DELTA M30A_230 Grid tie Transformerless Solar Inverter Instruction Manual

June 25, 2024
Delta

DELTA M30A_230 Grid tie Transformerless Solar Inverter

Specifications

  • Product Name: M30A_230 Grid-tie Transformerless Solar Inverter
  • Phase: Three-phase
  • Input Voltage: Direct current from PV array
  • Output: Grid-compliant three-phase current
  • Features: 3 Maximum Power Point (MPP) tracking inputs
  • Compatibility: PV modules with coupling capacity not exceeding 10F

Product Usage Instructions:

1. Safety Information

1.1 Information of the Inverter:

The M30A_230 inverter is designed for installation, commissioning, operation, and maintenance by well-trained technicians. The technician must have basic and advanced skills for handling the inverter.

1.2 General Safety:

  • IMPORTANT SAFETY INSTRUCTIONS: Please read and save these instructions for future use.
  • ATTENTION: NO GALVANIC ISOLATION – Do not operate with grounding PV modules.

2. Conditions of Use

The M30A_230 is a transformerless solar inverter with 3 MPP tracking inputs. Ensure PV modules used are compatible and have a coupling capacity not exceeding 10F. Operate only in approved countries by DELTA and the grid operator.

3. Symbols

The manual contains various symbols indicating different levels of warnings and information. Follow all safety instructions to prevent hazards.

4. Introduction

The M30A_230 is designed for high efficiency and long operating life using advanced technology. It is suitable for outdoor use.

FAQs

  • Q: Can I connect the L1, L2, L3, and N terminals to ground?
    • A: No, it is prohibited to connect the L1, L2, L3, and N terminals to ground as the inverter does not have galvanic isolation.
  • Q: What should I do if I encounter a warning symbol while using the inverter?
    • A: If you encounter any warning symbol, refer to the manual for detailed instructions on how to proceed safely and prevent any hazards.

The power behind competitiveness
Grid-tie Transformerless Solar Inverter
M30A_230 Operation and Installation Manual

English

1

67

www.deltaww.com

Safety

1cSafety
1.1 Information of the Inverter
1.1.1 Legal Provisions
Copyright ­ DELTA ELECTRONICS, INC. – All rights reserved. This manual accompanies our product for use by the end users. The technical instructions and illustrations contained in this manual are to be treated as confidential and no part may be reproduced without the prior written permission of DELTA ELECTRONICS, INC. Service engineers and end users may not divulge the information contained herein or use this manual for purpose other than those strictly connected with correct use of the product. All information and specifications are subject to change without notice. DELTA ELECTRONICS, INC. shall have no obligation to either personal injury and property damage claims hereinafter with respect to any actions — (a) the product has been installed and/or repaired improperly; (b) the product has been misused without following the instructions on this user manual; (c) the product has failed due to incorrect unpacking.
1.1.2 Target Group
This manual of the solar inverter is prepared for the use by a well-trained technician for installing, commissioning, operation, and maintenance. The technician must have the following basic and advanced skills:
· Knowledge of the fundamentals of electricity, wiring, electrical components and electrical schematic symbols.
· Knowledge of how a solar inverter works and is operated. · Training in the installation and commissioning of electrical devices and installations. · Training in how to deal with the dangers and risks associated with installing
and using electrical devices and installations. · Compliance with this manual and all safety information.
8

Safety
1.2 General Safety
IMPORTANT SAFETY INSTRUCTIONS : SAVE THESE INSTRUCTIONS !
– Please read these instructions carefully and save them for later use.
To prevent personal injury and/or property damage, and also to ensure long term operation of the solar inverter, it is imperative this section be read carefully and all the safety instructions understood before using this inverter. This user manual provides important instructions for DELTA grid-tie transformerless solar inverter. The product is designed, tested, verified, and certified according to international safety requirements, certifications, and standards but precautions must be observed when installing and operating the product. This product is suitable for indoor and outdoor use.
ATTENTION : NO GALVANIC ISOLATION
– The inverter is not equipped with a transformer and has no galvanic isolation. – Do not operate with grounding PV modules. – It is prohibited to connect L1, L2, L3 and N terminal to ground.
1.2.1 Condition of Use
– The M30A_230 is a transformerless solar inverter with 3 MPP tracking inputs, which converts the direct current from the PV array into grid-compliant three- phase current and feeds it into the utility grid.
– The photovoltaic modules used must be compatible with the inverter. PV modules with a high capacitance to ground must only be utilized if the coupling capacity does not exceed 10F.
– The inverter must only be operated in countries for which it is approved by DELTA and the grid operator.
9

Safety
1.2.2 Symbols
This section describes the definition of the symbols in this manual. In order to prevent both personal injury and property damage, and to ensure long-term operation of the product, please read this section carefully and follow all the safety instructions while you use the product.
DANGER!
– This warning indicates an immediate hazard which will lead to death or serious injury.
WARNING !
– This warning indicates a possible hazard which may lead to death or serious injury.
CAUTION !
– This warning indicates a possible hazard which may lead to minor injury.
ATTENTION
– This warning indicates a condition of potential damage to property and/or the environment.
10

Safety
INFORMATION
– An exclamation mark enclosed in a double circle indicates additional important information is contained in the following section and the user should follow the instructions to prevent any hazards.
DANGER : ELECTRICAL HAZARD!!
– This warning indicates an immediate electrical hazard that unheeded can lead to death or serious injury.
CAUTION : HOT SURFACES, DO NOT TOUCH!
– This warning indicates a potential burn hazard. – Use care when touching surfaces when operating the product. – Do not perform any task until the product cools down sufficiently.
– This icon indicates that a prescribed time delay must elapse before engaging in an indicated action.
– Patientez le délai requis avant d’entreprendre l’action indiquée.
– This symbol indicates the location of an equipment grounding conductor (EGC) terminal.
11

Introduction

2cIntroduction
M30A_230 is designed to enable the highest levels of efficiency and provide longest operating life of transformerless three-phase PV inverter by state-of- the-art high-frequency and low EMI technology. It is suitable for outdoor use.
ATTENTION : NO GALVANIC ISOLATION
– The inverter is not equipped with a transformer and has no galvanic isolation. – Do not operate with grounding PV modules. – It is prohibited to connect L1, L2, L3 and N terminal to ground.
2.1 Valid Model
The user manual is valid for the following device types: · M30A_230 This user manual must be followed during installation, operation, and maintenance. DELTA reserves the right to make modifications to the content and technical data in this user manual without prior notice.
12

2.2 Product Overview
The components are shown as Figure 2-1.

Introduction

Figure 2-1: Components

Object 1 Delta Solar Inverter
2 Mounting Bracket

3

User Manual

4

AC Plug

5

H4 Connector

6

H4 Wrench

7

Hexagon Driver

(Installed on latch lock cover)

8

Wi-Fi Antenna

9

Security Seal

Table 2-1: Packing list

M30A_230

Qty

Description

1 pc

Solar inverter

1 pc

Wall mounting bracket (Material: Aluminum/Thickness: 3mm)

Important instructions for solar inverter.

1 pc

Safety instructions should be followed

during installation and maintenance.

1 set

Connector for AC connection

6 pairs DC String inputs

2 pcs To disconnect H4 connector

1 pc

To unscrew the latch lock cover and secure the door from closing.

1 pc

Antenna for Wi-Fi

6 pcs Tamper stickers for Taiwan use only

13

Introduction

Figure 2-2: Overview

Table 2-2: Overview description

NO. Component 1 Toggle Latch 4 Reserved* 7 Cable gland for RS-485

NO. Component 2 LED 5 Cable gland for AC output 8 DC input (H4) x 6 strings

NO. Component 3 DC Switch 6 Wi-Fi Antenna port

*Always keep nut and screws properly tightened on the case. Water leakage may cause serious damage.

14

Figure 2-3 below, shows the certification and rating label. Table 2-3 defines the symbol markings on this label.

Introduction

Figure 2-3: Rating label

Table 2-3: Rating label explanation

Symbol

Definition

60 seconds

Danger to life through electric shock Potentially fatal voltage is applied to the inverter during operation. This voltage persists even 60 seconds after disconnection of the power supply. Never open the inverter. The inverter contains no components that must be maintained or repaired by the operatoror installer. Opening the housing will void the warranty.

Beware of hot surface. This inverter can get hot during operation.

Before working with the inverter, you must read the supplied manual and follow the instructions contained therein.

This inverter is not separated from the grid with a transformer.
The housing of the inverter must be grounded if this is required by local regulations.

WEEE marking
The inverter must not be disposed of as standard household waste, but in accordance with the applicable electronic waste disposal regulations of your country or region.

15

Installation

3 Installation
WARNING !
– Do not install the unit near or on flammable surfaces. – Please mount the unit tightly on a solid / smooth surface.
CAUTION !
– High temperature may result in derated power output, the unit should not be installed in direct sunlight.
– Risk of injury when lifting the inverter or if it is dropped.
CAUTION !
The product supports wireless communication. – Install the product as far away as possible from devices that emit strong radio
waves, such as civil band radio equipment. – Do not install the product in metal box and make sure there is no metal barrier
between the product and connecting devices to prevent the communication signal attenuation. – When using Wi-Fi to connect the inverter, the connection signal strength is recommended to be at least -70 dBm to ensure good communication quality. The chapter contains instructions for (1) Vertical wall mount (2) Electrical installation (3) Communication setup
16

Installation
3.1 Unboxing & Review
The unpacking procedure is shown as Figure 3-1. The position of hook attachment for crane transporting is shown as Figure 3-2.
Figure 3-1: Steps to unpacke the inverter 17

Installation

Hoisting Hook

Figure 3-2: Attaching the Hoisting hooks

651 mm

220 mm

556 mm 520 mm 490 mm

Figure 3-3: Inverter dimensions 18

Installation
3.2 Vertical wall mount
Refer to Figures 3-4 to Figure 3-7.
1. Ensure the surface to which the unit is to be mounted is sufficiently strong enough to carry the weight of inverter.
2. Orient the wall bracket (Figure 3-4) horizontally (perpendicular to the floor). 3. Secure the mounting bracket on the wall with 12 M6 screws. 4. Hang the inverter on the wall mounting bracket. 5. Secure the inverter by 2 M5 screws on the position* shown as Figure 3-5.

  • These are also grounding points for equipment grounding. (To ground the inverter, please refer to Section 3.5)
    CAUTION !
    – The mounting bracket provided with the unit is specially designed and is the only certified mounting device for mounting the inverter.
    – Secure the mounting bracket on the wall with at least 6 M6 screws. – Failure to comply with following mounting instructions including permitted
    orientations and designated clearances may result in derated power output and may void the warranty.

CAUTION !
To avoid malfunction of inverter caused by extreme weather (ex: snow, hail…etc) or non-proper installation/ maintenance, an additional protection cover is strongly recommended to be installed by DELTA. For more details, please contact local service team.

Protection cover

19

Installation unit: mm

460

400

30

6.5

82

82

82

82

82 25

410.6 17 27 31

500 Figure 3-4: Mounting bracket dimensions Positions for least amount of mounting bracket screws

8.5 5.5

or

  • Screw: M6

  • Screw: M5

Figure 3-5Positions of mounting screws 20

300mm

200mm >300mm

Installation >200mm

300mm

500mm *

500mm *

  • Make sure it is high enough to have sufficient space for wiring. Figure 3-6: Separation distance of plural inverters

90 Figure 3-7: Permitted and prohibited mounting positions

21

Installation
3.3 Electrical Installation for AC Wiring
DANGER : ELECTRICAL HAZARD!!
– To avoid shock hazard during wiring, ensure any live grid connections are removed from the inverter.
WARNING !
– Code compliance is the installer’s responsibility.
CAUTION : INVERTER AND EQUIPMENT DAMAGE MAY OCCUR !
– Installation for AC plug must meet the local electrical code. – Failed to follow the instructions may damage AC cable. – If there is any conflict between installation instruction and electrical code,
please follow the electrical code.
ATTENTION
– The inverter may be damaged due to dust intrusion. – Please do not open the lid of the inverter.
22

Installation

3.3.1 AC Grid Types and Connections

ATTENTION

The default AC Grid connection is 3Ø-4W. It can also connect 3Ø-3W without Neutral (N). The inverter will operate from the following grid connections without need of an external transformer:

TNC system 220/380V, 230/400V
L1 L2 L3 PE/N
M30A_230

TNC-S system 220/380V, 230/400V
L1 L2 L3 N PE
M30A_230

TNS system 220/380V, 230/400V
L1 L2 L3 N PE
M30A_230

TT system 220/380V, 230/400V
L1 L2 L3 N
M30A_230

IT system 220/380V, 230/400V
L1 L2 L3
M30A_230

3.3.2 Required Protective Devices
It is recommended to install an upstream AC line disconnection and over current protection device. Please refer to your local rules for the required product.
The inverter integrates Residual Current Monitoring Unit (RCMU) for the detection of residual current and does not require an external residual- current protective device. However, if an external RCD is required by installation standard, a RCB/ RCBO of type A or B with rating 300mA should be used.

23

Installation

3.3.3 AC Wiring Preparation
The AC wires must be jacketed and meet the specifications in Table 3-1. If there is any conflict with local electrical code, please follow the electrical code.

Table 3-1: AC wires requirement

Size of each wire

Cable diameter Recommended Torque

13.3~25 mm² (6~4 AWG)

20~26 mm

2.0~4.0 Nhm

Follow the steps below to strip the wires before assembling the AC plug: · Strip the outer jacket from the cable for 70mm. · Strip 22 ± 2mm of insulation from all wires ends.

70 mm (MAX) 22±2 mm
PE N L1 L2 L3

Outer Jacket

Figure 3-8 : Strip the wires

CAUTIONMachine and equipment damage may occur.
– Make sure to choose proper size for AC cable. – Failed to follow these instructions may cause AC plug damage. – If there is any conflict between installation instruction and electrical code,
please follow the electrical code.

24

Installation
3.3.4 AC Wiring
1. The packing has a AC Plug (item 4, Table 2-1) please rotate it to release part A & B shown as Figure 3-9.
2. Insert the cable into Part A (AC gland), and fix the internal wires (tighten by 4.0mm wrench with 2.0~4.0 Nm torque) into Part B . (Figure 3-11)
3. Rotate part A & B as Figure 3-12 to fit and fix it onto the inverter.
B

A
Figure 3-9 : Assemble the AC plug

140 (REF)

F

32.2 ± 0.8

Part A D1

Cable range: 20~26 mm

Cable range

D1

20 ~ 26 mm

Part A fastening torque 3 ~ 5 Nm

Part B fastening torque 1.5 ~ 1.7 Nm

  • The connector is not designed for solid wire but only for stranded wires with end sleeves. * The terminal gets a silver surface treatment.
    Figure 3-10 : The rubber rings of AC gland

25

Installation

B

A

Part B 13.3~25 mm² (6~4 AWG) Tightening torque: M8/ 2~4 Nhm

For 3P4W Power system :
There are 5 wires that include (L1L2L3N) + PE

L2

L3

L1

N

PE

For 3P3W Power system :
There are 4 wires that include (L1L2L3) + PE

L2

L3

L1 PE

Figure 3-11 : AC wiring
B

A
Figure 3-12 : Rotate the AC plug to fit
26

Installation
3.4 Electrical Installation for DC Wiring
DANGER : ELECTRICAL HAZARD!!
– PV arrays convert sunlight into electric power with high DC voltage and high DC current which can cause dangerous electrical shock! – Use opaque material to cover the PV arrays before wiring or cabling. – Ensure the correct polarities are connected when DC cabling is applied. – The amount of PV module of each string within one MPPT should be the same to avoid the circulating current between the strings.
WARNING !
– The inverter may overheat and catch fire under fault conditions. – Only PV modules that are listed with system voltage under 1100V are permitted
for use. – Make sure the DC switch is in the “OFF” position, and disconnect the PV array
before plug in/out the DC connectors. – Inverter warranty void if the DC input voltage exceeds 1100 Vdc.
ATTENTION
– The PV Array current carrying conductors (positive or negative) must not be referenced to ground.
– Before plug in the DC connectors, please notice the polar of connectors. Reverse positive and negative voltage will make damage.

– Do not remove the waterproof plug for unused DC strings.

ATTENTION
– According to different local regulations, if the external string fuse is required, please contact Delta dealers.

H4+

H4-

XX: Fuse rating 20A / 25A / 30A 27

Installation
Please read the following instructions for connecting DC connector : · Ensure the DC conductors used are Cu and sized to the correct ampacity per
NEC or other local code · Strip off all wires for 6.5~7.5 mm. · The cross- sectional area for each DC conductor is 12~10 AWG (4~6 mm²). · Choose the DC string wire size based on NEC requirements or other local code.
M30A_230 uses H4 type connectors mounted on the bulkhead to connect the string to the inverter. Mating connectors (See Figure 3-13) are provided within the packing.
6.5 d7.5 mm

H4CFC4D-MS

H4CMC4D-MS

“CLICK”

Figure 3-13: DC wiring illustration

The polarities of DC wiring are divided into positive and negative, layout of the connectors is shown as Figure 3-14.

28

Installation
Figure 3-14: Location of H4 connectors to connect array wiring (DC)
ATTENTION
– For unused DC connectors, please keep the cap on to prevent water or dirt intrusion.
29

Installation
3.5 Equipment Grounding
To ground the inverter, please crimp the grounding wire to ring terminal lug and fix it on the grounding point shown as Figure 3-15.

A

A

B

B

  • A- Screw: M6 / Torque: 3.9 Nhm B- Screw: M5
    Figure 3-15: Mount the equipment grounding

30

Installation
3.6 Communication Module Connections
The communication module of M30A_230 is shown in Figure 3-16. It provides VCC(12V), RS-485, dry contact, EPO, and digital input terminals for various applications, and it can be extended to ability to use Sub_1G.
V1 x1 & EPO x1 VCC & RS-485 Digital Inputs x6
+ 12V

1

Terminal Resistor

Dry Contact

Rapid Shutdown System Connection (optional)

Figure 3-16: Communication module layout

31

Installation
3.6.1 Accessing the Communication Module
The communication module consists of an assembly with a PCB and a plastic carrier. It is located in slot through the bottom of the chassis. It can be accessed from the chassis bottom outside. The carrier is fixed to the chassis by two self-retaining screws. See Figure 3-17. Loose the self-retaining screws from the chassis, and gently pull the carrier straight out of the chassis to withdrawthe communication module. After passing the required signal cable through the wiring gland provided or a connected conduit and making the electrical connections as shown in the following sections, the module can be reinstalled in the opposite direction described above.

  • Screw torque: 0.8 Nhm
    7.2mm* 10mm

7.2mm 10mm Remove the rubber stopper in the 7.2 mm hole can extend it to 8.7 mm for use.
Figure 3-17: Location and access to communication module

ATTENTION
This inverter is compliant with the “Technical Specification for Security Inspection of Solar Inverter and Monitoring Units” required by BSMI. After completing the communication wiring, please apply a brand new one-time-use security seal (item 9, Table2-1) on the carrier. We will not be liable or responsible for any security incident caused by an improper application of the sticker.

security seal

32

Installation

3.6.2 RS-485 Connection
The pin definition for the RS-485 terminal block is shown in Table 3-2. – Pins 1 and 2 provide a 12VDC bus for use with accessories.
(If use of the 12VDC bus is necessary, please set switch 1 to the ON position.) – Pins 3 and 5 are both connected to the DATA+ input. – Pins 4 and 6 are both connected to the DATA – input. These connections allow easy daisy- chaining of multiple inverters. A 120ohm bus termination resistor and associated control switch are located on the communication board. The switch function is as shown in Table 3-3. Different RS-485 connection scenarios require different set up for the 120ohm bus termination resistor. · When multiple inverters are cascaded (i.e., “daisy-chained”), only the last inverter
in the chain must have its bus termination resistor switched ON.(Figure 3-18) · If the length of any RS-485 bus is greater than 610m, it is recommended to use
Belden 3105A cable (or equivalent cable) to ensure communication quality.
ATTENTION
– It is recommended to use twisted-pair as a communication cable for well transmission quality.

Table 3-2: RS-485 Terminal block wiring

Pin

Function

1

VCC (+12V)

123456

2 GND (It is NOT the PE)

3

DATA+

4

DATA-

5

DATA+

6

DATA-

VCC GND D+ D- D+ D-

INFORMATION

When the RS-485 cable needs to be grounded, please follow the steps below.

1. strip a wire from the shielding layer and properly insulate it

2. crimp the insulated wire to the Y-type lug and fix it in position A

shielding layer

SNYBL1-4

A

strip from shielding layer (cross-section: 0.5~1.5 mm²)

Insulation Tape 33

  • Screw torque: 0.8 Nhm

Installation

Terminal Resistor
120(1/2W) DATA+ to DATA-

RS485/USB or
RS485/RS232

Figure 3-18: Multiinverter connection illustration

Table 3-3: Bus Termination switch settings

Switch 1

ON

Terminal Resistor ON

OFF

Terminal Resistor OFF

34

Installation
3.6.3 EPO Function & Digital Input
The communication Module has an emergency power off function (EPO). Users can customize EPO function in APP or Delta Solar System (DSS).
COMM. card

V1 K0 K1 K2 K3 K4 K5 K6

Figure 3-19: EPO and digital input function terminal block
Once enabled, the EPO function can be used to turn off the inverter through the relayless contacts connected to terminals [V1 & K0]. A digital power reduction control function is provided, which can be set to limit the available active output power of the inverter. The control settings for this function are made by placing a hardware short circuit (jumper or relay) between the two terminals of the terminal block shown in Table 3-4. For Australia and Newzealand, please refer to Table 3-5.

Table 3-4: Definition of digital input & EPO function

Short terminals Inverter’s action

V1 & K0

Emergency power off (EPO)

V1 & K1

0% active power

V1 & K2

Maximum 30% rated power

V1 & K3

Maximum 60% rated power

V1 & K4

Maximum 100% rated power

V1 & K5

Reserved

V1 & K6

Reserved

Short V1 & K1 V1 & K2 V1 & K3 V1 & K4 V1 & EPO

Tabel 3-5: Definition of DRMs for Australia and New Zealand
Inverter’s action DRM5 (0% active power) DRM6 (Maximum 50% active power) DRM7 (Maximum 75% active power and sink reactive power) DRM8 (Maximum 100% active power and sink reactive power) DRM0 (Emergency power off)

35

Installation
3.6.4 Dry Contact Connection
M30A_230 provides 1 set of dry contacts, which can be used to control external devices according to the operating status of the inverter. The terminal block for this function is shown in Figure 3-20. The terminals marked in the figure identify the dry contact connection. The dry contacts operation are usually open. User can customize the function of this contact through the the APP or DSS.
COMM. card

Figure 3-20: Dry Contact connection

3.6.5 Rapid shutdown system connection (optional)
M30A_230 provides a terminal to control the rapid shutdown system. This terminal provides a 12 VDC, Max.1 A power in normal condition, but the power will turn-off in 2 seconds when the AC grid outage. The terminal block for this function is shown in Figure 3-21. 1. 22~12 AWG solid or stranded wire is available for the terminal hole and wire
length is limited to 10 M. 2. Stripping length is 6 ~ 7 mm.

COMM. card

DC+ 12V GND

Figure 3-21: Rapid Shutdown System connection

36

Installation
3.7 Wi-Fi
The communication module supports the inverter to communicate with devices (such as smartphones, tablets, etc.) via Wi-Fi (base WPA2-PSK). User can restart the function through the APP or DSS. There is an antenna for Wi-Fi in the package (item 8,Table 2-1), which must be mounted on the plastic carrier as the procedure below. 1. Remove the protective nut. 2. Tighten the antenna.
Figure 3-22: Installation of Wi-Fi antenna
ATTENTION
– Please properly install the antenna as shown below to keep communication quality and avoid equipment damage.
– More detail for Wi-Fi connection and APP : https://mydeltasolar.deltaww.com/index.php?p=manual
– To establish a successful communication between Inverter Wi-Fi to MyDeltaSolar Cloud, in the Wi-Fi connection setup page, the signal strength must be above -70dBm between each Wi-Fi device (Wi-Fi router, inverter, DC1…etc.). In case the signal strength is below -70dbm, it may cause certain communication errors which may prevent a successful Wi-Fi communication. To avoid such issues, please adjust the Wi-Fi device position to improve the signal strength/quality.
37

Commissioning

4 Commissioning
CAUTION : HOT SURFACES, DO NOT TOUCH!
– Use care to avoid hot surfaces when operating the product! – Do not perform any task until the unit cools down or wear appropriate personal
protective equipment.

4.1 LED Signals
M30A_230 with 3 LEDs can visually display the status of the inverter, as shown in Figure 4-1. Table 4-1, 4-2 provide the information of LED indicators.

LED Indicator LED Indicator LED Indicator

(GRN)

(RED/YEL)

(GRN)

Figure 4-1: LED indicators

Condition Countdown
On Grid Inverter Fault / Remote off
Inverter Warning Field Fault
Field Warning NO DC
FW Upgrade Standby
Check PV Power System Lock
*FLASH: ON 1s / OFF 1s FLASH FAST: ON 0.25s / OFF 0.25s FLASH SLOW: ON 5s / OFF 10s

Table 4-1: Inverter status Grid (Green) FLASH ON OFF ON (or OFF) OFF ON OFF FLASH FLASH FLASH FAST OFF

Alarm (Red/Yellow) OFF / OFF OFF / OFF ON / OFF
FLASH / OFF OFF / ON
OFF / FLASH OFF / FLASH SLOW
FLASH / OFF OFF / FLASH OFF / FLASH FAST FLASH / FLASH

Table 4-2: Wireless communication status

Connection Status

COMM. (Green)

Offline

OFF

Wi-Fi

FLASH (ON 1s / OFF 2s)

38

Commissioning
4.2 Auto ID Commission
The Auto ID function can set all inverter IDs at once by DSS (Delta Solar System) or DeltaSolar APP. – DSS Connect the inverter through RS-485 or Wi-Fi with computer. – APP Connect the inverter through Wi-Fi with mobile device. (please refer to chapter 4.3 for operation manual.)
4.2.1 Commission Setting (DSS)
Select the corresponding model Select RS485 or Wi-Fi to connect the computer and inverter If use RS485, select communication port (automatic detection by the system) Click

Figure 4-2: DSS Commission setting 39

Commissioning

4.2.2 Scan inverter

Click “Auto ID

Enter numbers of inverters.

Click “Scan”.

Figure 4-3: Steps of scanning inverters 40

Commissioning
4.2.3 Set ID
The serial number of the successfully scanned device will be displayed below, the default ID can be changed.
After ID setting is completed, click “Set ID”.

Figure 4-4: Steps of ID setting
41

Commissioning
4.2.4 Set Country
Click to select the country of inverter. (For compliance with AS/NZS 4777.2:2020, please select from Region Australia A/B/C and NZ.) Click “Set”.

Figure 4-5: Steps of country setting
4.2.5 Synchronize time

Click “Sync Clock

” to Synchronize time.

Figure 4-6: Steps of time synchronization 42

Commissioning

4.3 Delta Function Setting
Delta offers two setting tools: DSS (Delta Solar System Software) and APP (DeltaSolar)

Function

Active power control

Q(U) control (volt-var control)

P-F control (watt-frequecy control)

Q by night(Q setting 24/7)

P(U) control (volt-watt control)

Anti-PID

Fixed cos

Dry contact

Fixed Q(%)

ARC fault detection

Auto ID

Wi-fi

Please refer to the following link for operation manual.

DSS Operation Manual:

https://mydeltasolar.deltaww.com/manual/eng/SUB_1G/DSS.pdf DeltaSolar (APP) Operation and Installation Manual:

https://mydeltasolar.deltaww.com/index.php?p=manual

43

Maintenance

5cMaintenance
Regular maintenance can ensure that the inverter maintains great performance. DELTA recommends that the unit should be inspected at least every 6 months. The maintenance frequency should be adjustable, depending on the sit environment, different seasons and weather effects.
DANGER : ELECTRICAL HAZARD!!
– Make sure that both AC breaker and DC switch are turned off and the LED indicators are off to avoid the risk of electric shock!
5.1 Open and Close the Door
In order to ensure the normal long-term operation of the inverter, the M30A_230 door must be opened and closed according to the following step.
5.1.1 Open Door
WARNING ! – Do not attempt to open the door under raining condition. – Before opening the front door, please wipe the inverter case if it is wet to
avoid water seepage. 1. Loosen the screws on both latch covers with hexagon wrench attached on the
latch cover. (Figure 5-1) 2. Open the latch covers and release latches to open the door. (Figure 5-1) 3. Use the hexagon wrench to secure the door from closing. (Figure 5-2)

Figure 5-1: Open and close the door
44

Maintenance

Figure 5-2: To secure door by hexagon driver

5.1.2 Close Door
ATTENTION
– Due to corrosion of live parts, excessive moisture or dust in the inverter may cause accidental damage. Ensuring that the inner of the inverter is clean free from unreasonable pollution is important for long service operating systems.
– After cabling or maintenance for the inverter, please lock both toggle latch to make sure the inverter will remain IP66 protection.

1. Ensure that the gasket in the mounting slot and mating surface on the enclosure are clean and in good condition.
2. Make sure all protective covers are properly installed. 3. Remove the hexagon wrench and close the door. 4. Buckle the latch and apply a one-time- use security seal (item 9, Table 2-1) on
the top toggle latch as the following attention. 5. Secure the latch cover with the hexagon wrench. 6. The hexagon wrench can be fixed on the latch cover.

ATTENTION
– This inverter is compliant with the “Technical Specification for Security Inspection of Solar Inverter and Monitoring Units” required by BSMI. After closing the door, please apply a security seal on the toggle latch. We will not be liable or responsible for any security incident caused by an improper application of the sticker.

security seal

45

Maintenance
5.2 Replacement of Surge Protection Devices (SPD)
M30A_230 has Surge Protection Devices (SPD) for AC and DC wiring, which is located behind the protective cover and can be replaced if damaged.

AC SPD

DC SPD

Figure 5-3: Location of AC and DC SPD board

AC SPD

DC SPD

Figure 5-4: AC and DC SPD module If the warning message “AC Surge” or “DC Surge” appears on the APP and DSS, please follow the steps below to replace the SPD.
46

Maintenance
5.2.1 Replace AC SPD
1. Turn off the AC and DC power, and wait until the LED indicators turns off. 2. Follow Section 5.1.1 to open the door. 3. Loosen the screw and remove protective cover. 4. Loosen 3 screws, remove wires and disconnect signal cable to take off AC SPD. 5. Install the new AC SPD unit with procedures above in reverse order and
tighten the screw with 0.8 Nm torque. 6. Install the protective cover and tighten the screw with 0.8 Nm torque. 7. Follow Section 5.1.2 to close the door.

  • Screw torque: 0.8 Nhm
  • Screw torque: 0.8 Nhm
    Figure 5-5: Steps of changing AC SPD 47

Maintenance

  • Screw torque: 0.8 Nhm
    Figure 5-6: Remove wirings as connectors of AC SPD
    48

Maintenance
5.2.2 Replace DC SPD
1. Turn off the AC and DC power, and wait until the LED indicators turns off. 2. Follow Section 5.1.1 to open the door. 3. Slide open the protective cover. 4. Loosen 3 screws, remove wires and disconnect signal cable to take off DC SPD. 5. Install the new DC SPD unit with procedures above in reverse order and
tighten the screw with 0.8 Nm torque. 6. Install the protective cover properly. 7. Follow Section 5.1.2 to close the door.

  • Screw torque: 0.8 Nhm Figure 5-7: Steps of changing DC SPD 49

Maintenance

FRONT

  • Screw torque: 0.8 Nhm
    BACK

Figure 5-8: Remove wirings as connectors of DC SPD
5.3 External String Fuse
According to different local regulations, if the external string fuse is required, please contact Delta dealers.

H4+

H4-

XX: Fuse rating 20A / 25A / 30A 50

Maintenance
5.4 Replacement of Internal Fan
1. Turn off the AC and DC power, and wait until the LED indicators turns off. 2. Follow Section 5.1.1 to open the door. 3. Disconnect the cable on the DC SPD board. 4. Loosen the screws and remove the fan cabinet. 5. Loosen the screws to lift the entire fan assembly. 6. Clean assembly or replace with a unit. 7. Install the internal fan with procedures above in reverse order and tighten the
screws with recommended torque in Figure 5-10. 8. Follow Section 5.1.2 to close the door.
FAN 2

FAN 1

DC SPD

Figure 5-9: Location of internal fans and fan connectors 51

Maintenance FAN 1

  • Screw torque: 0.8 Nhm FAN 2

  • Screw torque: 0.6 Nhm

  • Screw torque: 0.8 Nhm

  • Screw torque: 0.6 Nhm

Figure 5-10: Replacement of internal fans

52

Maintenance
5.5 De-Commissioning
If it is necessary to remove the inverter from active operation for maintenance or replacement, please follow the instructions below.
DANGER : ELECTRICAL HAZARD!!
To avoid serious injury, please follow the procedure below.
CAUTION : HOT SURFACES, DO NOT TOUCH !
– Please be careful of hot surfaces if the inverter is just shutting down. – Not to do any maintenance until inverter is sufficiently cooled down.
CAUTION : POSSIBILE INJURY !
The inverter weighs 42 kg (92 lb). When the inverter is improperly handled or dropped during transportation or removed from the rack, it may cause personal injury.
– Switch off external AC circuit breaker or switch to disconnect the electrical grid from the inverter chassis.
– Switch off the DC switch to cease inverter operation. – Use H4 wrench tool to disconnect each string from the chassis mounted H4terminals. – Remove Wi-Fi antenna from the bottom of the cassis.
RS-485 Communication module 1. Remove the communication module from inverter. 2. Remove all communication cables from the module terminals. 3. Reinstall the communication board assembly in inverter.
53

Error Message and Trouble Shooting

6cError Message and Trouble Shooting
While Delta Electronics endeavors to build electronic products with high reliability standards, there may still be situations where the inverter may not operate properly. In this case, please follow the instructions in the “Troubleshooting Guide” (Tables 6-1 ~ 6-4) to attempt to clear the fault. If the problem can’t be solved, please contact customer service for technical support.

6.1 Error Codes (Field Fault)

Table 6-1A: Error Codes (Field Fault) & Messages

Message

Description

Action

AC Freq High (E01)

Grid frequency high

AC Freq Low (E02)

Grid frequency low

1. Check the utility frequency 2. Check Grid code & Grid setting

Island (E03,E04,E05)

Islanding is detected

Check Grid breaker

AC phase jump (E06)

Phase jump of Grid voltage

If repeated occurrence, contact customer service for technical support

Grid Quality (E07)
AC phase abnormal
(E08)

Non-linear load in Grid and near to inverter
Wrong connection in AC plug

If repeated occurrence, contact customer service for technical support
Check the AC connection in accordance with the user manual

No Grid 1. AC breaker is OFF (E09) 2. Disconnect in AC plug

1. Switch on AC breaker 2. Check the connection in AC plug and
make sure it connects to inverter

AC Volt Low (E10)
AC Volt High (E11)

1. Actual utility voltage is under the UVR setting
2. Incorrect Grid Code or Grid setting 3. Wrong connections in AC plug
1. Actual utility voltage is over the OVR setting
2. Incorrect Grid Code or Grid setting

1. Check the utility voltage within the suitable range
2. Check Grid code & Grid setting 3. Check the connection in AC plug

EPO (E25)

EPO is operated by user

Release the EPO button

DC Voltage

High

Input voltage is over 1000Vdc

(E30)

Modify the solar array setting, and make the Voc less than 1000Vdc

Insulation Fault (E34)

Insulation problem of PV array to ground

1. Check if panel enclosure ground conpletely 2. Check if inverter ground conpletely 3. Check if the DC breakers get wet

Remote OFF Remote OFF by external (E36) communication

Check if remote OFF function is active

54

Error Message and Trouble Shooting

6.2 Fault Codes (Inverter Fault)

Table 6-2A: Fault Codes (inverter fault) & Messages

Message

Description

Action

DC Injection (F01,F02,F03,F04)

Utility waveform is abnormal

Contact customer service for technical support

Temperature High (F05)

The internal ambient temperature Check the installation ambient and

is over limit

environment

Amb Temp Fault Ambient temperature detection

(F06)

failure

Contact customer service for technical support

Temperature Low (F07)

The internal ambient temperature Check the installation ambient and

is under limit

environment

Boost Temp Fault (F08)

Boost module temperature detection failure

Contact customer service for technical support

Bidir. Temp Fault (F09)
Inveter Temp Fault (F10)
AC RLY Fault (F13)

The boost/bidir. NTC temperature
Inverter module temperature detection failure 1. Defective relay driver circuit 2. Relay(s) failure

Contact customer service for technical support
Contact customer service for technical support
Contact customer service for technical support

FW Unmatch (F14)

Firmware Incompatibility

Contact customer service for technical support

AC Sensor Fault (F15)

Auxiliary power circuit failure

1. Check the polarity of PV connection (if the error code comes along with W08)
2. Contact customer service for technical support

Vdc Sensor Fault (F16)

DSP Vdc sensor circuit defective

Contact customer service for technical support

Idc Sensor Fault (F17)

Auxiliary power circuit failure

1. Check the polarity of PV connection (if the error code comes along with W08)
2. Contact customer service for technical support

AC Sensor Fault (F18)

Auxiliary power circuit failure

Contact customer service for technical support

Idc Sensor Fault (F19)

Auxiliary power circuit failure

Contact customer service for technical support

Red COMM Fault (F22)

The internal communication connection is disconnected

Contact customer service for technical support

55

Error Message and Trouble Shooting

Table 6-2B: Fault Codes (inverter fault) & Messages

Message

Description

Action

DSP COMM Fault The internal communication

(F23)

connection is disconnected

Check the connection interface RS-485

Ground Cur. High (F24)

Insulation problem of PV array to ground

1. Check the insulation of Solar inputs 2. Contact customer service for
technical support

Iac Unbalance (F26)
RCMU Fault (F27)

1. Power line is disconnected 2. Current feedback circuit is
defective
RCMU circuit is disconnected

Check the connection in AC plug
Contact customer service for technical support

AC RLY Short (F28)

Grid relay short

Contact customer service for technical support

AC RLY Open (F29)

Grid relay open

Contact customer service for technical support

Bus Unbalance (F30)

Voltage unbalance of DC link

Restart inverter by DC switch

Bus Voltage High (F31, F32, F33 High bus capacitor voltage F34, F35)

AC Current High (F36,F37,F38 Surge occurs during operation F39,F40,F41)

AC CT Fault (F42,43,44)

Phase R / S / T CT is defective

1.Restart inverter by DC switch 2.Check the solar array setting, and make sure the Voc less than Max. Vdc of Inverter (if the error code comes along with E30)
Contact customer service for technical support
Contact customer service for technical support

AC Current High (F45)

AC current over range

ZC Circuit Fault The zero crossing circuit

(F50)

is defective

Inv Circuit Fault (F51)

The inverter circuit is defective

Boost Circuit Fault (F52)

The boost circuit is defective

Arc circuit fail 1. AFCI is not installed

(F58)

2. AFCI self-test is fail

Arc fault (F59)

The inverter detects arcing occurs

Restart the inverter by DC switches
Contact customer service for technical support
Contact customer service for technical support
Contact customer service for technical support
Check the AFCI detection circuit board for making sure it is connected correctly
1. Check if there are any cable damaged at DC side.
2. Replace DC cable and unlock the Arc fault from DSS
3. Contact customer service for technical support

56

Error Message and Trouble Shooting

Table 6-2C: Fault Codes (inverter fault) & Messages

Message

Description

Action

DC Current High (F60,F61,F70,F71)

DC current over range

Restart inverter by DC switches

Ext COMM. Fault (F74)

The external communication connection is disconnected

1. Check the connection between external unit and COMM
2. Contact customer service for tech. support

6.3 Warning Codes (Field Warning)

Table 6-3A: Warning Codes (Field warning) & Messages

Message

Description

Action

De-rating (W07)
String fault (W08)
String Current Low (W23)

1. Over temperature 2. Power Limit function 3. Power vs. Frequency function 4. P(V) function 5. Grid Voltage low 6. Solar Voltage low 7. Solar Voltage High 8. Ramp up function

1. Check the installation ambient and environment
2. Check Grid Code & Grid setting 3. Check the utility frequency on the inverter
terminal 4. Check the utility voltage on the inverter
terminal 5-1. Check the utility voltage on the inverter
terminal 5-2. Check reactive power setting 6. Check the Solar voltage on the inverter
terminal 7. Check the Solar voltage on the inverter
terminal 8. Check Ramp up setting

1. Polarity of DC connectors is

1. Check the polarity of PV connection

incorrect

2. Restart DC switch and AC breaker

2. String current monitoring function 3. Contact customer service for

is fail

technical support

Disconnection in DC connectors

1. Check String Connector and Fuse 2. Contact customer service for
technical support

6.4 Warning Codes (Inverter Warning)

Table 6-4A: Warning Codes (inverter warning) & Messages

Message

Description

Action

Fan Fail (W11)

1. One or more fans are locked 2. One or more fans are defective 3. One or more fans are
disconnected

Contact customer service for technical support

DC SPD Fault AC SPD Fault (W17) (W18)

1. One or more SPD are defective 2. One or more SPD are
disconnected

1. Replace the defective SPD 2. Check the connections of SPDs

Boost Circuit Fault (W30)

The boost circuit defective

Contact customer service for technical support

6.5 Earth Fault Alarm
The inverter complies with IEC 62109. When the earth fault occurs, the Yellow LED Alarm indicator will light up and a notification email will be sent to the customer.

57

Technical Information

7cTechnical Information

Model Occasionally Max. Voltage

Table 7-1A: Specifications M30A_230 DC Input 1100 V *1

M30A_230 (Korea) 1000 V

Operating Voltage Range

200 – 1000 V

MPP Voltage Range @ AC400V

480 – 900 V

480 – 800 V

Start Voltage

250 V

Nominal DC Voltage

600 V

Max. Input Current

Each MPPT: 30 A, Total: 72 A

Max. Input Power

Each MPPT: 20.4 kW

Max. Allowable Array Isc

50A per MPPT

MPP Tracker

3

Connection Type

2 strings / MPPT, Amphenol H4 Connector

DC Switch

Built-in

String Monitoring

Built-in

Arc Fault Detection

Built-in

Surge Protection

Type II SPD

AC Output

Rated Output Power

30 kW

Max. Apparent Power

33 kVA

Max. Output Power

30 kW @ 40°C ; 33 kW @ 35°C

Max. Output Current

50 A

Nominal AC Voltage Operating Voltage Range

3 Ph 220 / 380, 230 / 400V Y or 80% to 130% of Nominal AC Voltage

Operating Frequency Range

50 / 60Hz ± 5Hz

Power Factor

0.8 ind – 0.8 cap (Adjustable)

Surge Protection

Type II SPD

T.H.D Night Time Consumption *2

< 3% < 2 W

Inrush Current Max. Output Fault Current (rms)

110 A / 50 s 60 A

Max. Output Over Current Protection (peak)

116 A

1 The max withstand voltage is 1100Vdc. (Inverter stops output when the PV voltage is over 1000Vdc) 2 Night time consumption with standby communication.

58

Model
Peak Efficiency Euro Efficiency
Communication Port
Grid support
Operating Temp. Range Protection Level Operating Elevation Cooling Noise Dimension (W x H x D) Weight Relative Humidity Pollution Degree Overvoltage Category Back-Feed Current to the Array Galvanic Isolation

Technical Information

Table 7-1B: Specifications M30A_230 Efficiency

M30A_230 (Korea)

98.6 %

Information

98.2 %

RS-485 (built-in) / Wi-Fi (built-in) / SUB_1G (optional)

Regulation

IEC 62109-1/-2 IEC 62920 CNS 15382
CNS 15426-1/-2 VDE-AR-N 4105 VDE-AR-N 4110 EN/IEC 61000-6-1/-2 EN/IEC 61000-6-3/-4 AS4777.2 : 2020
General Data

KN 62920 KS C 8567 KS C 8565

-25 to +60°C (Derating Above 40°C)

IP66

< 4000 m

Natural cooling

45.9 dBA @1m, Amb 25°C

651 x 520 x 220 mm

42 kg

0%-100% non-condensing

II

AC Output: III, DC Input: II

0

No

59

Technical Information

Efficiency(%)
100 % 99 % 98 % 97 % 96% 95% 94% 93% 92% 91% 90% 0%

Efficiency
Output voltage at 230Vac / 400Vac

Pn=30kW

480 V 600 V 800 V

20%

40%

60%

80%

Output Power (%)

Figure 7-1: Efficiency Curve

100%

60

Technical Information

P/Pn(%)

Power Derating Curve with Ambient Temprature

Output voltage at 230Vac / 400Vac PF=1

Pn=30kW

110 %

100 %

90 %

80 %

70 % 60 %

480V 600V 800V 900V

50 % 0

10

20

30

40

50

60

Ambient Temperature (°C)

Figure 7-2: Power Derating Curve with Ambient Temprature (PF=1)

P/Pn(%)

Power Derating Curve with Ambient Temprature

Output voltage at 230Vac / 400Vac PF=0.9

Pn=30kW

110 %

100 %

90 %

80 %

70 % 60 %

480V 600V 800V 900V

50 % 0

10

20

30

40

50

60

Ambient Temperature (°C)

Figure 7-3: Power Derating Curve with Ambient Temprature (PF=0.9)

61

Technical Information

P/Pn(%)
120 %

Power De-rating Curves with PV Voltage
Output voltage at 230Vac / 400Vac PF=1

Pn=30kW

100 %

80 %

60 %

40 %
20 %
0% 200

35 C 40 C 50 C 60 C

300

400

500

600

700

800

900

1000

PV Voltage (V)

Figure 7-4: Power De-rating Curves with PV Voltage

62

Appendix: Assembly Note

Technical Information

Appendix-1: Assembly Note-1

NO

Location

1

Wi-Fi module cover

2

Communication cover

Screw torque 8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm)

63

Technical Information

H4CFC4D-MS
H4CMC4D-MS

Appendix-2: Assembly Note-2

NO

Location

Screw torque

1

Internal fan 2

8.0 kgf-cm (0.8Nhm)

2

Internal fan 2 cover

6.0 kgf-cm (0.6Nhm)

3

Internal fan 1

8.0 kgf-cm (0.8Nhm)

4

Internal fan 1 cover

6.0 kgf-cm (0.6Nhm)

5

H4 wire

Conductor cross-section 12/10 AWG (4/6mm²)

64

Technical Information

NO Location 1 AC SPD cover 2 AC SPD board 3 DC SPD board 4 Communication port 5 AC wire

Appendix-3: Assembly Note-3

Screw torque 8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm)

Conductor cross-section –

25.5 kgf-cm (2.5Nhm)

20 AWG (0.5mm²) 6 AWG (13.3 mm²)~4 AWG (25 mm²)

65

The power behind competitiveness

M30A_230

English

1

67

www.deltaww.com

Contents
1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 1.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 1.1.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 1.1.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 1.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 1.2.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 1.2.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 2.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 2.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 3.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 3.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 3.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 3.3.1 AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 3.3.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 3.3.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 3.3.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 3.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 3.4.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 3.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 3.6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 3.6.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 3.6.2 RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 3.6.3 EPO . . . . . . . . . . . . . . . . . . . . . . . . . . .101 3.6.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102 3.7 Wi-Fi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103
69

4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 4.1 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 4.2 ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 4.2.1 DSS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 4.2.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 4.2.3 ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 4.2.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 4.2.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 4.3 Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 5.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 5.1.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 5.1.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 5.2 (SPD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 5.2.1 AC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 5.2.2 DC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 5.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 5.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 5.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 6.1 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 6.2 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6.3 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 6.4 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
70

Figure

2-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

2-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

2-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

3-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

3-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3-4: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

3-5: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

3-6: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

3-7: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

3-8: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

3-9:

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

3-10: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

3-11: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

3-12: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

3-13: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

3-14: H4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

3-15: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

3-16: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

3-17: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

3-18: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

3-19: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

3-20: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

3-21: Wi-Fi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

4-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

4-2: DSS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

4-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

4-4: ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

4-5: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

4-6: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108

71

5-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 5-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 5-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 5-4: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 5-5: AC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 5-6: AC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 5-7: DC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 5-8: DC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 5-9: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 5-10: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 7-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 7-2: (PF=1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 7-3: (PF=0.9) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 7-4: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
72

Table
2-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 2-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 2-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 3-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 3-2: RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 3-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 3-4: EPO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 4-1: LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 4-2: LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 6-1A: () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 6-2A: () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6-2B: () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 6-2C: () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 6-3A: () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 6-4A: () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 7-1A: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 7-1B: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 -1: -1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 -2: -2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 -3: -3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
73

1
1.1
1.1.1
~ DELTA ELECTRONICS, INC. – All rights reserved. DELTA ELECTRONICS, INC. DELTA ELECTRONICS, INC.
1.1.2

74

1.2

DELTA

– , – () – L1, L2, L3, N

1.2.1
– M30A_230 3 MPP
– – 10F – DELTA

75

1.2.2


76


!!

– –
– –
77

2
M30A_230 EMI

– , – () – L1, L2, L3, N
2.1
: · M30A_230 DELTA
78

2.2
2-1

1 DELTA

2

3

4

5

H4

6

H4

7

()

8

Wi-Fi

9

2-1 :

2-1 :

M30A_230

1

1

: / : 3mm

1

1

6

2

H4

1

1

Wi-Fi

6

79

2-2 :

2-2 :

NO.
1 4 * 7

NO.
2 LED 5 8 (H4) x 6 strings

NO.
3 6 Wi-Fi

80

2-32-3

2-3 :

2-3 :

60 seconds

60

,

, WEEE marking ,

81

3

– –

– –

Wi-Fi -70 dBm
1. 2. 3.
82

3.1
3-1 3-2
3-1: 83

3-2: 651 mm

220 mm

556 mm 520 mm 490 mm

3-3: 84

3.2
3-43-7
1. 2. ()3-4 3. 12M6(3-5) 4. 5. 2M53-5
3.5

– 6M6 – –

(, …) /,

85

unit: mm

460

400

30

6.5

82

82

82

82

82 25

410.6 17 27 31

500
3-4:

8.5 5.5

or

  • : M6

  • : M5

3-5 : 86

300mm

200mm >300mm

200mm
300mm

500mm *

500mm *

  • 3-6:

90 3-7:

87

3.3
!!

– – –

– –
88

3.3.1

3Ø-4W 3Ø-3W N

TNC system 220/380V, 230/400V
L1 L2 L3 PE/N
M30A_230
TNS system 220/380V, 230/400V
L1 L2 L3 N PE M30A_230

TNC-S system 220/380V, 230/400V
L1 L2 L3 N PE M30A_230
TT system 220/380V, 230/400V
L1 L2 L3 N
M30A_230

IT system 220/380V, 230/400V
L1 L2 L3
M30A_230

3.3.2

89

3.3.3
3-1

13.3~25 mm² (6~4 AWG)

3-1: 20~26 mm

2.0~4.0 Nhm

70 mm 22±2 mm

70 mm (MAX) 22±2 mm
PE N L1 L2 L3

Outer Jacket

3-8 :

– –

90

3.3.4
1. 3-9AB 2. A()2~4 Nhm
4mmB ( 3-11) 3. AB3-12
B

A
3-9 :

140 (REF)

F

32.2 ± 0.8

Part A D1

Cable range: 20~26 mm

Cable range

D1

20 ~ 26 mm

Part A fastening torque 3 ~ 5 Nm

Part B fastening torque 1.5 ~ 1.7 Nm

3-10 :

91

B

A

Part B 13.3~25 mm² (6~4 AWG) Tightening torque: M8/ 2.0~4.0 Nhm

3P4W : (L1L2L3N) + PE

L2

L3

L1

N

PE

3P3W : (L1L2L3) + PE

L2

L3

L1 PE

3-11 :
B

A
3-12 :
92

3.4
:!!
– – – – MPPT
!
– – 1100V – “” – 1100V

– –

– DC

H4+

H4-

XX: Fuse rating 20A / 25A / 30A

93

3.4.1
: · NEC · 6.5-7.5mm · 12/10 AWG (4/6mm2)
3-13~3-14
M30A_230 H4 (2-1, 5)
6.5 d7.5 mm

H4CFC4D-MS H4CMC4D-MS

“CLICK” 3-13:

94

3-14 : H4

– 95

3.5
O 3-15

A

A

B

B

  • A-: M6 / : 3.9 Nhm B-: M5
    3-15 :

96

3.6
3-16 12VVCCRS-485EPO SUB_1G

VCC & RS-485

V1 x1 & EPO x1 x6

+ 12V

ON 11

3-16 :

()

97

3.6.1
3-17

  • : 0.8 Nm
    7.2mm* 10mm

7.2mm 10mm 7.2 mm 8.7 mm 3-17:

(2-1 9)

98

3.6.2 RS-485
RS-4853-2 -1212V
(12VON) -35 RS-485DATA+ -46 RS-485DATA- 120 3-3 RS-485 · 3-18 · RS- 485610mBelden 3105A

3-2: RS-485

Pin

Function

1

VCC (+12V)

2

GND ()

123456

3

DATA+

4

DATA-

5

DATA+

6

DATA-

VCC GND D+ D- D+ D-

RS-485 1. (: 0.5~1.5 mm²) 2. Y(: SNYBL1-4)

SNYBL1-4

A

(: 0.5~1.5 mm²)

99

  • : 0.8 Nhm

120(1/2W) DATA+ to DATA-

RS485/USB or
RS485/RS232

3-18 :

3-3 :

ON

ON

1

OFF

100

3.6.3 EPO
(EPO) APPDelta Solar System (DSS)

V1 K0 K1 K2 K3 K4 K5 K6

3-19 :

V1K0EPO 3-4

3-4: EPO

V1 & K0

(EPO)

V1 & K1

0 %

V1 & K2

30 %

V1 & K3

60 %

V1 & K4

100 %

V1 & K5

V1 & K6

101

3.6.4
M30A_230 3-20 APPDSS
3-20 :
102

3.7 Wi-Fi
Wi-Fi(WPA2-PSK) APPDSSWi-Fi (8, 2-1)Wi-Fi 1. 2.
3-21 : Wi-Fi


– Wi-FiAPPQR-code https://mydeltasolar.deltaww.com/index.php?p=manual
– Wi-FiWi-Fi(Wi-Fi, , DC1…) -70dbm<-70dbm
103

4

– –

4.1 LED
M30A_230 3LED4-1 LED4-14-2

LED ()

LED (/)

LED ()

Countdown
On Grid Inverter Fault / Remote off
Inverter Warning Field Fault
Field Warning NO DC
FW Upgrade Standby
Check PV Power System Lock
*FLASH: ON 1s / OFF 1s FLASH FAST: ON 0.25s / OFF 0.25s FLASH SLOW: ON 5s / OFF 10s

4-1 :
4-1: LED Grid () FLASH ON OFF
ON (or OFF) OFF ON OFF
FLASH FLASH FLASH FAST
OFF

Alarm (/) OFF / OFF OFF / OFF ON / OFF
FLASH / OFF OFF / ON
OFF / FLASH OFF / FLASH SLOW
FLASH / OFF OFF / FLASH OFF / FLASH FAST FLASH / FLASH

4-2:

Offline

COMM. () OFF

Wi-Fi

FLASH (ON 1s / OFF 2s)

104

4.2 ID
IDID – DSS (Delta Solar System) RS485Wi-FiDSS – DeltaSolar APP Wi-Fi()APP
4.2.1 DSS
“RS485” ()

4-2 : DSS 105

4.2.2

“Auto ID

“Scan”

4-3 : 106

4.2.3 ID
IDID ID”Set ID”

4-4 : ID 107

4.2.4
“Set ”

4.2.5

4-5 :

“Sync Clock

4-6 : 108

4.3 Delta
Delta : DSS (Delta Solar System Software) APP(MyDeltasSolar)

Active power control

Q(U) control (volt-var control)

P-F control (watt-frequecy control)

Q by night(Q setting 24/7)

P(U) control (volt-watt control)

Anti-PID

Fixed cos Fixed Q(%)

Dry contact ARC fault detection

Auto ID

Wi-fi

DSS : https://mydeltasolar.deltaww.com/manual/eng/SUB_1G/DSS.pdf

APP (DeltaSolar) : https://mydeltasolar.deltaww.com/index.php?p=manual

109

5

!!
– LED
5.1

5.1.1
!
– – 1. ( 5-1) 2. ( 5-1) 3. ( 5-2)

5-1 : 110

5-2 :

5.1.2


– IP66

1. 2. 3. 4. (2-1 9) 5. 6.

()

111

5.2 (SPD)
M30A_230

AC SPD

DC SPD

5-3 :

5-4 : APPDSSW18- AC Surge W17- DC Surge
112

5.2.1 AC SPD
1. LED 2. 5.1.1 3. 4. 3AC SPD 5. AC SPD0.8 Nm3 6. 0.8 Nm 7. 5.1.2

  • : 0.8 Nhm

  • : 0.8 Nhm
    5-5 : AC SPD 113

  • : 0.8 Nhm
    5-6 : AC SPD
    114

5.2.2 DC SPD
1. LED 2. 5.1.1 3. 5-7 4. 3DC SPD 5. DC SPD0.8 Nm3 6. 7. 5.1.2

  • : 0.8 Nhm

5-7 : DC SPD 115

  • : 0.8 Nhm

5-8 : DC SPD
5.3

H4+

H4-

XX: Fuse rating 20A / 25A / 30A 116

5.4
1. LED 2. 5.1.1 3. DC SPD 4. 5. 6. 7. 5-10 8. 5.1.2
FAN 2

FAN 1

DC SPD

5-9 : 117

FAN 1

  • : 0.8 Nhm FAN 2

  • : 0.6 Nhm

  • : 0.8 Nhm

  • : 0.6 Nhm

5-10 :

118

5.5
:!!

: !
– –
: !
– 42
– AC – DC – H4H4 – Wi-Fi RS-485 1. 2. 3.
119

6
(6-1~6-4)

6.1 ()

6-1A: ()

AC Freq High (E01)
AC Freq Low (E02)

1. 2.

Island (E03,E04,E05)

AC

AC phase jump (E06)

Grid Quality

(E07)

AC phase abnormal
(E08)
No Grid (E09)

AC 1. AC 2. AC

AC 1. AC 2. AC

AC Volt Low (E10)
AC Volt High (E11)

1. 2. 3. AC 1. 2.

1. 2. 3. AC

EPO (E25)

EPO

DC Volt High (E30)

1000Vdc

Insulation Fault (E34)

solar arrayVoc1000Vdc 1. 2. 3.

Remote OFF (E36)

Remote OFF

120

6.2 ()

6-2A: ()

DC Injection (F01,F02,F03,F04)

Temperature High

(F05)

Amb Temp Fault (F06)

Temperature Low

(F07)

Boost Temp Fault (F08)

Bidir. Temp Fault (F09)

Inveter Temp Fault (F10)

AC RLY Fault (F13)

1. 2.

FW Unmatch (F14)

AC Sensor Fault (F15)

Vdc Sensor Fault (F16)

Idc Sensor Fault (F17)

AC Sensor Fault (F18)

Idc Sensor Fault (F19)

Red COMM Fault (F22)

DSP COMM Fault (F23)

1. (W08) 2. 1. (W08) 2. 1. (W08) 2.

121

6-2B: ()

Ground Cur. High
(F24)

Iac Unbalance 1.

(F26)

RCMU Fault (F27)

RCMU

AC RLY Short (F28)

AC

AC RLY Open (F29)

AC

Bus Unbalance (F30)

Bus Voltage High (F31, F32, F33, Bus
F34, F35)

AC Current High (F36,F37,F38,
F39,F40,F41)

AC CT Fault (F42)

R

AC CT Fault (F43)

S

AC CT Fault (F44)

T

AC Current High (F45)

ZC Circut Fault (F50)

Inv Circut Fault (F51)

Boost Circuit Fault (F52)

Arc Circut Fault 1.

(F58)

Arc Fault (F59)

1. 2. AC DC 1. DC 2. , Voc
1000Vdc (E30)
DC 1. 2. DSSARC
3.

122

6-2C: ()

DC Current High (F60,F61,F70,F71)

DC

Ext COMM. Fault (F74)

1. 2.

6.3 ()

De-rating (W07)
String fault (W08)
String Current Low (W23)

6-3A: ()

1. 2. 3. P-F 4. P(V) 5. 6. 7. 8.
1. 2. 3.
DC

1. 2. 3. 4. 5-1. 5-2. 6. PV panel 7. PV panel 8.
1. 2. PV panel 3. 4.
1. 2.

6.4 ()

Fan Fail (W11)

6-4A: ()

1. 2. 3.

DC SPD Fault (W17)
AC SPD Fault (W18)
Boost Circuit Fault (W30)

DC/AC SPD

1. DC/AC SPD 2. DC/AC SPD

123

7

Model
MPP @ AC400V MPP
() T.H.D *2 (rms) (peak)

7-1A: M30A_230 1100 V *1

M30A_230 (Korea) 1000 V

200 – 1000 V

480 – 900 V

480 – 800 V

250 V

600 V

Each MPPT: 30 A, Total: 72 A

Each MPPT: 20.4 kW

50 A per MPPT

3

2 strings / MPPT, Amphenol H4 Connector

Type II SPD 33 kVA

30 kW @ 40°C ; 33 kW @ 35°C

50 A

220 / 380V, 230 / 400V (3Ø3W or 3Ø4W) 80% to 130% of Nominal AC Voltage

50 / 60Hz ± 5Hz

0.8 ind – 0.8 cap

Type II SPD

< 3%

< 2 W 110 A / 50 s
60 A

116 A

1 1100 Vdc (1000 Vdc) 2

124

Model

(W x H x D)

7-1B: M30A_230

98.6 %

M30A_230 (Korea)

98.2 %

RS-485 / Wi-Fi

IEC 62109-1/-2 IEC 62920 CNS 15382
CNS 15426-1/-2 VDE-AR-N 4105 VDE-AR-N 4110 EN/IEC 61000-6-1/-2 EN/IEC 61000-6-3/-4 AS4777.2 : 2020

KN 62920 KS C 8567 KS C 8565

-25 to +60°C (Derating Above 40°C)

IP66

< 4000 m

45.9 dBA @1m, Amb 25°C 651 x 520 x 220 mm 42 kg
0%-100% non-condensing II
AC Output: III, DC Input: II 0 No

125

(%) 100 % 99 % 98 % 97 % 96% 95% 94% 93% 92% 91% 90%
0%

230Vac / 400 Vac

480 V 600 V 800 V

20%

40%

60%

(%)

7-1:

Pn=30kW

80%

100%

126

P/Pn(%)
110 % 100 % 90 % 80 % 70 % 60 % 50 %
0

230 Vac / 400 Vac PF=1

480V 600V 800V 900V

10

20

30

40

(°C)

7-2: (PF=1)

P/Pn(%)
110 % 100 % 90 % 80 % 70 % 60 % 50 %
0

230 Vac / 400 Vac PF=0.9

480V 600V 800V 900V

10

20

30

40

(°C)

7-3: (PF=0.9)

127

Pn=30kW

50

60

Pn=30kW

50

60

P/Pn(%)
120 %

230 Vac / 400 Vac PF=1

Pn=30kW

100 %

80 %

60 %

40 %
20 %
0% 200

35 C 40 C 50 C 60 C

300

400

500

600

700

800

(V)

7-4:

900

1000

128

:

-1: -1

NO

1

Wi-Fi

2

8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm)

129

H4CFC4D-MS
H4CMC4D-MS

NO

1

2

2

2

3

1

4

1

5

H4

-2: -2 8.0 kgf-cm (0.8Nhm) 6.0 kgf-cm (0.6Nhm) 8.0 kgf-cm (0.8Nhm) 6.0 kgf-cm (0.6Nhm) –
130

12/10 AWG (4/6mm²)

NO 1 2 3 4 5 AC

-3: -3

8.0 kgf-cm (0.8Nhm)

8.0 kgf-cm (0.8Nhm)

8.0 kgf-cm (0.8Nhm)

20 AWG (0.5mm²)

25.5 kgf-cm (2.5Nhm)

6 AWG (13.3 mm²)~4 AWG (25 mm²)

131

Version 07240426

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Delta User Manuals

Related Manuals