EMS FCX-532-001 Loop Module
Pre Installation
Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.
- Ensure the loop module is installed as per the site survey.
- Refer to step 3 to ensure optimized wireless performance.
- If using remote aerials with this product, refer to the remote aerial installation guide (MK293) for more information.
- A maximum of 5 loop modules can be connected per loop.
- This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.
Components
- 4x corner covers,
- 4 x lid screws,
- Loop module lid,
- Loop module PCB,
- Loop module back box
Mounting Location Guidelines
For optimum wireless performance, the following must be observed:
- Ensure the loop module is not installed within 2 m of other wireless or electrical equipment (not including the control panel).
- Ensure the loop module is not installed within 0.6 m of metal work.
Optional PCB Removal
- Remove the three circled retaining screws, before unclipping the PCB.
Remove Cable Entry Points
- Drill the cable entry points as necessary.
Fix to The Wall
- All five circled fixing positions are available for use as required.
- The key hole can also be used for locating and fixing where required.
Connection Wiring
- Loop cables should only be passed via the access points available.
- Flame retardant cable glands must be used.
- DO NOT leave excess cable inside the loop module.
Single loop module.
Multiple loop modules (max. 5)
Configuration
- Set the loop module address using the on-board 8 way switch.
- Available selections are shown in the table below.
DIL SWITCH SETTING
Addr.| 1……8
1| 10000000
2| 01000000
3| 11000000
4| 00100000
5| 10100000
6| 01100000
7| 11100000
8| 00010000
9| 10010000
10| 01010000
11| 11010000
12| 00110000
13| 10110000
14| 01110000
15| 11110000
16| 00001000
17| 10001000
18| 01001000
19| 11001000
20| 00101000
21| 10101000
22| 01101000
23| 11101000
24| 00011000
25| 10011000
26| 01011000
27| 11011000
28| 00111000
29| 10111000
30| 01111000
31| 11111000
32| 00000100
33| 10000100
34| 01000100
35| 11000100
36| 00100100
37| 10100100
38| 01100100
39| 11100100
40| 00010100
41| 10010100
42| 01010100
43| 11010100
44| 00110100
45| 10110100
46| 01110100
47| 11110100
48| 00001100
49| 10001100
50| 01001100
51| 11001100
52| 00101100
53| 10101100
54| 01101100
55| 11101100
56| 00011100
57| 10011100
58| 01011100
59| 11011100
60| 00111100
61| 10111100
62| 01111100
63| 11111100
64| 00000010
65| 10000010
66| 01000010
67| 11000010
68| 00100010
69| 10100010
70| 01100010
71| 11100010
72| 00010010
73| 10010010
74| 01010010
75| 11010010
76| 00110010
77| 10110010
78| 01110010
79| 11110010
80| 00001010
81| 10001010
82| 01001010
83| 11001010
84| 00101010
85| 10101010
86| 01101010
87| 11101010
88| 00011010
89| 10011010
90| 01011010
91| 11011010
92| 00111010
93| 10111010
94| 01111010
95| 11111010
96| 00000110
97| 10000110
98| 01000110
99| 11000110
100| 00100110
101| 10100110
102| 01100110
103| 11100110
104| 00010110
105| 10010110
106| 01010110
107| 11010110
108| 00110110
109| 10110110
110| 01110110
111| 11110110
112| 00001110
113| 10001110
114| 01001110
115| 11001110
116| 00101110
117| 10101110
118| 01101110
119| 11101110
120| 00011110
121| 10011110
122| 01011110
123| 11011110
124| 00111110
125| 10111110
126| 01111110
- The system can now be programmed.
- Refer to the Fusion programming manual (TSD062) for details of compatible Fire Cell devices and full programming information.
Apply Power
Apply power to the control panel. The normal LED states for the Loop Module are as below:
- The green POWER LED will illuminate.
- The other LEDs should be extinguished.
Close Loop Module
- Ensure that the loop module PCB is correctly inserted and the PCB retaining screws are refitted.
- Refit the loop module lid, ensuring LEDs are not damaged by the light pipe when refitting.
Specification
Operating temperature -10 to +55 °C
Storage temperature 5 to 30 °C
Humidity 0 to 95% non-condensing
Operating voltage 17 to 28 VDC
Operating current 17 mA (typical) 91mA (max.)
IP rating IP54
Operating frequency 868 MHz
Output transmitter power 0 to 14 dBm (0 to 25 mW)
Signalling protocol X
Panel protocol XP
Dimensions (W x H x D) 270 x 205 x 85 mm
Weight 0.95 kg
Location Type A: For indoor use
Specification Regulatory information
Manufacturer
Carrier Manufacturing Poland Sp. z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland
Year of manufacture
See devices serial number label
Certification
13
Certification body
0905
CPR DoP
0359-CPR-0222
Approved to
EN54-17:2005. Fire detection and fire alarm systems.
Part 17:Short-circuit isolators.
EN54-18:2005. Fire detection and fire alarm systems.
Part 18:Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems.
European Union
EMS declares that this device is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
Directives
2012/19/EU (WEEE directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at designated collection points.
For more information see www.recyclethis.info
Dispose of your batteries in an environmentally friendly manner according to
your local regulations.