PHILIPS BY020P G3 Ledinaire Highbay Ceiling Light Installation Guide

July 16, 2024
Philips

PHILIPS BY020P G3 Ledinaire Highbay Ceiling Light

Specifications

  • Product: Ledinaire Highbay
  • Model Numbers: BY020P/BY021P/BY022 G3
  • Application: Indoor
  • Input Voltage: 220V – 240V
  • Frequency: 50Hz – 60Hz
  • Rated Lifetime: 50,000 hours @ L80
  • Energy Efficiency Class: Class I
  • IP Rating: IP65
  • IK Rating: IK06

Product Usage Instructions

  • Installation:
    • The luminaire should be installed by a qualified electrician following the latest IEE electrical regulations or national requirements.
    • Do not switch on the luminaire before completing installation.
    • The suggested height between the luminous surface and the ground should be more than 5m.
    • The height between the bottom of the luminaire and the mounting surface must be more than 0.3m.
  • Safety:
    • Ensure proper power connection with PE (Protective Earth), L (Brown), and N (Blue) wires.
    • Use a safety chain during installation (not included in the box).
    • Tighten power connection screws to 1.5-2.5Nm.
  • Maintenance:
    • Refer to the user manual for maintenance instructions.
    • Regularly inspect the luminaire for any signs of damage or wear.

FAQs

  • Q: Can the luminaire be mounted on a pipe?
    • A: Yes, there is an optional pipe mounting feature available. Refer to the user manual for detailed instructions.
  • Q: What is the maximum number of luminaires that can be connected?
    • A: The maximum number varies depending on the model. Refer to the electrical characteristics section in the manual for specific details.

WHAT INBOX

FEATURE

Light Source

Dimensions

Dimensions in mm

Optional

Inrush current

BY020P G3          BY021P G3           BY022P G3

Electrical characteristics


Imax (A)| 40|  | 42|  | 54
Tref (µs)| 600|  | 650|  | 750
MCB|  | Maximum| number| of| luminaires
B- 16 A| 8| 6| 6
C- 16 A| 13| 8| 8

Hook Mounting

Optional: Pipe Mounting

Optional: Bracket Mounting

Optional: Reflector Mounting

Safety string Mounting

Power connection

  • The luminaire shall be installed by a qualified electrician and wired following the latest IEE electrical regulations or national requirements.
  • Do not switch the luminaire on before completing installation.
  • The height between the luminous surface and the ground is suggested to be more than 5m, and the height between the bottom of the luminaire and the mounting surface must be more than 0.3m.
  • If the customer requires a luminous surface level <1, the pipe mounting method is recommended, and suggests to use gradient to precisely measure and adjust.
  • If the external flexible cable or cord of this luminaire is damaged. It shall be exclusively replaced by the manufacturer or his service agent or a similarly qualified person to avoid a hazard.
  • The light source contained in this luminaire shall only be replaced by the manufacturer his service agent or a similar qualified person.
  • The corrosive atmosphere or hazardous materials such as sulfur, chlorine, phthalate, etc must be avoided during the use and storage.
  • Luminaires don’t have any evaluation on additional protective measures to prevent luminaire from high-altitude falling and windproof structures, therefore it can’t be used as flood and tunnel luminaire.
  • Not suitable for use in harsh vibration and often causing vibration or swinging environment. Also not suitable for areas prone to hurricanes and extreme winds.
  • The installer needs to arrange the Chain / Pipe for mounting. The default product is supplied with a mounting hook.
  • Do not stare at the operating light source.