BLUE SEA 1841 M2 OLED Temperature Monitor User Manual
- June 3, 2024
- BLUE SEA
Table of Contents
- Installation Checklist
- Specifications
- Warning and Caution Symbols
- Installation
- Mounting Templates
- Mounting Considerations
- Pin-out Table
- Meter Power Supply Connections
- Temperature Connections
- Detailed Wiring
- M2 Relay Connections
- Getting Started
- Other Display Indications
- Alarm Setup & Control
- Relay Setup & Control
- Display Setup
- Temperature Channel Setup
- Additional Temperature Settings
- Software Upgrade
- Documents / Resources
1841 M2 OLED Temperature Monitor
User Manual
M2 OLED Temperature Monitor Instructions
PN 1841
Installation Checklist
- Check for components included
- Read Warning and Cautions
- Read page 3 for mounting instructions
- Read System Overview, Mounting Considerations, Detailed Wiring, and Sensing Description
- Follow Initial System Setup instructions
- Configure Displays
- Configure Alarms
- Configure Relays
Specifications
Display Size | 55mm x 28mm |
---|---|
Power Supply | 7V–70V DC |
Power Consumption | 0.3W–1.0W* |
Sensors | Blue Sea Systems PN (1821) |
Sensor Range | -40°F – 250°F (-40°C –120°C) |
Sensor Resolution | 1% |
Temp Alarms | 80dB |
External Relay | 0.5A DC |
- Variable with voltage, display intensity, and sleep mode
Regulatory
Monitor face is IP66 protected against powerful water jets when installed according to instructions
Warning and Caution Symbols
WARNING: The symbol refers to possible injury to the user or significant
damage to the meter if the user does not follow the procedures.
CAUTION: The symbol refers to restrictions and rules with regard to
preventing damage to the meter.
WARNING
- If you are not knowledgeable about electrical systems, have an electrical professional install this unit. The diagrams in these instructions pertain to the installation of M2 Digital Meters and not to the overall wiring of the vessel.
- If an inverter is installed on the vessel, its power leads must be disconnected at the battery before the meter is installed.
- If an AC generator is installed on the vessel, it must be stopped and rendered inoperable before the meter is installed.
- Verify that no other DC or AC sources are connected to the vessel’s wiring before installing the meter.
CAUTION
- The back of the unit is not waterproof. Do not install where the back of the meter is exposed to water.
Components Included
360 Panel Mounting Kit (PN 1525 sold separately)
Installation
- Make all connections to the meter’s terminal block before connecting the terminal block to the unit. Keep hands away from the terminal block when applying power to the meter.
- As the final DC connection, insert a fuse into the in-line fuse holder on the wire to the positive (+) battery terminal.
Mounting Templates
Mounting Considerations
M2 Digital Meters have three mounting methods: surface mount, flat panel mount, and 360 panel mount. When surface mounted per instructions the unit face is waterproof to IP66. Flat panel and 360 panel mounting systems are not waterproof. The unit should not be flat panel or 360 panel mounted if used in an exposed location. For all mountings, the back of the unit is not waterproof and must be kept dry.
Temperature Functions (1841)
Monitor up to four temperatures. Provides High/Low level alarms for each
channel.
Connections
IMPORTANT! The Sensing Description section of this manual gives important
details to the location of sensors in the AC and DC electrical systems of the
boat. Improper location and configuration of sensors can result in erroneous
readings and possible damage to components.
Pin-out Table
1841 Connector Pin Assignment Table
**8 Pin Connector*** | Functio n |
---|---|
1 Required Connection | DC Negative |
2 Required Connection | DC Supply |
3 | Relay DC Out to Load |
4 | Relay DC + |
5 | Temperature 1 |
6 | Temperature 2 |
7 | Temperature 3 |
8 | Temperature 4 |
USB | Micro USB Port |
*The 8 pin low voltage connector supports wire sizes from 16-26 AWG
Meter Power Supply Connections
All meters must have pins 1 (DC Negative) and 2 (DC Supply) connected. These pins are used to provide power to the meter. Connect pin 1 to ground and pin 2 to a 12V to 48V power source.
Temperature Connections
Use Blue Sea Systems Temperature Sensor 1821 Only use Blue Sea Systems temperature sensor PN 1821. Other temperature sensors may not give the correct temperature result. The negative lead of all the temperature sensors should terminate as close as possible to pin 1. For a simple and clean installation, use Blue Sea Systems PN 2304 as a small common bus bar for all of the meters DC negative connection. There should be one connection between pin 1 of the meter and the bus bar using 18 AWG wire. This connection should be as short as possible to minimize temperature reading errors.
Detailed Wiring
1841 Temperature Monitor
Note : The negative feed of all of the temperature sensors should
terminate as close as possible to pin 1. Use Blue Sea Systems’ PN 2304 Mini
Bus with a short 18 AWG guage wire from pin 1 to the Mini Bus.
Temperature Sensor Connections 1821
M2 Relay Connections
M2 Meters contains an internal MOSFET relay that can drive external DC loads
up to 0.5A. The input is protected with a thermally activated auto-resetting
fuse that will protect against shorts. In addition, an inline fuse rated at 5A
should be used to protect against shorts. In typical applications, a power
source is connected to the Relay+ pin and a load is connected to the Relay Out
to Load connection. External LED
An external LED such 8171 can be connected to the Relay Output terminal. If
the system is going to operate at more than 24V nominal, an additional 4K Ohms
of resistance should be placed in-line with the LED.
External Alarm (1070 Floyd Bell Turbo)
The Relay+ terminal can support an external audible alarm. Such as the Floyd
Bell Turbo Alarm (1070). External Alarm Supply 5 to 30V DC
External Relay
If you need to switch more than 0.5 A, you can use an external relay such as
PN 7713, 12V or PN 7717, 24V Remote Battery Switch. Connect the Relay+
terminal to the red control wire. Activating the internal relay will also
activate PN 7713.
NOTE: 9012, 7700, 7701, 7702, & 7703 Remote Battery Switches are not compatible with the internal relay.
Getting Started
Example Screens From PN 1841 Temperature Meter
When an M2 Meter is initially powered up, it will display the Blue Sea Systems
Logo, its serial number and its Software revision. After a couple of seconds,
the unit will display a high-level System Summary screen.
Pressing any button will display a temporary pop-up menu. Select an option by
pressing the button beneath it. The pop-up menu will disappear after the first
button is pressed.
The menu system is a two dimensional matrix. Pressing the NEXT button will
transition the display between the System Summary screen which displays
summary information for each of the “temperature” channels.
Press the UP or DOWN arrow buttons to display more detailed information about
an input channel or to show a single parameter, such as “T1” in the display
(see example below).
Press the Menu button to bring up the Setup menus. Press the UP and DOWN arrow
buttons to move the cursor over the options and press the Select button to see
a selected display. To return to the previous display, press the Back button.
Other Display Indications
The dotted lines in T4 indicate the Hi and Lo Alarm Levels. The Hi and Lo
Relay levels are not shown. If Display MinMax is on, then split triangles on
the right side of the each graph indicate the minimum and maximum levels. A
single triangle indicates that the minimum and maximum levels are close to
each other. The following temperature error messages may be displayed under
certain error conditions.
HI — The temperature is greater than 275°F (135°C).
LO — The temperature is less than -40°F (-40°C).
NC — The temperature sensor is not connected.
Configuring the Meter
Meter settings can be configured from the Setup menu. This menu can be
accessed by pressing the Menu button and then scrolling to and selecting
Setup. Press the UP and DOWN arrow buttons to move the cursor. The different
setup options are described below.
Alarm Setup & Control
The meter’s alarm can be set to trigger when a temperature exceeds a
threshold. Alarms can be set from the Alarm Setup menu. To get there, first
navigate to the Setup menu. Then scroll to Alarm Setup and press the Select
button.
Setting Alarms
The M2 Meter family provides monitoring capability of temperature input
channels. Alarms are triggered if a channel is above or below a certain user
selected threshold value. The following example indicates how to setup an over
temperature alarm.
- Go to the Alarm Setup menu.
- Scroll to the desired input channel (i.e., Temp. 1 Hi).
- Press the Select button and the cursor should start blinking.
- Set the temperature threshold using the and buttons. (Holding down the buttons allows faster selection)
- Press the Enter button to save the change or the Cancel button to cancel any change.
NOTE: A low temperature level threshold cannot be set above a high temperature threshold. Likewise, a high temperature threshold cannot be set below the low temperature threshold. The meter will automatically increase or decrease the temperature settings to enforce this.
NOTE: The display can be changed from °F to °C in the Display Setup screen.
NOTE: The alarm levels are graphically displayed on the main menu screen.
Temp n Delay
Set the Alarm hold off time in minutes. The hold off timer operates as a
count-up/count-down timer. When the temperature exceeds the alarm value then
the timer will start counting up until it reaches the delay time. When it
reaches the delay timer, an alarm will sound. If the alarm condition goes away
before the delay timer has been met, then the timer will count down until the
timer is zero again. For example, if the Alarm Delay is set for 5 minutes and
an alarm condition is active for 4 minutes and then inactive for 1 minutes
then if the alarm condition is active again, the alarm will sound in 2 minutes
(5 minutes – 4 minutes + 1 minute).
Note that there is only one delay per channel.
Clearing Alarms
When an alarm occurs, the buzzer will sound, the red ALARM LED will light, and
the screen will display which alarm was triggered, the Alarm set point and the
current value. Pressing any button silences the buzzer and another button
press returns to the previous display.
Until the cause of the alarm is resolved, the ALARM LED will remain on and the
channel that triggered the alarm will blink.
Viewing Alarms Status
For any active alarm, the parameter will flash if it is displayed. To view a
complete list of active alarms, press Menu>Setup>Alarm Setup. Any active alarm
will flash. You may have to scroll through the menu to see all of the alarms.
Relay Setup & Control
M2 Meters provide an option to control an external relay. The M2 can trigger
the relay based on high or low temperature levels. These relay options can be
set from the Relay Setup menu. To get there, first navigate to the Setup menu.
Then scroll to Relay Setup and press the Select button.
Relay Normally On/Off
This setting sets the normal operating state of the connected relay. The
options are ON or OFF where ON means the relay is on (contacts closed) in
normal operation and OFF means it is normally off (open contacts). Scroll to
Relay Normally, press Select (selection will flash), then press the LEFT or
RIGHT arrow buttons to change the setting. Press Enter to save your selection.
Press Cancel to cancel a change.
Notification
The Notification setting controls whether or not a notification is displayed
when a relay is activated. Notifications will show which relay threshold was
surpassed and for which channel. Scroll to Notification and press Select to
change the setting. Press the LEFT or RIGHT arrow buttons to choose either ON
or OFF. ON will display notifications and OFF will not. Use this option if you
don’t want to be notified that the relay is activating. Press Enter to save
the setting or Cancel to cancel a change.
Silence Relay
Turn this option on if you want the relay to de-activate after the user
presses a key on the display. The key press will only de-activate the relay
and will not engage any functions on the meter. For example, this option could
be used to silence an external buzzer. Scroll to Silence and press Select to
change the setting. Press the LEFT or RIGHT arrow buttons to choose either ON
or OFF. Press Enter to save the setting or Cancel to cancel any change.
Temp n Delay (Relay)
Set the Alarm hold off time in minutes. The hold off timer operates as a
count-up/count-down timer. When the temperature exceeds the alarm value then
the timer will start counting up until it reaches the delay time. When it
reaches the delay timer, an alarm will sound. If the alarm condition goes away
before the delay timer has been met, then the timer will count down until the
timer is zero again. For example, if the Alarm Delay is set for 5 minutes and
an alarm condition is active for 4 minutes and then inactive for 1 minutes
then if the alarm condition is active again, the alarm will sound in 2 minutes
(5 minutes – 4 minutes + 1 minute). Note that there is only one delay per
channel.
Viewing Relay Status
To view a complete list of active relays, press Menu>Setup>Relay Setup. Any
active relay will flash.
Setting Input Thresholds
Settings for each channel’s high and low temperature thresholds are provided.
The connected relay’s normal operating state will toggle (change state) if
these thresholds are met. For both high and low thresholds, the activation and
deactivation levels are different to prevent the relay from rapidly toggling
(cycling on and off). Each channel has Hi ON and Hi OFF settings and Lo ON and
Lo OFF settings.
LEGEND
Temp Level
Example. This setting can be used to notify if there is an over heated
wet exhaust line or if the exhaust line is approaching freezing. If the relay
is Normally On (closed) and Temperature 3 is configured as above, then it will
open when the temperature on channel 3 is greater than Temp 3 Hi On (80°C). To
close, the level must drop below Temp3 Hi Off (75°C). Similarly, the relay
will open when the temperature is below Temp3 Lo On (4°C, not shown) and then
close again when the temperature is above Temp3 Lo Off (6°C).
To change one of the settings, scroll to desired setting and press Select.
Press the LEFT or RIGHT arrow buttons to change the temperature value and then
press Enter to save the setting. Press Cancel to cancel the change.
NOTE: Lower threshold settings cannot be set above higher temperature
threshold settings. Similarly, higher temperature thresholds cannot be set
below lower temperature thresholds. The meter will automatically increase or
decrease the temperature thresholds to enforce this.
Clearing Relay Notification
If the Notification option is set to ON then any time the relay is opened
(Normally Off) or closed (Normally On). A message will be displayed on the
main screen. Pressing a key will clear this notification. If Silence is set to
ON then the relay will be opened (Normally Off) or closed (Normally On).
Viewing Relay Status
For any active alarm, the parameter will flash if it is displayed. To view
a complete list of active alarms, press Menu>Setup>Relay Setup. Any active
relay will flash.
Display Setup
The meter display settings can be accessed from the Display Setup menu. From
the setup screen, scroll to Display Setup and press the Select button. The
different display settings are described below. To change a setting, press
Enter and press the LEFT or RIGHT arrow buttons to view the available setting
options. Press Enter to save the setting. Press Cancel to cancel a change.
Brightness
This setting is for adjusting the brightness of the display. The value is a
percentage where 0 % is dimmest and 100 % is brightest.
Sleep Timer
Following a certain period of inactivity, the meter will enter a sleep mode
and will turn off the display. Any button may be pressed to exit the sleep
mode and restore the display. The Sleep Timer sets the number of minutes from
0 to 600 before entering sleep mode. This feature will be disabled by changing
the setting to OFF.
Dim Timer
In addition to sleep mode, the meter can also dim its display after a period
of inactivity. The duration of delay in minutes from 0 to 600 can be adjusted
with this setting. This feature will be disabled by changing the setting to
OFF. By continuously pressing the LEFT button the meter can be placed in AUTO
dim mode. In this mode the meter will automatically dim after two minutes when
the ambient light is low (night mode). When the light comes back on, the meter
will revert to its normal brightness.
Units
The temperature meter can display temperatures in °F or °C. Press the LEFT or
RIGHT arrow buttons to toggle to toggle between the °F or °C.
Display Min/Max
Minimum and maximum temperature indicators can be displayed on the main screen
by turning this setting to on. The minimum and maximum values can be
individually reset in the individual temperature setting menus. The default
setting is off.
Demo Mode
With Demo Mode ON, the meter displays factory programmed values. Changing the
setting to OFF returns the meter to display actual measured values. This mode
is typically used for commercial or promotional purposes. Note: Alarms and
Relay settings will still respond to the actual settings and not the Demo
settings. To enter Demo Mode, press Menu>Setup>Display Setup>Demo Mode. Press
the LEFT or RIGHT arrow buttons to toggle Demo Mode ON or OF
Temperature Channel Setup
Changing System Labels
The M2 allows the user to change the labels that are displayed above each
channel. Each channel can have a maximum of 16 characters however in the
summary screens only the first 11 or 12 characters of the channel label are
displayed.
Changing Label Names
To change the name of a temperature channel, follow the instructions below:
- Navigate to the setup menu for the desired temperature channel. Menu- >Setup->Temp. 1 Setup
- In the battery setup menu, move the cursor to temperature channel name to be changed (indicated by the >> symbol)
- Press Select to enter the name editing mode.
- Use the LEFT and RIGHT arrow buttons to move the cursor over the characters
- When the cursor is over a character, press Enter to edit that character. The cursor will start blinking.
- Use the UP and DOWN arrow buttons to select a new character and press Ok to set that character.
- Once all desired characters have been changed, press the Cancel button to exit the name editing mode.
Note: Although the maximum label length is 14 characters, some screens may only be able to display the first 5 or so characters.
Additional Temperature Settings
The meter provides custom settings for each temperature input. To access these
settings, first go to the Setup menu. Scroll to the desired temperature
channel. The temperature setup settings are described below. To make a change,
scroll to setting and press Enter. Press the LEFT or RIGHT arrow buttons to
view the available setting options. Press Enter to save the setting. Press
Cancel to cancel a change.
Enable
To display the temperature and its measurements, change this setting to ON. If
enable is OFF, the temperature along with its measured values will not be
displayed. However, any associated alarm or relay settings are still activate.
To de-active the alarm or relay, disable them in the Alarm Setup and Relay
Setup menus.
Min/Max Reset
Resets the minimum and maximum values for the temperature channel.
Graph Hi/Graph Lo
On the graphical summary screens, set the highest and lowest value on the
graph. For example, if we were monitoring our ice box temperature, we might
want to have the maximum temperature displayed at 50°F and the minimum value
set to 30°F.
Version Info
The Version Info option in the Setup menu displays the product name, serial
number, and software version. This information will be displayed on a screen
after scrolling to Version Info and pressing Select. Pressing any button will
return to the Setup menu.
Factory Reset
The Factory Reset option in the Setup menu allows the user to restore the
meter’s factory default settings. First scroll to Factory Reset and press
Select. Text will appear asking to confirm or cancel the reset request. Press
Yes to confirm or No to cancel the reset.
Software Upgrade
The meter firmware can be updated in one of two ways. The first option is to
use the Software Upgrade option in the Setup menu. The second option is to
force the meter into upgrade mode on startup. Each method involves using a USB
memory stick connected to the USB port on the back of the meter. The USB port
is a type A/B micro USB port. This port is also known as a Micro USB Host OTG.
Available at Best Buy or Amazon: http://amzn.com/B00J631SU8
CAUTION Removing power or the USB memory stick during the upgrade process
will render the meter inoperable.
Both methods are described below:
Upgrade via Software Upgrade Option
Download a new version from http://www.bluesea.com/m2firmware.
Copy firmware to a USB Memory Stick. The file name should be image.1841.bin.,
where 1841 is the PN of the meter. i.e., image.1841.bin, etc. Remove USB dust
cover plug. Insert memory stick into the USB socket on back of the meter.
Note: You made need an adapter dongle to interface between the memory stick
and the meter (http://a.co/6eHeaMK).
Select Software Upgrade option.
Answer Yes to “Are you sure you want to update the Flash?”
The red LED on the M2 will rapidly flash for about 10 seconds.
If the upgrade was successful, a message with the new software version will be
displayed. If there is an error then a message will be displayed (see error
messages below). Remove USB memory stick. Replace USB dust cover with “USB”
text right side up.
Download a new version from
http://www.bluesea.com/m2.
Copy firmware to a USB Memory Stick. The file name should be image.1841.bin.,
where 1841 is the model number of the meter. i.e., image.1841.bin, etc. Turn
off the power to the unit. Remove USB dust cover plug. Insert the memory stick
into the USB socket on back of the unit.
Note: You made need an adapter dongle to interface between the memory stick
and the meter: (http://a.co/6eHeaMK).
While pressing and holding the leftmost and rightmost keys, turn the power to
the meter ON. The red LED on the M2 will rapidly flash for about 10 seconds.
If the upgrade was successful, a message with the new software version will be
displayed. If there is an error then a message will be displayed (see error
message below). Remove USB memory stick. Replace USB dust cover with USB label
facing up. Upgrade via Forcing Meter into Upgrade Mode
Upgrade Messages
Flash Successful / SW Version: xxx – Upgrade successful. File Not Found – A
valid flash image was not found on the meter. The downloaded upgrade filename
should be image.1841.bin, where xxxx is the model number of the meter. i.e.,
image.1830.bin, image.1841.bin, etc. Corrupted File – The image is not valid
or corrupted. Re-download the updated image from
www.bluesea.com. No USB Device – The USB memory
card is not plugged in or the cable is defective. Wrong Model Number – The
image file is for a different meter. Download a new file from
www.bluesea.com/m2firmware. Wrong HW
Version – The new image file does not support this revision of hardware.
14 425 Sequoia Drive
Bellingham, WA 98226 USA
p 360.738.8230
p 800.222.7617 USA and Canada Customer Service f 360.734.4195
conductor@bluesea.com
www.bluesea.com
980023530 Rev. 002
Documents / Resources
| BLUE
SEA 1841 M2 OLED Temperature
Monitor
[pdf] User Manual
1841 M2 OLED Temperature Monitor, 1841, M2, OLED Temperature Monitor,
Temperature Monitor, Monitor
---|---
References
- Blue Sea Systems - Innovative electrical systems — Built to last
- OLED Digital Monitors - Blue Sea Systems
- M2 Firmware Upgrade - Blue Sea Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>