L2004552 DucoBox Energy Premium Instruction Manual

June 29, 2024
Duco

L2004552 DucoBox Energy Premium

“`html

Specifications

  • Product: DucoBox Energy
  • Type: Mechanical Ventilation System
  • Manufacturer: VERO DUCO
  • Country of Origin: Belgium

Product Usage Instructions

Overview of Error Codes

If you encounter error codes on the display of the DucoBox
Energy, refer to the following table for error descriptions and
solutions:

Error Code Type of Error Error Description and Problem Statement Solution
No error code The DucoBox Energy is live but does not respond Check

and/or replace the circuit board, see page 20
141| Error| No response from the extractor fan; check and/or replace the
extractor fan| Check and/or replace the fan, see page 9
311| Error| ODA (outdoor air to the unit) temperature sensor value is too
low; check and/or replace the sensor| Check and/or replace the temperature sensor, see page 12

Service Instructions

Always ensure that the product is correctly installed before
attempting any service or repair. Follow these steps for common
service tasks:

Check and/or Replace the Fan (Error Code 141)

  1. Refer to the wiring diagram for DucoBox Energy Comfort (Plus)
    or Premium.

  2. Locate the fan component.

  3. If necessary, replace the fan following the instructions
    provided on page 9.

Check and/or Replace the Temperature Sensor (Error Code

  1. Refer to the electrical diagram for DucoBox Energy Comfort
    (Plus) or Premium.

  2. Identify the temperature sensor.

  3. If needed, replace the temperature sensor as per the guidance
    on page 12.

Frequently Asked Questions (FAQ)

Q: Can I perform repairs on the DucoBox Energy myself?

A: Installation, connection, maintenance, and repairs should be
done by an accredited installer to ensure safety and proper
functioning of the product.

“`

Error codes mechanical

ENGLISH

ventilation DucoBox Energy

Service instructions

L2004552 (revision B | 06.05.2024)

ENGLISH

Table of contents
01 Overview of error codes 3 02 Overview of solutions 7
02.A Schematic representation (printed circuit board and wiring) of the DucoBox Energy 7 Of the DucoBox Energy Comfort (Plus) 7 Of the DucoBox Energy Premium 8
02.B Check and/or replace the fan 9 Additional explanations 9 Possible causes 9 Service instruction 9 Electrical diagram of DucoBox Energy Comfort (Plus) 10 Electrical diagram of DucoBox Energy Premium 11
02.C Check and/or replace the temperature sensor 12 Additional explanations 12 Possible causes 12 Service instruction 12 Electrical diagram of DucoBox Energy Comfort (Plus) 13 Electrical diagram of DucoBox Energy Premium 14

02.D Check and/or replace the pressure sensor 15 Additional explanations 15 Possible causes 15 Service instruction 15 Electrical diagram of DucoBox Energy Comfort (Plus) 16 Electrical diagram of DucoBox Energy Premium 17
02.E Check and/or replace the user controller/room sensor18 Additional explanations 18 Possible causes 19 Service instruction 19 Wiring diagram DucoBox Energy Comfort (Plus) 20 Wiring diagram DucoBox Energy Premium 20
02.F Check and/or replace the circuit board 21 Additional explanations 21 Possible causes 21 Service instruction 21 Electrical diagram of DucoBox Energy Comfort (Plus) 22 Electrical diagram of DucoBox Energy Premium 23

Copyright rules: all rights reserved Translation from Dutch of the original instructions Changes based on technical improvements reserved For information regarding warranty, installation, technical data, etc, see wwwducoeu Installation, connection, maintenance and repairs are to be carried out by an accredited installer The electronic components of this product may be live Avoid contact with water
Always check that the product is correctly installed according to the installation manual before consulting the service manual.

VERO DUCO – Handelsstraat 19 – 8630 Veurne – Belgium tel +32 58 33 00 33 – info@duco.eu – www.duco.eu

2

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH

01 Overview of error codes

If the troubleshooting shows that the problem can be solved by replacing a component, please refer to the spare parts list
Various error codes may appear on the display of a ventilation system Below you will find an overview of these codes, each with the error description and problem statement next to it and a hyperlink to the solution (to extra info on what exactly to do and how)

ERROR CODE

TYPE OF ERROR

ERROR DESCRIPTION AND PROBLEM STATEMENT

SOLUTION

No error code

/

The DucoBox Energy is live but does not respond

Check and/or replace the circuit board, see page 20

141

error

No response from the extractor fan; check and/or replace the extractor fan

Check and/or replace the fan, see page 9

311

error

ODA (outdoor air to the unit) temperature sensor value Check and/or replace the temperature

is too low; check and/or replace the sensor

sensor, see page 12

312

error

ODA (outdoor air to the unit) temperature sensor value Check and/or replace the temperature

is too high; check and/or replace the sensor

sensor, see page 12

313 314 315

error error error

ODA (outdoor air to the unit) temperature sensor cannot Check and/or replace the temperature

be read; check and/or replace the sensor

sensor, see page 12

ODA (outdoor air to the unit) temperature sensor has been measuring the same temperature for a long time; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

ODA (outdoor air to the unit) temperature sensor is short-circuited; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

316 411 412 413 414 415 416 611 612 613

error error error error error error error error error error

ODA (outdoor air to the unit) temperature sensor has a Check and/or replace the temperature

bad connection; check and/or replace the sensor

sensor, see page 12

ETA (extract air from the house to the unit) temperature sensor value is too low; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

ETA (extract air from the house to the unit) temperature sensor value is too high; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

ETA (extract air from the house to the unit) temperature Check and/or replace the temperature sensor cannot be read; check and/or replace the sensor sensor, see page 12

ETA (extract air from the house to the unit) temperature sensor has been measuring the same temperature for a long time; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

ETA (extract air from the house to the unit) temperature sensor is short- circuited; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

ETA (extract air from the house to the unit) temperature sensor has a bad connection; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

EHA (exhaust air from the unit to the outside) temperature sensor value is too low; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

EHA (exhaust air from the unit to the outside) temperature sensor value is too high; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

EHA (exhaust air from the unit to the outside) temperature sensor cannot be read; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

3

ENGLISH

ERROR CODE 614
615 616 1611 1612 1613 1614 1615 1616 2841 2911 2912 2913 2914 2915 2916 3011 3012 3013

TYPE OF ERROR error
error error error error error error error error error error error error error error error error error error

ERROR DESCRIPTION AND PROBLEM STATEMENT

SOLUTION

EHA (exhaust air from the unit to the outside) temperature sensor has been measuring the same temperature for a long time; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

EHA (exhaust air from the unit to the outside) temperature sensor is short- circuited; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

EHA (exhaust air from the unit to the outside) temperature sensor has a bad connection; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

Extract air pressure sensor value is too low; check and/ Check and/or replace the pressure sensor,

or replace the sensor

see page <?>

Extract air pressure sensor value is too high; check and/ Check and/or replace the pressure sensor,

or replace the sensor

see page <?>

Extract air pressure sensor cannot be read; check and/ Check and/or replace the pressure sensor,

or replace the sensor

see page <?>

The extract air pressure sensor has been measuring the same value for a long time; check and/or replace the sensor

Check and/or replace the pressure sensor, see page <?>

The extract air pressure sensor is short-circuited; check Check and/or replace the pressure sensor,

and/or replace the sensor

see page <?>

The extract air pressure sensor has a bad connection; Check and/or replace the pressure sensor,

check and/or replace the sensor

see page <?>

No response from the supply fan; check and/or replace Check and/or replace the fan, see

the supply fan

page 9

The supply air pressure sensor is too low; check and/or Check and/or replace the pressure sensor,

replace the sensor

see page <?>

The supply air pressure sensor is too high; check and/or Check and/or replace the pressure sensor,

replace the sensor

see page <?>

The supply air pressure sensor cannot be read; check Check and/or replace the pressure sensor,

and/or replace the sensor

see page <?>

The supply air pressure sensor has been measuring the same value for a long time; check and/or replace the sensor

Check and/or replace the pressure sensor, see page <?>

The supply air pressure sensor is short-circuited; check Check and/or replace the pressure sensor,

and/or replace the sensor

see page <?>

The supply air pressure sensor has a bad connection; check and/or replace the sensor

Check and/or replace the pressure sensor, see page <?>

SUP (supply air from the unit to the house) temperature sensor value is too low; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

SUP (supply air from the unit to the house) temperature sensor value is too high; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

SUP (supply air from the unit to the house) temperature Check and/or replace the temperature sensor cannot be read; check and/or replace the sensor sensor, see page 12

4

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH

ERROR CODE 3014 3015 3016

TYPE OF ERROR error
error
error

ERROR DESCRIPTION AND PROBLEM STATEMENT

SOLUTION

SUP (supply air from the unit to the house) temperature sensor has been measuring the same temperature for a long time; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

SUP (supply air from the unit to the house) temperature sensor is short- circuited; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

SUP (supply air from the unit to the house) temperature sensor has a bad connection; check and/or replace the sensor

Check and/or replace the temperature sensor, see page 12

31191

warning Replace the filters

See maintenance instructions

32101 33101 35171 35172 35173 36241 36242 37171 37172 37173 40171 40172 40173 42221 42222

warning

Outdoor temperature too low – ventilation is switched off for 8h

/

error

Outdoor temperature too low – ventilation is permanently switched off Restart the DucoBox later

/

error

Temperature sensor value is too low; check and/or replace the sensor

/

error

Temperature sensor value is too high; check and/or replace the sensor

/

error

The value of the temperature sensor cannot be read; check and/or replace the sensor

/

error

The connection to the weather station has been lost Check the connection

/

error

The connection with the outdoor temperature sensor has been lost Check the connection

/

error

The value of the CO2 sensor is too low; check and/or replace the sensor

Check and/or replace the user controller/ room sensor, see page 18

error

The value of the CO2 sensor is too high; check and/or replace the sensor

Check and/or replace the user controller/ room sensor, see page 18

error

The value of the CO2 sensor cannot be read; check and/ Check and/or replace the user controller/

or replace the sensor

room sensor, see page 18

error

The value of the Humidity sensor is too low; check and/ Check and/or replace the user controller/

or replace the sensor

room sensor, see page 18

error

The value of the Humidity sensor is too high; check and/ Check and/or replace the user controller/

or replace the sensor

room sensor, see page 18

error error error

The value of the Humidity sensor cannot be read; check Check and/or replace the user controller/

and/or replace the sensor

room sensor, see page 18

The number of connected valves is too high The maximum number is given in the manual
The number of connected valves is too low The minimum is 2

See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium
See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

5

ENGLISH

ERROR CODE 43231 43232 4461 4462

TYPE OF ERROR warning
warning
error
error

ERROR DESCRIPTION AND PROBLEM STATEMENT

SOLUTION

The adjustment has not yet happened or has failed Do the adjustment (again)
The desired flow rate cannot be achieved Check the entire installation
There is no connection to the Duco Pre-Heater Check the connection
A Duco Pre-Heater is connected to the DucoBox Go to settings to configure it

See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium
See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium
See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium
See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium

6

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
02 Overview of solutions
02.A Schematic representation (printed circuit board and wiring) of the DucoBox Energy
Of the DucoBox Energy Comfort (Plus)

FAN 1

FAN 2

Power Connector

DESCRIPTION PE N L

COLOUR Yellow/Green
Blue Brown

TEMP

T1 T2 T3 T4

FAN 1
F1

M0 M1 P1/P2 F2 FAN 2

PCB

P1 P2

  • Not present with the D325

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

7

ENGLISH
Of the DucoBox Energy Premium
FAN 2

FAN 1

Power Connector

DESCRIPTION PE N L

COLOUR Yellow/Green
Blue Brown

F1

TEMP

M0

P1/P2

M1

F2

T1 T2
T3
P1
T4 P2

PCB

8

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
02.B Check and/or replace the fan
Error codes 141 and 2841
Additional explanations
The confirmation signal that the fan is rotating is missing, or the fan cannot reach the required speed In the latter case, the speed (rpm) can optionally be read via the Duco Network Tool
Possible causes
· The power cable or communication wires are not properly connected to the fan · The fan motor is blocked or has failed · The pressure sensor is damaged · The mains voltage of the DucoBox is abnormal · The DucoBox circuit board is damaged · The ventilation ducts to and from the DucoBox are blocked · The fan or fan cable is physically damaged
Service instruction
Error code 1.4.1 / 28.4.1

Are the extractor fan power wires or communication wires correctly connected to the circuit board? See DucoBox Energy electrical diagrams on the following
pages Yes
Is the fan motor blocked?
No
Does the fan still run?
Yes
The error has been resolved?

No

Make sure power and communication wires are

connected correctly

Yes

Remove the obstacles in the ventilation ducts or in the

DucoBox

No Replace the fan See QR code below

If not

Contact DUCO Service

Service & Maintenance DucoBox Energy Comfort D325 fans

Service & Maintenance DucoBox Energy Premium fans

Service & Maintenance DucoBox Energy Comfort D400 and Comfort Plus fans
Specifically for a DucoBox Energy Comfort D325, you may wish to order the “Scroll puller DucoBox Energy Comfort”

L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

9

ENGLISH
Electrical diagram of DucoBox Energy Comfort (Plus)

FAN 1 FAN 2

FAN 1

FAN 2

Power Connector DESCRIPTION PE N L
Control connector DESCRIPTION GND 0-10V PWM 10V Tacho

COLOUR Yellow/Green
Blue Brown
COLOUR Blue or brown
Yellow Red or green
White

FUNCTION Grounding Neutral conductor/ 230VAC Phase wire / 230VAC
FUNCTION Ground
Input: 0-10V-PWM Output: 10VDC Tacho output

10 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

With the DucoBox Energy Comfort D325, the shape of
the fan differs

Electrical diagram of DucoBox Energy Premium
FAN 2

ENGLISH

FAN 1

FAN 1

FAN 2

Power Connector DESCRIPTION PE N L
Control connector DESCRIPTION GND 0-10V PWM 10V Tacho

COLOUR Yellow/Green
Blue Black
COLOUR Blue or brown
Yellow Red or green
White

FUNCTION Grounding Neutral conductor/ 230VAC Phase wire / 230VAC
FUNCTION Ground
Input: 0-10V-PWM Output: 10VDC Tacho output
11 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
02.C Check and/or replace the temperature sensor
Error codes 311 to 316; error codes 411 to 416; error codes 611 to 616; error codes 3011 to 3016
Additional explanations
The temperature sensor is not read correctly by the DucoBox or the connection between the DucoBox and the temperature sensor is interrupted
Possible causes
· The temperature sensor is damaged · The connection to the temperature sensor is interrupted · The DucoBox Energy printed circuit board is damaged
Service instruction
Error codes 3.1.x / 4.1.x / 6.1.x / 30.1.x

Can you read the value of the 4 temperature sensors via the display of the DucoBox?

No

Replace the temperature sensor See QR code below

Yes Is the measured value in the display realistic?

Yes Contact DUCO Service if an error code still appears

No
Is the DucoBox configured correctly left/right?
Yes Clean the temperature sensor
Is the problem solved? Nee

No Refer to the manual to reset and reinstall the unit
Yes The error code has disappeared

Vervang de defecte temperatuursensor Zie QR-code hieronder

Service & Maintenance DucoBox Energy Comfort (Plus) temperature sensors
12 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

Service & Maintenance DucoBox Energy Premium temperature sensors

Electrical diagram of DucoBox Energy Comfort (Plus)

ENGLISH

TEMP
T1 T2 T3 T4

TEMP. (°C) -10 -5 0 5 10 15 20 25 30

RESISTANCE (Ohm) 55218 42268 32624 25381 19897 15711 12493 10000 8056

13 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
Electrical diagram of DucoBox Energy Premium

TEMP

T1 T2
T3

TEMP. (°C)

RESISTANCE (Ohm)

-10

55218

T4

-5

42268

0

32624

5

25381

10

19897

15

15711

20

12493

25

10000

30

8056

14 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
02.D Check and/or replace the pressure sensor
Error codes 1611 to 1616; error codes 2911 to 2916
Additional explanations
The pressure sensor ETA or SUP is not being read correctly by the DucoBox or the connection between the DucoBox and the pressure sensor is interrupted
Possible causes
· There are air leaks in and around the DucoBox (eg careless installation of the front panel) · The pressure sensor was not correctly mounted in the casing · The connection to the pressure sensor is broken · An air duct to or from the DucoBox is blocked · The pressure sensor is damaged or dirty · The DucoBox Energy printed circuit board is damaged
Service instruction
Error code 16.1.x / 29.1.x

Can you read the value of the 2 pressure sensors via the DucoBox’s display?
Yes
From the display menu, go to calibration and reduce the pressure Is the unit running stably and has the
engine speed dropped?
Yes

No

Check the connection If the problem is not solved:

replace the pressure sensor concerned See QR code

below

No Replace the pressure sensor See QR code below

Contact DUCO Service

Service & Maintenance DucoBox Energy Comfort (Plus) pressure sensors

Service & Maintenance DucoBox Energy Premium pressure sensors

15 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
Electrical diagram of DucoBox Energy Comfort (Plus)
P1/P2
P1 P2
16 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

Electrical diagram of DucoBox Energy Premium

ENGLISH

P1/P2
P1 P2
17 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
02.E Check and/or replace the user controller/room sensor
Error codes 37171 to 37173; error codes 40171 to 40173
Additional explanations
The measured value of the room sensor is too high, too low or cannot be read correctly by the DucoBox, via the Duco Network Tool or via the Duco Installation App
18 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH

Possible causes
· The room sensor is damaged · The cabling (Wired) from the DucoBox to the room sensor is
interrupted
Service instruction

· The room sensor is outside the RF range of the DucoBox · The room sensor is exposed to direct sunlight

Error code 37.17.x / 40.17.x

Is the room sensor Wired? No

Yes

Do you measure 24V DC on the

No

Measure the power source to the sensor (replace either the

component?

transformer or the wiring) See

wiring diagrams on page 20

Yes

Measure the communication wiring (A, B, GND)

No

from the room sensor to the DucoBox Is the

communication OK?

Connect the component correctly to the DucoBox according to the wiring
diagram

Yes

Perform a hard power interruption (10 seconds

Yes

of power off) Does the error disappear?

Problem solved

No Replace the room sensor See QR code below

No Is there 230V mains voltage on the RF component?

Provide correct connection to the mains

Yes
Check the signal strength with the Duco Network tool See info sheet RF communication Is the signal
strength OK?

No

Add an extra repeater (an RF component) to the

installation or move the DucoBox’s RF antenna using a

coaxial cable until the signal strength is OK

Yes
Replace the room sensor: see installation manual for the remote control

Installation guide Control / Room sensor

Info sheet RF communication

19 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
Wiring diagram DucoBox Energy Comfort (Plus)

24 VDC
POWER SUPPLY 230 VAC Duco Reference*

A B GND

24 VDC
POWER SUPPLY
230 VAC

Min 0,75 mm²
24 VDC A B GND

230 VAC RF

RF

User controller

User controller

Max. of 50 components of which no more than 25 RF

RF obstacle-free zone (at least 30 cm)

Wiring diagram DucoBox Energy Premium

230 VAC

POWER SUPPLY
24 VDC

230 VAC A B GND

GND B A

Duco Wired

24 VDC A B GND

230 VAC RF

RF

User controller

User controller

Max. of 50 components of which no more than 25 RF

RF obstacle-free zone (at least 30 cm)

20 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

02.F Check and/or replace the circuit board
No error code
Additional explanations
The display does not start up and/or no LED indicator is lit on the DucoBox’s circuit board
Possible causes
· Poor connection of the power cables on the DucoBox board · The display is damaged · There is no mains voltage on the DucoBox Energy · The DucoBox Energy printed circuit board is damaged
Service instruction
The DucoBox printed circuit board or display does not respond.

ENGLISH

Is mains power present on the DucoBox?

No

Check in the meter box whether the fuse has blown

Or the power cable is not connected correctly

Check and reconnect the power cable to the socket

Yes

Does the circuit board still respond to manual action

Yes

(pressing the ‘Inst’ button)?

Exchange the damaged Display See QR code below

No
Replace the circuit board, see QR code below or complete the complaint form online and submit it to
DUCO Service

Service & Maintenance DucoBox Energy Comfort (Plus) PCB

Service & Maintenance DucoBox Energy Premium PCB

21 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

ENGLISH
Electrical diagram of DucoBox Energy Comfort (Plus)

F1 Power Connector

DESCRIPTION PE N L

COLOUR Yellow/Green
Blue Brown

TEMP

M0 M1 P1/P2 F2

PCB

22 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)

Electrical diagram of DucoBox Energy Premium

ENGLISH

Power Connector

DESCRIPTION PE N L

COLOUR Yellow/Green
Blue Brown

F1

TEMP

M0

P1/P2

M1

F2

PCB

23 L2004552 Service instructions error codes mechanical ventilation systems (Revision B | 06.05.2024)