RENOGY RIV1210PU-126 Pure Sine Wave Inverter with Transfer Switch User Manual

July 5, 2024
Renogy

RENOGY RIV1210PU-126 Pure Sine Wave Inverter with Transfer Switch

Product Information

Specifications:

  • Brand: Renogy
  • Product: Pure Sine Wave Inverter with Transfer Switch
  • Voltage: 12V
  • Power Options: 1000W/2000W/3000W
  • Model Numbers: RIV1210PU-126/RIV1220PU-126/RIV1230PU-126
  • Version: A0

Product Usage Instructions

Before Getting Started

The user manual contains essential operation and maintenance instructions for the Renogy Pure Sine Wave Inverter with Transfer Switch. It is crucial to read the manual carefully before using the inverter to prevent any accidents or damage.

Key Features:

  • Uninterrupted Power Supply (UPS): The inverter seamlessly switches to grid power using the built-in transfer switch, providing uninterrupted power supply.
  • Safe for Use: Offers multiple protection mechanisms including overload, overtemperature, overvoltage, short-circuit, undervoltage protections, and a Ground Fault Circuit Interrupter (GFCI).
  • Guaranteed Appliance Protection: The pure sine wave technology ensures appliance longevity by delivering clean power comparable to grid power, eliminating buzzing sounds.
  • Easy to Use: Features a built-in USB port, AC outlets, Hardwired AC Output Terminal Block, and a Wired Remote Port for convenience.

FAQs

  • Q: Can I connect multiple appliances to the inverter?
    • A: Yes, you can connect multiple appliances to the inverter as long as the total power consumption does not exceed the inverter’s wattage rating.
  • Q: How do I know if the inverter is functioning correctly?
    • A: You can check the inverter’s status indicators and monitor the power output to ensure it is functioning correctly. Refer to the user manual for detailed troubleshooting steps.

Renogy
Pure Sine Wave Inverter with Transfer Switch

12V 1000W/2000W/3000W

RIV1210PU-126/RIV1220PU-126/RIV1230PU-126

VERSION A0

USER MANUAL

Before Getting Started

The user manual provides important operation and maintenance instructions for Renogy 12V 1000W/2000W/3000W Pure Sine Wave Inverter with Transfer Switch (hereinafter referred to as inverter).
Read the user manual carefully before operation and save it for future reference. Failure to observe the instructions or precautions in the user manual can result in electrical shock, serious injury, or death, or can damage the inverter, potentially rendering it inoperable.
Renogy ensures the accuracy, su¤À×cy, and the applicability of information in the user manual at the time of printing due to continual product improvements that may occur.
Renogy assumes no responsibility or liability for personal and property losses, whether directly and indirectly, caused by the user’s failure to install and use the product in compliance with the user manual.
Renogy is not responsible or liable for any failure, damage, or injury resulting from repair attempts by unqualiªéëïÝ××ÐÀÖéroper installation, or inappropriate operation.
The illustrations in the user manual are for demonstration purposes only. Details may appear slightly dierent depending on product revision and market region.
Renogy reserves the right to change the information in the user manual without notice. For the latest user manual, visit renogy.com.

Disclaimer

Renogy 12V 1000W/2000W/3000W Pure Sine Wave Inverter with Transfer Switch User Manual © 2023 Renogy. All rights reserved.

RENOGY and

are registered trademarks of Renogy.

All information in the user manual is subject to copyright and other intellectual property rights of Renogy and its licensors. The user manual may not be modiªreproduced, or copied, in whole or in part, without the prior written permissions of Renogy and its licensors.
The registered trademarks in the user manual are the property of Renogy. The unauthorized use of the trademarks is strictly prohibited.

Symbols Used

The following symbols are used throughout the user manual to highlight important information.
WARNING: Indicates a potentially dangerous condition which could result in injury or death. CAUTION: Indicates a critical procedure for safe and proper installation and operation. NOTE: Indicates an important step or tip for optimal performance.

Introduction

Renogy 12V 1000W/2000W/3000W Pure Sine Wave Inverter with Transfer Switch is ideal for a wide range of o-grid applications, including vans, semi-trucks, ·õ½ wheels, cabins, and remote locations that require reliable power sources. The inverter converts DC Power stored in batteries into usable AC Power for appliances. Renogy’s advanced pure sine wave technology empowers you to run a wide variety of AC appliances without the risk of damaging even your most sensitive equipment.
Key Features
Powerful DC-AC Conversion Continuous rated output power with a conversion e¤À×cy greater than 92%, and up to 2x surge for start-up loads.
Uninterrupted Power Supply (UPS) Utilizing the built-in transfer switch, this inverter seamlessly switches to grid power, bypassing the inverter when it’s available, thereby directly supplying the load with grid power.
Safe for Use The inverter provides multiple protection mechanism such as overload, overtemperature, overvoltage, short-circuit, and undervoltage protections as well as an integrated Ground Fault Circuit Interrupter (GFCI).
Guaranteed Appliance Protection Our pure sine wave technology ensures appliance longevity by delivering a clean sine wave that’s comparable to or even better than grid power. Say goodbye to annoying buzzing sounds and enjoy the smooth operation of all your devices.
Easy to Use Oers a built-in 5V/2.1A USB port, AC Outlets, Hardwired AC Output Terminal Block, and a Wired Remote Port.
Dependable Quality The inverter is UL certiª to 458, CSA 22.2 No. 107.1-01, and FCC Part 15 Class B standards, ensuring reliability and safety for all users.
SKU

Renogy 12V 1000W Pure Sine Wave Inverter with Transfer Switch Renogy 12V 2000W Pure Sine Wave Inverter with Transfer Switch Renogy 12V 3000W Pure Sine Wave Inverter with Transfer Switch

RIV1210PU-126 RIV1220PU-126 RIV1230PU-126

— 1 —

What’s In the Box?
Renogy 12V 1000W/2000W/3000W Pure Sine Wave Inverter with Transfer Switch × 1

Renogy Pure Sine Wave Inverter with Transfer Switch

12V 1000W/2000W/3000W

RIV1210PU-126/RIV1220PU-126/RIV1230PU-126

VERSION A0

USER MANUAL
User Manual × 1

ON

ERR

RMS-P2

Cables (3ft) × 2 (only 1000W/2000W inverter)

Wired Remote Control × 1

RJ12 Ethernet Cable (5m) × 1

Make sure that all accessories are complete and free of any signs of damage.
The accessories and product manual listed are crucial for the installation, excluding warranty information and any additional items. Please note that the package contents may vary depending on the speci¤éroduct model.
The 1000W inverter comes with 4 AWG Cables. The 2000W inverter comes with 1/0 AWG Cables. The 3000W inverter does not include cables, so you will need to prepare them yourself. We recommend using 3/8in Lugs (M10 Ring Terminals) and 2/0 AWG Cables.

Required Tools & Accessories

Choose proper mounting screws speci¤ to your installation site. This manual takes self-tapping screws for wooden walls as an example.

14 mm

14 mm

14 mm

Phillips Screwdriver (#1)

Wrench (9/16 in)

Insulating Gloves

Slotted Screwdriver (1 mm)

Wire stripper

Self-tapping Screws (ST4 or ST6) × 4

Prior to installing and con¸ùëÀ׸ the inverter, prepare the recommended tools, components, and accessories.

— 2 —

Get to Know Renogy 12V 1000W Pure Sine Wave Inverter

AC Side View GFCI LED Indicator
Power LED Indicator

Fault LED Indicator
AC Input and High Output AC
Terminals

USB Power Port Remote Control Terminal
AC Output Frequency
DC Side View Cooling Fan

ON/OFF/REM Switch
AC Outlets N-G Bonding Relay
Ground, M4

Dimensions

Negative (-) DC Input, M8 8.96 in (227.5 mm)

Positive (+) DC Input, M8

15.3 in (388.5 mm) Dimension tolerance: ±0.2 in (0.5 mm)

3.8 in (95.3 mm)
8.1 in (205.4 mm)

— 3 —

Get to Know Renogy 12V 2000W Pure Sine Wave Inverter

AC Side View GFCI LED Indicator
Power LED Indicator

Fault LED Indicator
AC Input and High Output AC
Terminals

USB Power Port
Remote Control Terminal

ON/OFF/REM Switch

AC Output Frequency
DC Side View Cooling Fans

AC Outlets N-G Bonding Relay
Ground, M4

Negative (-) DC Input, M8

Dimensions

12.1 in (307 mm)

Positive (+) DC Input, M8

18.3 in (468.3 mm) Dimension tolerance: ±0.2 in (0.5 mm)

3.8 in (95.3 mm)
9.9 in (250.4 mm)

— 4 —

Get to Know Renogy 12V 3000W Pure Sine Wave Inverter

AC Side View GFCI LED Indicator

Fault LED Indicator

Power LED Indicator

AC Input and High Output AC
Terminals

USB Power Port
Remote Control Terminal

ON/OFF/REM Switch

AC Output Frequency
DC Side View Cooling Fans

AC Outlets N-G Bonding Relay
Ground, M4

Negative (-) DC Input, M8

Dimensions

12.8 in (327.5 mm)

Positive (+) DC Input, M8

19.2 in (488.8 mm) Dimension tolerance: ±0.2 in (0.5 mm)

3.8 in (95.3 mm)
10.4 in (263.4 mm)

— 5 —

Part Description

Part

Description

ON/OFF/REM Switch Turns the inverter ON, OFF, or REMOTE.

Power LED Indicator Indicates the operational status of the inverter.
GFCI LED Indicator Indicates that the ground fault circuit has been interrupted. In such case, restart the inverter.
Fault LED Indicator Indicates that the inverter shuts down due to overheating, overload, undervoltage, or overvoltage. Solution: Immediately turn o all AC appliances. Allow the inverter to cool before continuing. Make sure that the ventilation vents are not blocked. Ensure all cables are of proper sizes and lengths.
AC Outlets 120V AC, 50/60 Hz.
Up to 10A x 2 for Renogy 12V 1000W Pure Sine Wave Inverter Up to 16A x 2 for Renogy 12V 2000W Pure Sine Wave Inverter Up to 16A x 3 for Renogy 12V 3000W Pure Sine Wave Inverter
USB Power Port Supplies 5V/2.1A for charging tablets, smartphones, and other small appliances.
Remote Control Terminal Connects to the Wired Remote Control.

AC Output Frequency Con¸ùre the AC output frequency of the inverter in accordance with the frequency of the connected AC loads.
N-G Bonding Relay The inverter is equipped with a Neutral to Ground (N-G) bonding relay that ensures that either the neutral in or out contact of the RV is always grounded. You can manually enable or disable the N-G Bonding Relay as needed.

— 6 —

High Output AC Terminals Connect to 120V AC devices operating at higher than 10A/20A/30A or distributed wiring with multiple AC outlets. Remove the two screws on the protective cover to access the terminals. Terminal layout (facing the front panel):
Left: Ground (G) Middle: Live (L) Right: Neutral (N) AC Input Terminals When the inverter is connected to single-phase 120V power systems through the AC Input Terminals, the grid power can directly supply power to the load through bypass. Remove the two screws on the protective cover to access the terminals. Terminal layout (facing the front panel): Left: Live (L) Middle: Neutral (N) Right: Ground (G)
How to Properly Install Cable Clamps?
The AC Input Terminals and AC Output Terminals are equipped with cable clamps to ensure that the wiring connections remain secure and do not come loose due to vibrations. Step 1: Remove the two screws on the protective cover to access the terminals. Step 2: Loosen the screws on a cable clamp with a Phillips Screwdriver. Step 3: Lift the clamp, and run the cables through the clamp. Step 4: Secure the clamp by fastening the screws. Step 5: Install the protective cover and secure it using two screws.
— 7 —

System Setup System Wiring

Solar Panel

Solar Panel Fuse

Charge Controller

Battery Fuse

Battery Fuse

Battery Fuse

Battery

Starter Battery

Battery Fuse

Battery Charger

Grid Power

Inverter

AC Loads

Positive (DC)

Negative (DC)

AC

The wiring diagram only shows the key components in a typical DC-coupled o-grid energy storage system for the illustrative purpose. The wiring might be dierent depending on the system con¸ùration. Additional safety devices, including disconnect switches, emergency stops, and rapid shutdown devices, might be required. Wire the system in accordance with the regulations at the installation site.
The grid supplies the connected loads only. It does not charge the battery.

— 8 —

Inverter Wiring

The wiring diagram provided in this section is tailored for a 1000W inverter model. Similar wiring rules apply to other models.

AC Side View

Wired Remote Control

ON

ERR

RMS-P2

Loads (USB)

AC Loads

Ground Fault Circuit Interrupter
(GFCI)

AC Loads

Grid Power
Singlephase 120V

Live wire (AC) Neutral wire (AC) DC Side View

Ground AC

Remote control USB

Battery

+ Fuse

Positive (DC)

12V Battery Negative (DC)

Ground

Ground

— 9 —

Size a Battery Bank

Battery types and capacity relate to the overall inverter performance. To size a proper battery bank, you need to identify the loads that you will be utilizing, as well as an estimate duration (hours/day) you will be using the load. The inverter is only compatible with 12V battery banks, and oversizing should be considered due to e¤À×cy losses. 1. Determine Your Watts (Amps x Volts)
Every electronic device will have a sticker or plate identifying the watts directly (W) or will show you the voltage value (V) as well as amperage (A) which need to be multiplied to get Watts. The formula is below: Watts (W) = Volts (V) x Amps (A) Example: Fan Watts = 120V * 0.4A = 48Watts 2. Estimate Load Run-Time in Watt-Hours (Wh) Estimate how many hours per day you will be using the load and multiply this by your Watts per load. Example: Fan Watts x 12 hours = Watt-Hour (Wh) 48W x 12h = 576Wh 3. Determine Battery Capacity in Amp-Hour (Ah) Divide your Load Run Watt-Hour result by the battery voltage. Load Run-Time (Wh)/Battery Voltage (V) = Amp-Hour (Ah) Use 12V, supported voltage of the inverter as a reference. 576Wh/12V = 48 Ah 4. Oversize the Battery The calculated Amp-Hour value represents the minimum size battery capacity to run your load for your intended time. Note that this assumes 100% use of a battery, which is not recommended. Assuming 50% depth of discharge, you want to multiply this value by 2 and you also want to multiply by 1.25 to account for some e¤À×cy losses. Formula: 48Ah x Oversize x E¤À×cy Losses = Recommended Amp-Hour
Therefore, a 115Ah battery bank, or close, will be able to support a 12-hour run time while also prolonging battery life for the best system size possible.
Actual battery quantities vary by battery capacity and rates of discharge.
Step 1. Wear Insulating Gloves
This manual utilizes the 1000W Inverter as a reference for its illustrations. The wiring techniques remain consistent across all inverter models, though there may be variations in terminal positions.
Insulating Gloves
— 10 —

Step 2.

Plan a Mounting Site

Follow the guidelines below:
Cool, dry, and well-ventilated area The inverter must be installed in a site where the fans are not blocked or where they are not hit directly by the sun. The site should be free of any kind of moisture with a clearance of at least 10 inches around the inverter for adequate ventilation. Protection against re hazard The inverter should be away from any ÖÖ£ÐÖaterial, liquids, or any other combustible material.
Close proximity to battery bank Put the inverter close to batteries banks to prevent excessive voltage drop. Choose a proper sized wire going from the battery bank to the inverter.
Limiting electromagnetic interference (EMI) Ensure the inverter is ëÖÐy grounded to a building or vehicle. Alternatively, it can be earth grounded. Keep the inverter away from EMI receptors such as TVs, radios, and other audio/ visual electronics to prevent damage/interference.
Secure mounting The inverter should be stand-alone or mounted by using the outlying terminals with ST4 and ST6 screws on the inverter.

KEEP DRY

FRAGILE

VENTILATION

-4°F to 113°F / -20°C to 45°C

Do not over-torque or overtighten the terminals. This could potentially damage the unit.
Refer to the technical speci¤ations for maximum wire sizes on the controller and for the maximum amperage going through wires.
Ensure the inverter is in the OFF position before connecting to anything.
Do not install the inverter in the same compartment as the battery bank because it could serve as a potential re hazard.
Never mount the inverter vertically on a vertical surface since it would present a hazard for the fan opening, undermining cooling the inverter.

— 11 —

Step 3. Grounding
Grounding is highly recommended for both when using the inverter in a mobile application, such as an RV, or in a building. If available, the chassis ground lug should be connected to a ground point such as a vehicle chassis or boat grounding system. In xed locations, connect the ground lug to earth ground. The connections to ground must be tight and against bare metal.
Recommended Components

3/16 in (M4) Grounding Cable

Model 1000W Pure Sine Wave Inverter 2000W Pure Sine Wave Inverter 3000W Pure Sine Wave Inverter

Recommended Size 14 AWG 12 AWG 10 AWG

When the GFCI fails to operate normally after grounding the inverter, please refer to “N-G Bonding Relay” for details.

Grounding Cable
Grounding
Step 4. DC Wiring
The inverter is suitable for 12V battery bank systems ONLY. Not following the minimum DC requirement will cause irreversible damage to the device. The input terminals of the inverters are embedded with large capacitors. The input circuit is completed once the terminals are connected to both positive and negative wires. This commences drawing a heavy current momentarily. As a result, there may be a sparking occurring even if the inverter is in the o position. To minimize sparking, it is recommended that you should choose an appropriate sized wire feeding into the inverters and/or install an external fuse leading into the inverter.
Be careful of the positive and negative poles. Reversing the poles might cause permanent damage to the inverter and will void the warranty.
— 12 —

For your safety, it is recommended that you should use a battery fuse on the positive end.

Model Continuous Output Power
Battery Fuse

RIV1210PU-126 1000W 150A

RIV1220PU-126 2000W 250A

RIV1230PU-126 3000W 400A

Step 1: On the AC side, set the ON/OFF Switch to the OFF position.

Step 2: On the DC side, remove the protection caps.

Step 3: Unscrew Positive and Negative DC Input Terminals, connect a battery bank to the terminals, and tight the terminal screws. Torque: 14(±0.5) N·m

  • 12V Battery

Cables (3ft) Battery Fuse

— 13 —

Step 5.

AC Output Wiring

Recommended Ground-Fault Circuit Interrupter (GFCI)
A ground-fault circuit interrupter, or GFCI, is a device that helps protect people from electric shocks by de-energizing a circuit or portion of a circuit within an established period of time when a current to ground exceeds some predetermined value that is less than that required to operate the overcurrent device (circuit breaker or fuse) of the supply circuit. GFCIs are usually required in wet or damp locations.
While the inverter is equipped with a GFCI, an external GFCI is strongly recommended to elevate system safety.
The following table lists GFCIs that meet the speci¤ations and will function properly when they are connected to the AC Outlets of the inverter.

Manufacturer Leviton Hubbell Hubbell

Tested GFCI Models

Model Number GFNT2
GFP1305 GF15WLA

Risk of electrical shock. Use only ground-fault circuit interrupters [receptacle(s) or circuit breaker(s)] compatible with your inverter. GFCIs shall be installed in a recreational vehicle’s wiring system to protect all branch circuits.
AC Outlets
You can plug your AC loads directly into the AC Outlets on the inverter’s AC side.

High Output AC Terminals
Additionally, you have the option to establish a permanent connection from the AC output by linking it through the High Output AC Terminals to a GFCI, a load sub-panel, or supplementary AC outlets that receive power from the inverter. From left to right, the terminal block indicates: Ground (G), Live/Hot (L), and Neutral (N).
— 14 —

Ground Fault Circuit Interrupter
(GFCI)
For details on how to connect loads and the inverter to the GFCI, read the user manual of the speci¤>FCI.
Step 6. AC Input Wiring (Optional)
Utilizing the built-in transfer switch, this inverter seamlessly switches to grid power, bypassing the inverter when it’s available, thereby directly supplying the load with grid power. From left to right, the terminal block indicates: Live/Hot (L), Neutral (N), and Ground (G).
Grid Power (Single-phase 120V) L N PE Risk of electric shock! Ensure the grid or the AC generator is turned o before connecting them to the inverter. — 15 —

Power On/`
Operations on Inverter After proper battery and AC load connections, you can operate the inverter. 1. On the AC side, rock the ON/OFF Switch to the ON position. 2. The inverter is operating normally. When ×Àï½À׸ùïÀ׸ the inverter, power o the AC loads ëïõת then rock the ON/OFF Switch to the OFF position.
When the inverter turns on, it is normal to see the fans run for a second and hear a beep.
Avoid powering on the inverter with the load (electronic devices) already switched on. This may trigger an overload since some electronic devices have an initial high power surge to start. When switching o the inverter, turn o the electronic devices ëst. Although the inverter is o, the terminal capacitors will still have a charge, so the DC and AC terminals must be disconnected if altering the circuitry.
Wired Remote Control The Wired Remote Control gives you the opportunity to power on/o the inverter from a distance (approximately 16.4 ft / 5 m). Note that the inverter ON/OFF switch should be in the REM position. Step 1: Connect the Wired Remote Control to the inverter via the Remote Control Connector.

ON

ERR

RMS-P2

RJ12 Ethernet
Cable

— 16 —

Step 2: Rock the ON/OFF Switch to the REM position, and you can power on/o the inverter via the Wired Remote Control.

ON

ERR

RMS-P2

N-G Bonding Relay

The inverter is equipped with a Neutral to Ground (N-G) bonding relay that ensures that either the neutral in or out contact of the RV is always grounded.

This helps prevent electrical shock caused by contact between the neutral contacts of the RV and external AC power sources.

By default, the Neutral to Ground bonding relay is enabled when the inverter is shipped from the factory.

When there is AC input current, the N-G bonding relay automatically opens the neutral-toground connection as shown in the ¸ùre below, and the system connects to the grid ground
contact.

Grid Power

Inverter

AC Loads

L

N

AC

PE

input

L

AC

N

output PE

N-G Bonding

GND

GND

When there is no AC input current, the N-G bonding relay automatically closes and connects to the ground contact of the inverter. In this case, the inverter supplies loads with the connected battery.

Battery

Inverter

AC Loads

Positive Negative DC

L

AC

N

output

PE

N-G Bonding

GND

— 17 —

In scenarios where the N-G bonding relay is disabled, the N-G bonding relay connects to the ground contact of the inverter only.
You have the option to manually enable or disable the N-G Bonding Relay.

Enabled

Disable

The N-G bonding relay must be enabled when the battery supplies the connected loads because the GFCI will be unavailable if the N-G bonding relay is disabled. In scenarios when N-G bonding relay is disabled, the inverter must be grounded.
Monitor the Inverter
Depending on the speci¤ééÐÀ¤ation, the inverter can establish either short- range or longrange communication connections with monitoring devices. These monitoring devices facilitate real-time monitoring, programming, and complete system management, oering comprehensive control and enhanced exibility.
The version of the DC Home app might have been updated. Illustrations in the user manual are for reference only. Follow the instructions based on the current app version. Make sure that the inverter is properly installed and powered on before it is paired with the DC Home app. To ensure optimal system performance, keep the phone within 10 feet (3 m) of the inverter. Download the DC Home app. Login to the app with your account.
DC Home App
Download on the
— 18 —

Short-Range Monitoring via DC Home App
If only short-range monitoring is required, connect the inverter to the DC Home app directly through the Bluetooth of your phone.

My Renogy
Time remaining —

No device found
Tap + in the upper-right corner to add your first device.

Device

Community

Select

Me

HUB Mode
Searching for device
Please make sure: 1. Bluetooth on this phone/tablet is turned on. 2. The device is running properly. 3. The device’s Bluetooth is turned on.
Identifying device… Found Devices
Inverter
RIV1210PU-126

Cancel

Confirm

My Renogy
25%

Device Battery
RBT12400LFPL-
25 % 0A

Inverter
RIV1210PU-126 A
0W 12.0 V

Device

Scene

Community

Me

Wireless Long-Range Monitoring
If long-range communication and programming are required, connect the inverter to Renogy ONE (sold separately) through Bluetooth, and the Renogy ONE to the DC Home app through Wi-Fi.
Recommended Components

RENOGY ONE Core or Renogy ONE M1
Components marked with “
” are available on renogy.com. For instructions on Renogy ONE, see Renogy ONE Core User Manual and Renogy ONE M1 User Manual.

Internet

My Renogy
25%

Devices Battery
RBT12400LFPL-
25 % 0A

Inverter
RIV1210PU-126 A
0W 12 V

Device

Scene

Community

Me

— 19 —

LED Overview & Troubleshooting

LED Status LED in À¤ker red
Power LED in solid green

Alarm Alarm beeps

Protection & Alarm

Inverter Status

Input voltage is below 11V.

Keep input voltage above 11V.

Input voltage is above 15.5V.

Keep input voltage below 15.5V.

No sound

Recovery from undervoltage

Normal output from the inverter.

GFCI LED in solid Long steady

yellow

beeping sound

No sound and
the inverter is o

Fault LED in solid red

Long steady beeping sound

GFCI protection

GFCI tripped
Overtemperature protection
Undervoltage shutdown
Short circuit protection Overvoltage protection

1. No output from the inverter. 2. Disconnect all appliances, and use the ON/OFF/Remote switch to reset the inverter. Attempt to connect various appliances one at a time, observing if the yellow LED on the inverter remains illuminated. If it stays o, this suggests a current leakage issue with one of the appliances. If the LED remains on, kindly reach out to Renogy via renogy.com/ contact-us for further assistance.
Disconnect appliances, and use the ON/OFF/Remote switch to reset the inverter.
1. No output from the inverter. 2. Allow the inverter to cool down. 3. Check for adequate ventilation. 4. Reduce the load on the inverter.
No output from the inverter. Keep input voltage above 10.5V.
No output from the inverter. After 5s, the inverter automatically restarts. After ve times of failed restart, the inverter needs to be restored by manually turning it on.
No output from the inverter. Keep input voltage below 16V.

— 20 —

LED Status

Alarm

Protection & Alarm

Inverter Status

Fault LED in solid red

Long steady beeping sound

Automated recovery after 20 Overload protection seconds (manual restart required if
automated recovery fails).

For further assitance, contact Renogy technical support service at https://www.renogy. com/contact-us.

Pure Sine Wave

The inverter outputs a pure sine wave similar to the waveform of the grid power. In a pure sine wave, the voltage rises and falls in a smooth fashion with very low harmonic distortion and cleaner utility-like power.
Pure Sine Waveform
200

150

Amplitude (Volts)

100

50

0

-50

-100

-150

-200

-0.02 -0.015 -0.01 -0.005

0

0.005

0.01

0.015

0.02

Time (Seconds)

This technology allows the inverter to supply electronic devices that require a high quality
waveform with little harmonic distortion. In addition, the technology enables the inverter to be more e¤Ànt than traditional ones, allowing you to use less energy to supply more devices. The inverter can provide su¤Ànt, stable power for tools, fans, lights, computers, and other
electronics without any interference.

— 21 —

Speci¤ations

General Data

Model

RIV1210PU-126

RIV1220PU-126

RIV1230PU-126

Output Waveform

Pure Sine Wave

AC Terminals

2 x AC sockets 1 x AC high-output
terminal block

2 x AC sockets 1 x AC high-output
terminal block

3 x AC sockets 1 x AC high-output
terminal block

DC Terminals

M8 x 25 mm

Operating Temperature

-4°F to 113°F / -20°C to 45°C

Storage Temperature

-40°F to 158°F / -40°C to 70°C

Humidity

Max 95%, non-condensing

Cooling

Fans

Dimensions (L x W x H)

15.3 x 8.1 x 3.8 in / 18.3 x 9.9 x 3.8 in / 19.2 x 10.4 x 3.8 in /

388.5 x 205.4 x 95.3 468.3 x 250.4 x 95.3 488.8 x 263.4 x 95.3

mm

mm

mm

Weight
Regulatory and Safety Speci¤ations

8.2 lb / 3.7 Kg

12.8 lb / 5.8 Kg

14.8lb / 6.7 Kg

UL certiª to 458 and to CSA 22.2 No. 107.1-01, FCC Prat15 Class B

Electrical Data

Continuous Output Power

1000W

2000W

3000W

Continuous Output Current

8.3A AC

16.6A AC

25.0A AC

Total Harmonic Distortion (THD)

< 3%

Power Factor

1

Surge Rating (after 2S the overload protection)

2000W (@2s)

4000W (@2s)

6000W (@2s)

Output Voltage

120V AC (±3%)

Output Frequency

50Hz / 60Hz

Rated Battery Input Voltage

12V DC

Battery Input Voltage Range

11.0V to 15.5V DC

Rated AC Input Voltage Range

90V to 140V AC

Transfer From AC Mains Supply to Battery

20 ms

Transfer From Battery Supply to AC Mains

20 ms

— 22 —

Maximum Continuous Battery Output Current
Inverter E¤À×cy Full Load E¤À×cy Power Consumption Battery Overoltage
Shutdown Battery Low Voltage Alarm
Battery Low Voltage Shutdown
Front Plate Dimensions Wired Length

105A

210A

310A

< 12W

92%, MAX 87% < 18W

< 18W

16.0V (±0.3V) DC

11.0V (±0.3V) DC

10.5V (±0.3V) DC

Wired Remote Data 2.8 x 4.3 x 1.3 in / 70 x 110 x 31.8 mm 16.4 ft / 5 m

General Safety Information

WARNING Have the inverter installed by a qualiª technician in accordance with the local and national electric codes (NEC). There are no serviceable parts for this inverter. Do not disassemble or attempt to repair the inverter. Ensure all connections going into and from the inverter are tight. There may be sparks when making connections; therefore, there should not be ÖÖ£ÐÖaterials or gases near the installation site. The inverters are suitable for 12V battery banks ONLY. Always ensure the inverter is in OFF position and disconnect all AC and DC devices associated with the inverter. Never connect the AC output of the inverter directly to an Electrical Breaker Panel or Load Center which is also fed from the utility power or generator. Please conëÖ the polarity of the devices before connection. A reverse polarity contact can cause injury and damage the device. Be careful when touching bare terminals of capacitors as they may retain high lethal voltages even after power is removed. Do not let the positive (+) and negative (-) terminals of the battery touch each other. Use only deep-cycle sealed lead-acid, Ýݪª¸ÐÝr lithium batteries. Risk of explosion! Never install the inverter in a sealed enclosure with Ýݪª£atteries! Do not install in a conתrea where battery gases can accumulate. Be careful when working with large lead acid batteries. Wear eye protection and have fresh water available in case there is contact with the battery acid. Overcharging and excessive gas precipitation may damage the battery plates and activate material shedding on them. Too high of an equalizing charge or too long of one may cause damage. Carefully review the requirements of the speci¤£attery in use. CAUTION
Install the inverter in a well-ventilated, cool, and dry environment. Make sure the fans of the inverter and the ventilation holes are not blocked. Do not expose the unit to rain, moisture, snow, or liquids of any type.
— 23 —

Renogy Support

To discuss inaccuracies or omissions in this quick guide or user manual,visit or contact us at:

renogy.com/support/downloads

contentservice@renogy.com

Questionnaire Investigation

To explore more possibilities of solar systems,visit Renogy Learning Center at: renogy.com/learning-center

For technical questions about your product in the U.S.,contact the Renogy technical support team through:

renogy.com/contact-us

1(909)2877111

For technical support outside the U.S.,visit the local website below:

Canada

ca.renogy.com

China

www.renogy.cn

Australia

au.renogy.com

Japan

renogy.jp

South Korea

kr.renogy.com

Germany

de.renogy.com

United Kingdom uk.renogy.com

Other Europe

eu.renogy.com

— 24 —

FCC Statement

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause
undesired operation. Any Changes or modi¤ations not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment o and on, the user is encouraged to try to correct the interference by one or more of the following measures: (1) Reorient or relocate the receiving antenna. (2) Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit dierent from that to which the receiver is
connected. (4) Consult the dealer or an experienced radio / TV technician for help.
FCC Radiation Exposure Statement
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20 cm between the radiator & your body.
— 25 —

Renogy Empowered
Renogy aims to empower people around the world through education and distribution of DIY-friendly renewable energy solutions. We intend to be a driving force for sustainable living and energy independence.
your carbon footprint by reducing the need for grid power.

Live Sustainably with Renogy
Did you know? In a given month, a 1 kW solar energy system will… Save 170 pounds of coal from being burned Save 300 pounds of CO from being released into the atmosphere Save 105 gallons of water from being consumed

Renogy Power PLUS
Renogy Power Plus allows you to stay in the loop with upcoming solar energy innovations, share your experiences with your solar energy journey, and connect with like-minded people who are changing the world in the Renogy Power Plus community.

@Renogy Solar

@Renogy

Renogy reserves the right to change the contents of this manual without notice.

RENOGY.COM

FCC ID : 2ANPB-RIV12S0PU

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals