capable
of acting as a stand-alone device or as part of a building automation system
via BACnet® MS/TP protocol.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B
DM-DDB-B
DS-WP-B
DM-DOB-B
DS-RPM-B
DM-DCC-B
Segmentation Capability:
Segmented requests not supported Segmented responses not supported
Network/Modbus Communications
67
Standard Object Types Supported:
Analog Input Analog Value
Binary Input
Binary Value
Multi-state Input Multi-state Value Device Object
Dynamically Createable
No No
No
No
No
No
No
Dynamically Deletable
No No
No
No
No
No
No
Optional Properties Supported
Active_Text, Inactive_Text Active_Text, Inactive_Text State_Text
State_Text
Writable Properties (Data Type)
Present_Value (Real)
Present_Value (Enumerated)
Present_Value (Unsigned Int) Object Name (Char String) Max Master (Unsigned
Int)
Data Link Layer Options: BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) MS/TP master (Clause 9), baud rate(s): 76.8k 38.4k, 19.2k, 9600 bps MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11), medium: Other:
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way
communication with MS/TP slaves and certain other devices.) Yes No
Networking Options: Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD)
Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4 ISO 10646 (UCS-2)
IBM®/Microsoft® DBCS ISO 10646 (UCS-4)
ISO 8859-1 JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: Not Applicable
68
Appendix B
Model 8681-BAC BACnet® MS/TP Object Set
Object Type Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value Analog Value
Device Instance
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 12 13 14
*Units ft/min, m/s, in. H2O,
Pa
cfm, l/s
Description Room Pressure
Supply Flow Rate
cfm, l/s cfm, l/s
General Exhaust Flow Rate Hood Flow Rate
cfm, l/s
Supply Flow Setpoint
cfm, l/s cfm, l/s
General Exhaust Flow Setpoint Current Flow Offset
°F, °C
Temperature
% Open % Open % Open
Supply Damper Position Exhaust Damper Position Reheat Valve Position
MAC Address
ft/min, m/s, in. H2O, Pa
ft/min, m/s, in. H2O, Pa
ft/min, m/s, in. H2O, Pa
cfm, l/s
Room Pressure Setpoint Low Pressure Alarm
High Pressure Alarm
Vent Min Setpoint
cfm, l/s
Cooling Flow Setpoint
cfm, l/s
Unocc Flow Setpoint
cfm, l/s
Min Offset
cfm, l/s
Max Offset
cfm, l/s
Max Supply Setpoint
cfm, l/s
Min Exhaust Setpoint
cfm, l/s
Min Supply Alarm
cfm, l/s
Max Exhaust Alarm
°F, °C
Temperature Setpoint
1 to 127
-0.19500 to 0.19500 in. H2O -0.19500 to 0.19500 in. H2O -0.19500 to 0.19500 in. H2O 0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
0 to 30,000 cfm
50 to 85 °F
Network/Modbus Communications
69
Object
Device
Type
Instance
*Units
Description
Analog Value
15
°F, °C
Unocc Temp Setpoint 50 to 85 °F
Binary Value
1
Occ/Unocc Mode
0 Occupied 1 Unoccupied
Multi-State
Status Index
1 Normal
Input
2 Low Press Alarm
3 High Press Alarm
1
4 Max Exhaust Alarm
5 Min Supply Alarm
6 Data Error
7 Emergency
Multi-State
Emergency Mode
1 Exit Emergency Mode
Value
2
2 Enter Emergency Mode
3 Normal
Multi-State
Units Value
1 ft/min
Value
3
2 m/s 3 in. H2O
4 Pa
Device 868001**
TSI8681
- The units are based on the value of the Units Value object. When the Units Value is set to 1 or 3
the units are in English form. When the Units Value is set to 2 or 4 the units are metric. English is
the default value.
** The device instance is 868000, summed with the MAC address of the device.
70
Appendix B
Appendix C
Wiring Information
Back Panel Wiring
PIN # 1, 2
Input / Output / Communication DIM / AOC Input
3, 4 5, 6 7, 8 9, 10
Output Input Communications Output
11, 12 Input 13, 14 Output
15, 16 Communications
17, 18 Output
19, 20 Input
21, 22 Input 23, 24 Input 25, 26 Output
27, 28 Input
Description
24 VAC to power Digital Interface Module (DIM).
NOTICE
24 VAC becomes polarized when connected to DIM. 24 VAC power for Pressure
Sensor 0 to 10 VDC pressure sensor signal RS-485 communications between DIM
and pressure sensor 0 to 10 VDC, general exhaust control signal. 10 VDC = open
(n.o. damper)
– See menu item CONTROL SIG 0 to 10 VDC flow station signal – fume exhaust
(HD1 FLOW IN). Alarm relay – N.O., closes in low alarm condition.
– See menu item ALARM RELAY RS – 485 communications; AOC to building
management system. 0 to 10 VDC, supply air control signal. 10 VDC = open (n.o.
damper)
– See menu item CONTROL SIG 0 to 10 VDC flow station signal – General exhaust
(EXH FLOW IN) . 0 to 10 VDC flow station signal – Supply air (SUP FLOW IN).
1000 platinum RTD temperature input signal 0 to 10 VDC, reheat valve control
signal. 10 VDC = open (n.o. damper)
– See menu item REHEAT SIG 0 to 10 VDC flow station signal – fume exhaust (HD2
FLOW IN). BACnet® MSTP communications to building management system.
WARNING
The wiring diagram shows polarity on many pairs of pins: + / -, H / N, A / B.
Damage to DIM may occur if polarity is not observed.
NOTICES
Terminals 27 & 28 are utilized for BACnet® MSTP communications for Model
8681-BAC.
The Model 8681-BAC controller cannot accept a second fume hood flow input; and
all second fume hood flow menu items will be deleted from the menu structure.
71
WARNING
Controller must be wired exactly as wire diagram shows. Making modifications
to the wiring may severely damage the unit.
Figure 10: Adaptive Offset Wiring Diagram – Damper System with Electric
Actuator
72
Appendix C
WARNING
Controller must be wired exactly as wire diagram shows. Making modifications
to the wiring may severely damage the unit.
Figure 11: Offset (Flow Tracking) Wiring Diagram – Damper System with Electric
Actuator
Wiring Information
73
(This page intentionally left blank)
74
Appendix C
Appendix D
Access Codes
There is one access code for all menus. Each menu can have the access code ON or OFF. If ON the access code must be entered. Pressing the key sequence below allows access to the menu. The access code must be entered within 40 seconds and each key must be pressed within 8 seconds. Incorrect sequence will not allow access to the menu.
Key # 1 2 3 4 5
Access Code Emergency Mute Mute Menu Aux
75
(This page intentionally left blank)
76
Appendix D
TSI Incorporated Visit our website www.tsi.com for more information.
USA UK France Germany
Tel: +1 800 680 1220 Tel: +44 149 4 459200 Tel: +33 1 41 19 21 99 Tel: +49 241 523030
India
Tel: +91 80 67877200
China
Tel: +86 10 8219 7688
Singapore Tel: +65 6595 6388
P/N 1980476 Rev. F
©2024 TSI Incorporated
Printed in U.S.A.