Pre-installation

Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.

  • Ensure the loop module is installed as per the site survey.
  • Refer to step 3 to ensure optimised wireless performance.
  • If using remote aerials with this product, refer to the remote aerial installation guide for more information.
  • A maximum of 5 loop modules can be connected per loop.
  • This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.

Components

EMS FCX-532-001 Fusion Loop Module 1

  1. 4x corner covers
  2. 4x lid screws
  3. Loop module lid
  4. Loop module PCB
  5. Loop module back box

Mounting location guidelines

For optimum wireless performance,the following must be observed:

EMS FCX-532-001 Fusion Loop Module 2

  • Ensure the loop module is not installed within 2 m of other wireless or electrical equipment (not including the control panel).
  • Ensure the loop module is not installed within 0.6 m of metal work.

Optional PCB removal

Remove the three circled retaining screws, before unclipping the PCB.

EMS FCX-532-001 Fusion Loop Module 3

Remove cable entry points

Drill the cable entry points as necessary.

Fix to the wall

  • All five circled fixing positions are available for use as required.
  • The key hole can also be used for locating and fixing where required.

EMS FCX-532-001 Fusion Loop Module 5

Connection wiring

  • Loop cables should only be passed via the access points available.
  • Flame retardant cable glands must be used.
  • DO NOT leave excess cable inside the loop module.

Single loop module

EMS FCX-532-001 Fusion Loop Module 6

Multiple loop modules (max. 5)

EMS FCX-532-001 Fusion Loop Module 7

Configuration

  • Set the loop module address using the on-board 8 way switch.
  • Available selections are shown in the table below.

EMS FCX-532-001 Fusion Loop Module 8

  • The system can now be programmed.
  • Refer to the Fusion programming manual (TSD062) for details of compatible FireCell devices and full programming information.

Apply power

Apply power to the control panel. The normal LED states for the Loop Module are as below:

  • The green POWER LED will illuminate.
  • The other LEDs should be extinguished.

EMS FCX-532-001 Fusion Loop Module 9

Close loop module

  • Ensure that the loop module PCB is correctly inserted and the PCB retaining screws are refitted.
  • Refit the loop module lid, ensuring LEDs are not damaged by the light pipe when refitting.

EMS FCX-532-001 Fusion Loop Module 10

Specification

  • Operating temperature: -10 to +55 °C
  • Storage temperature: 5 to 30 °C
  • Humidity: 0 to 95% non-condensing
  • Operating voltage : 17 to 28 VDC
  • Power requirements : 17 mA at 24 VDC
  • IP rating:  IP54
  • Operating frequency: 868 MHz
  • Output transmitter power : 0 to 14 dBm (0 to 25 mW)
  • Dimensions (W x H x D): 270 x 205 x 75 mm
  • Weight: 0.95 kg
  • Location: Type A: For indoor use

Regulatory information

  • Manufacturer: Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 24. 39-100 Ropczyce, Poland
  • Year of  manufacture Certification body: See devices serial number label
  • CPR DoP: 0359-CPR-0222
  • Approved to: EN54-17:2005. Fire detection and fire alarm systems. Part 17:Short-circuit isolators. EN54-18:2005. Fire detection and fire alarm systems. Part 18:Input/output devices. EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems.
  • European Union directives: EMS declares that this device is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk 

2012/19/EU (WEEE directive):
Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals