Specifications
- Lifetime: 50,000 to 100,000 hours
- Input Voltage: 220-240VAC
- Lumen Output: Varies based on model
- Color Temperature: 3000K/4000K
- Energy Efficiency Class: Varies based on model
- IP Rating: IP44
- IK Rating: IK06
Product Usage Instructions
Mounting Options:
- Suspended mounting with accessory SM155Z Suspension set CL fastset
- Horizontal wire mounting with accessory SM155Z Suspension set CL fastset
- Besa Bracket mounting with accessory SM155Z Besa Bracket set CL fastset
- Direct ceiling/wall mounting with specified distances
- Side entry/line mounting with recommended cable diameter
Installation Steps:
- Follow the provided diagram for smooth installation.
- Ensure sealings are properly installed.
- For MultiColour/MultiLumen switches, set luminous flux directly on driver.
- For MultiColour switches, set color temperature to 3000K or 4000K.
- Turn off power before making any switch settings.
Cable Mounting Instructions:
The cable diameter should be between 2mm and 11mm. It is recommended to use
white cable. Ensure luminous flux settings are consistent for different cable
lengths in one line.
Luminaire Configuration:
Refer to the table for the maximum number of luminaires per MCB type based on
the specific model.
Please refer to the InterAct commissioning guide to enable wireless InterAct Ready functionality
WHAT’S IN THE BOX
REQUIRED TOOLS
SYMBOLS
DIMENSION
INRUSH CURRENT
WARNINGS
ASSEMBLY INSTRUCTIONS
Direct ceiling/wall mounting
Ceiling mounting with 20 mm distance
Suspended mounting
Horizontal wire mounting
Besa Bracket mounting
Side entry / line mounting
MultiColour/MultiLumen switches (PSU)
MultiColour switches (WIA)
Closing the luminaire
Service
The light source and/or control gear and/or the external flexible cable contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similarly qualified person.
ATTENTION
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC-SENSITIVE DEVICES
The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
- For non-user replaceable light sources:
- “The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person”.
- During installation or maintaining the luminaire please use gloves to avoid spots on the cover.
To remove dirt and spots use the following:
- Dust: use micro hiber cloths only.
- Fingerprints, etc.: use a cleaner for synthetic materials with antistatic properties.
- Luminaires are not suitable for covering with thermally insulating material.
- For controllable luminaires, the classification of insulation between LV supply and control conductors shall be basic insulation at least.
- Luminaire must not be used or stored in a corrosive environment where hazardous materials such as Sulphur, Chlorine, Phthalates, etc, are present.
- Only use in environments where no accumulation of dust is expected.
- For indoor use only.
Disconnect before servicing
Luminaire has basic insulation between Low Voltage supply and control conductors
Storage, installation, use, operation and maintenance of the products need to be performed exactly according the instructions in this manual and/or other instructions as may be provided by us to guarantee safe use of the product over its entire lifetime. Failure to adhere to these instructions will invalidate your entitlement to warranty. Bolts with an indication of torque strength on the drawing need to be tightened using a calibrated torque wrench. Pre-assembled bolts need to be retightened again to the required torque specification to ensure maximum strength over a lifetime.
SR compatibility – For SR-based luminaires only SR-certified components/sensors are to be used (see also: http://www.lighting.philips.co.uk/oem-emea/products/driving-connected- lighting). The functional compatibility of two (SR-certified) components/sensors to be used in combination, as well as the override possibility of any line-switch function used in an SR-based luminaire, is to be released by the master component/sensor supplier. If using a NEMA 7-pin socket on an SR-based luminaire, a full system verification is required. Not following this advice can/will cause risk of damage and non-compliance for which Signify cannot take any responsibility.
WEEE Statement
Please inform yourself about the local waste disposal, separation and
collection system for electrical and electronic products and packaging. Please
act according to your local rules and do not dispose your old product and
packaging with your normal household waste. The correct disposal of the
packaging, your product and/or batteries will help prevent potential negative
consequences for the environment and human health. Batteries should be
disposed of separately from the municipal waste stream via designated
collection facilities. When disposing a product that contains non-user-
replaceable batteries, the non-user-replaceable batteries shall be removed by
a professional.
© 01/2024 Signify Holding.
All rights reserved. This document contains information relating to the product portfolio of Signify which information may be subject to change. No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V.. All other trademarks are owned by Signify Holding or their respective owners.
Signify Holding.
The Netherlands
FAQ
Q: How do I enable wireless InterAct Ready functionality?
A: Please refer to the InterAct commissioning guide for detailed instructions
on enabling wireless InterAct Ready functionality.
Q: What is the default color temperature setting?
A: The default setting is 4000K. For MultiColour switches, you can choose
between 3000K or 4000K.