HBLC-OIL Liquid Level Sensors User Guide
- June 26, 2024
- HB
Table of Contents
Liquid Level Sensor
**selection guide
**
HBLC-OIL Liquid Level Sensors
Liquid Level Sensors for different types of liquids
24V AC or DC
Liquid temp. max 80°C
(176°F)
Ambient temp. -30°C to
50°C (-22°F to 122°F)| Oil| R744 CO2
R600 Butane
R600a Isobutane
R290 Propane| Synthetic
refrigerants
HFC/HFO/CFC| R717 NH3
R718 Water
Alcohols| Dirty water
In a metal vessel/tank
---|---|---|---|---|---
Rigid probe
analog output only| HBLC-OIL
200-3000 mm| HBLC-CO2
200-3000 mm| HBLC-HFC
200-3000 mm| HBLT-A3
200-3000 mm| HBLC
200-2000 mm
Rigid probe
analog and direct
control output| HBSLC-OIL/C
HBSLC-OIL/S
HBSLC-OIL/PWM
200-3000 mm| HBSLC-CO2/C
HBSLC-CO2/S
HBSLC-CO2/PWM
200-3000 mm| HBSLC-HFC/C
HBSLC-HFC/S
HBSLC-HFC/PWM
200-3000 mm| HBSLT-A3/C
HBSLT-A3/S
HBSLT-A3/PWM
200-3000 mm| HBSLC/C
HBSLC/S
HBSLC/PWM
200-2000 mm
Wire/Flex probe
analog output only| HBLT-FLEX
300-2000 mm| HBLT-FLEX
300-2000 mm| HBLT-W-Wire
600-6000 mm| HBLT-W-Wire
600-6000 mm| HBLT-W-Wire
600-6000 mm
Wire/Flex probe
analog and direct
control output| HBSLT-FLEX/C
HBSLT-FLEX/S
HBSLT-FLEX/PVM
300-2000 mm| HBSLT-FLEX/C
HBSLT-FLEX/S
HBSLT-FLEX/PVM
300-2000 mm| HBSLT-W-Wire/C
HBSLT-W-Wire/S
HBSLT-W-Wire/PWM
600-6000 mm| HBSLT-W-Wire/C
HBSLT-W-Wire/S
HBSLT-W-Wire/PWM
600-6000 mm| HBSLT-W-Wire/C
HBSLT-W-Wire/S
HBSLT-W-Wire/PWM
600-6000 mm
Low-cost probe
analog output only| HBLC- thin
200-1600 mm| On request| HBLC- Fgas
200-1600 mm| HBLC
200-2000 mm| HBLC
200-2000 mm
Low-cost probe
analog and direct control output| On request| On request| On request| HBLC/C
HBLC/S
HBLC/PWM
200-2000 mm| HBLC/C
HBLC/S
HBLC/PWM
200-2000 mm
Indicate if the sensor is available in a special ATEX/IECEx version.
Connection diameter available
Settings and Connections
Settings
free from our web page.
an USB/M12 connection cable.
The tool can be downloaded for The sensor can be connected to a PC with HB
tool installed using measurement more accur ate pro vide alarms etc.
All the sensors has numerous settings for making the
Sensors with analog output
All sensors has an analog output.
Sensor with M12 c onnector
- +24 VDC or 24VAC (Brown)
- – common or 24VAC (White)
- Remote input 4-20 mA (Blue)
- Analog output 4-20 mA (Black)
- Run-in signal (Grey)
Sensor with ISO 4400 connector
Sensors with direct valve control and analog output
Sensors with an output cable can control a valve directly. Three different
versions exist
/C for modulating valve
/S for stepper motor
/PWM for pulse modulating valve
90-240V versions
- +24 VDC or 24VAC (Brown)
- – common or 24VAC (White)
- Remote input 4-20 mA (Blue)
- Analog output 4-20 mA (Black)
- Run-in signal (Grey)
ATEX/IECEx approved sensors with IEC 61076-2-101 M12 plug
Most of the 24V sensors are available in an ATEX/IECEx approved version. The
switch has a two-wire analog output which will grow linear to the level from 4
to 20 mA. The switch has settings which can be changed when connecting it to
the HB-tool.
The sensor is used together with a barrier to comply with ATEX/ IECEx
requirements.
- +24 VDC
- Not used
- Not used
- Analog output
- Not used