EMS 900 Series Fire Alarm Control Panels Installation Guide

July 12, 2024
EMS

EMS-logo

EMS 900 Series Fire Alarm Control Panels

Specifications:

  • Product: 2X-A Series Fire Alarm Control Panels
  • Protocol: 900 Series
  • Requirements: EN 54-13
  • Supervision: Class A loop supports up to 126 devices

Product Usage Instructions

Adding the Menu Inserts:
Add the control panel interface menus as shown below.

    • Figure 1: Adding the menu inserts

Fixing the Cabinet to the Wall:

  1. Measure and mark drill points on the wall ensuring levelness using the built-in spirit level.
  2. Drill required holes and insert wall plugs.
  3. Hang the cabinet on a screw at position (1).
  4. Tighten screws at positions (2) and (3).
  5. Ensure all screws are tightened securely.
    Figure 2: Mounting hole locations

Installing the Cabinet:
Install the control panel in a dust-free, debris-free area with stable temperature and humidity levels. Ensure there is ample space for servicing and that the user interface is at eye level.

Connecting Loops and Loop Devices:
Refer to the product manual for detailed information on connecting loops. Ensure proper termination of unused loops for supervision.

    • Figure 3: Overview of typical fire system connections using a single Class A loop

Connecting Inputs and Outputs:
Follow specific connection instructions provided, ensuring proper termination and polarity. Install necessary components to avoid circuit faults.

Mains Fuse and Batteries :
Refer to the product manual for detailed information on mains fuse and battery installation.

FAQ:

  • Q: What should I do if I encounter an open circuit fault?
    A: Install a 15 k end-of-line resistor across unused terminals to avoid an open circuit fault.

  • Q: How many devices can a Class A loop support?
    A: Each Class A loop can support up to 126 devices.

2X-A Series Quick Installation Guide

Overview

  • This document includes quick installation information for your 2X-A Series Fire Alarm Control Panels running the 900 Series protocol.
  • For detailed installation information (including EN 54-13 requirements) and for configuration options, see the product installation manual.
  • WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.
  • Caution: Equipment damage hazard. This product is sensitive to electrostatic discharge (ESD). To avoid damage, follow accepted ESD handling procedures.

Adding the menu inserts

  • Add the ccontrol panel interface menus as shown below.
  • Figure 1: Adding the menu inserts
  • The inserts are numbered 1 and 2F and are inserted at the locations indicated above (with the printed area facing the front of the control panel).

Installing the cabinet

  • Where to install the control panel
  • Install the control panel in a location that is free from construction dust and debris, and immune to extreme temperature ranges and humidity.
  • Provide enough floor and wall space to allow the control panel to be installed and serviced without any obstructions. The cabinet should be mounted so that the user interface is at eye level.
  • © 2024 Carrier. All rights reserved.

Fixing the cabinet to the wall

Fix the cabinet to the wall using five M4 × 30 screws and five 6 mm wall plugs, as shown below.

  1. Hold the cabinet to the wall at the required installation height.
  2. Ensure that the cabinet is level using the built-in spirit level and mark drill points on the wall.
  3. Drill all required holes and insert a 6 mm wall plug into each.
  4. Insert a screw in position (1) and hang the cabinet onto this screw.
  5.  Insert screws in positions (2) and tighten.
  6. Insert screws in position (3) and tighten.
  7. Tighten screw in position (1).

Figure 2: Mounting hole locations

Connecting loops and loop devices

  • EMS-900-Series-Fire-Alarm-Control-Panels- \(2\)See Figure 3 on page 2 for an overview of typical fire system connections using a single Class A loop.
  • Use 0.13 to 3.31 mm² (26 to 12 AWG) shielded or unshielded twisted-pair cable with 52 Ω (26 Ω per wire) and 500 nF/km maximum.
  • Earth connection: Connect one side to the earth studs in the control panel cabinet (not to the loop EARTH terminal), the other side can be left floating.
  • Class A loops are supervised for open and short circuits. Terminate unused Class A loops A (+) to B (+) and A (−) to B (−). Each Class A loop can support up to 126 devices
  • See the product installation manual for Class B loop connection information.

Figure 3: Overview of typical fire system connections using a single Class A loop

EMS-900-Series-Fire-Alarm-Control-Panels- \(3\)

Connecting inputs and outputs

  • Caution: The following connection information does not apply to installations requiring EN 54-13 compliance. If EN 54-13 compliance is required, see the product installation manual.
  • All inputs and outputs (except 24V AUX) require a 15 kΩ end-of-line resistor for termination to detect open or short circuits. If an input or output is not used, install a 15 kΩ end-of-line resistor across the unused terminals to avoid an open circuit fault.
  • Connect input switches to INPUT1 and INPUT2 (62 Ω ≤ active value ≤ 8 kΩ).
  • When connecting outputs, observe polarity or install a 1N4007 diode or equivalent to avoid inverted activation issues.
  • See the product installation manual for input and output configuration options.

Mains fuse and batteries

  • Use a T4A-250V mains fuse for both 110 VAC and 240 VAC operation. Check the product installation manual for 110 VAC operation requirements.

  • Depending on the model and power supply, the control panel requires two 12 V, 7.2, 12, 17/18, 36/38, or 65 Ah rechargeable sealed lead-acid batteries.

  • Caution : Not all compatible batteries can be used with all control panels. Some compatible batteries must be installed in an external battery box (not supplied).

  • For a list of compatible batteries and the battery installation location, see the product installation manual.

  • Configuration
    See your product installation manual for detailed configuration information. The default installer password is 4444.

  • Contact information and product  documentation
    For contact information or to download the latest product documentation, visit firesecurityproducts.com.

Product warnings and disclaimers

  • THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED PROFESSIONALS. CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY  PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY  INSTALL FIRE AND SECURITY RELATED PRODUCTS.

For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/product-warning/ or scan the QR code:

P/N BCN-3100014-EN • REV 001 • ISS 07JUN24

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals