Carrier 50FE-4-7-01SI Single Package Rooftop Cooling Instruction Manual
- July 4, 2024
- Carrier
Table of Contents
- Carrier 50FE-4-7-01SI Single Package Rooftop Cooling
- Specifications
- Product Usage Instructions
- FAQs
- SAFETY CONSIDERATIONS
- INSTALLATION
- ELECTRIC SHOCK HAZARD
- THERMOSTAT
- SEQUENCE OF OPERATION
- REASON
- ECONOMIZER SETTINGS
- Functions
- ECONOMIZER CONDITION MET
- DESCRIPTION
- SETUP AND CONFIGURATION
- TROUBLESHOOTING
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Carrier 50FE-4-7-01SI Single Package Rooftop Cooling
Specifications
- Model Number: 04-53500386-01
- Indoor Airflow: Rated
Product Usage Instructions
Installation
- Jobsite Survey: Assess the location for unit installation.
- Plan for Unit Location: Determine the optimal position for the unit.
- Plan for Sequence of Unit Installation: Outline the steps for installing the unit.
- Inspect Unit: Check the unit for any damages or issues.
- Provide Unit Support: Ensure proper support for the unit.
- Field Fabricate Ductwork: Fabricate ductwork as required.
- Rig and Place Unit: Lift and position the unit securely.
- Convert to Horizontal and Connect Ductwork (if needed): Adjust unit orientation and connect ductwork if necessary.
- Install Outside Air Hood: Attach the outside air hood.
- Units with Hinged Panels Only: Follow specific instructions for units with hinged panels.
- Install External Condensate Trap and Line: Set up the condensate trap and line.
- Make Electrical Connections: Connect the unit to the electrical supply.
Safety Considerations
Installation and servicing of this product should only be carried out by trained personnel. Basic maintenance tasks can be performed by untrained individuals, but all other operations must be handled by professionals. Safety precautions, including wearing safety glasses and gloves, should always be followed. Ensure compliance with safety codes and use appropriate equipment for all operations.
Start-Up Checklist
Refer to the provided start-up checklist (CL-1) to ensure all installation steps have been completed correctly before starting the unit.
FAQs
- Q: Can untrained individuals perform maintenance tasks on this product?
- A: Untrained personnel can perform basic maintenance functions like cleaning coils and filters, but all other operations should be done by trained service personnel.
- Q: What refrigerant does this unit use?
- A: This unit uses R454B, which is an A2L refrigerant. All service equipment or components must be A2L refrigerant rated when working with this unit.
WeatherMaker® 50FE-*04-07 Single Package Rooftop Cooling Only with R-454B Refrigerant
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due
to system pressure and electrical components. Only trained and qualified
service personnel should install, repair, or service air-conditioning
equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils
and filters and replacing filters. All other operations should be performed by
trained service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit, and other
safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching
cloth for unbrazing operations. Have fire extinguisher available for all
brazing operations.
It is important to recognize safety information. This is the safety-alert
symbol . When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500386-01
Printed in U.S.A.
Form No. 50FE-4-7-01SI Rev B
Pg 1
4-24
Replaces: New
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words
are used with the safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death. WARNING
signifies hazards which could result in personal injury or death. CAUTION is
used to identify unsafe practices, which may result in minor personal injury
or product and property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
DANGER
ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal
injury or death. Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and lockout tag(s).
Ensure electrical service to rooftop unit agrees with voltage and amperage
listed on the unit rating plate. Unit may have more than one power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause
personal injury, death and/or equipment damage. R454B is an A2L refrigerant.
All service equipment or components must be A2L refrigerant rated. Do not use
non-A2L rated equipment or components on R-454B refrigerant equipment
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final
unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and
other ignition sources away from refrigerants and oils.
CAUTION
PERSONAL INJURY HAZARD Failure to follow this caution may result in personal
injury. Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when handling parts
and servicing air conditioning equipment.
MODEL NUMBER NOMENCLATURE AND DIMENSIONS
See Fig. 1 for 50FE model number nomenclature. See Fig. 2 for unit dimensional
drawings and service clearance dimensions.
Rated Indoor Airflow
Table 1 lists the rated indoor airflow used for the AHRI efficiency rating for
the units covered in this document.
Table 1 — Rated Indoor Airflow
MODEL NUMBER 50FE-A/B04 50FE-A/B05 50FE-A/B06 50FE-M/N07
RATED INDOOR AIRFLOW (cfm) 1050 1500 1500 2400
2
Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Example: 5 0 F E – A 0 4 A 2 A 6 – 0 A 0 A 0
Unit Heat Type 50 = Cooling Only Packaged Rooftop
with Optional Electric Heat
Model Series — WeatherMaker® FE = Entery Tier Puron Advance
Heat Size – = No Heat (Field Installed Available)
Refrig. Systems Options A = Std One Stage Cooling Modelsa B = Std One Stage
Cooling Models with Humidi-MiZer® a, b M = Single Circuit, Two Stage Cooling
Modelsc N = Single Circuit, Two Stage Cooling Models with
Humidi-MiZerb, c
Cooling Tons 04 = 3 tons 05 = 4 tons 06 = 5 tons 07 = 6 tons
Sensor Options A = None B = Return Air (RA) Smoke Detector C = Supply Air (SA)
Smoke Detector D = RA + SA Smoke Detector J = Condensate Overflow Switch K =
Condensate Overflow Switch and RA Smoke Detector L = Condensate Overflow
Switch and RA + SA Smoke Detectors M = Condensate Overflow Switch and SA Smoke
Detector
Fan Options 2 = Standard/Medium Static — EcoBlue Vane Axial Fan 3 = High
Static — EcoBlue Vane Axial Fan 5 = Standard/Medium Static — EcoBlue Vane
Axial Fan and
Filter Status Switch 6 = High Static — EcoBlue Vane Axial Fan and Filter
Status Switch
Coil Options (Outdoor – Indoor — Hail Guard) A = Al/Cu – Al/Cu B = Precoat
Al/Cu – Al/Cu C = E-coat Al/Cu – Al/Cu D = E-coat Al/Cu – E-coat Al/Cu M =
Al/Cu – Al/Cu — Louvered Hail Guard N = Precoat Al/Cu – Al/Cu — Louvered Hail
Guard P = E-coat Al/Cu – Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu – E-coat
Al/Cu — Louvered Hail Guard R = Cu/Cu – Al/Cu — Louvered Hail Guard S = Cu/Cu
– Cu/Cu — Louvered Hail Guard
Packaging & Seismic Compliance 0 = Standard
Electrical Options A = None C = Non-Fused Disconnect (NFDC) D = Thru-the-Base
(TTB) Connections F = Non-Fused Disconnect and TTB Connections N = Phase
Monitor Protection (PMR) Q = PMR + NFDC R = PMR + TTB T = PMR + NFDC + TTB 1 =
HSCCRd (High Short Circuit Current Rating) 2 = HSCCRd + TTB
Service Options 0 = None 1 = Unpowered Convenience Outlet (NPCO) 2 = Powered
Convenience Outlet (PCO) 3 = Hinged Panels (HP) 4 = Hinged Panels + NPCO 5 =
Hinged Panels + PCO 6 = MERV-13 Filters (M13) 7 = NPCO + MERV-13 Filters 8 =
PCO + MERV-13 Filters 9 = Hinged Panels + MERV-13 Filters A = HP + NPCO +
MERV-13 Filters B = HP + PCO + MERV-13 Filters
Intake / Exhaust Options A = None B = Standard Leak Economizer with Barometric
Relief F = Standard Leak Enthalpy Economizer with
Barometric Relief L = ULL (Ultra Low Leak) Temperature Economizer
with Barometric Relief and CO2 Sensor M = ULL Enthalpy Economizer with
Barometric
Relief and CO2 Sensor U = ULL Temperature Economizer with Barometric Relief W
= ULL Enthalpy Economizer with Barometric Relief
Base Unit Controls 0 = Electromechanical Controls (allows for use of field-
installed economizers) 3 = SystemVuTM Controls 8 = Electromechanical Controls
— can be used with POL224
EconomizerONE (With Fault Detection and Diagnostic)
Design Revision – = Factory Design Revision
Voltage 1 = 575-3-60 3 = 208/230-1-60a, e 5 = 208/230-3-60 6 = 460-3-60
a Size 04/05/06 models only. b Units with Humidi-MiZer System include Low
Ambient controller. c Size 07 models only. d HSCCR is not available on units
with: 575V, Low Ambient Controls,
Phase Loss Monitor, Non-Fused Disconnect, or Powered Convenience Outlet. e The
following are not available as a factory-installed options for models with
this voltage code: Humidi-MiZer System, Coated Coils or Cu Fin Coils, Louvered
Hail Guards, Economizer, Powered Convenience Outlet or Upgraded MERV filters.
Fig. 1 — 50FE 04-07 Model Number Nomenclature (Example)
3
4
Fig. 2 — 50FE 04-07 Unit Dimensional Drawing
5
Fig. 2 — 50FE 04-07 Unit Dimensional Drawing (cont)
6
Fig. 2 — 50FE 04-07 Unit Dimensional Drawing (cont)
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code)
ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit
lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that
provides for minimum clearances required for safety (including clearance to
combustible surfaces), unit performance and service access below, around and
above unit as specified in unit drawings. See Fig. 2 on page 5.
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class A, B, or C roof-
covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near
exhaust vents or other sources of contaminated air.
Although unit is weatherproof, avoid locations that permit water from higher
level runoff and overhangs to fall onto unit.
Select a unit mounting system that provides adequate height to allow
installation of condensate trap per requirements. Refer to “Install External
Condensate Trap and Line” on page 12 for required trap dimensions.
ROOF MOUNT
Check building codes for weight distribution requirements. Unit operating
weight is shown in Table 2.
Table 2 — Operating Weights
50FE-*
Base Unit Economizer
Vertical Horizontal Humidi-MiZer® System Cu Fins Powered Outlet Curb 14 in.
(356 mm) 24 in. (610 mm)
UNIT lb (kg)
04
05
06
07
437 (198) 498 (226) 511 (232) 562 (255)
50 (23) 80 (36)
50 (23)
25 (11) 35 (16)
50 (23) 80 (36)
50 (23)
43 (20) 35 (16)
50 (23) 80 (36)
80 (36)
56 (25) 35 (16)
50 (23) 80 (36)
80 (36)
56 (25) 35 (16)
115 (52) 115 (52) 115 (52) 115 (52) 197 (89) 197 (89) 197 (89) 197 (89)
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the
steps of unit installation. For example, on curbmounted units, some
accessories must be installed on the unit before the unit is placed on the
curb. Review the following for recommended sequences for installation steps.
INSTALLATION
CURB-MOUNTED INSTALLATION
1. Install curb.
2. Install field-fabricated ductwork inside curb.
3. Install accessory thru-base service connection package (affects curb and
unit) (refer to accessory installation instructions for details).
4. Prepare bottom condensate drain connection to suit planned condensate line
routing (refer to Step 10 for details).
5. Rig and place unit.
6. Install outdoor air hood.
7. Install condensate line trap and piping.
8. Make electrical connections.
9. Install other accessories.
PAD-MOUNTED INSTALLATION
1. Prepare pad and unit supports. 2. Check and tighten the bottom condensate
drain connection
plug.
3. Rig and place unit.
4. Convert unit to side duct connection arrangement.
5. Install field-fabricated ductwork at unit duct openings.
6. Install outdoor air hood.
7. Install condensate line trap and piping.
8. Make electrical connections.
9. Install other accessories.
FRAME-MOUNTED INSTALLATION
Frame-mounted applications generally follow the sequence for a curb
installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation
agency. Confirm before installation of unit that voltage, amperage and circuit
protection requirements listed on unit data plate agree with power supply
provided. On units with hinged panel option, check to be sure all latches are
snug and in closed position. Locate the carton containing the outside air hood
parts. Do not remove carton until unit has been rigged and located in final
position.
Step 4 — Provide Unit Support
ROOF CURB MOUNT
Accessory roof curb details and dimensions are shown in Fig. 3 (on page 8).
Assemble and install accessory roof curb in accordance with instructions
shipped with the curb. Curb should be level. This is necessary for unit drain
to function properly. Unit leveling tolerances are shown in Fig. 4 (on page
9). Refer to Accessory Roof Curb Installation Instructions for additional
information as required. Install insulation, cant strips, roofing felt, and
counter flashing as shown. Ductwork must be attached to curb and not to the
unit. The accessory thru-the-base power and gas connection package must be
installed before the unit is set on the roof curb. If electric and control
wiring is to be routed through the basepan, attach the accessory thru-the-base
service connections to the basepan in accordance with the accessory
installation instructions. NOTE: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the roof curb as
shown in Fig. 3. Improperly applied gasket can also result in air leaks and
poor unit performance.
7
ROOF CURB ACCESSORY # CRRFCURB001A01
CRRFCURB002A01
A
14″ [356] 24″ [610]
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1″] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
CRBTMPWR001A01
THRU THE CURB
3/4″ [19] NPT
CRBTMPWR003A01
THRU THE BOTTOM
1/2″ [12.7] NPT
POWER WIRING FITTING
CONTROL WIRING ACCESSORY CONVENIENCE
FITTING
OUTLET WIRING CONNECTOR
3/4″ [19] NPT
1/2″ [12.7] NPT
1/2″ [12.7] NPT
1-3/4″ [44.5]
5.42″ [137.7] 21.74″ [552.2]
4.96″ [126.0]
15.19″ [385.8]
3.00″ [76.2]
14.00″ [355.6] 1.75″ [44.5]
4 9/16″ [115.5]
1/4″ [7.0]
11.96″ [303.8]
“A”
1.00″ [25.4]
11 3/4″[298.5] WIDE INSULATED DECK PANELS
70.87″ [1800.2]
1/3/4″[44.5] 21.84″ [554.7] SUPPLY AIR OPENING
RETURN AIR OPENING
E
16.03″ [407.2]
E
32.19″ [817.6]
20.41″ [518.3] 40.69″ [1033.5]
3.00″ [76.2] 13.78″ [350.0]
SUPPLY AIR
RETURN AIR
1-3/4″ [44.4] SECTION E-E
SCALE 0.250
8 9/16″[217.5] WIDE INSULATED DECK PANEL
GAS SERVICE PLATE THRU THE CURB DRILL HOLE 2″ [50.8] @ ASSEMBLY (IF REQUIRED)
(SEE NOTE #8)
1′ 4-13/16″ [427] INSIDE
2-3/8″ [61]
SEE NOTE #2
VIEW “B”
CORNER DETAIL
SUPPLY AIR
RETURN AIR
1-3/4″ [44.5]
1-3/4″ [44.4]
GASKET (SUPPLIED WITH CURB)
DUCT (FIELD SUPPLIED)
UNIT
7/16″ [11]
NAIL (FIELD SUPPLIED) TYPICAL (4) SIDES
COUNTER FLASHING (FIELD SUPPLIED)
“A”
3′-1 3/16″ [944.6]
5′ 7-3/8″ [1711.3]
ROOFING FELT (FIELD SUPPLIED)
CANT STRIP (FIELD SUPPLIED)
ROOFING MATERIAL (FIELD SUPPLIED)
RIGID INSULATION (FIELD SUPPLIED)
OVERALL DIM. 5′-7 3/8″ WAS 5′-7 7/8; 18GA A MATERIAL WA 16 GA.; NAIL FIELD
SUPPLIED WAS
WITH CURB
REV
REVISION RECORD
04/22/13 MMC –
–
DATE
BY CHK’D APP’D
SEE VIEW “B”
CERTIFIED DRAWING
DRAWING RELEASE LEVEL:
PRODUCTION
1067898 ECN NO.
THIRD ANGLE PROJECTION
MATERIAL
–
ENGINEERING REQUIREMENTS
T-005, Y-002
WEIGHT: –
SURFACE FINISH MFG/PURCH
–
PURCH
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES TOLERANCES ON:
1 DEC 2 DEC 3 DEC
ANG
–
–
–
–
AUTHORIZATION NUMBER 1041738
TITLE
CURB ASY, ROOF
ENGINEERING
MANUFACTURING
–
—
– SIZE DRAWING NUMBER
REV
DRAFTER MMC 06/17/11 –
CHECKER
-D
48TC400427
B
SHEET 5 OF 5
MODEL (INTERNAL USE ONLY)
NEXT DRAWING
SCALE
DISTRIBUTION
–
N/A
MMC
8
Fig. 3 — Roof Curb Details
C
A MAXIMUM ALLOWABLE
B
DIFFERENCE, in. (mm)
A-B
B-C
A-C
0.5 (13) 1.0 (25) 1.0 (25)
Fig. 4 — Unit Leveling Tolerances
SLAB MOUNT (HORIZONTAL UNITS ONLY)
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond
unit cabinet. Install a gravel apron in front of condenser coil air inlet to
prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR SLAB MOUNT)
A non-combustible sleeper rail can be used in the unit curb support area. If
sleeper rails cannot be used, support the long sides of the unit with a
minimum of 3 equally spaced 4 in. x 4 in. (102 mm x 102 mm) pads on each side.
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition) shall not exceed
0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without
economizer.
For vertical ducted applications, secure all ducts to roof curb and building
structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to
or greater than the unit supply duct opening dimensions for the first 18 in.
(458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with
a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted
through the roof deck to comply with applicable fire codes.
CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to
roofing materials. Membrane roofs can be cut by sharp sheet metal edges. Be
careful when placing any sheet metal parts on such roof.
FOR UNITS WITH ACCESSORY ELECTRIC HEATERS
All installations require a minimum clearance to combustible surfaces of 1 in.
(25 mm) from duct for first 12 in. (305 mm) away from unit. Outlet grilles
must not lie directly below unit discharge.
WARNING
PERSONAL INJURY HAZARD Failure to follow this warning could cause personal
injury. For vertical supply and return units, tools or parts could drop into
ductwork and cause an injury. Install a 90 degree turn in the return ductwork
between the unit and the conditioned space. If a 90 degree elbow cannot be
installed, then a grille of sufficient strength and density should be
installed to prevent objects from falling into the conditioned space. Due to
electric heater, supply duct will require 90 degree elbow.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are required. Rollers may be
used to move unit across a roof. Level by using unit frame as a reference. See
Table 2 on page 7 and Fig. 5 on page 10 for additional information. Lifting
holes are provided in base rails as shown in Fig. 5. Refer to rigging
instructions on unit. Rigging materials under unit (cardboard or wood to
prevent base pan damage) must be removed PRIOR to placing the unit on the roof
curb. When using the standard side drain connection, ensure the red plug in
the alternate bottom connection is tight. Do this before setting the unit in
place. The red drain plug can be tightened with a 1/2 in. square socket drive
extension. For further details see Step 10 — Install External Condensate Trap
and Line on page 12. Before setting the unit onto the curb, recheck gasketing
on curb.
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage. All panels must be in place when rigging. Unit is not designed for
handling by fork truck when packaging is removed. If using top crate as
spreader bar, once unit is set, carefully lower wooden crate off building roof
top to ground. Ensure that no people or obstructions are below prior to
lowering the crate.
POSITIONING ON CURB
Position unit on roof curb so that the following clearances are maintained:
1/4 in. (6.4 mm) clearance between the roof curb and the base rail inside the
front and back, 0.0 in. clearance between the roof curb and the base rail
inside on the duct end of the unit. This will result in the distance between
the roof curb and the base rail inside on the condenser end of the unit being
approximately 1/4 in. (6.4 mm). Although unit is weatherproof, guard against
water from higher level runoff and overhangs. After unit is in position,
remove rigging skids and shipping materials.
9
“B” Required Spreader
Bars
36-54 in. (914-1371 mm)
Place all seal strips in place before placing unit on roof curb
Duct End
Detail “A”
“C”
Fan Side
“A” See Detail “A”
NOTE(S): 1. SPREADER BARS ARE REQUIRED. Top damage will occur if spreader bars
are not used. 2. Hook rigging shackles through holes in base rail, as shown in
Detail A. Holes in base rails are centered around the unit center
of gravity. Use wooden top to prevent rigging straps from damaging unit.
UNIT
50FE-04 50FE-05 50FE-06 50FE-07
MAXIMUM WEIGHT
lb
kg
749
340
851
386
864
392
981
445
A
in.
mm
74.5
1890
74.5
1890
74.5
1890
74.5
1890
DIMENSIONS
B
in.
mm
36.6
930
35.5
900
35.5
900
35.0
890
C
in.
mm
33.5
850
33.5
850
33.5
850
41.5
1055
Fig. 5 — Rigging Details
Step 7 — Convert to Horizontal and Connect Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without factory-
installed economizer or return-air smoke detector option may be field-
converted to horizontal ducted configuration. To convert to horizontal
configuration, remove screws from side duct opening covers (see Fig. 6) and
remove covers. Use the screws to install the covers on vertical duct openings
with the insulation-side down. The panels must be inserted into the notches on
the basepan to properly seal. The notches are covered by the tape used to
secure the insulation to the basepan and are not easily seen. See Fig. 7 for
position of the notches in the basepan. Seals around duct openings must be
tight. Secure with screws as shown in Fig. 8. Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct openings and all
ductwork should be secured to the flanges. Insulate and weatherproof all
external ductwork, joints, and roof or building openings with counter flashing
and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when
insulating horizontal ductwork.
Removable Horizontal Return Duct Opening Cover
Removable Horizontal Supply Duct Opening Cover
Fig. 6 — Horizontal Conversion Panels
Notches
Notches
Basepan
Fig. 7 — Location of Notches 10
Screws
Hood Parts
Duct Covers Sheet Metal Face Up
Basepan
Fig. 8 — Horizontal Duct Panels In Place
Step 8 — Install Outside Air Hood
ECONOMIZER HOOD AND TWO-POSITION DAMPER HOOD PACKAGE REMOVAL AND SETUP
(FACTORY OPTION) NOTE: Economizer and two-position damper are not available as
factory installed options for single phase (-3 voltage code) models. Two-
position damper is not available for 07 models. The hood is shipped in knock-
down form and must be field assembled. The indoor coil access panel is used as
the hood top while the hood sides, divider and filter are packaged together,
attached to a metal support tray using plastic stretch wrap, and shipped in
the return air compartment behind the indoor coil access panel. The hood
assembly’s metal tray is attached to the basepan and also attached to the
damper using 2 plastic tie-wraps. 1. To gain access to the hood, remove the
filter access panel.
(See Fig. 9.)
Filter Access Panel
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
Fig. 10 — Economizer and Two-Position Damper Hood Parts Location
3. Carefully lift the hood assembly (with metal tray) through the filter
access opening and assemble per the steps outlined in the following section
Economizer Hood and 2-Position Hood.
ECONOMIZER AND 2-POSITION HOOD NOTE: If the power exhaust accessory is to be
installed on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power exhaust hood
assembly. 1. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of the indoor coil access
panel. See Fig. 11.
Top Panel
Compressor Access Panel
Outdoor-Air Opening And Indoor Coil Access Panel
Fig. 9 — Typical Access Panel Locations
2. Locate the (2) screws holding the metal tray to the basepan and remove.
Locate and cut the (2) plastic tie-wraps securing the assembly to the damper.
(See Fig. 10.) Be careful to not damage any wiring or cut tie-wraps securing
any wiring.
Indoor Coil Access Panel
Caulk Here
Top Panel
Indoor Coil Access Panel
Fig. 11 — Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 12.
11
Top Panel
Indoor Coil Access Panel
Left Hood Side
19-1/16 in. (483mm)
Screw
33-3/8 in. (848mm)
Hood Divider
Fig. 12 — Economizer Hood Construction
3. Remove the shipping tape holding the economizer barometric relief damper
in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 12 and 13. Secure
hood divider with 2 screws on each hood side. The hood divider is also used as
the bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the hood top. Insert
the aluminum filter into the bottom filter rack (hood divider). Push the
filter into position past the open filter clips. Close the filter clips to
lock the filter into place. See Fig. 13.
6. Caulk the ends of the joint between the unit top panel and the hood top.
7. Replace the filter access panel.
Divider
Outside Air
Hood
Barometric Relief
Cleanable Aluminum Filter Filter
Filter Clip
Fig. 13 — Economizer Filter Installation
Step 9 — Units with Hinged Panels Only
If the unit does not have hinged panels, skip this step and continue at Step
10 below.
Relocate latch shipped inside the compressor compartment behind the hinged
compressor door to location shown in Fig. 14 after unit installation.
Compressor Door
Outdoor Coil Latch
Fig. 14 — Compressor Door Latch Location
Step 10 — Install External Condensate Trap and Line
The unit has one 3/4 in. condensate drain connection on the end of the
condensate pan and an alternate connection on the bottom. See Fig. 15. Unit
airflow configuration does not determine which drain connection to use. Either
drain connection can be used with vertical or horizontal applications.
Condensate Pan (Side View)
Standard Side Drain
Drain Plug (Factory-Installed)
Alternate Bottom Drain
Fig. 15 — Condensate Drain Pan (Side View)
To use the alternate bottom drain connection, remove the red drain plug from
the bottom connection (use a 1/2 in. square socket drive extension) and
install it in the side drain connection.
The piping for the condensate drain and external trap can be completed after
the unit is in place. See Fig. 16.
NOTE: If the alternate bottom drain is not used, check the drain plug for
tightness prior to setting the unit on the roof curb.
Minimum Pitch 1 in. (25 mm) Per 10 ft (3 m) of Line
Base Rail
3 in. (76 mm) Open Min Vent
To Roof Drain
See Note
Drain Plug
Roof Curb
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4 in. (102 mm) trap is recommended.
Fig. 16 — Condensate Drain Piping Details
All units must have an external trap for condensate drainage. Install a trap at least 4 in. (102 mm) deep and protect against freezeup. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4 in.).
12
Step 11 — Make Electrical Connections
WARNING
ELECTRIC SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupted, unbroken electrical ground to
minimize the possibility of personal injury if an electrical fault should
occur. This ground may consist of electrical wire connected to unit ground lug
in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC; ANSI/NFPA 70, latest edition (in Canada,
Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and
local electrical codes.
NOTE: Check all factory and field electrical connections for tightness. Field-
supplied wiring shall conform with the limitations of minimum 63°F (33°C)
rise.
FIELD POWER SUPPLY
If equipped with optional powered convenience outlet: the power source leads
to the convenience outlet’s transformer primary are not factory connected.
Installer must connect these leads according to required operation of the
convenience outlet. If an alwaysenergized convenience outlet operation is
desired, connect the source leads to the line side of the unit-mounted
disconnect. (Check with local codes to ensure this method is acceptable in
your area.) If a de-energize via unit disconnect switch operation of the
convenience outlet is desired, connect the source leads to the load side of
the unit disconnect. On a unit without a unit-mounted disconnect, connect the
source leads to compressor contactor C pressure lugs with unit field power
leads.
Refer to Fig. 17 for power transformer connections and the discussion on
connecting the convenience outlet on page 14.
Units Without Non-Fused Disconnect Option
TB
TB
11 12
11 12 13
Disconnect per NEC
Disconnect per NEC
208/230-1-60
L1 L2 L3
208/230-3-60 460-3-60 575-3-60
Units With Non-Fused Disconnect Option
L1
2
1
L2
Optional
4
Disconnect
3
Switch
Factory Wiring
L3
6
5
Disconnect factory test leads; discard.
Fig. 17 — Power Wiring Connections
Field power wires are connected to the unit at line-side pressure lugs on
compressor contactor C (see wiring diagram label for control box component
arrangement) or at factory-installed option non-fused disconnect switch.
Maximum wire size is No. 2 AWG (copper only). (See Fig. 17 and 18.)
NOTE: TEST LEADS – Unit may be equipped with short leads (pigtails) on the
field line connection points on contactor C or optional disconnect switch.
These leads are for factory run-test purposes only; remove and discard before
connecting field power wires to unit connection points. Make field power
connections directly to line connection pressure lugs only.
WARNING
FIRE HAZARD Failure to follow this warning could result in personal injury,
death, or property damage. Do not connect aluminum wire between disconnect
switch and unit. Use only copper wire.
Electric Disconnect
Switch
Copper Wire Only
Aluminum Wire
Fig. 18 — Disconnect Switch and Unit
UNITS WITH FACTORY-INSTALLED NON-FUSED DISCONNECT
The factory-installed option non-fused disconnect (NFD) switch is located in a
weatherproof enclosure located under the main control box. The manual switch
handle and shaft are shipped in the disconnect enclosure. Assemble the shaft
and handle to the switch at this point. Discard the factory test leads (see
Fig. 17).
Connect field power supply conductors to LINE side terminals when the switch
enclosure cover is removed to attach the handle.
Field-Install the NFD Shaft and Handle
1. Remove the control box access panel. The NFD enclosure is located below
the control box (see Fig. 19).
2. Remove (3) cap head screws that secure the NFD enclosure front cover — (2)
on the face of the cover and (1) on the left side cover. See Fig. 20.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at OFF position (the arrow
on the black handle knob is at OFF).
5. Insert the shaft with the cross pin on the top of the shaft in the
horizontal position. See Fig. 20.
6. Measure from the tip of the shaft to the top surface of the black pointer;
the measurement should be 3.75 to 3.88 in. (95 to 99 mm).
7. Tighten the locking screw to secure the shaft to the NFD.
8. Turn the handle to the OFF position with red arrow pointing at OFF.
9. Install the handle on to the painted cover horizontally with the red arrow
pointing to the left.
10. Secure the handle to the painted cover with (2) screws and lock washers
supplied.
11. Engaging the shaft into the handle socket, re-install (3) hex screws on
the NFD enclosure.
12. Re-install the unit front panel.
13
BLK YEL BLU
Fig. 19 — NFD Enclosure Location
connected line-side pressure lugs on the power terminal block or at factory-
installed option non-fused disconnect.
CONVENIENCE OUTLETS
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circuits may use multiple disconnects. Check
convenience outlet for power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it. Lock-out and tag-out this
switch, if necessary.
Two types of convenience outlets are offered on 50FE models: non-powered and
unit-powered. Both types provide a 125-v GFCI (ground-fault circuit-
interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access
cover, located on the end panel of the unit. See Fig. 21.
Figure 22 shows the Convenience Outlet Utilization label which is located
below the convenience outlet.
Convenience Outlet GFCI
PWD-CO Fuse Switch
Fig. 20 — NFD Handle and Shaft Assembly
UNITS WITHOUT FACTORY-INSTALLED NON-FUSED DISCONNECT
When installing units, provide a disconnect switch per NEC (National
Electrical Code) of adequate size. Disconnect sizing data is provided on the
unit informative plate. Locate on unit cabinet or within sight of the unit per
national or local codes. Do not cover unit informative plate if mounting the
disconnect on the unit cabinet.
ALL UNITS
All field wiring must comply with NEC and all local codes. Size wire based on
MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 17 and the
unit label diagram for power wiring connections to the unit power terminal
blocks and equipment ground. Maximum wire size is No. 2 ga AWG per pole.
Provide a ground-fault and short-circuit over-current protection device (fuse
or breaker) per NEC Article 440 (or local codes). Refer to unit informative
data plate for MOCP (Maximum Overcurrent Protection) device size.
All field wiring must comply with the NEC and local requirements.
All units except 208/230-v units are factory wired for the voltage shown on
the nameplate. If the 208/230-v unit is to be connected to a 208-v power
supply, the control transformer must be rewired by moving the black wire with
the 1/4 in. female spade connector from the 230-v connection and moving it to
the 200-v 1/4 in. male terminal on the primary side of the transformer. Refer
to unit label diagram for additional information. Field power wires will be
PWD-CO Transformer
Fig. 21 — Convenience Outlet Location
Fig. 22 — Convenience Outlet Utilization Notice Label NOTE: Unit powered
convenience outlets are not available as factory installed options for size
04-06 single phase (-3 voltage code) models. Installing Weatherproof Cover A
weatherproof while-in-use cover for the factory-installed convenience outlets
is now required by UL standards. This cover cannot be factory-mounted due its
depth; it must be installed at unit installation. For shipment, the
convenience outlet is covered with a blank cover plate. On units with
electromechanical controls the weatherproof cover kit is shipped in the unit’s
control box. The kit includes the hinged cover, a backing plate and gasket.
14
On units with a factory installed direct digital controller (DDC; SystemVuTM
controls or RTU Open controller) the weatherproof cover kit is secured to the
basepan underneath the control box. See Fig. 23.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET. LOCK-OUT AND TAG-OUT ALL
POWER.
Remove the blank cover plate at the convenience outlet; discard the blank
cover.
Weatherproof Cover
Fig. 23 — Weatherproof Cover — Shipping Location on Units with Factory-
Installed DDC
Loosen the 2 screws at the GFCI duplex outlet, until approximately 1/2 in. (13
mm) under screw heads are exposed. Press the gasket over the screw heads. Slip
the backing plate over the screw heads at the keyhole slots and align with the
gasket; tighten the 2 screws until snug (do not over-tighten).
Mount the weatherproof cover to the backing plate as shown in Fig. 24. Remove
2 slot fillers in the bottom of the cover to permit service tool cords to exit
the cover. Check for full closing and latching.
Cover — While-In-Use Weatherproof
GFCI Receptacle Not Included
Unit-Powered Convenience Outlet
A unit-mounted transformer is factory-installed to stepdown the main power
supply voltage to the unit to 115-v at the duplex receptacle. This option also
includes a manual switch with fuse, located in a utility box and mounted on a
bracket behind the convenience outlet; access is through the unit’s control
box access panel. See Fig. 21.
The primary leads to the convenience outlet transformer are not factory-
connected. Selection of primary power source is a customer option. If local
codes permit, the transformer primary leads can be connected at the line-side
terminals on the unit-mounted nonfused disconnect or HACR (Heating, Air
Conditioning, and Refrigeration) breaker switch; this will provide service
power to the unit when the unit disconnect switch or HACR switch is open.
Other connection methods will result in the convenience outlet circuit being
de-energized when the unit disconnect or HACR switch is open. See Fig. 25.
Using Unit-Mounted Convenience Outlets
Units with unit-mounted convenience outlet circuits will often require that 2
disconnects be opened to de-energize all power to the unit. Treat all units as
electrically energized until the convenience outlet power is also checked and
de-energization is confirmed. Observe National Electrical Code Article 210,
Branch Circuits, for use of convenience outlets.
TOP
TOP
TOP
WET LOCATIONS
WET LOCATIONS
Gasket
Baseplate For GFCI Receptacle
Fig. 24 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose 125-v 15-A
circuit powered from a source elsewhere in the building. Observe national and
local codes when selecting wire size, fuse or breaker requirements and
disconnect switch size and location. Route 125-v power supply conductors into
the bottom of the utility box containing the duplex receptacle.
UNIT VOLTAGE 208, 230
460
575
CONNECT AS 240
480
600
PRIMARY CONNECTIONS
L1: RED +YEL L2: BLU + GRA
L1: RED Splice BLU + YEL
L2: GRA
L1: RED L2: GRA
TRANSFORMER TERMINALS
H1 + H3 H2 + H4
H1 H2 + H3
H4
H1 H2
Fig. 25 — Powered Convenience Outlet Wiring
Test the GFCI receptacle by pressing the TEST button on the face of the
receptacle to trip and open the receptacle. Check for proper grounding wires
and power line phasing if the GFCI receptacle does not trip as required. Press
the RESET button to clear the tripped condition.
Fuse On Power Type
The factory fuse is a BussmannTM1 “FusetronTM1” T-15, non-renewable screw-in
(Edison base) type plug fuse.
1. Third-party trademarks and logos are the property of their respective
owners.
15
FACTORY OPTION THRU-BASE CONNECTIONS
This service connection kit consists of a 1/2 in. electrical bulkhead
connector and a 3/4 in. electrical bulkhead connector, connected to an “L”
bracket covering the embossed (raised) section of the unit basepan in the
condenser section (see Fig. 26 for shipping position).
The 3/4 in. bulkhead connector enables the low-voltage control wires to pass
through the basepan. The 1/2 in. bulkhead connector allows the high-voltage
power wires to pass through the basepan. See Fig. 27.
Fig. 26 — Thru-the-Base Fitting Assembly (Shown in Shipping Position)
High Voltage Conduit Connector
Low Voltage Conduit Connector
Auxiliary Power Supply (Optional)
Fig. 27 — Thru-Base Connection Fittings
1. Remove the “L” bracket assembly from the unit. 2. Remove connector plate
assembly from the “L” bracket and
discard the “L” bracket, but retain the washer head screws and the gasket
(located between the “L” bracket and the connector plate assembly).
NOTE: Take care not to damage the gasket, as it is reused in the following
step. 3. Place the gasket over the embossed area in the basepan, align-
ing the holes in the gasket to the holes in the basepan. See Fig. 27.
4. Install the connector plate assembly to the basepan using 8 of the washer
head screws.
NOTE: If electrical connections are not going to occur at this time, tape or
otherwise cover the fittings so that moisture does not get into the building
or conduit in the interim.
Check tightness of connector lock nuts before connecting electrical conduits.
Field-supplied and field-installed liquid-tight conduit connectors and conduit
may be attached to the connectors on the basepan. Pull correctly rated high
voltage and low voltage through appropriate conduits to maintain separation
between low voltage and high voltage wires in accordance with UL and NEC
requirements. Connect the power conduit to the internal disconnect (if unit is
so equipped) or to the external disconnect (through unit side panel). Remove
one of the two knockouts located on the bottom left side of the unit control
box. Use this hole for the control conduit.
UNITS WITHOUT THRU-BASE CONNECTIONS
1. Install power wiring conduit through side panel openings. Install conduit
between disconnect and control box.
2. Install power lines to terminal connections as shown in Fig. 17.
Voltage to compressor terminals during operation must be within voltage range
indicated on unit nameplate. On 3-phase units, voltages between phases must be
balanced within 2% and the current within 10%. Use the formula shown below to
determine the percent of voltage imbalance. Operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate any applicable Carrier
warranty.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage average voltage
Example: Supply voltage is 230-3-60
AB C
MOTOR
AB = 224-v BC = 231-v AC = 226-v
(224 + 231 + 226)
681
Average Voltage =
=
= 227
3
3
Determine maximum deviation from average voltage. (AB) 227-224 = 3-v (BC) 231-227 = 4-v (AC) 227-226 = 1-v Maximum deviation is 4-v. Determine percent of voltage imbalance.
4
% Voltage Imbalance = 100x
= 1.76%
227
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
FIELD CONTROL WIRING
The 50FE unit requires an external temperature control device. This device can
be a thermostat (field-supplied) or a SystemVuTM controller (available as
factory-installed option for use on a Carrier Comfort Network® or as a stand-
alone control). All field added wire must comply with UL and local NEC
standards.
16
THERMOSTAT
Select a Carrier-approved accessory thermostat. When electric heat is
installed in the 50FE unit, the thermostat must be capable of energizing the G
terminal whenever there is a space call for heat (energizing the W1 terminal).
The accessory thermostats listed on the unit price pages can provide this
signal but they are not configured to enable this signal as shipped.
Install the accessory thermostat according to installation instructions
included with the accessory.
Locate the thermostat accessory on a solid wall in the conditioned space to
sense average temperature in accordance with the thermostat installation
instructions.
If the thermostat contains a logic circuit requiring 24-v power, use a
thermostat cable or equivalent single leads of different colors with minimum
of 7 leads. If the thermostat does not require a 24-v source (no “C”
connection required), use a thermostat cable or equivalent with minimum of 6
leads. See Fig. 28. Check the thermostat installation instructions for
additional features which might require additional conductors in the cable.
For wire runs up to 50 ft (15 m), use No. 18 AWG (American Wire Gauge)
insulated wire [35°C (95°F) minimum]. For 50 to 75 ft (15 to 23 m), use No. 16
AWG insulated wire [35°C (95°F) minimum]. For over 75 ft (23 m), use No. 14
AWG insulated wire [35°C (95°F) minimum]. All wire sizes larger than No. 18
AWG cannot be directly connected to the thermostat and will require a junction
box and splice at the thermostat.
Typical Thermostat Connections
C
Unit Control Board
C
G
W2
W1
O/B/Y2
(Note 1)
Y1
(Note 3) (Note 2)
HUM T
G
H
E
W2
R
M
W1
O S
T
Y2
A
T Y1
R
R
NOTES: 1. Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2. 2. Y2 to Y2 connection required on single-stage
cooling units when
integrated economizer function is desired. 3. W2 connection not required on
units with single-stage heating.
Field Wiring
Fig. 28 — Typical Low-Voltage Control Connections
UNIT WITHOUT THRU-BASE CONNECTION KIT
Pass the thermostat control wires through the hole provided in the corner
post, then feed the wires through the raceway built into the corner post to
the control box. Pull the wires over to the terminal strip on the upper-left
corner of the Unit Control Board. See Fig. 29.
Raceway
Hole In End Panel (Hidden)
Fig. 29 — Field Control Wiring Raceway
NOTE: If thru-the-bottom connections accessory is used, refer to the accessory
installation instructions for information on routing power and control wiring.
HEAT ANTICIPATOR SETTINGS
Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for
second-stage heating, when available.
ELECTRIC HEATERS
The 50FE units may be equipped with field-installed accessory electric
heaters. The heaters are modular in design, with heater frames holding open
coil resistance wires strung through ceramic insulators, line-break limit
switches and a control contactor.
Heater modules are installed in the compartment below the indoor (supply) fan
outlet. Access is through the indoor access panel. See Fig. 30-32.
Not all available heater modules may be used in every unit. Use only those
heater modules that are UL listed for use in a specific size unit. Refer to
the label on the unit cabinet for the list of approved heaters.
Refer to the Small Roof Top Units Accessory Electric Heater and Single Point
Box installation instructions for further details.
Control Box Access Panel
Indoor Access Panel
Fig. 30 — Typical Access Panel Location
17
Optional
Main
Factory-Installed Control
Disconnect
Box
Single Point Box
Vane Axial Center Indoor Fan Post System
Manual Reset Limit Switch
Control Wire Heater Terminal Block Cover
Heater Mounting Bracket
Fig. 31 — Typical Component Location
All fuses on 50FE units are 60-A. (Note that all heaters are qualified for use
with a 60-A fuse, regardless of actual heater ampacity, so only 60-A fuses are
necessary.)
SINGLE POINT BOXES WITHOUT FUSES
Unit heater applications not requiring supplemental fuses require a special
single point box without any fuses. The accessory single point boxes contain a
set of power taps and pigtails to complete the wiring between the single point
box and the unit’s main control box terminals. Refer to accessory heater and
single point box installation instructions for details on tap connections.
LOW-VOLTAGE CONTROL CONNECTIONS
Pull the low-voltage control leads from the heater module — VIO and BRN (2 of
each if a 2-circuit heater module is installed; identify for circuit no. 1) —
to the 4-pole terminal board TB4 located on the heater bulkhead to the left of
the Heater module. Connect the VIO lead from Heater circuit no. 1 to terminal
TB4-1. For 2 stage heating, connect the VIO lead from Heater circuit no. 2 to
terminal TB4-2. See Fig. 34.
UCB 2
3
PNK ORN
Heater Module
Fig. 32 — Typical Heater Module Installation
SINGLE POINT BOXES AND SUPPLEMENTARY FUSES
When the unit MOCP device value exceeds 60-A, unit-mounted supplementary fuses
are required for each heater circuit. These fuses are included in accessory
single point boxes, with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box, just to the left of
the partition separating the indoor section (with electric heaters) from the
outdoor section. The single point box has a hinged access cover. See Fig. 33.
The single point box also includes a set of power taps and pigtails to
complete the wiring between the single point box and the unit’s main control
box terminals. Refer to the Small Roof Top Units Accessory Electric Heater and
single point box installation instructions for details on tap connections.
Control Wiring
Foam
Power Wiring
Heater Relay
Heater Mounting Screws
Fig. 33 — Typical Single Point Installation
TRAN 1 C
ORN
TB4
1
PNK 2
BRN 3
VIO
Field Connections
VIO BRN BRN
Elec Htr VIO HR2
BRN
VIO HR1 BRN
HR1: Heater Circuit 1 HR2: Heater Circuit 2
(if two-circuit module installed)
Fig. 34 — Accessory Electric Heater Control Connections
HUMIDI-MIZER SYSTEM CONTROL CONNECTIONS
Humidi-MiZer Space RH Controller
NOTE: The Humidi-MiZer system is a factory-installed option. Humidi-MiZer
system is not available for single phase (-3 voltage code) models.
The Humidi-MiZer dehumidification system requires a fieldsupplied and field-
installed space relative humidity control device. This device may be a
separate humidistat control (contact closes on rise in space RH above control
set point) or a combination thermostat-humidistat control device such as
Carrier’s Edge® Pro ThermidistatTM device with isolated contact set for
dehumidification control. See Fig. 35 and 36. The humidistat is normally used
in applications where a temperature control is already provided (units with
SystemVuTM control).
18
% RELATIVE HUMIDITY
Fig. 35 — Accessory Field-Installed Humidistat
®
Fig. 36 — Edge Pro Thermidistat Connecting the Carrier Humidistat (HL38MG029)
- Route the humidistat 2-conductor cable (field-supplied)
through the hole provided in the unit corner post. 2. Feed wires through the raceway built into the corner post (see
Fig. 29) to the 24-v barrier located on the left side of the
control box. The raceway provides the UL-required clearance between high-
voltage and low-voltage wiring.
3. Connect one of the leads from the 2-conductor cable to the HUM terminal on
the UCB (Unit Control Board). Connect the other lead to the R terminal on the
UCB. See Fig. 37.
Unit Control Board
Humidistat
C HUM G W2
W1 Y2 Y1 R
Thermostat
Fig. 37 — Humidistat Connections to UCB
Connecting the Thermidistat device (33CS2PPRH-01)
1. Route the Thermidistat multi-conductor thermostat cable (field-supplied)
through the hole provided in the unit corner post.
2. Feed wires through the raceway built into the corner post (see Fig. 29) to
the 24-v barrier located on the left side of the control box. The raceway
provides the UL-required clearance between high-voltage and low-voltage
wiring.
3. The Thermidistat has dry contacts at terminals D1 and D2 for
dehumidification operation (see Fig. 38). Connect D1 to the R terminal on the
UCB. Connect D2 to the HUM terminal on the UCB. Refer to the installation
instructions included with the Carrier Edge® Pro Thermidistat device for more
information.
TYPICAL UNIT WIRING DIAGRAMS
See Fig. 39-44 for examples of typical unit control and power wiring diagrams.
These wiring diagrams are mounted on the inside of the unit control box cover.
19
Programmable Thermostat
Rc Rh W1 G Y2
C O/W2/B
Y1
OAT RRS S RTN HUM
D1 D2 V+ Vg
Unit Control Board Thermostat Connections
C HUM G W2
W1 Y2 Y1 R
Fig. 38 — Typical Rooftop Unit with Humidi-MiZer® Adaptive Dehumidification System and Edge® Pro Thermidistat Device
20
21
Fig. 39 — Typical 50FE 04-06 Control Wiring Diagram, Electromechanical with POL224 EconomizerONE
22
Fig. 40 — Typical 50FE 07 Control Wiring Diagram, Electromechanical with POL224 EconomizerONE
T
Fig. 41 — Typical 50FE 04-07 Power Wiring Diagram, 460/575V Unit Shown 23
24
Fig. 42 — Typical 50FE 04-06 SystemVuTM Control Wiring Diagram
25
Fig. 43 — Typical 50FE 07 SystemVuTM Control Wiring Diagram
Fig. 44 — Typical 50FE 04-07 SystemVuTM Control Power Wiring Diagram, 460/575V Unit Shown 26
Leak Dissipation System
50FE units use R-454B refrigerant. These units are equipped with a factory
installed R-454B leak dissipation system to ensure safe operation in the event
of a refrigerant leak. This systems consists of an A2L sensor (Fig. 45) and
the dissipation control board (see Fig. 46) which are located in the Indoor
Coil section of the unit (see the view labeled “BACK” in Fig. 2 on page 6).
The A2L sensor is located between the indoor coil and the air filters.
A2L Sensor
SEQUENCE OF OPERATION
The control functions as an R454B refrigerant dissipation system. If the
refrigerant detection sensor sends a signal indicating a refrigerant leak, the
control board will prevent heating and cooling operation and begin dissipating
the sensed refrigerant with a blower request. The refrigerant dissipation
board will display a flash code from the yellow status LED (see Fig. 47)
indicating the sensor that detected the refrigerant. See Fig. 49 on page 29
for the full text on the Dissipation Control dust cover label.
When the sensor signal indicates the refrigerant has dissipated, the
dissipation board yellow status LED will display a flash code 3 and return to
its normal state and allow unit operations after a 5 minute delay.
LEAK DISSIPATION SYSTEM SELF-TEST
Power on the unit and verify proper functioning of equipment. The yellow
Status LED on the dissipation board should be steady (see Fig. 47). If flash
codes are present, see Troubleshooting on page 29.
NOTE: Operation of the Test Mode is only possible if no faults exist on the
dissipation board.
Remove the dust cover from the Dissipation control board to access the Test
button (see Fig. 48). The Test button is located above the COMM LED.
Fig. 45 — Location of A2L Sensor
Dissipaton Board
See Detail A
Fig. 46 — Location of Dissipation Control Board (Shown with Dust Cover
Removed)
The A2L detection sensor communicates via a wiring harness to the dissipation
board The sensor harness is routed on the bottom of the filter rack towards
the unit bulkhead and secured with wire ties. The sensor harness then runs up
the side of the filter rack and exits over the top of the rack towards the
dissipation board.
NOTE: The drain wire must be properly connected to the ground lug on the
dissipation board via the quick connect and ground harness. Failure of proper
sensor harness grounding can lead to false dissipation events.
Status LED
Detail A
Fig. 47 — Yellow STATUS LED
27
See Detail A
See Detail B
Detail A — Test Button
Detail B — Status LED
Fig. 48 — Dissipation Control Board — Shown without Dust Cover
Press the Test button on the dissipation system control board to ensure proper dissipation system operation under each test condition listed below. After pressing the Test button, system will enter Dissipation Mode for 60 seconds to help verify correct operation.
IMPORTANT: Press the Test button for roughly ONE SECOND to enter Test Mode. Pressing the Test button for a longer periods enables different functions (see Table 3).
Table 3 — Dissipation Board Test Button Functions
HOLD BUTTON TIME (SEC)
FUNCTION
1-4
Dissipation Mode for 60 seconds
5-29
Display flash code history
30+
Flash code 6
3 Rapid Presses
Clear flash code history
Ensure that the unit is able to meet the minimum required dissipation mode airflows. These required minimum airflow rates during Dissipation Mode are listed in Table 4. They are based on the total system refrigerant charge quantity.
Table 4 — Minimum Dissipation Air Flows
MINIMUM DISSIPATION AIR FLOW (cfm)
UNIT
cfm
50FE-A04
190
50FE-A05
390
50FE-A06
340
50FE-M07
350
50FE-B04
300
50FE-B05
570
50FE-B06
620
50FE-N07
810
Table 5 details the required operational checks to ensure proper dissipation system function.
28
Table 5 — Dissipation System Required Operational Checks
TEST NO. 1 2 3
4 5 6
NORMAL OPERATION
UNIT DEMAND
COMPRESSOR
INDOOR FAN
None
Off
Off
Cool
On
On
Heat
On
On
DISSIPATION ACTIVATED
None
Off
On
Cool
Off
On
Heat
Off
On
ELECTRIC/ GAS HEAT
Off Off On
Off Off Off
Figure 49 shows the flash codes displayed on the Dissipation Control Board.
Fig. 49 — Dissipation Control Cover Label
TROUBLESHOOTING
For all flash codes, first try power cycling the system to remove the code. No
Power Verify the wiring to/from pins 1 and 8 on the power harness plug. Check
the 24V system wiring from the transformer. See Table 6 for details on the
operating status and troubleshooting of the Dissipation system for the various
flash codes.
Table 6 — Status LED Troubleshooting Table
STATUS LED Flashing 1 Flashing 2 Flashing 3
Flashing 4 Flashing 5 Flashing 6 Flashing 7
Flashing 8 Flashing 9a Flashing 10a Flashing 11a Flashing 12 Flashing 13
REASON
CONTROL VERBIAGE
Sensor 1 20% LFL
SENSOR 1 R454B LEAK
Sensor 1 Open
SENSOR 1 OPEN
5 Minute Blower Operating, Sensor < 20% LFL and sensors are not opened MITIGATION OFF DELAY ACTIVE (done after fault 1, 2, 9 and 10)
0 VAC sensed on G output.
BLOWER OUTPUT NOT OPERATING
Fault with the A2L digital sensor
SENSOR 1 FAULT
If KY1 is stuck pressed for more than 30 seconds.
TEST BUTTON STUCK
Y out switched with Y in or W out switched with W in
Y (K4) OR W (K1) WIRING INVERTED
Y or W shorted (relay detects both sides are high)
Y (K4) OR W (K1) OUTPUT SHORTED TO Y (K4) OR W (K1) INPUT
Sensor 2 20% LFL
SENSOR 2 R454B LEAK
Sensor 2 Open
SENSOR 2 OPEN
Fault with the second A2L digital sensor
SENSOR 2 FAULT
High temperature sensor attached on commercial
INCORRECT TEMP SENSOR
G input signal is lost. Indicates another unit safety will override dissipation.
EXT SAFETY OVERRIDE
MODE Dissipation in Process Dissipation in Process
Dissipation in Process
Dissipation in Process Dissipation in Process To prevent a shorted KY1 to keep
the mitigation running continuously. Normal mode
Normal mode
Dissipation in Process Dissipation in Process Dissipation in Process
Normal mode
Normal mode
NOTE(S):
a. There is only one sensor mounted in these units. This table represents the
standard label being put on all commercial equipment. The hardware changes
only allow one sensor to be connected to the board; the software remains the
same for a one or two sensor board. Although unlikely these flash codes may
appear if the board malfunctions.
LEGEND
LFL
— Lower Flammable Limit
29
Humidi-MiZer® Dehumidification System (Optional)
Units with the factory-installed Humidi-MiZer system option are capable of
providing multiple modes of improved dehumidification as a variation of the
normal cooling cycle. The Humidi-MiZer system option includes additional
valves in the liquid line and discharge line of the refrigerant circuit and a
reheat coil downstream of the evaporator. Humidi-MiZer system operation
requires the installation and configuration of a relative humidity switch
input or a space relative humidity sensor. These provide the dehumidification
demand to the control.
With Humidi-MiZer system units, there are two additional HVAC modes available
for the user: Dehumidification and Dehum/Mech Cooling. Selection of the
Dehum/Mech Cooling mode is determined by the dehumidification demand and the
cooling demand. Table 7 shows the corresponding circuit mode and output status
for the different demand combinations.
NORMAL COOLING
This mode is the standard rated cooling system performance, and occurs when
there is cooling demand without dehumidification demand.
For 50FE 04-06 units, refrigerant flows through the outdoor condenser and is
diverted away from the reheat coil with the open Cooling Liquid Valve (CLV)
into the expansion device. Figure 50 shows the complete refrigerant flow. The
Reheat Discharge Valve (RDV) is closed.
For 50FE 07 units, refrigerant flows through the outdoor condenser and is
diverted away from the reheat coil with the closed Reheat Liquid Valve (RLV)
and open CLV into the expansion device. Figure 51 shows the complete
refrigerant flow. The RDV is closed.
DEHUM/MECH COOLING (SUBCOOLING) MODE
This mode increases the latent heat removal and decreases sensible cooling
compared to normal cooling. This occurs when there is a cooling and
dehumidification demands.
For 50FE 04-06 units, refrigerant flows through the outdoor condenser and is
diverted through the reheat coil with the closed CLV into the expansion
device. Figure 52 shows the complete refrigerant flow. The RDV is closed.
For 50FE 07 units, refrigerant flows through the outdoor condenser and is
diverted through the reheat coil with the open RLV and closed CLV into the
expansion device. Figure 53 shows the complete refrigerant flow. The RDV is
closed.
DEHUMIDIFICATION (HOT GAS REHEAT) MODE
This mode provides maximum latent cooling with little to no sensible capacity.
This occurs when there is a dehumidification demand and no cooling demand.
For 50FE 04-07 units, this is the same as the Subcooling mode but the RDV is
open, which provides some compressor discharge gas to the reheat condenser to
further increase the reheat of the evaporator air stream. (See Fig. 54 and
55.)
REHEAT CONTROL
When there is only a cooling demand, the unit will operate in normal cooling
mode. When there is only dehumidification demand, the unit will operate in
Dehumidification mode (Hot Gas Reheat). When there is both cooling demand and
dehumidification demand, the unit will operate in Dehum/Mech Cooling mode
(Subcooling). During Dehumidification and Dehum/Mech cooling mode, the unit
will run all cooling stages.
Table 7 — Humidi-MiZer System Control Modes
DEMAND AND MODE
Dehumidification Demand
Cooling Demand
No Power
No Power
Mode No power
No
No
Off
No
Yes
COOL
Yes
No
DEHUM
Yes
Yes
DEHUM/MECH COOL
Compressor Off Off On On On
OUTPUTS
RDV
CLV
De-energized (no flow)
De-energized (no flow)
De-energized (no flow)
Energized (flow)
De-energized (no flow)
De-energized (flow)
De-energized (flow)
De-energized (flow)
Energized (no flow)
Energized (no flow)
RLV (50FE 07 only)
De-energized (flow)
Energized (no flow)
Energized (no flow)
De-energized (flow)
De-energized (flow)
RDV Valve
Condenser Coil
Indoor Leaving Air
Hot Gas Reheat Coil
Reheat Mode Metering
Device (TXV)
Outdoor Air Compressor
CLV Valve
Evaporator Coil
= Closed Valve = Open Valve
Indoor Entering Air
Fig. 50 — Normal Cooling Mode Humidi-MiZer System with Single Stage Cooling, 50FE 04-06
30
RDV Valve
Condenser Coil
RLV Valve
Indoor Supply Air
Hot Gas Reheat Coil
Outdoor Air Compressor
CLV Valve
Expansion Valve (TXV)
Evaporator Coil
= Closed Valve = Open Valve
Indoor Return Air
Fig. 51 — Normal Cooling Mode Humidi-MiZer System with 2 Stage Cooling, 50FE 07
RDV Valve
Condenser Coil
Indoor Leaving Air
Hot Gas Reheat Coil
Reheat Mode Metering
Device (TXV)
Outdoor Air Compressor
CLV Valve
Evaporator Coil
= Closed Valve = Open Valve
Indoor Entering Air
Fig. 52 — Subcooling Mode Humidi-MiZer System with Single Stage Cooling, 50FE 04-06
RDV Valve
Indoor Supply Air
Condenser Coil Outdoor Air
Compressor
RLV Valve
CLV Valve
Hot Gas Reheat Coil
Expansion Valve (TXV)
Evaporator Coil
= Closed Valve = Open Valve
Indoor Return Air
Fig. 53 — Subcooling Mode Humidi-MiZer System with 2 Stage Cooling, 50FE 07
31
RDV Valve
Condenser Coil
Indoor Leaving Air
Hot Gas Reheat Coil
Reheat Mode Metering
Device (TXV)
Outdoor Air Compressor
CLV Valve
Evaporator Coil
= Closed Valve = Open Valve
Indoor Entering Air
Fig. 54 — Hot Gas Reheat Mode Humidi-MiZer System with Single Stage Cooling, 50FE 04-06
RDV Valve
Indoor Supply Air
Condenser Coil Outdoor Air
Compressor
RLV Valve
CLV Valve
Hot Gas Reheat Coil
Expansion Valve (TXV)
Evaporator Coil
= Closed Valve = Open Valve
Indoor Return Air
Fig. 55 — Hot Gas Reheat Mode Humidi-MiZer System with 2 Stage Cooling, 50FE 07
32
EconomizerONE (Factory Option)
ECONOMIZER SETTINGS
Interface Overview
EconomizerONE
This option consists of the following:
· Low Leak Economizer Assembly
· HH79NZ039 OA (Outdoor Air) Dry Bulb Sensor
· HH79NZ039 Mixed Air Sensor
· POL224 Controller
· 48TC005897 Harness
POL224 Economizer Module Wiring
The economizer controller used on electromechanical units is a Siemens POL224,
which is to be located in the RTU base unit’s control box. See Fig. 56 for
button description of the POL224 controller. Refer to the unit dimensional
drawing for the location of the control box access panel.
The POL224 controller provides the following:
1. One-line LCD (Liquid Crystal Display) — After a period of inactivity, the
controller displays the default HMI (Human Machine Interface) screen (free
cooling status, 1FREE-COOL YES or 1FREE COOL NO). See Fig. 56-60.
2. Operation button (Up button) — Move to the previous value, step, or
category.
3. Operation button (Down Button) — Move to the next value, step, or
category.
4. Operation Button (Enter Button):
a. Press Enter to edit the current value or option.
b. Press Enter to confirm a newly selected value or option.
c. Press Enter + Up to jump up one entire category.
d. Press Enter + Down to jump down one entire category.
User Interface and Keypad
The controller user interface consists of an LCD display and a 3-button keypad
for input. The LCD is a 16 character by 1-line dot matrix display. The keypad
is used to navigate and change the desired menu items on the display. See Fig.
56.
The ClimatixTM1 mobile application allows for installation, commissioning, and
servicing. Scanning a QR code on the controller allows users to download the
mobile application on AndroidTM1 or Apple iOS®1, but a Wi-Fi/WLAN stick is
needed. See Fig. 56 and 57. Plug Wi-Fi/WLAN stick into controller USB port for
temporary connection for mobile application setup. The Wi-Fi/WLAN stick can be
used for multiple units.
Menu Structure
Menus are displayed in the economizer controller via categories. There are
eight first-level menus, each of which is represented by a number at the
beginning of the line on the LCD. Pressing Enter + Up or Down can toggle
between different first-level menus. Submenus follow the numbered first-level
menus closely. Pressing Up or Down can toggle between different submenus.
At the end of the line, the LCD displays the value of the current submenu (if
any). If the value is editable, pressing Enter will put the terminal in Edit
mode. The value is then highlighted for change. After making a change by
pressing Up or Down, press Enter to confirm the change and exit the Edit mode.
See Fig. 59.
Powering the Economizer Controller
The POL224 controller power connections are made through the economizer
harness (P/N 48TC005897). Connections from
the harness are made to the C (24 vac common) and R (24 vac power) terminals
of the economizer controller. See Fig. 58.
LED Indication
NOTE: If different faulty events occur at the same time, then sensor/DAC LED
lights up following the priority below: Red Yellow Off. For example, if there
is a humidity sensor error and air temperature failure at the same time, then
the sensor LED turns red rather than yellow. See Fig. 60 and Table 8.
IMPORTANT: After the Economizer controller enters the running state, it may
take one minute for peripheral devices to complete initialization. Before
that, LED indication might be unstable.
1
2
3
4 5 6
NOTE: QR codes in this image are for reference only.
NO.
DESCRIPTION
1 USB port for Wi-Fi/WLAN stick.
2 QR code to download ClimatixTM mobile application.
One-line LCD. After a period of inactivity, the controller
3
displays the default: HMI screen (free cooling status, 1FREECOOL YES or
1FREECOOL NO)
4
Operation button (Up button) – Move to the previous value, step or category.
5
Operation button (Down button) – Move to the next value, step or category.
Operation button (Enter button):
· Press to edit the current value or option.
6
· Press to confirm a newly selected value or option. · Press Enter + Up to jump up one entire category.
· Press Enter + Down to jump down one entire
category.
Fig. 56 — POL224 Controller
1. Third-party trademarks and logos are the property of their respective owners.
NOTE: QR codes in this image are for reference only.
Fig. 57 — Wi-Fi/WLAN Stick
33
Power
Fig. 58 — Powering the EconomizerONE Controller
1
2
3
No. Description
1 Number representing the first-level menu of Status Display. Different
numbers represent different menus: 1: Status Display 2: Basic Settings 3:
Advanced Settings 4: Alarms 5: Enter Configuration State and Reset 6: I/O
Config 7: Testing 8: Enter Running State
2 Submenu
3 Value of the current submenu
*See “Setup and Configuration” on page 43 for detailed submenus together with possible values or ranges.
Fig. 59 — Menu Structure Descriptions
Table 8 — LED Indication
STATUS
FREE COOLING
LED
Commissioning mode
Yellow Blinking
Power start up
Yellow On
Free cooling is running
Green On
Free cooling is available but not running
Green Blinking
Not economizing when it should
Red Blinking
Economizing when it should not
Red On
Sensor working okay
—
Humidity sensor error
—
CO2 sensor error
—
Air temperature fault/failure
—
Excess outdoor air
—
Damper working okay
—
Damper not modulating
—
Damper slippage
—
Damper unplugged
—
Terminal ACT-FB is
configured but no available
—
feedback signal
SENSOR LED
Yellow Blinking Yellow On
—
—
—
—
Green On Yellow On
LED Off Red On
Red Blinking
— —
—
—
—
DAC LED
Yellow Blinking Yellow On
—
—
—
—
— — — —
—
Green On Red On
Red Blinking Fast Red Blinking
LED Off
Functions
Free Cooling Economizing
Free cooling uses unconditioned outside air to cool the space directly. The
economizer controller enables or disables free cooling after it judges which
control mode is active. It also uses hysteresis to ensure a smooth switchover.
Depending on the sensors that are used, there are four different control
modes. In different control modes, the assessed conditions are different. See
Table 9.
Default Hysteresis Setting
Hysteresis setting (DB) defaults to 2°F (17°C). See Fig. 61.
DB On
123
NO.
DESCRIPTION
1
Free Cooling LED
2
Sensor LED
3
DAC LED
Fig. 60 — LED Indication
Off
ShutOff SP LEGEND OAT — Outside Air Temperature DB — Deadband SP — Set Point
OAT
Fig. 61 — Hysteresis Settings
34
Table 9 — Free Cooling Functions
CONTROL MODE
Control Mode 1 · Fixed Dry bulb
SENSORS USED
OA (outside air) temperature sensor and MA (Mixed Air) temperature sensor
Control Mode 2
OA temperature sensor, RA (Return Air)
· Differential Dry bulb temperature sensor and MA temperature
(Dual Dry bulbs) sensor
Control Mode 3 · Combination Fixed OA temperature and humidity sensor, and MA
Enthalpy and Fixed temperature sensor Dry bulb Control
Control Mode 4
· Combination of
OA temperature and humidity sensor, RA
Differential
temperature and humidity sensor,
Enthalpy and Fixed and MA temperature sensor
Dry bulb
ENABLE FREE COOLING?
The outside air dry bulb temperature is compared with the set temperature
shutoff setpoint. If the outside air dry bulb temperature is below the
temperature shutoff setpoint, then the outside air is used to meet all or part
of the cooling demand.
The outside-air dry bulb temperature is compared with the return air dry bulb
temperature. If both OAT and RAT are higher than the temperature high
limitation, then free cooling is prohibited. If OAT or RAT is lower than the
temperature high limitation and the outside air dry bulb temperature is lower
than the return air dry-bulb temperature, then the outside air is used to meet
all or part of the cooling demand.
The outside air dry bulb temperature and enthalpy are compared with the set
temperature and enthalpy shutoff setpoints. If the outside air enthalpy is
lower than the set enthalpy shutoff setpoint, and the outside air dry bulb
temperature is lower than the temperature shutoff setpoint, then the outside
air can be used for economizing.
The outside air dry bulb temperature and enthalpy are compared with the
temperature shutoff setpoint and return air enthalpy. If both OA enthalpy and
RA enthalpy are higher than the enthalpy high limitation, then free cooling is
prohibited. If OA enthalpy or RA enthalpy is lower than the enthalpy high
limitation, outside air enthalpy is lower than the return-air enthalpy, and
the outside air dry bulb temperature is lower than the set temperature shutoff
setpoint, then outside air can be used for economizing.
Damper Modulation During Free Cooling
Once outside air is suitable for free cooling, the controller modulates the
damper based on MAT (mixed air temperature, default) or OAT (outside air
temperature). Refer to Table 9.
If MAT is used when free cooling is enabled, MAT setpoint (3MAT SET,
configurable in “Parameter Settings — Advanced” on page 46) is used for MAT
modulating. When MAT falls below the anti-freeze setpoint (3FRZ PROT), the
damper either fully closes or opens to the minimum position (configurable in
“Parameter Settings — Advanced” on page 46).
1. If MAT is lower than MAT setpoint, then the damper is modulated to
maintain MAT setpoint, towards fully closed or open to the minimum position
based on occupancy status if MAT continues dropping.
2. If MAT is in the range [MAT setpoint, (MAT setpoint + neutral zone band
[1°F by default])], then the damper position does not change.
3. If MAT is higher than (MAT setpoint + neutral zone band), then the damper
opens towards fully open.
4. If MAT is 10°F higher than MAT setpoint, then the damper fully opens to
100%.
If OAT is used when there is a cooling demand, the damper can be opened to
different positions depending on different outside air temperatures:
1. If outside air is higher than 50°F but lower than the temperature shutoff
setpoint, then the damper is fully open.
2. If outside air is higher than OAT lockout setpoint but lower than 50°F,
then linear modulation is applied when only
Cooling Stage 1 input (Y1I) is ON. Result of the following formula indicates
the damper’s open position:
([OAT – OAT Lockout Setpoint] / [50 – OAT Lockout Setpoint]) * (80% – MIN POS)
- MIN POS
NOTE: When both free cooling and mechanical cooling are on, damper remains fully open regardless of the modulating logic.
Location-Based Shutoff Setpoints
The economizer controller can get location-based temperature and enthalpy shutoff setpoints automatically if it is connected to the ClimatixTM mobile application. Once a Wi-Fi/WLAN stick is plugged in, the economizer controller can establish network connection with the mobile application. The temperature and enthalpy shutoff setpoints obtained via the phone or tablet’s GPS functionality can then be synchronized to the economizer controller.
Cooling Stage Operation
The economizer controller accepts inputs for 1 and 2-stage cooling inputs and reroutes to the RTU through the relay connection Y1 and Y2.
The operation of the cooling stages is determined by the availability of Free Cooling provided by the economizer operation mode. See Cooling Stage I/O Logic Tables 10-11. Based on the use of Free Cooling, the operating modes are as follows:
· Y1 is Stage 1 Cooling Demand.
· Y2 is Stage 2 Cooling Demand.
· Free Cooling is always the first cooling stage.
· Cooling Stage 1 call from the Commercial Thermostat (Y1) energizes the Y1 input to the economizer controller.
· Cooling Stage 2 call from the Commercial Thermostat (Y2) energizes the Y2 input to the economizer controller.
35
Table 10 — 1 and 2-Stage Cooling Stage I/O Logic
ECONOMIZER CONDITION MET
Y1
NO
On
NO
On
NO
Off
YES
On
YES
On
YES
Off
Y2
COOLING COOLING STAGE 1 STAGE 2
On
On
On
Off
On
Off
Off
Off
Off
On
On
On/Offa
Off
Off
Off
Off
Off
Off
NOTE(S):
a. If OAT MAT setpoint (3MAT SET), then Relay 2 is always OFF to disable
Cooling Stage 2. Otherwise, if both stages of cooling (Y1 and Y2) are ON for
more than a set time (15 minutes by default), Y2 remains ON, and the OAT is
higher than MAT setpoint, then Relay 2 energizes to allow Y2 pass-through to
enable Cooling Stage 2.
Table 11 — 2-Stage Cooling Stage I/O Logic
ECONOMIZER CONDITION MET
Y1
NO
On
NO
On
NO
On
NO
Off
YES
On
YES
On
YES
On
YES
Off
Y2
COOLING COOLING STAGE 1 STAGE 2
On
On
On
On
On
On
Off
On
Off
Off
Off
Off
On
On
On
On
On
On/Off
Off
Off
Off
Off
Off
Off
IMPORTANT: The economizer controller can tolerate thermostat wiring mismatch, e.g. Thermostat Y1 Economizer Y2-In, Thermostat Y2 Economizer Y1-In. The handling logic is Stage =Y1I + Y2I. For example, Y1O =1 if Stage > =1, Y2O =1 if Stage > = 2.
Multi-Speed Fan Support
The economizer controller supports connection to 2-speed fans. When the unit
is equipped with a multi-speed fan, the damper responds to multiple fan speeds
via multiple minimum positions (MIN POS) to keep minimum airflow. See Tables
12-14.
Table 12 — Damper MIN POS for 2-Speed Fana
Y1
Y2
W1 OR O/B
SPD L
SPD H
POS L
POS H
X
—
—
X
—
X
—
X
X
—
—
X
—
X
—
—
X
—
X
—
X
NOTE(S):
a. A multi-speed fan is not controlled by the economizer controller but by an
external logic board.
LEGEND
POS L — Damper MIN POS for Low-Speed Fan POS H — Damper MIN POS for High-Speed
Fan SPD L — Low-Speed (Fan) SPD H — High-Speed (Fan)
Table 13 — Different Fan Speeds with Different Configured Outputsa
FAN TYPE 1-SPEED
FANc
2-SPEED FANc
1-SPEED COOLINGb
· Spd H (regardless of cooling demand, OCC=Yes)
· Spd L (0 or 1 cooling demand)
· Spd H (2 cooling demands)
2-STAGE COOLINGb
· Spd H (regardless of cooling demand, OCC=Yes)
· Spd L (0 or 1 cooling demand)
· Spd H (2 cooling demands)
NOTE(S):
a. If a single-speed fan connects to the Controller, it opens directly on the
call of cooling/heating. The damper position is Pos H.
b. Configured by Y1O or Y2O. c. Configured by 6FAN.
LEGEND
Spd L — Low Speed (Fan) Spd H — High Speed (Fan)
Table 14 — Different Damper Minimum Positions with Different Configured Outputs
FAN TYPE
1-SPEED FANb
2-SPEED FANb
1-SPEED COOLINGa
· Pos H (regardless of cooling demand, OCC=Yes)
· Pos H (regardless of cooling demand, OCC=Yes)
2-STAGE COOLINGb
· Pos H (regardless of cooling demand, OCC=Yes)
· Pos L (0 or 1 cooling demand)
· Pos H (2 cooling demands)
NOTE(S):
a. Configured by Y1O or Y2O. b. Configured by 6FAN.
LEGEND
Pos L — Damper MIN POS for Low-Speed Fan Pos H — Damper MIN POS for High-Speed
Fan
If DCV (demand controlled ventilation) is enabled, each fan speed corresponds
to two damper position ventilation setpoints (VENT MIN, VENT MAX), e.g., Pos L
corresponds to 2VENTMIN L… 2VENTMAX L. See Table 15 for Different Damper
Position Setting with Different Configured Outputs with DCV enabled.
If CO2 sensor is connected but DCV is disabled, then each fan speed
corresponds to one minimum damper position ventilation setpoint. See Table 16
for Different Damper Position Setting with Different Configured Outputs with
DCV disabled.
36
Table 15 — Different Damper Position Settings with Different Configured Outputs (DCV is Enabled)
FAN TYPE 1-SPEED FANb
2-SPEED FANb
NOTE(S): a. Configured by Y1O or Y2O. b. Configured by 6FAN.
1-STAGE COOLINGa · 2VENTMIN H to 2VENTMAX H (regardless of
cooling demand, OCC=Yes)
· 2VENTMIN H to 2VENTMAX H (regardless of cooling demand, OCC=Yes)
2-STAGE COOLINGa
· 2VENTMIN H to 2VENTMAX H (regardless of cooling demand, OCC=Yes)
· 2VENTMIN L to 2VENTMAXL (0 or 1 cooling demand)
· 2VENTMIN H to 2VENTMAX H (2 cooling demands)
Table 16 — Different Damper Position Settings with Different Configured Outputs (DCV is Disabled, CO2 sensor is connected)
FAN TYPE 1-SPEED FANb
2-SPEED FANb
1-STAGE COOLINGa · 2VENTMIN H (regardless of cooling demand,
OCC=Yes)
· 2VENTMIN H (regardless of cooling demand, OCC=Yes)
2-STAGE COOLINGa
· 2VENTMIN H (regardless of cooling demand, OCC=Yes)
· 2VENTMIN L (0 or 1 cooling demand)
· 2VENTMIN H (2 cooling demands)
NOTE(S):
a. Configured by Y1O or Y2O. b. Configured by 6FAN.
Cooling Delay via Increasing Fan Speed
If there is cooling demand while outside air is suitable for economizing, then
the economizer controller tries to increase fan speed to maximize the use of
outside air first. If the cooling demand is not reached within a set time,
then mechanical cooling will be enabled.
Typical field application:
1. Prerequisites:
· Outside air is suitable for economizing and free cooling is ON.
· Fan connected to the controller supports multiple speeds. Cooling delay
function does not work if only a one-speed fan is connected to the controller.
2. If it is a 2-speed fan and there are two cooling demand inputs/outputs and
Y1-Input is called, then the controller sets fan speed to Speed Low. Damper is
fully open (100%).
If Y2-Input is also called, then the controller increases fan speed to Speed
High and starts fan delay (2FAN DLY) time. After the delay time runs out, the
controller starts Y1-Output.
Demand Controlled Ventilation (DCV)
If a field-installed CO2 sensor is connected to the EconomizerONE controller,
then a demand controlled ventilation strategy will operate automatically. As
the CO2 level in the space increases above the setpoint (on the EconomizerONE
controller), the minimum position of the dampers will be increased
proportionally until the Maximum Ventilation setting is reached. As the space
CO2 level decreases because of the increase in fresh air, the outdoor damper
will follow the higher demand condition from the DCV mode or from the free
cooling mode.
The controller modulates the outside air damper based on the CO2 level through
the ppm value selected between the range of 500 and 2000 ppm. The measured CO2
concentration value is compared with the set DCV setpoint. If the measured CO2
concentration value is below the DCV setpoint, then keep the damper to the
minimum position. Otherwise, enable DCV. Once DCV is enabled, the DCV PID
starts to run to control the indoor CO2 concentration value towards the DCV
setpoint. The damper opens to the maximum position.
NOTE: DCV is disabled if the controller receives no occupancy signal.
DCV operation is available in Occupied and Unoccupied periods with the
EconomizerONE system. However, a control modification will be required on the
unit system to implement the Unoccupied period function. Refer to controller
accessory installation instruction manual for further controls and command
operation information.
High Humidity Limitation
The economizer controller applies high limit of humidity to enthalpy-based
economizing. When the OA dew point is below the dew point setpoint, enthalpy-
based economizing is available. Otherwise, enthalpy-based economizing is
unavailable.
Anti-Freeze Protection
The economizer controller initiates the anti-freeze protection if MAT or OAT
temperature falls below the anti-freeze setpoint.
MAT-Based Anti-Freeze Protection
1. If MAT temperature falls below the anti-freeze setpoint (3FRZ PROT), then:
· The controller closes both damper and compressor if unit type is
conventional unit and cooling/heating conventional operation mode is enabled.
· The controller closes the damper if unit type is heat pump and heat pump
operation mode is enabled.
2. If the MAT sensor fails, MAT is substituted by OAT to continue the anti-
freeze assessment. If OAT fails too, the controller closes the damper
immediately.
OAT-Based Anti-Freeze Protection
If OAT temperature falls below the OAT lockout setpoint (3OAT LOCK):
1. The controller stops the compressor from running if unit type is
conventional unit and cooling/heating conventional operation mode is enabled.
2. The controller compressor is bypassed if unit type is heat pump and heat
pump operation mode is enabled.
37
Exhaust Fan Operation
Up to two exhaust fans can be connected to the economizer controller.
· If Exhaust Fan 1 is connected and configured, then Exhaust Fan 1 parameter
group (L, M and H) is available, depending on fan configuration.
· If Exhaust Fan 2 is connected and configured, then Exhaust Fan 2 parameter
group (L, M and H) is available, depending on fan configuration.
· The controller energizes Exhaust Fan Relay 1 and Exhaust Fan Relay 2 if the
damper position reaches Exhaust Fan 1 parameter setting and Exhaust Fan Relay
2 parameter setting respectively. The selection of L, M, or H matches the
current fan speed.
NOTE: If terminal ACT-FB is configured, then the damper position is the damper
feedback position. If feedback signal is unavailable, it is the simulated
position.
Occupancy Input
The economizer controller can receive an occupancy signal from the connected
thermostat or work under Occupied mode all the time. This is configurable in
the Thermostat setup from the ClimatixTM mobile application or under the I/O
Configuration menu on the inbuilt display. See “Parameter Settings — I/O
Configurations” on page 46 for more information.
IMPORTANT: On the call of cooling, when the controller is configured to
receive signal from the thermostat but the thermostat is working under the
Unoccupied mode, the damper is fully closed if outside air is not suitable for
economizing. If outside air is suitable for economizing, the damper is fully
open.
Pre-occupancy Purge
The pre-occupancy purge demand comes from the configuration of the Auxiliary
features in the ClimatixTM mobile application or 6AUX2-I under the I/O
Configuration menu on the inbuilt display.
During pre-occupancy purge on the call of heating or when there is no
cooling/heating demand, the damper position is MIN POS.
During pre-occupancy purge on the call of cooling, the damper position is MIN
POS if outside air is not suitable for economizing. If outside air is suitable
for economizing, then the damper is fully open.
Airflow Commissioning
Airflow measurement station (differential pressure signal) can connect to the
controller temporarily to run airflow commissioning to calculate, calibrate,
and store 4 fan speed characteristic curves automatically at damper positions
40%, 60%, 80%, and 100%. The controller places the damper to a proper position
to meet minimum or any other airflow requests in cfm.
Users can enable this function only from the ClimatixTM mobile application if
the related function is available in the current mobile application version.
Fault Detection and Diagnostics The economizer controller can detect and
diagnose free cooling faults, sensor operation faults, and damper modulating
faults. It can also report anti-freeze and shutdown notifications and actuator
errors. Following is a list of all detectable or reportable information: ·
Sensor disconnected or has no signal. · Sensor short or high signal (under
range or over range). · Not economizing. · Unexpected economizing. · Excess
outdoor air. · Damper not modulating. · Input power monitor and brownout.
After detecting
brownout, the economizer controller enters the brownout protection mode and
disables all of the relay outputs. · Anti-freeze notifications. · Shutdown
notifications. · Actuator errors. · Too low or too high leaving air
temperature. · Cooling/heating error. · Damper actuator cycle count. Parameter
1ACT CNT indicates number of times actuator has cycled. It is resettable via
HMI item 8ACT CNT RESET.
IMPORTANT: The first 6 faults are detectable via LEDs or alarm reports on the
LCD. See LED Indication on page 34 and Alarms on page 47 for fault
indications. These faults can also be displayed in the Operating section of
the ClimatixTM mobile application.
Firmware Update NOTE: Back up configurations before firmware update. All the
previous configuration data are erased after firmware update. NOTE: Contact
Application Engineering for more information on support for firmware.
IMPORTANT: If the controller enters the configuration state for the
convenience of I/O configurations, then users can manually switch to the
running state after finishing configurations. To do so, press Enter + Up at
the same time, and then press Enter to confirm the switch after 8RUN STATE
appears on the LCD.
38
WIRING
WARNING
Failure to follow this caution may result in damage to equipment. Be sure to
allow enough time for compressor startup and shutdown between checkout tests
so that the compressors do not short-cycle. Mounting Devices Connected to the
Economizer Controller Devices like damper actuators, sensors (temperature
sensor, humidity sensor, combination temperature and humidity sensor, CO2
sensor), thermostats, and exhaust fans can be connected to the economizer
controller. For information on how to mount the devices, see the device’s
installation instructions. See Fig. 62 and Table 17 for economizer controller
wiring details.
Fig. 62 — EconomizerONE Control Wiring
39
Table 17 — EconomizerONE Control Wiring Settings
NO.
LABEL
TYPE
1
RS485 Modbus A
2
–
RS485 Modbus B
3
¬
GND_ISO
4
MAT Type II NTC 10K or 0-10 vdc
5
COM COM
6
OAT
Type II NTC 10K or 0-10 vdc
7
OAH 0-10 vdc or 4-20mA
8
COM COM
9
AUX-AI 0-10 vdc, 2-10 vdc or 0-5 vdc
10
RAT
Type II NTC 10K or 0-10 vdc
11
RAH 0-10 vdc or 4-20mA
12
S-COM COM
13
S-24V 24 vac
14
ACT-FB 2-10 vdc
15
ACT2-10 2-10 vdc
16
ACT-COM COM
17
ACT-24V 24 vac
18
AUX2-O 24 vac OUT
19
COM COM
20
AUX2-I 24 vac IN
21
AUX1-O 24 vac OUT
22
COM COM
23
AUX1-I 24 vac IN
24
OCC 24 vac IN
25
Y2O
24 vac OUT
26
Y2I
24 vac IN
27
Y1O
24 vac OUT
28
Y1I
24 vac IN
29
C
COM
30
R
24 vac
DESCRIPTION
Line A
Line B
Earth Ground
Mixed or Discharge Air Temperature Sensor
Mixed or Discharge Air Temperature Sensor Common
Outside Air Temperature Sensor
Outside Air Relative Humidity Sensor
Outside Air Temperature Sensor or Outside Air Relative Humidity Sensor Common
Air Quality Sensor or Pressure Sensor
Return Air Temperature Sensor
Return Air Relative Humidity Sensor
24 vac Common
24 vac Power Out to Sensors
Damper Actuator Feedback
Damper Actuator Output
Damper Actuator Output Common
24 vac Power Out to Damper Actuator
Configurable: · Exhaust Fan (1 or 2) · System Alarm output (Title 24)
24 vac Common
Configurable: · Shut Down · Heat Conventional (W1) · Heat Pump Changeover
(reversing valve OB) · Pre-occupancy
Configurable: · Exhaust Fan (1 or 2) · System Alarm output (Title 24)
24 vac Common
Configurable: · Shut Down · Heat Conventional (W1) · Heat Pump Changeover
(reversing valve OB) · Pre-occupancy
Occupancy Input
Cooling Stage 2 Output to Stage 2 Mechanical Cooling
Cooling Stage 2 Input from Commercial Thermostat
Cooling Stage 1 Output to Stage 1 Mechanical Cooling
Cooling Stage 1 Input from Commercial Thermostat
24 vac Common
24 vac Power
40
Connecting Peripheral Devices to the Economizer Controller See Fig. 63-67 for wiring details.
· Outside Air:
Connect to the
Mixed or Discharge Air Temperature Sensor
OAT and COM
terminals of the device.
Outside Air Temperature Sensor
· Return Air
(Differential): Connect to the RAT
Return Air Temperature Sensor
and S-COM
terminals of the
device.
· Mixed Air: Connect
to the MAT and
COM terminals of
the device.
Fig. 63 — Temperature Sensor Connection
· Outside Air
Relative Humidity:
Connect to the
OAH and COM
terminals of the
Outside Air Relative Humidity Sensor
device.
· Return Air Relative
Humidity: Connect to the RAH and
Return Air Relative Humidity Sensor
S-COM terminals of
the device.
Fig. 64 — Relative Humidity Sensor Connection
41
· Outside
Combination
Temperature/
Humidity: Connect Combo Temperature and Humidity Sensor
to the OAT, COM,
and OAH terminals
of the device.
· Return
Combo Temperature and Humidity Sensor
Combination
Temperature/
Humidity: Connect
to the RAT, S-COM,
and RAH terminals
of the device.
Fig. 65 — Combination Temperature/Humidity Sensor Connection
· Connect to the
AUX-AI, S-COM, and S-24V terminals of the device.
Air Quality Sensor or Pressure Sensor
Fig. 66 — CO2 / Pressure Sensor Connection
· Connect to the
ACT 2-10,
ACT-COM, and
ACT-24V terminals
of the device.
Damper Actuator: Power and 2-10 Vdc
Fig. 67 — Damper Actuator Connection
42
SETUP AND CONFIGURATION
IMPORTANT: Before setup and configuration, it is recommended to obtain some
location-based values, such as shutoff points, or utilize the location
services in the ClimatixTM mobile application.
Set up and configure the economizer controller before putting it into usage.
This can be accomplished by using the ClimatixTM mobile application or the
inbuilt display. After sensor, compressor, thermostat, or actuator is
connected to the economizer controller, values/statuses are displayed in the
Operating section of the mobile application and on the LCD. Users can manually
change basic and advanced settings, configure I/Os, and test the damper
operation and any configured outputs by modifying the corresponding parameter
values in the local device or mobile application. See Tables 18-25 for
complete list of all parameters available on the LCD display. Refer to it
during the setup and configuration process.
NOTE: For all units, the Climatix application login is: Administrator. For
units coming from the factory with CO2 configuration or single enthalpy
(control mode 3), the controller password is OneBT2.1. For all other units,
use the controller password OneBT.
NOTE: Parameters and display menus may display differently/dynamically if
different applications are configured. See Tables 18-25.
IMPORTANT: Not all operations are available on the local POL224. For example,
users can only obtain shutoff setpoints and perform cfm commissioning via the
ClimatixTM mobile application. Setup and configuration on the local device are
only recommended if operations from the mobile application are unavailable.
Check the mobile application for all operations that can be performed from the
mobile application end.
IMPORTANT: By connecting the RS485 port to a PC, all parameters are also
readable or writable from PC tools such as Modbus Poll.exe via Modbus®a and
Yabe.exe via BACnetTMa MSTP (Bps 38400 [default], Bps 9600, Bps 19200, Bps
115200). Note that an external End of Line (EOL) element is required to
achieve Baud Rate 115200 at a maximum cable length of 4000 ft (1.2 km).
NOTE(S): a. Third-party trademarks and logos are the property of their
respective owners.
43
PARAMETER 1FREECOOL 1ECON ENAB 1OCCUPIED 1Y1-IN 1Y1-OUT 1Y2-IN 1Y2-OUT 1AUX1-I
1AUX1-O 1AUX2-I 1AUX2-O
1COMP STAGE 1HEAT ENAB 1MIX AIR LOW
1MAT PRES 1LAT PRES 1OAT PRES 1OAH PRES 1RAT PRES 1RAH PRES 1CO2 PRES
1DCV STATUS
1FAN SPD LV 1ACT OUT 1ACT FB 1ACT POS 1ACT CNT
1EQUIP
1OAT LOCK 1INS
Table 18 — Status Display
DESCRIPTION Indicates whether the system can use outdoor air for free cooling. Indicates whether outdoor air is being used for the first stage of cooling. Indicates whether the space is occupied. If users choose ALWAYS for 6OCC when configuring I/Os, then the parameter value is YES; if users keep the default selection T-STAT for 6OCC and the controller receives 24-v signal from OCC input, then the value is YES. Otherwise, the value is NO. Y1-In call from thermostat for Cooling Stage 1. Y1-Out signal to compressor for Cooling Stage
- Y2-In call from thermostat for Cooling Stage 2. Y2-Out signal to compressor
for Cooling Stage 2. Dynamic item: Appears only if Y2-Out terminal is
configured. Aux1-In signal Dynamic item: Appears only if Aux1-In terminal is
configured. Aux1-Out signal Dynamic item: Appears only if Aux1-Out terminal is
configured. Aux2-In signal Dynamic item: Appears only if Aux2-In terminal is
configured. Aux2-Out signal Dynamic item: Appears only if Aux2-Out terminal is
configured.
Indicates compressor current stage.
Indicates whether heating is enabled. Indicates whether the anti-freeze protection function is enabled for a mixed air temperature sensor. If the detected air temperature is lower than the anti-freeze protection setpoint (3FRZ PROT), then the parameter value is YES. Otherwise, it is NO. Indicates the present value of the mixed air temperature (MAT) sensor. Dynamic item: Appears only if MAT or AUTO is selected for 3DIF T LOC under Parameter Settings — Advanced on page 46. Indicates the present value of the leaving air temperature (LAT) sensor. Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC. Indicates the present value of the outdoor air temperature (OAT) sensor. Dynamic item: Appears only if an OAT sensor is configured. Indicates the present value of the outdoor air relative humidity (OAH) sensor. Dynamic item: Appears only if an OAH sensor is configured. Indicates the present value of the return air temperature (RAT) sensor. Dynamic item: Appears only if a RAT sensor is configured. Indicates the present value of the return air relative humidity (RAH) sensor. Dynamic item: Appears only if a RAH sensor is configured. Indicates the present value of the CO2 sensor. Dynamic item: Appears only if a CO2 sensor is configured. Indicates the demand controlled ventilation (DCV) status. Dynamic item: Appears only if a CO2 sensor is configured. Displays ON if the measured CO2 concentration value is above the DCV setpoint and OFF if below the DCV setpoint. Indicates the current fan speed status (low, medium, or high). If a one-speed fan is connected and configured, then this item is invisible. Dynamic item: Appears only if “6FAN” is configured as “2SPEED” under Parameter Settings — I/O Configurations on page 46. Indicates current position of damper actuator in V. Indicates feedback signal of damper actuator in V. Indicates current position of damper actuator in % Open. Indicates number of times actuator has cycled (1 cycle = 180 degrees of movement in any direction). Resettable via HMI item 8ACT CNT RESET under Enter Running State on page 48.
Indicates the equipment type. If HP(O) or HP(B) is chosen for 6AUX1-I, then the parameter value is HP(O) or HP(B) respectively. If neither is chosen, then the value is CON RTU.
Indicates status of the OAT cooling lockout function.
Indicates the installation date of the economizer controller. If the installation date is incorrect, press Enter to change and confirm month, date, and year.
VALUE
YES NO
ON OFF
Off 1 2 3 YES NO
The corresponding detected value is displayed on the LCD.
ON OFF
L H
The corresponding detected value is displayed on the LCD.
HP(O) HP(B) CON RTU
NO LCKOUT
OVRD —
44
PARAMETER 2 TEMP OFF
2ENTH OFF
2DVC
2FAN L ACT 2FAN H ACT 2VENTMAX L 2VENTMAX H 2VENTMIN L 2VENTMIN H CFM COMM
2DEGREES 2FAN 2EX1 L
2EX1 H
2EX2 L
2EX2 H 2THL 2EHL 2FAN DLY
Table 19 — Parameter Settings — Basic
DESCRIPTION
RANGE
Temperature shutoff setpoint can be obtained automatically if a smartphone or tablet with the mobile application installed on it is connected to the network provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This can also be a manually defined setpoint.
48…80°F; increment by 1
Enthalpy shutoff setpoint can be obtained automatically if a smartphone or tablet with the mobile application installed on it is connected to the network provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This 22…30 Btu/lbm; increment by 1 can also be a manually defined setpoint. Dynamic item: Appears only if an OAH sensor is configured.
Demand controlled ventilation setpoint can be obtained automatically if a smartphone or tablet with the mobile application installed on it is connected to the network provided by a Wi-Fi/WLAN stick plugged into the economizer controller. This can also be a manually defined setpoint. Dynamic item: Appears only if a CO2 sensor is configured.
300…2000PPM; increment by 100
Damper minimum position when fan runs at a low speed. Dynamic item: Appears only if “6FAN” is configured as “2SPEED” under Parameter Settings — I/O Configurations on page 46.
2…10V; increment by 0.1
Damper minimum position when fan runs at a high speed. Dynamic item: Appears only if “6FAN” is configured as “1SPEED” or “2SPEED”.
2…10V; increment by 0.1
DCV maximum position when fan runs at a low speed.
Dynamic item: Appears only if a CO2 sensor is configured and “6FAN” is
configured as “2SPEED”.
2…10V; increment by 0.1
DCV maximum position when fan runs at a high speed.
Dynamic item: Appears only if a CO2 sensor is configured and “6FAN” is
configured as “1SPEED” or “2SPEED”.
2…10V; increment by 0.1
DCV minimum position when fan runs at a low speed.
Dynamic item: Appears only if a CO2 sensor is configured and “6FAN” is
configured as “2SPEED”.
2…10V; increment by 0.1
DCV minimum position when fan runs at a high speed.
Dynamic item: Appears only if a CO2 sensor is configured and “6FAN” is
configured as “1SPEED” or “2SPEED”.
2…10V; increment by 0.1
Air Flow Chart: CFM commissioning can only be initiated from the mobile
application. When CFM commissioning is in progress, the local device
—
reads “CFM COMM”.
Temperature unit (°F or °C).
—
Fan cfm.
100…50,000cfm; increment by 100
Exhaust Fan 1 low-speed parameter setting. Dynamic item: Appears only if: · Exhaust Fan 1 is configured. · “6FAN” is configured as “2SPEED”.
0…100%; increment by 1
Exhaust Fan 1 high-speed parameter setting. Dynamic item: Appears only if: · Exhaust Fan 1 is configured. · “6FAN” is configured as “1SPEED” or “2SPEED”.
0…100%; increment by 1
Exhaust Fan 2 low-speed parameter setting. Dynamic item: Appears only if: · Exhaust Fan 2 is configured. · “6FAN” is configured as “2SPEED”.
0…100%
Exhaust Fan 2 high-speed parameter setting. Dynamic item: Appears only if: · Exhaust Fan 2 is configured. · “6FAN” is configured as “1SPEED” or “2SPEED”.
0…100%; increment by 1
Temperature high limitation. Dynamic item: Appears only if an RAT sensor is configured.
0…100%; increment by 1
Enthalpy high limitation. Dynamic item: Appears only if an RAH sensor is configured.
30…50 Btu/lbm; increment by 1
Cooling delay via increasing fan speed.
0…30 min; increment by 1
DEFAULT 63°F
28 Btu/lbm
1100PPM
3.6V 2.8V 3.6V 3.6V 3.1V 2.3V
— °F 5000cfm 65%
50%
80%
75% 83% 33 Btu/lbm 5 min.
45
Table 20 — Parameter Settings — Advanced
PARAMETER 3FREEZE POS
DESCRIPTION Anti-freeze protection damper position (closed or minimum).
3SD ACT POS Damper position during shutdown (open or closed).
3DIF T LOC
MAT sensor location: · Choose MAT if the sensor is installed before the DX (Direct Expansion) coil. · Choose LAT if the sensor is installed after the DX coil. · Choose AUTO to let the economizer controller automatically detect the location.
3LAT LOW
Low limit of leaving air temperature. Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
3LAT HIGH
High limit of leaving air temperature. Dynamic item: Appears only if LAT or AUTO is selected for 3DIF T LOC.
3OAT CAL
OAT sensor calibration.
3RAT CAL
RAT sensor calibration. Dynamic item: Appears only if an RAT sensor is configured.
3OAH CAL
OAH sensor calibration. Dynamic item: Appears only if an OAH sensor is configured.
3RAH CAL
RAH sensor calibration. Dynamic item: Appears only if an RAH sensor is configured.
3MAT CAL
MAT or LAT sensor calibration.
3MAT SET
Setpoint of MAT or LAT sensor.
3FRZ PROT
Anti-freeze protection setpoint of MAT sensor.
3ACT TOLR
Actuator tolerance setpoint between output (in percent) and feedback (in percent).
3OAT LOCK
OAT lockout set point for anti-freeze protection.
3OAT LCKOVRD
When OAT LOCKOUT is enabled, choose to override the cooling lockout function or not.
3OAT LOCKODLY Indicates the overridden time if “YES” is selected for “3OAT LCKOVRD”.
VALUE/RANGE CLO MIN CLO OPN MAT LAT AUTO
35…65°F; increment by 1
70…180°F; increment by 1 2.5…2.5°F; increment by 0.5 2.5…2.5°F; increment by
0.5
10…10%; increment by 0.5
2.5…2.5°F; increment by 0.5 38…70°F; increment by 1 35…55°F; increment by 1
0…15%; increment by 1 45…80°F; increment by 1 YES NO 0…300 min; increment by
1
DEFAULT CLO CLO
LAT
45°F 80°F 0°F
—
0%
0°F 53°F 45°F 8% 32°F NO 45 min.
PARAMETER 6OCC
6AUX1-I
6AUX2-I
6OAT SIG 6RAT SIG 6OAH SIG 6RAH SIG 6MAT SIG 6AUX-AI1 6X-AI1 SIG 6CO2 Rng L
6C02 Rng H 6AUX-AI2
Table 21 — Parameter Settings — I/O Configurations
DESCRIPTION Configures whether occupancy status receives signal from the
connected thermostat or is displayed as ALWAYS in the economizer controller.
Auxiliary DI-1. Configurable as: · None · Heat Conventional (W1) from
thermostat · Heat pump (reversing valve O) · Heat pump (reversing valve B) ·
Pre-occupancy signal from thermostat · Shutdown signal from unit Auxiliary
DI-2. Configurable as: · None · Heat stage 1 (W1) from thermostat · Heat pump
(reversing valve O) · Heat pump (reversing valve B) · Pre-occupancy signal
from thermostat · Shutdown signal from unit NOTE: Whichever is chosen for
6AUX1-I does not appear in the list of 6AUX2-I.
Configures signal type of OAT sensor.
Configures signal type of RAT sensor.
Configures signal type of OAH sensor.
Configures signal type of RAH sensor.
Configures signal type of MAT or LAT sensor.
Auxiliary AI-1. Configurable as: · CO2 sensor · Static pressure (temporarily
for cfm commissioning) sensor · None
Configures CO2 sensor type. Dynamic item: Appears only if “CO2” is selected
for “6AUX-AI1”.
Configures the low limit of CO2 measuring range. Dynamic item: Appears only if
“CO2” is selected for “6AUX-AI1”. Configures the high limit of CO2 measuring
range. Dynamic item: Appears only if “CO2” is selected for “6AUX-AI1”. Choose
ACT FB if feedback signal is available from the connected damper actuator.
Otherwise, choose NONE.
VALUE T-STAT ALWAYS
NONE HP(O) HP(B) PREOCC SHUTDWN
NONE W1
HP(O) HP(B) PREOCC SHUTDWN
0-10V NTC10K
0-10V NTC10K NONE
0-10V 4-20mA NONE 0-10V NTC10K
PRESSURE CO2 NONE
0-10V 2-10V 0-5V
0…500; increment by 10
1000…3000; increment by 50
ACT FB NONE
DEFAULT T-STAT
W1
NONE
NTC10K NONE NONE NTC10K NONE 0-10V
0 2000 ACT FB
46
Table 21 — Parameter Settings — I/O Configurations (cont)
PARAMETER 6Y2O 6AUX1-O
6AUX2-O 6RS485
DESCRIPTION
Choose “COOL 2” if Cooling Stage 2 is available (another compressor is
connected to the Economizer). Otherwise, choose “NONE”.
Auxiliary DO-1. Configurable as: · None. · Exhaust fan (1 or 2). · Alarm
output to thermostat (Title 24).
Auxiliary DO-2. Configurable as: · None. · Exhaust fan (1 or 2). · Alarm
output to thermostat (Title 24). NOTE: Except for Exhaust Fan, whichever is
chosen for 6AUX1-O does not appear in the list of 6AUX2-O.
Switch between MSTP and Modbus.
VALUE COOL 2 NONE
NONE ALARM EXHAUST
NONE ALARM EXHAUST
MSTP MODBUSSLV
DEFAULT COOL 2 EXHAUST
ALARM MSTP
Table 22 — Alarm Parametersa,b
PARAMETER NO ALARM 4MAT SEN ALARM 4CO2 SEN ALARM 4OAT SEN ALARM 4OAH SEN ALARM 4RAT SEN ALARM 4RAH SEN ALARM 4FREEZE ALARM 4RTU SHUTDOWN 4ACTUATOR ALARM 4ACT UNDER V 4ACT OVER V 4ACT STALLED 4ACT SLIPPING 4NOT ECON 4ECON SHOULDNT 4EXCESS OA 4LLA ALARM 4HLA ALARM
DESCRIPTION No alarm is activated. MAT sensor has failed, gone out of range, or become disconnected. CO2 sensor has failed, gone out of range, or become disconnected. OAT sensor has failed, gone out of range, or become disconnected. OAH sensor has failed, gone out of range, or become disconnected. RAT sensor has failed, gone out of range, or become disconnected. RAH sensor has failed, gone out of range, or become disconnected. Anti-freeze notification when MAT sensor is below anti-freeze protection setpoint. Notification of Shutdown Active when SHUTDWN is chosen for 6AUX1-I or 6AUX2-I. Actuator gets disconnected or has failed. Voltage received by the actuator is below expected range. Voltage received by the actuator is above expected range. Damper actuator stopped before achieving commanded position. Damper actuator slips after reaching commanded position. Not economizing when it should. Economizing when it should not. Excess outdoor air. Outside air intake is significantly higher than it should be. Leaving air temperature is lower than the low limit (3LAT LOW). Leaving air temperature is higher than the high limit (3LAT HIGH).
NOTE(S):
a. All alarms are dynamic items. An alarm appears only if a related symptom
mentioned above is detected. b. An alarm activation triggers a general alarm
and then the configured system alarm output (AUX1-O or AUX2-O) is activated.
If there is no alarm, then NO ALARM is
displayed on the HMI.
PARAMETER 7DAMPER MIN POS 7DAMPER CLOSE 7DAMPER OPEN 7DAMPER ALL 7DAMPER 7Y1O
7Y2O
7AUX1-O 7AUX2-O
Table 23 — Test Commands
DESCRIPTION Press Enter to test whether the economizer controller can drive
damper to minimum position. Press Enter to test whether the economizer
controller can drive damper to 100% Closed. Press Enter to test whether the
economizer controller can drive damper to 100% Open. Press Enter to perform
all the above tests. Press Enter to test whether the economizer controller can
drive damper to the selected voltage. Press Enter to test whether the
economizer controller can turn on or off the first stage of cooling (close or
open relay Y1O). Press Enter to test whether the economizer controller can
turn on or off the second stage of cooling (close or open relay Y2O). Press
Enter to test AUX1-O connection (close or open relay AUX1-O). Press Enter to
test AUX2-O connection (close or open relay AUX2-O).
47
8RUN STATE 8ENTER RUN?
PARAMETER
8FACTORY DEF
8DEF CONFIRM? 8ACT CNT RESET 8VER x.x.x
PARAMETER 5CONFIG STATE 5ENTER CONFIG? 5RESTART 5CONF RESTART
Table 24 — Enter Running State
DESCRIPTION Change to Running State. Press Enter to confirm the change.
Confirm the change to Running State. Perform factory reset. Press Enter to
confirm the reset. (This action resets the controller password to default:
OneBT.) Confirm the factory resetting. Damper count reset. Firmware version
information such as 0.1.10.
Table 25 — Enter Configuration State and Restart
DESCRIPTION Change to Configuration State. Press Enter to confirm the change.
Confirm the change to Configuration State. Restart the economizer controller.
Press Enter to confirm the restart. Confirm the restart.
INSTALLING OPTIONAL HH57LW001 SINGLE
OUTSIDE AIR ENTHALPY SENSOR
When using the HH57LW001 enthalpy sensor (see Fig. 68) for outside air
changeover, the existing HH79NZ039 dry bulb sensor (see Fig. 69) must be
removed. The enthalpy sensor will be mounted in the same location as the dry
bulb sensor (see Fig. 70). When the enthalpy sensor’s OA (Outside Air)
temperature, enthalpy, and dew point are below their respective setpoints, the
outside air can be used for free cooling. When any of these are above the
setpoint, free cooling will not be available. Enthalpy setpoints are
configurable and create an enthalpy boundary according to the user’s input.
For additional details, see Fig. 71-72 and Table 26.
Harness 48TC005213 is required to be connected between the EconomizerONE
harness in the return air chamber. Harness 48TC005213 has a 5-pin plug that
connects directly to the HH57LW001 enthalpy sensor.
Enthalpy Control Sensor Configuration
The optional enthalpy control sensor (P/N: HH57LW001) communicates with the
POL224 economizer controller using the 5-wire harness, 48TC005213. The
HH57LW001 sensor can be used as a single outside air enthalpy, a differential
return enthalpy, or a differential return temperature sensor. Refer to the
base unit control wiring diagrams found earlier in this book to wire the
HH57LW001 enthalpy sensor for each option. Use Fig. 68 and Table 28 on page 51
to locate the wiring terminals for each enthalpy control sensor.
48
Fig. 68 — HH57LW001 Dimensional, Connection and Switching Information
Fig. 69 — HH79NZ039 Dry Bulb and Mixed Air Sensor Wiring
Actuator
Wiring Harness
16
1
2
11
HH79NZ039 Outside Air Temperature Sensor
Outside Air Damper
Fig. 70 — EconomizerONE Component Locations (CRECOMZR108A00 Shown) 49
12
16 3
4
13
16
14 5
6 9
10
8 7 14
15 15
Fig. 71 — California Title 24 Zones
U.S. and Canada I-Codes / ASHRAE Zones
Climate Zone 1
Climate Zone 5 and Marine
Climate Zone 2
Climate Zone 6
Climate Zone 3
Climate Zone 7 and 8
Climate Zone 4 (Except Marine)
Fig. 72 — U.S. and Canada Climate Zones
Table 26 — Enthalpy Manual Entry Setpoints for EconomizerONE Per Climate Zone
CLIMATE ZONESa 2 TEMP OFF
1 2 3 4 5 6 7 and 8 CALIFORNIA TITLE 24 ZONESb 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CONTROLLER DEFAULT SETTINGS DEFAULT SET POINTS
65°F 65°F 65°F 65°F 70°F 70°F 75°F
2 TEMP OFF
75°F 73°F 75°F 73°F 75°F 71°F 69°F 71°F 71°F 73°F 75°F 75°F 75°F 75°F 75°F
75°F
2 TEMP OFF
63°F
LOWEST SETTING 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22
Btu/lbm 22 Btu/lbm LOWEST SETTING 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm
22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm
22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm 22 Btu/lbm
—
—
NOTE(S):
a. See Fig. 72 for map of U.S. and Canada climate zones. b. See Fig. 71 for
map of California Title 24 zones.
RH%
43% 43% 43% 43% 28% 28% 19%
RH%
19% 22% 19% 22% 19% 28% 32% 28% 28% 22% 19% 19% 19% 19% 19% 19%
—
—
2 ENTH OFF
28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm
2 ENTH OFF
28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm
28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm 28 Btu/lbm
28 Btu/lbm 28 Btu/lbm
2 ENTH OFF
28 Btu/lbm
RH%
86% 86% 86% 86% 65% 65% 50%
RH%
50% 55% 55% 55% 50% 62% 68% 62% 62% 55% 50% 50% 50% 50% 50% 50%
—
94%
2THL
83°F 83°F 83°F 83°F 83°F 83°F 83°F
2THL
83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F 83°F
83°F
2THL
83°F
2EHL
33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm
2EHL
33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm
33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm 33 Btu/lbm
33 Btu/lbm 33 Btu/lbm
2EHL
33 Btu/lbm
RH%
48% 48% 48% 48% 48% 48% 48%
RH%
48% 48% 48% 48% 48% 48% 48% 48% 48% 48% 48% 48% 48% 48% 48% 48%
RH%
48%
50
Economizers are shipped standard with an HH79NZ039 outside air dry bulb sensor
(see Fig. 69). System default setting (high temp limit) is 63°F (17°C) and has
a range of 48°F to 80°F (9°C to 27°C). Sensor is factory installed on
economizer.
NOTE: A second HH79NZ039 sensor is provided for mixed air temperature.
NOTE: California high temperature setting requirements by region are shown in
Table 27.
Enthalpy Settings (Enthalpy Option)
If installing the optional HH57LW001 enthalpy sensor, the HH79NZ039 dry bulb
outside air sensor must first be removed. Wire sensor to harness 48TC005213
and the (5) wires from the harness to the EconomizerONE harness in the return
air chamber. Harness 48TC005213 has a 5-pin plug that connects directly to the
HH57LW001 enthalpy sensor. Refer to the base unit control wiring diagrams
earlier in this book for wiring connections. Refer to Fig. 68 and Table 28.
California’s Title 24 High Temperature Limit Settings
California’s Title 24 code requires a high temperature limit setting for all
dry bulb outside air economizer changeover. The temperatures vary by the
region within California. See Table 27 for high limit settings.
Table 27 — California Title 24 Regional High Limit Dry Bulb Temperature Settingsa
DEVICE TYPEb
FIXED DRY BULB
DIFFERENTIAL DRY BULB
FIXED ENTHALPYc + FIXED DRY
BULB
CLIMATE ZONES 1, 3, 5, 11-16 2, 4, 10 6, 8, 9
7 1, 3, 5, 11-16
2, 4, 10
6, 8, 9
7
All
REQUIRED HIGH LIMIT (ECONOMIZER OFF WHEN):
DESCRIPTION OAT exceeds 75°F (23.8°C) OAT exceeds 73°F (22.7°C) OAT exceeds
71°F (21.6°C) OAT exceeds 69°F (20.5°C)
OAT exceeds RA temperature OAT exceeds return air temperature 2°F (18.8°C)
OAT exceeds return air temperature
4°F (20°C) OAT exceeds return air temperature
6°F (21.1°C)
OAT exceeds 28 Btu/lb of dry airb or OAT exceeds 75°F (23.8°C)
NOTE(S):
a. This table sourced from 2019 California Energy Code, Title 24, Part 6,
Table 140.4-E Air Economizer High Limit Shut Off Control Requirements.
b. Only the high limit control devices listed are allowed to be used and at
the set points listed. Others such as Dew Point, Fixed Enthalpy, Electronic
Enthalpy, and Differential Enthalpy Controls, may not be used in any climate
zone for compliance with Section 140.4(e)1 unless approval for use is provided
by the Energy Commission Executive Director.
c. At altitudes substantially different than sea level, the Fixed Enthalpy
limit value shall be set to the enthalpy value at 75°F and 50% relative
humidity. As an example, at approximately 6,000 foot elevation, the fixed
enthalpy limit is approximately 30.7 Btu/lb.
LEGEND
OAT — RA —
Outdoor-air Thermostat Return Air
Table 28 — HH57LW001 Sensor Wiring Terminations
NUMBER 1 2 3 4 5
TERMINAL
LABEL TCOM TSIG HSIG HCOM H24V
TYPE
NTC 10k NTC 10k 0-10 vdc COMMON 24 vac
DESCRIPTION
Outside Air Temperature Sensor Output Outside Air Temperature Sensor Output
Outside Air Relative Humidity Sensor Output
Sensor 24-v Common Input Sensor 24-v Operating Voltage Input
51
CHECKOUT
Inspect all wiring connections at the economizer module’s terminals, and
verify compliance with the installation wiring diagrams. For checkout, review
the Status of each configured parameter and perform the Test Commands tests
(refer to Table 23). For information about menu navigation and use of the
keypad see Interface Overview on page 33.
WARNING
ELECTRIC SHOCK HAZARD Failure to follow this warning could result in personal
injury, property damage, or death. Before performing service or maintenance
operations on unit, always turn off main power switch to unit and install
lock(s) and lockout tag(s). Unit may have more than one power switch. Ensure
electrical service to rooftop unit agrees with voltage and amperage listed on
the unit rating plate. If any wiring changes are required, first be sure to
remove power from the economizer module before starting work. Pay particular
attention to verifying the power connection (24 vac).
Power Up After the POL224 module is mounted and wired, apply power. Initial
Menu Display On initial start up, “Welcome” displays on the economizer HMI
screen. After a brief pause, the Parameter Settings — I/O Configuration (refer
to Table 21) of the software appears, allowing the user to check that presets
and default values are configured correctly. Power Loss (Outage or Brownout)
All set points and advanced settings are restored after any power loss or
interruption. NOTE: All settings are stored in non-volatile flash memory.
Status Use the Status menu (refer to Table 18) to check the parameter values
for the various devices and sensors configured. NOTE: For information about
menu navigation and use of the keypad, see Interface Overview on page 33.
Checkout Tests Use the Test Commands menu (refer to Table 23) to test the
damper operation and any configured outputs. Only items that are configured
are shown in the Test Commands menu. NOTE: For information about menu
navigation and use of the keypad, see Interface Overview on page 33. To
perform a Test Command test: 1. Scroll to the desired test in Test Command
menu 7 using the
Up and Down buttons. 2. Press the Enter button to select the item. RUN?
appears.
3. Press the Enter button to start the test. The unit pauses and then
displays IN PROGRESS. When the test is complete, DONE appears.
4. When all desired parameters have been tested, press Enter + Up to end the
test.
The Checkout tests can all be performed at the time of installation or at any
time during the operation of the system as a test that the system is operable.
CAUTION
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage. Be sure to allow enough time for compressor start-up and shutdown
between checkout tests so that you do not shortcycle the compressors.
52
TROUBLESHOOTING
For EconomizerONE troubleshooting issues see Table 29.
Table 29 — Operating Issues and Concerns
SYMPTOM
REASON
SOLUTION
An alarm is displayed on the Sensor, damper, or the whole working
LCD
system may not work properly
Check sensor, damper, or the whole working system following the detailed alarm information.
DAC LED is blinking RED Damper slippage
Check whether the damper works properly.
DAC LED is blinking RED quickly
Damper unplugged
Check whether the damper is connected.
DAC LED is OFF
Terminal ACT-FB is configured but there is no available feedback signal
Check whether the feedback signal is connected; check if ACT-FB is faulty.
Shutoff SP setting error
Economizer controller has
no alarm, but the Free
OA temp is too low
Cooling LED will not turn on
when the OA seems to be
suitable for Free Cooling
OA temp is too high or too humid
Shutoff temperature and/or enthalpy set point is incorrectly set up. Consult
an HVAC professional to set up the shutoff set point correctly.
The OA temperature is too low; therefore, there is no cooling demand. This
could possibly enable anti-freeze protection.
In DIFF mode, even though OA temperature is lower than RA temperature, if both
OA and RA temperatures exceed the high limit, then Free Cooling turns off. In
Differential Enthalpy control mode, even though OA enthalpy is lower than RA
enthalpy, if both OA and RA enthalpy exceed the high limit, then Free Cooling
turns off.
No input power
Use a multi-meter to check whether there is 24 vac ± 25% (18-30 vac) at the POWER terminals. If there is no voltage or if the voltage is significantly low, then check the transformer output voltage at the RTU. If 24-v is not present at the transformer secondary side, then check the primary line voltage to the transformer. If the line voltage is not present at the transformer primary side, then check the primary power to the RTU, fuses, circuit breaker, and so on.
Economizer controller/mechanical cooling is not operating
Brownout
Y1/Y2 signal is missing from the thermostat
If voltage is below 17-v, then the economizer controller may be in Brownout
Protection mode. This mode disables all of the relay outputs. When the power
is 19 vac or higher, the economizer controller and RTU operate normally.
Mechanical cooling does not run until there is cooling demand (Y1/Y2 Active).
Check the wiring from Y1I and Y2I terminals to the commercial thermostat. 24-v
should be present between Y1I/Y2I and Y1O/Y2O respectively.
24 vac~ and 24 vac are incorrectly wired
24 vac power supply has polarity when all devices are powered by the same 24 vac transformer; reversing polarity may cause a short circuit that can damage the system. Follow the transformer polarity mark, check the wiring of 24-v~ (or G or 24-v+), and ensure that they are tied to the same polar of 24 vac power supply; while checking the wiring of (or G0 or 24-v- or COM), ensure that they are all tied to another polar of 24 vac power supply.
Firmware update failure
Application file is damaged, operation is incorrect, and/or USB flash disk does not work properly
Reload a BIN file, restart the controller, update firmwarea, or change a USB flash disk. Contact service provider if failure still exists.
Free Cooling LED is solid RED
Sensor, damper, or whole working system may not work properly
Check sensor, damper, or the whole working system following the detailed alarm information.
Free Cooling LED is blinking RED
Not economizing when it should
Check the whole economizer working system, such as the sensor, damper, and thermostat.
Incorrect controller password error on mobile application
For CO2 and single enthalpy (control mode 3) configurations from the factory, the password has changed
For units coming from the factory with CO2 configuration or single enthalpy (control mode 3), use the controller password OneBT2.1. For all other units, use the controller password OneBT. Performing a factory reset on the controller will also reset the password to OneBT.
RS485 communication failure
RS485 signal or configuration error
Check wiring, configuration, Baud Rate (using mobile application), and other network communication parameters.
Sensor LED is blinking RED Excess outdoor air
Check the whole economizer working system, such as the sensor, damper, and thermostat.
Mixed Air (MA) sensor error
Check the MA sensor. It must be either a Type II NTC 10K or 0-10 vdc sensor.
Sensor LED is solid RED
Outside Air (OA)/Return Air (RA) sensor error
Check the wiring and signal of the OA sensor. If in Differential (DIFF) mode, also check the RA sensor. The following sensor signals are valid: Type II NTC 10K or 0-10 vdc temperature. 0-10 vdc or 4-20 mA humidity.
Air temperature failure/fault
Check the air temperature sensor signal. The valid signal must be Type II NTC 10K or 0-10 vdc.
Sensor LED is OFF
CO2 sensor error
Check CO2 sensor connection, sensor signal (under range or over range), and sensor signal type.
Sensor LED is YELLOW
Humidity sensor error
Check humidity sensor connection, sensor signal (under range or over range), and sensor signal type.
Wi-Fi connection failure
Wi-Fi/WLAN stick error or wrong user name and password
Unplug and re-plug in the Wi-Fi/WLAN stick, enter a correct user name and password, restart the controller, or replace the Wi-Fi/WLAN stick. If the Wi- Fi/WLAN stick is POL903.00/100, then the default user name and password are Siemens-WLAN-Stick and SIBPAdmin. DNS name is siemens.wlanstick. Contact Application Engineering for information on this accessory.
NOTE(S):
a. Back up configurations before firmware update. All the previous
configuration data is erased after firmware update. Contact Application
Engineering for more information on support for firmware. IMPORTANT: If the
controller enters the configuration state for the convenience of I/O
configurations, then users can manually switch to the running state after
finishing configurations. To do so, press Enter + Up at the same time, then
press Enter to confirm the switch after 8RUN STATE appears on the LCD.
53
SystemVuTM Controller (Factory Option)
For details on operating 50FE-*04-07 units equipped with the factory-installed
SystemVu controller option, refer to the FE/GE Series Single Package Rooftop
Units with SystemVu Controller Controls, Start-up, Operation and
Troubleshooting manual.
Controller Options
LOW AMBIENT
If the unit comes with electromechanical (EM) control, then no adjustment is
necessary.
If the unit comes with the SystemVuTM controller option, then refer to its
installation control manual for details on adjusting “Cooling Lock-Out”
setting and configure for the specific job requirements.
Smoke Detectors
Smoke detectors are available as factory-installed options on 50FE models.
Smoke detectors may be specified for supply air only, for return air without
or with economizer, or in combination of supply air and return air. Return-air
smoke detectors are arranged for vertical return configurations only. All
components necessary for operation are factory-provided and mounted. The unit
is factory-configured for immediate smoke detector shutdown operation;
additional wiring or modifications to unit terminal board may be necessary to
complete the unit and smoke detector configuration to meet project
requirements.
Units equipped with factory-optional return-air smoke detectors require a
relocation of the sensor module at unit installation. See Fig. 73 for the as-
shipped location.
Completing Return Air Smoke Sensor Installation
1. Unscrew the 2 screws holding the return-air smoke detector assembly. See
Fig. 74, Step 1. Save the screws.
2. Turn the assembly 90 degrees and then rotate end to end. Make sure that
the elbow fitting is pointing down. See Fig. 74, Step 2.
3. Screw the sensor and detector plate into its operating position using
screws from Step 1. See Fig. 74, Step 3.
4. Connect the flexible tube on the sampling inlet to the sampling tube on
the basepan.
Additional Application Data Refer to the application data document “Factory
Installed Smoke Detectors for Small and Medium Rooftop Units 2 to 25 Tons” for
discussions on additional control features of these smoke detectors including
multiple unit coordination.
Return Air Smoke Detector (As Shipped)
Fig. 73 — Return Air Smoke Detector, Shipping Position
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>