DELTA M30A_230 Grid tie Transformerless Solar Inverter Instruction Manual
- June 25, 2024
- Delta
Table of Contents
DELTA M30A_230 Grid tie Transformerless Solar Inverter
Specifications
- Product Name: M30A_230 Grid-tie Transformerless Solar Inverter
- Phase: Three-phase
- Input Voltage: Direct current from PV array
- Output: Grid-compliant three-phase current
- Features: 3 Maximum Power Point (MPP) tracking inputs
- Compatibility: PV modules with coupling capacity not exceeding 10F
Product Usage Instructions:
1. Safety Information
1.1 Information of the Inverter:
The M30A_230 inverter is designed for installation, commissioning, operation, and maintenance by well-trained technicians. The technician must have basic and advanced skills for handling the inverter.
1.2 General Safety:
- IMPORTANT SAFETY INSTRUCTIONS: Please read and save these instructions for future use.
- ATTENTION: NO GALVANIC ISOLATION – Do not operate with grounding PV modules.
2. Conditions of Use
The M30A_230 is a transformerless solar inverter with 3 MPP tracking inputs. Ensure PV modules used are compatible and have a coupling capacity not exceeding 10F. Operate only in approved countries by DELTA and the grid operator.
3. Symbols
The manual contains various symbols indicating different levels of warnings and information. Follow all safety instructions to prevent hazards.
4. Introduction
The M30A_230 is designed for high efficiency and long operating life using advanced technology. It is suitable for outdoor use.
FAQs
- Q: Can I connect the L1, L2, L3, and N terminals to ground?
- A: No, it is prohibited to connect the L1, L2, L3, and N terminals to ground as the inverter does not have galvanic isolation.
- Q: What should I do if I encounter a warning symbol while using the inverter?
- A: If you encounter any warning symbol, refer to the manual for detailed instructions on how to proceed safely and prevent any hazards.
The power behind competitiveness
Grid-tie Transformerless Solar Inverter
M30A_230 Operation and Installation Manual
English
1
67
Safety
1cSafety
1.1 Information of the Inverter
1.1.1 Legal Provisions
Copyright DELTA ELECTRONICS, INC. – All rights reserved. This manual
accompanies our product for use by the end users. The technical instructions
and illustrations contained in this manual are to be treated as confidential
and no part may be reproduced without the prior written permission of DELTA
ELECTRONICS, INC. Service engineers and end users may not divulge the
information contained herein or use this manual for purpose other than those
strictly connected with correct use of the product. All information and
specifications are subject to change without notice. DELTA ELECTRONICS, INC.
shall have no obligation to either personal injury and property damage claims
hereinafter with respect to any actions — (a) the product has been installed
and/or repaired improperly; (b) the product has been misused without following
the instructions on this user manual; (c) the product has failed due to
incorrect unpacking.
1.1.2 Target Group
This manual of the solar inverter is prepared for the use by a well-trained
technician for installing, commissioning, operation, and maintenance. The
technician must have the following basic and advanced skills:
· Knowledge of the fundamentals of electricity, wiring, electrical components
and electrical schematic symbols.
· Knowledge of how a solar inverter works and is operated. · Training in the
installation and commissioning of electrical devices and installations. ·
Training in how to deal with the dangers and risks associated with installing
and using electrical devices and installations. · Compliance with this manual
and all safety information.
8
Safety
1.2 General Safety
IMPORTANT SAFETY INSTRUCTIONS : SAVE THESE INSTRUCTIONS !
– Please read these instructions carefully and save them for later use.
To prevent personal injury and/or property damage, and also to ensure long
term operation of the solar inverter, it is imperative this section be read
carefully and all the safety instructions understood before using this
inverter. This user manual provides important instructions for DELTA grid-tie
transformerless solar inverter. The product is designed, tested, verified, and
certified according to international safety requirements, certifications, and
standards but precautions must be observed when installing and operating the
product. This product is suitable for indoor and outdoor use.
ATTENTION : NO GALVANIC ISOLATION
– The inverter is not equipped with a transformer and has no galvanic
isolation. – Do not operate with grounding PV modules. – It is prohibited to
connect L1, L2, L3 and N terminal to ground.
1.2.1 Condition of Use
– The M30A_230 is a transformerless solar inverter with 3 MPP tracking inputs,
which converts the direct current from the PV array into grid-compliant three-
phase current and feeds it into the utility grid.
– The photovoltaic modules used must be compatible with the inverter. PV
modules with a high capacitance to ground must only be utilized if the
coupling capacity does not exceed 10F.
– The inverter must only be operated in countries for which it is approved by
DELTA and the grid operator.
9
Safety
1.2.2 Symbols
This section describes the definition of the symbols in this manual. In order
to prevent both personal injury and property damage, and to ensure long-term
operation of the product, please read this section carefully and follow all
the safety instructions while you use the product.
DANGER!
– This warning indicates an immediate hazard which will lead to death or
serious injury.
WARNING !
– This warning indicates a possible hazard which may lead to death or serious
injury.
CAUTION !
– This warning indicates a possible hazard which may lead to minor injury.
ATTENTION
– This warning indicates a condition of potential damage to property and/or
the environment.
10
Safety
INFORMATION
– An exclamation mark enclosed in a double circle indicates additional
important information is contained in the following section and the user
should follow the instructions to prevent any hazards.
DANGER : ELECTRICAL HAZARD!!
– This warning indicates an immediate electrical hazard that unheeded can lead
to death or serious injury.
CAUTION : HOT SURFACES, DO NOT TOUCH!
– This warning indicates a potential burn hazard. – Use care when touching
surfaces when operating the product. – Do not perform any task until the
product cools down sufficiently.
– This icon indicates that a prescribed time delay must elapse before engaging
in an indicated action.
– Patientez le délai requis avant d’entreprendre l’action indiquée.
– This symbol indicates the location of an equipment grounding conductor (EGC)
terminal.
11
Introduction
2cIntroduction
M30A_230 is designed to enable the highest levels of efficiency and provide
longest operating life of transformerless three-phase PV inverter by state-of-
the-art high-frequency and low EMI technology. It is suitable for outdoor use.
ATTENTION : NO GALVANIC ISOLATION
– The inverter is not equipped with a transformer and has no galvanic
isolation. – Do not operate with grounding PV modules. – It is prohibited to
connect L1, L2, L3 and N terminal to ground.
2.1 Valid Model
The user manual is valid for the following device types: · M30A_230 This user
manual must be followed during installation, operation, and maintenance. DELTA
reserves the right to make modifications to the content and technical data in
this user manual without prior notice.
12
2.2 Product Overview
The components are shown as Figure 2-1.
Introduction
Figure 2-1: Components
Object 1 Delta Solar Inverter
2 Mounting Bracket
3
User Manual
4
AC Plug
5
H4 Connector
6
H4 Wrench
7
Hexagon Driver
(Installed on latch lock cover)
8
Wi-Fi Antenna
9
Security Seal
Table 2-1: Packing list
M30A_230
Qty
Description
1 pc
Solar inverter
1 pc
Wall mounting bracket (Material: Aluminum/Thickness: 3mm)
Important instructions for solar inverter.
1 pc
Safety instructions should be followed
during installation and maintenance.
1 set
Connector for AC connection
6 pairs DC String inputs
2 pcs To disconnect H4 connector
1 pc
To unscrew the latch lock cover and secure the door from closing.
1 pc
Antenna for Wi-Fi
6 pcs Tamper stickers for Taiwan use only
13
Introduction
Figure 2-2: Overview
Table 2-2: Overview description
NO. Component 1 Toggle Latch 4 Reserved* 7 Cable gland for RS-485
NO. Component 2 LED 5 Cable gland for AC output 8 DC input (H4) x 6 strings
NO. Component 3 DC Switch 6 Wi-Fi Antenna port
*Always keep nut and screws properly tightened on the case. Water leakage may cause serious damage.
14
Figure 2-3 below, shows the certification and rating label. Table 2-3 defines the symbol markings on this label.
Introduction
Figure 2-3: Rating label
Table 2-3: Rating label explanation
Symbol
Definition
60 seconds
Danger to life through electric shock Potentially fatal voltage is applied to the inverter during operation. This voltage persists even 60 seconds after disconnection of the power supply. Never open the inverter. The inverter contains no components that must be maintained or repaired by the operatoror installer. Opening the housing will void the warranty.
Beware of hot surface. This inverter can get hot during operation.
Before working with the inverter, you must read the supplied manual and follow the instructions contained therein.
This inverter is not separated from the grid with a transformer.
The housing of the inverter must be grounded if this is required by local
regulations.
WEEE marking
The inverter must not be disposed of as standard household waste, but in
accordance with the applicable electronic waste disposal regulations of your
country or region.
15
Installation
3 Installation
WARNING !
– Do not install the unit near or on flammable surfaces. – Please mount the
unit tightly on a solid / smooth surface.
CAUTION !
– High temperature may result in derated power output, the unit should not be
installed in direct sunlight.
– Risk of injury when lifting the inverter or if it is dropped.
CAUTION !
The product supports wireless communication. – Install the product as far away
as possible from devices that emit strong radio
waves, such as civil band radio equipment. – Do not install the product in
metal box and make sure there is no metal barrier
between the product and connecting devices to prevent the communication signal
attenuation. – When using Wi-Fi to connect the inverter, the connection signal
strength is recommended to be at least -70 dBm to ensure good communication
quality. The chapter contains instructions for (1) Vertical wall mount (2)
Electrical installation (3) Communication setup
16
Installation
3.1 Unboxing & Review
The unpacking procedure is shown as Figure 3-1. The position of hook
attachment for crane transporting is shown as Figure 3-2.
Figure 3-1: Steps to unpacke the inverter 17
Installation
Hoisting Hook
Figure 3-2: Attaching the Hoisting hooks
651 mm
220 mm
556 mm 520 mm 490 mm
Figure 3-3: Inverter dimensions 18
Installation
3.2 Vertical wall mount
Refer to Figures 3-4 to Figure 3-7.
1. Ensure the surface to which the unit is to be mounted is sufficiently
strong enough to carry the weight of inverter.
2. Orient the wall bracket (Figure 3-4) horizontally (perpendicular to the
floor). 3. Secure the mounting bracket on the wall with 12 M6 screws. 4. Hang
the inverter on the wall mounting bracket. 5. Secure the inverter by 2 M5
screws on the position* shown as Figure 3-5.
- These are also grounding points for equipment grounding. (To ground the inverter, please refer to Section 3.5)
CAUTION !
– The mounting bracket provided with the unit is specially designed and is the only certified mounting device for mounting the inverter.
– Secure the mounting bracket on the wall with at least 6 M6 screws. – Failure to comply with following mounting instructions including permitted
orientations and designated clearances may result in derated power output and may void the warranty.
CAUTION !
To avoid malfunction of inverter caused by extreme weather (ex: snow,
hail…etc) or non-proper installation/ maintenance, an additional protection
cover is strongly recommended to be installed by DELTA. For more details,
please contact local service team.
Protection cover
19
Installation unit: mm
460
400
30
6.5
82
82
82
82
82 25
410.6 17 27 31
500 Figure 3-4: Mounting bracket dimensions Positions for least amount of mounting bracket screws
8.5 5.5
or
-
Screw: M6
-
Screw: M5
Figure 3-5Positions of mounting screws 20
300mm
200mm >300mm
Installation >200mm
300mm
500mm *
500mm *
- Make sure it is high enough to have sufficient space for wiring. Figure 3-6: Separation distance of plural inverters
90 Figure 3-7: Permitted and prohibited mounting positions
21
Installation
3.3 Electrical Installation for AC Wiring
DANGER : ELECTRICAL HAZARD!!
– To avoid shock hazard during wiring, ensure any live grid connections are
removed from the inverter.
WARNING !
– Code compliance is the installer’s responsibility.
CAUTION : INVERTER AND EQUIPMENT DAMAGE MAY OCCUR !
– Installation for AC plug must meet the local electrical code. – Failed to
follow the instructions may damage AC cable. – If there is any conflict
between installation instruction and electrical code,
please follow the electrical code.
ATTENTION
– The inverter may be damaged due to dust intrusion. – Please do not open the
lid of the inverter.
22
Installation
3.3.1 AC Grid Types and Connections
ATTENTION
The default AC Grid connection is 3Ø-4W. It can also connect 3Ø-3W without Neutral (N). The inverter will operate from the following grid connections without need of an external transformer:
TNC system 220/380V, 230/400V
L1 L2 L3 PE/N
M30A_230
TNC-S system 220/380V, 230/400V
L1 L2 L3 N PE
M30A_230
TNS system 220/380V, 230/400V
L1 L2 L3 N PE
M30A_230
TT system 220/380V, 230/400V
L1 L2 L3 N
M30A_230
IT system 220/380V, 230/400V
L1 L2 L3
M30A_230
3.3.2 Required Protective Devices
It is recommended to install an upstream AC line disconnection and over
current protection device. Please refer to your local rules for the required
product.
The inverter integrates Residual Current Monitoring Unit (RCMU) for the
detection of residual current and does not require an external residual-
current protective device. However, if an external RCD is required by
installation standard, a RCB/ RCBO of type A or B with rating 300mA should be
used.
23
Installation
3.3.3 AC Wiring Preparation
The AC wires must be jacketed and meet the specifications in Table 3-1. If
there is any conflict with local electrical code, please follow the electrical
code.
Table 3-1: AC wires requirement
Size of each wire
Cable diameter Recommended Torque
13.3~25 mm² (6~4 AWG)
20~26 mm
2.0~4.0 Nhm
Follow the steps below to strip the wires before assembling the AC plug: · Strip the outer jacket from the cable for 70mm. · Strip 22 ± 2mm of insulation from all wires ends.
70 mm (MAX) 22±2 mm
PE N L1 L2 L3
Outer Jacket
Figure 3-8 : Strip the wires
CAUTIONMachine and equipment damage may occur.
– Make sure to choose proper size for AC cable. – Failed to follow these
instructions may cause AC plug damage. – If there is any conflict between
installation instruction and electrical code,
please follow the electrical code.
24
Installation
3.3.4 AC Wiring
1. The packing has a AC Plug (item 4, Table 2-1) please rotate it to release
part A & B shown as Figure 3-9.
2. Insert the cable into Part A (AC gland), and fix the internal wires
(tighten by 4.0mm wrench with 2.0~4.0 Nm torque) into Part B . (Figure 3-11)
3. Rotate part A & B as Figure 3-12 to fit and fix it onto the inverter.
B
A
Figure 3-9 : Assemble the AC plug
140 (REF)
F
32.2 ± 0.8
Part A D1
Cable range: 20~26 mm
Cable range
D1
20 ~ 26 mm
Part A fastening torque 3 ~ 5 Nm
Part B fastening torque 1.5 ~ 1.7 Nm
- The connector is not designed for solid wire but only for stranded wires with end sleeves. * The terminal gets a silver surface treatment.
Figure 3-10 : The rubber rings of AC gland
25
Installation
B
A
Part B 13.3~25 mm² (6~4 AWG) Tightening torque: M8/ 2~4 Nhm
For 3P4W Power system :
There are 5 wires that include (L1L2L3N) + PE
L2
L3
L1
N
PE
For 3P3W Power system :
There are 4 wires that include (L1L2L3) + PE
L2
L3
L1 PE
Figure 3-11 : AC wiring
B
A
Figure 3-12 : Rotate the AC plug to fit
26
Installation
3.4 Electrical Installation for DC Wiring
DANGER : ELECTRICAL HAZARD!!
– PV arrays convert sunlight into electric power with high DC voltage and high
DC current which can cause dangerous electrical shock! – Use opaque material
to cover the PV arrays before wiring or cabling. – Ensure the correct
polarities are connected when DC cabling is applied. – The amount of PV module
of each string within one MPPT should be the same to avoid the circulating
current between the strings.
WARNING !
– The inverter may overheat and catch fire under fault conditions. – Only PV
modules that are listed with system voltage under 1100V are permitted
for use. – Make sure the DC switch is in the “OFF” position, and disconnect
the PV array
before plug in/out the DC connectors. – Inverter warranty void if the DC input
voltage exceeds 1100 Vdc.
ATTENTION
– The PV Array current carrying conductors (positive or negative) must not be
referenced to ground.
– Before plug in the DC connectors, please notice the polar of connectors.
Reverse positive and negative voltage will make damage.
– Do not remove the waterproof plug for unused DC strings.
ATTENTION
– According to different local regulations, if the external string fuse is
required, please contact Delta dealers.
H4+
H4-
XX: Fuse rating 20A / 25A / 30A 27
Installation
Please read the following instructions for connecting DC connector : · Ensure
the DC conductors used are Cu and sized to the correct ampacity per
NEC or other local code · Strip off all wires for 6.5~7.5 mm. · The cross-
sectional area for each DC conductor is 12~10 AWG (4~6 mm²). · Choose the DC
string wire size based on NEC requirements or other local code.
M30A_230 uses H4 type connectors mounted on the bulkhead to connect the string
to the inverter. Mating connectors (See Figure 3-13) are provided within the
packing.
6.5 d7.5 mm
H4CFC4D-MS
H4CMC4D-MS
“CLICK”
Figure 3-13: DC wiring illustration
The polarities of DC wiring are divided into positive and negative, layout of the connectors is shown as Figure 3-14.
28
Installation
Figure 3-14: Location of H4 connectors to connect array wiring (DC)
ATTENTION
– For unused DC connectors, please keep the cap on to prevent water or dirt
intrusion.
29
Installation
3.5 Equipment Grounding
To ground the inverter, please crimp the grounding wire to ring terminal lug
and fix it on the grounding point shown as Figure 3-15.
A
A
B
B
- A- Screw: M6 / Torque: 3.9 Nhm B- Screw: M5
Figure 3-15: Mount the equipment grounding
30
Installation
3.6 Communication Module Connections
The communication module of M30A_230 is shown in Figure 3-16. It provides
VCC(12V), RS-485, dry contact, EPO, and digital input terminals for various
applications, and it can be extended to ability to use Sub_1G.
V1 x1 & EPO x1 VCC & RS-485 Digital Inputs x6
+ 12V
1
Terminal Resistor
Dry Contact
Rapid Shutdown System Connection (optional)
Figure 3-16: Communication module layout
31
Installation
3.6.1 Accessing the Communication Module
The communication module consists of an assembly with a PCB and a plastic
carrier. It is located in slot through the bottom of the chassis. It can be
accessed from the chassis bottom outside. The carrier is fixed to the chassis
by two self-retaining screws. See Figure 3-17. Loose the self-retaining screws
from the chassis, and gently pull the carrier straight out of the chassis to
withdrawthe communication module. After passing the required signal cable
through the wiring gland provided or a connected conduit and making the
electrical connections as shown in the following sections, the module can be
reinstalled in the opposite direction described above.
- Screw torque: 0.8 Nhm
7.2mm* 10mm
7.2mm 10mm Remove the rubber stopper in the 7.2 mm hole can extend it to 8.7
mm for use.
Figure 3-17: Location and access to communication module
ATTENTION
This inverter is compliant with the “Technical Specification for Security
Inspection of Solar Inverter and Monitoring Units” required by BSMI. After
completing the communication wiring, please apply a brand new one-time-use
security seal (item 9, Table2-1) on the carrier. We will not be liable or
responsible for any security incident caused by an improper application of the
sticker.
security seal
32
Installation
3.6.2 RS-485 Connection
The pin definition for the RS-485 terminal block is shown in Table 3-2. – Pins
1 and 2 provide a 12VDC bus for use with accessories.
(If use of the 12VDC bus is necessary, please set switch 1 to the ON
position.) – Pins 3 and 5 are both connected to the DATA+ input. – Pins 4 and
6 are both connected to the DATA – input. These connections allow easy daisy-
chaining of multiple inverters. A 120ohm bus termination resistor and
associated control switch are located on the communication board. The switch
function is as shown in Table 3-3. Different RS-485 connection scenarios
require different set up for the 120ohm bus termination resistor. · When
multiple inverters are cascaded (i.e., “daisy-chained”), only the last
inverter
in the chain must have its bus termination resistor switched ON.(Figure 3-18)
· If the length of any RS-485 bus is greater than 610m, it is recommended to
use
Belden 3105A cable (or equivalent cable) to ensure communication quality.
ATTENTION
– It is recommended to use twisted-pair as a communication cable for well
transmission quality.
Table 3-2: RS-485 Terminal block wiring
Pin
Function
1
VCC (+12V)
123456
2 GND (It is NOT the PE)
3
DATA+
4
DATA-
5
DATA+
6
DATA-
VCC GND D+ D- D+ D-
INFORMATION
When the RS-485 cable needs to be grounded, please follow the steps below.
1. strip a wire from the shielding layer and properly insulate it
2. crimp the insulated wire to the Y-type lug and fix it in position A
shielding layer
SNYBL1-4
A
strip from shielding layer (cross-section: 0.5~1.5 mm²)
Insulation Tape 33
- Screw torque: 0.8 Nhm
Installation
Terminal Resistor
120(1/2W) DATA+ to DATA-
RS485/USB or
RS485/RS232
Figure 3-18: Multiinverter connection illustration
Table 3-3: Bus Termination switch settings
Switch 1
ON
Terminal Resistor ON
OFF
Terminal Resistor OFF
34
Installation
3.6.3 EPO Function & Digital Input
The communication Module has an emergency power off function (EPO). Users can
customize EPO function in APP or Delta Solar System (DSS).
COMM. card
V1 K0 K1 K2 K3 K4 K5 K6
Figure 3-19: EPO and digital input function terminal block
Once enabled, the EPO function can be used to turn off the inverter through
the relayless contacts connected to terminals [V1 & K0]. A digital power
reduction control function is provided, which can be set to limit the
available active output power of the inverter. The control settings for this
function are made by placing a hardware short circuit (jumper or relay)
between the two terminals of the terminal block shown in Table 3-4. For
Australia and Newzealand, please refer to Table 3-5.
Table 3-4: Definition of digital input & EPO function
Short terminals Inverter’s action
V1 & K0
Emergency power off (EPO)
V1 & K1
0% active power
V1 & K2
Maximum 30% rated power
V1 & K3
Maximum 60% rated power
V1 & K4
Maximum 100% rated power
V1 & K5
Reserved
V1 & K6
Reserved
Short V1 & K1 V1 & K2 V1 & K3 V1 & K4 V1 & EPO
Tabel 3-5: Definition of DRMs for Australia and New Zealand
Inverter’s action DRM5 (0% active power) DRM6 (Maximum 50% active power) DRM7
(Maximum 75% active power and sink reactive power) DRM8 (Maximum 100% active
power and sink reactive power) DRM0 (Emergency power off)
35
Installation
3.6.4 Dry Contact Connection
M30A_230 provides 1 set of dry contacts, which can be used to control external
devices according to the operating status of the inverter. The terminal block
for this function is shown in Figure 3-20. The terminals marked in the figure
identify the dry contact connection. The dry contacts operation are usually
open. User can customize the function of this contact through the the APP or
DSS.
COMM. card
Figure 3-20: Dry Contact connection
3.6.5 Rapid shutdown system connection (optional)
M30A_230 provides a terminal to control the rapid shutdown system. This
terminal provides a 12 VDC, Max.1 A power in normal condition, but the power
will turn-off in 2 seconds when the AC grid outage. The terminal block for
this function is shown in Figure 3-21. 1. 22~12 AWG solid or stranded wire is
available for the terminal hole and wire
length is limited to 10 M. 2. Stripping length is 6 ~ 7 mm.
COMM. card
DC+ 12V GND
Figure 3-21: Rapid Shutdown System connection
36
Installation
3.7 Wi-Fi
The communication module supports the inverter to communicate with devices
(such as smartphones, tablets, etc.) via Wi-Fi (base WPA2-PSK). User can
restart the function through the APP or DSS. There is an antenna for Wi-Fi in
the package (item 8,Table 2-1), which must be mounted on the plastic carrier
as the procedure below. 1. Remove the protective nut. 2. Tighten the antenna.
Figure 3-22: Installation of Wi-Fi antenna
ATTENTION
– Please properly install the antenna as shown below to keep communication
quality and avoid equipment damage.
– More detail for Wi-Fi connection and APP :
https://mydeltasolar.deltaww.com/index.php?p=manual
– To establish a successful communication between Inverter Wi-Fi to
MyDeltaSolar Cloud, in the Wi-Fi connection setup page, the signal strength
must be above -70dBm between each Wi-Fi device (Wi-Fi router, inverter,
DC1…etc.). In case the signal strength is below -70dbm, it may cause certain
communication errors which may prevent a successful Wi-Fi communication. To
avoid such issues, please adjust the Wi-Fi device position to improve the
signal strength/quality.
37
Commissioning
4 Commissioning
CAUTION : HOT SURFACES, DO NOT TOUCH!
– Use care to avoid hot surfaces when operating the product! – Do not perform
any task until the unit cools down or wear appropriate personal
protective equipment.
4.1 LED Signals
M30A_230 with 3 LEDs can visually display the status of the inverter, as shown
in Figure 4-1. Table 4-1, 4-2 provide the information of LED indicators.
LED Indicator LED Indicator LED Indicator
(GRN)
(RED/YEL)
(GRN)
Figure 4-1: LED indicators
Condition Countdown
On Grid Inverter Fault / Remote off
Inverter Warning Field Fault
Field Warning NO DC
FW Upgrade Standby
Check PV Power System Lock
*FLASH: ON 1s / OFF 1s FLASH FAST: ON 0.25s / OFF 0.25s FLASH SLOW: ON 5s / OFF 10s
Table 4-1: Inverter status Grid (Green) FLASH ON OFF ON (or OFF) OFF ON OFF FLASH FLASH FLASH FAST OFF
Alarm (Red/Yellow) OFF / OFF OFF / OFF ON / OFF
FLASH / OFF OFF / ON
OFF / FLASH OFF / FLASH SLOW
FLASH / OFF OFF / FLASH OFF / FLASH FAST FLASH / FLASH
Table 4-2: Wireless communication status
Connection Status
COMM. (Green)
Offline
OFF
Wi-Fi
FLASH (ON 1s / OFF 2s)
38
Commissioning
4.2 Auto ID Commission
The Auto ID function can set all inverter IDs at once by DSS (Delta Solar
System) or DeltaSolar APP. – DSS Connect the inverter through RS-485 or Wi-Fi
with computer. – APP Connect the inverter through Wi-Fi with mobile device.
(please refer to chapter 4.3 for operation manual.)
4.2.1 Commission Setting (DSS)
Select the corresponding model Select RS485 or Wi-Fi to connect the computer
and inverter If use RS485, select communication port (automatic detection by
the system) Click
Figure 4-2: DSS Commission setting 39
Commissioning
4.2.2 Scan inverter
Click “Auto ID
”
Enter numbers of inverters.
Click “Scan”.
Figure 4-3: Steps of scanning inverters 40
Commissioning
4.2.3 Set ID
The serial number of the successfully scanned device will be displayed below,
the default ID can be changed.
After ID setting is completed, click “Set ID”.
Figure 4-4: Steps of ID setting
41
Commissioning
4.2.4 Set Country
Click to select the country of inverter. (For compliance with AS/NZS
4777.2:2020, please select from Region Australia A/B/C and NZ.) Click “Set”.
Figure 4-5: Steps of country setting
4.2.5 Synchronize time
Click “Sync Clock
” to Synchronize time.
Figure 4-6: Steps of time synchronization 42
Commissioning
4.3 Delta Function Setting
Delta offers two setting tools: DSS (Delta Solar System Software) and APP
(DeltaSolar)
Function
Active power control
Q(U) control (volt-var control)
P-F control (watt-frequecy control)
Q by night(Q setting 24/7)
P(U) control (volt-watt control)
Anti-PID
Fixed cos
Dry contact
Fixed Q(%)
ARC fault detection
Auto ID
Wi-fi
Please refer to the following link for operation manual.
DSS Operation Manual:
https://mydeltasolar.deltaww.com/manual/eng/SUB_1G/DSS.pdf DeltaSolar (APP) Operation and Installation Manual:
https://mydeltasolar.deltaww.com/index.php?p=manual
43
Maintenance
5cMaintenance
Regular maintenance can ensure that the inverter maintains great performance.
DELTA recommends that the unit should be inspected at least every 6 months.
The maintenance frequency should be adjustable, depending on the sit
environment, different seasons and weather effects.
DANGER : ELECTRICAL HAZARD!!
– Make sure that both AC breaker and DC switch are turned off and the LED
indicators are off to avoid the risk of electric shock!
5.1 Open and Close the Door
In order to ensure the normal long-term operation of the inverter, the
M30A_230 door must be opened and closed according to the following step.
5.1.1 Open Door
WARNING ! – Do not attempt to open the door under raining condition. – Before
opening the front door, please wipe the inverter case if it is wet to
avoid water seepage. 1. Loosen the screws on both latch covers with hexagon
wrench attached on the
latch cover. (Figure 5-1) 2. Open the latch covers and release latches to open
the door. (Figure 5-1) 3. Use the hexagon wrench to secure the door from
closing. (Figure 5-2)
Figure 5-1: Open and close the door
44
Maintenance
Figure 5-2: To secure door by hexagon driver
5.1.2 Close Door
ATTENTION
– Due to corrosion of live parts, excessive moisture or dust in the inverter
may cause accidental damage. Ensuring that the inner of the inverter is clean
free from unreasonable pollution is important for long service operating
systems.
– After cabling or maintenance for the inverter, please lock both toggle latch
to make sure the inverter will remain IP66 protection.
1. Ensure that the gasket in the mounting slot and mating surface on the
enclosure are clean and in good condition.
2. Make sure all protective covers are properly installed. 3. Remove the
hexagon wrench and close the door. 4. Buckle the latch and apply a one-time-
use security seal (item 9, Table 2-1) on
the top toggle latch as the following attention. 5. Secure the latch cover
with the hexagon wrench. 6. The hexagon wrench can be fixed on the latch
cover.
ATTENTION
– This inverter is compliant with the “Technical Specification for Security
Inspection of Solar Inverter and Monitoring Units” required by BSMI. After
closing the door, please apply a security seal on the toggle latch. We will
not be liable or responsible for any security incident caused by an improper
application of the sticker.
security seal
45
Maintenance
5.2 Replacement of Surge Protection Devices (SPD)
M30A_230 has Surge Protection Devices (SPD) for AC and DC wiring, which is
located behind the protective cover and can be replaced if damaged.
AC SPD
DC SPD
Figure 5-3: Location of AC and DC SPD board
AC SPD
DC SPD
Figure 5-4: AC and DC SPD module If the warning message “AC Surge” or “DC
Surge” appears on the APP and DSS, please follow the steps below to replace
the SPD.
46
Maintenance
5.2.1 Replace AC SPD
1. Turn off the AC and DC power, and wait until the LED indicators turns off.
2. Follow Section 5.1.1 to open the door. 3. Loosen the screw and remove
protective cover. 4. Loosen 3 screws, remove wires and disconnect signal cable
to take off AC SPD. 5. Install the new AC SPD unit with procedures above in
reverse order and
tighten the screw with 0.8 Nm torque. 6. Install the protective cover and
tighten the screw with 0.8 Nm torque. 7. Follow Section 5.1.2 to close the
door.
- Screw torque: 0.8 Nhm
- Screw torque: 0.8 Nhm
Figure 5-5: Steps of changing AC SPD 47
Maintenance
- Screw torque: 0.8 Nhm
Figure 5-6: Remove wirings as connectors of AC SPD
48
Maintenance
5.2.2 Replace DC SPD
1. Turn off the AC and DC power, and wait until the LED indicators turns off.
2. Follow Section 5.1.1 to open the door. 3. Slide open the protective cover.
4. Loosen 3 screws, remove wires and disconnect signal cable to take off DC
SPD. 5. Install the new DC SPD unit with procedures above in reverse order and
tighten the screw with 0.8 Nm torque. 6. Install the protective cover
properly. 7. Follow Section 5.1.2 to close the door.
- Screw torque: 0.8 Nhm Figure 5-7: Steps of changing DC SPD 49
Maintenance
FRONT
- Screw torque: 0.8 Nhm
BACK
Figure 5-8: Remove wirings as connectors of DC SPD
5.3 External String Fuse
According to different local regulations, if the external string fuse is
required, please contact Delta dealers.
H4+
H4-
XX: Fuse rating 20A / 25A / 30A 50
Maintenance
5.4 Replacement of Internal Fan
1. Turn off the AC and DC power, and wait until the LED indicators turns off.
2. Follow Section 5.1.1 to open the door. 3. Disconnect the cable on the DC
SPD board. 4. Loosen the screws and remove the fan cabinet. 5. Loosen the
screws to lift the entire fan assembly. 6. Clean assembly or replace with a
unit. 7. Install the internal fan with procedures above in reverse order and
tighten the
screws with recommended torque in Figure 5-10. 8. Follow Section 5.1.2 to
close the door.
FAN 2
FAN 1
DC SPD
Figure 5-9: Location of internal fans and fan connectors 51
Maintenance FAN 1
-
Screw torque: 0.8 Nhm FAN 2
-
Screw torque: 0.6 Nhm
-
Screw torque: 0.8 Nhm
-
Screw torque: 0.6 Nhm
Figure 5-10: Replacement of internal fans
52
Maintenance
5.5 De-Commissioning
If it is necessary to remove the inverter from active operation for
maintenance or replacement, please follow the instructions below.
DANGER : ELECTRICAL HAZARD!!
To avoid serious injury, please follow the procedure below.
CAUTION : HOT SURFACES, DO NOT TOUCH !
– Please be careful of hot surfaces if the inverter is just shutting down. –
Not to do any maintenance until inverter is sufficiently cooled down.
CAUTION : POSSIBILE INJURY !
The inverter weighs 42 kg (92 lb). When the inverter is improperly handled or
dropped during transportation or removed from the rack, it may cause personal
injury.
– Switch off external AC circuit breaker or switch to disconnect the
electrical grid from the inverter chassis.
– Switch off the DC switch to cease inverter operation. – Use H4 wrench tool
to disconnect each string from the chassis mounted H4terminals. – Remove Wi-Fi
antenna from the bottom of the cassis.
RS-485 Communication module 1. Remove the communication module from inverter.
2. Remove all communication cables from the module terminals. 3. Reinstall the
communication board assembly in inverter.
53
Error Message and Trouble Shooting
6cError Message and Trouble Shooting
While Delta Electronics endeavors to build electronic products with high
reliability standards, there may still be situations where the inverter may
not operate properly. In this case, please follow the instructions in the
“Troubleshooting Guide” (Tables 6-1 ~ 6-4) to attempt to clear the fault. If
the problem can’t be solved, please contact customer service for technical
support.
6.1 Error Codes (Field Fault)
Table 6-1A: Error Codes (Field Fault) & Messages
Message
Description
Action
AC Freq High (E01)
Grid frequency high
AC Freq Low (E02)
Grid frequency low
1. Check the utility frequency 2. Check Grid code & Grid setting
Island (E03,E04,E05)
Islanding is detected
Check Grid breaker
AC phase jump (E06)
Phase jump of Grid voltage
If repeated occurrence, contact customer service for technical support
Grid Quality (E07)
AC phase abnormal
(E08)
Non-linear load in Grid and near to inverter
Wrong connection in AC plug
If repeated occurrence, contact customer service for technical support
Check the AC connection in accordance with the user manual
No Grid 1. AC breaker is OFF (E09) 2. Disconnect in AC plug
1. Switch on AC breaker 2. Check the connection in AC plug and
make sure it connects to inverter
AC Volt Low (E10)
AC Volt High (E11)
1. Actual utility voltage is under the UVR setting
2. Incorrect Grid Code or Grid setting 3. Wrong connections in AC plug
1. Actual utility voltage is over the OVR setting
2. Incorrect Grid Code or Grid setting
1. Check the utility voltage within the suitable range
2. Check Grid code & Grid setting 3. Check the connection in AC plug
EPO (E25)
EPO is operated by user
Release the EPO button
DC Voltage
High
Input voltage is over 1000Vdc
(E30)
Modify the solar array setting, and make the Voc less than 1000Vdc
Insulation Fault (E34)
Insulation problem of PV array to ground
1. Check if panel enclosure ground conpletely 2. Check if inverter ground conpletely 3. Check if the DC breakers get wet
Remote OFF Remote OFF by external (E36) communication
Check if remote OFF function is active
54
Error Message and Trouble Shooting
6.2 Fault Codes (Inverter Fault)
Table 6-2A: Fault Codes (inverter fault) & Messages
Message
Description
Action
DC Injection (F01,F02,F03,F04)
Utility waveform is abnormal
Contact customer service for technical support
Temperature High (F05)
The internal ambient temperature Check the installation ambient and
is over limit
environment
Amb Temp Fault Ambient temperature detection
(F06)
failure
Contact customer service for technical support
Temperature Low (F07)
The internal ambient temperature Check the installation ambient and
is under limit
environment
Boost Temp Fault (F08)
Boost module temperature detection failure
Contact customer service for technical support
Bidir. Temp Fault (F09)
Inveter Temp Fault (F10)
AC RLY Fault (F13)
The boost/bidir. NTC temperature
Inverter module temperature detection failure 1. Defective relay driver
circuit 2. Relay(s) failure
Contact customer service for technical support
Contact customer service for technical support
Contact customer service for technical support
FW Unmatch (F14)
Firmware Incompatibility
Contact customer service for technical support
AC Sensor Fault (F15)
Auxiliary power circuit failure
1. Check the polarity of PV connection (if the error code comes along with
W08)
2. Contact customer service for technical support
Vdc Sensor Fault (F16)
DSP Vdc sensor circuit defective
Contact customer service for technical support
Idc Sensor Fault (F17)
Auxiliary power circuit failure
1. Check the polarity of PV connection (if the error code comes along with
W08)
2. Contact customer service for technical support
AC Sensor Fault (F18)
Auxiliary power circuit failure
Contact customer service for technical support
Idc Sensor Fault (F19)
Auxiliary power circuit failure
Contact customer service for technical support
Red COMM Fault (F22)
The internal communication connection is disconnected
Contact customer service for technical support
55
Error Message and Trouble Shooting
Table 6-2B: Fault Codes (inverter fault) & Messages
Message
Description
Action
DSP COMM Fault The internal communication
(F23)
connection is disconnected
Check the connection interface RS-485
Ground Cur. High (F24)
Insulation problem of PV array to ground
1. Check the insulation of Solar inputs 2. Contact customer service for
technical support
Iac Unbalance (F26)
RCMU Fault (F27)
1. Power line is disconnected 2. Current feedback circuit is
defective
RCMU circuit is disconnected
Check the connection in AC plug
Contact customer service for technical support
AC RLY Short (F28)
Grid relay short
Contact customer service for technical support
AC RLY Open (F29)
Grid relay open
Contact customer service for technical support
Bus Unbalance (F30)
Voltage unbalance of DC link
Restart inverter by DC switch
Bus Voltage High (F31, F32, F33 High bus capacitor voltage F34, F35)
AC Current High (F36,F37,F38 Surge occurs during operation F39,F40,F41)
AC CT Fault (F42,43,44)
Phase R / S / T CT is defective
1.Restart inverter by DC switch 2.Check the solar array setting, and make sure
the Voc less than Max. Vdc of Inverter (if the error code comes along with
E30)
Contact customer service for technical support
Contact customer service for technical support
AC Current High (F45)
AC current over range
ZC Circuit Fault The zero crossing circuit
(F50)
is defective
Inv Circuit Fault (F51)
The inverter circuit is defective
Boost Circuit Fault (F52)
The boost circuit is defective
Arc circuit fail 1. AFCI is not installed
(F58)
2. AFCI self-test is fail
Arc fault (F59)
The inverter detects arcing occurs
Restart the inverter by DC switches
Contact customer service for technical support
Contact customer service for technical support
Contact customer service for technical support
Check the AFCI detection circuit board for making sure it is connected
correctly
1. Check if there are any cable damaged at DC side.
2. Replace DC cable and unlock the Arc fault from DSS
3. Contact customer service for technical support
56
Error Message and Trouble Shooting
Table 6-2C: Fault Codes (inverter fault) & Messages
Message
Description
Action
DC Current High (F60,F61,F70,F71)
DC current over range
Restart inverter by DC switches
Ext COMM. Fault (F74)
The external communication connection is disconnected
1. Check the connection between external unit and COMM
2. Contact customer service for tech. support
6.3 Warning Codes (Field Warning)
Table 6-3A: Warning Codes (Field warning) & Messages
Message
Description
Action
De-rating (W07)
String fault (W08)
String Current Low (W23)
1. Over temperature 2. Power Limit function 3. Power vs. Frequency function 4. P(V) function 5. Grid Voltage low 6. Solar Voltage low 7. Solar Voltage High 8. Ramp up function
1. Check the installation ambient and environment
2. Check Grid Code & Grid setting 3. Check the utility frequency on the
inverter
terminal 4. Check the utility voltage on the inverter
terminal 5-1. Check the utility voltage on the inverter
terminal 5-2. Check reactive power setting 6. Check the Solar voltage on the
inverter
terminal 7. Check the Solar voltage on the inverter
terminal 8. Check Ramp up setting
1. Polarity of DC connectors is
1. Check the polarity of PV connection
incorrect
2. Restart DC switch and AC breaker
2. String current monitoring function 3. Contact customer service for
is fail
technical support
Disconnection in DC connectors
1. Check String Connector and Fuse 2. Contact customer service for
technical support
6.4 Warning Codes (Inverter Warning)
Table 6-4A: Warning Codes (inverter warning) & Messages
Message
Description
Action
Fan Fail (W11)
1. One or more fans are locked 2. One or more fans are defective 3. One or
more fans are
disconnected
Contact customer service for technical support
DC SPD Fault AC SPD Fault (W17) (W18)
1. One or more SPD are defective 2. One or more SPD are
disconnected
1. Replace the defective SPD 2. Check the connections of SPDs
Boost Circuit Fault (W30)
The boost circuit defective
Contact customer service for technical support
6.5 Earth Fault Alarm
The inverter complies with IEC 62109. When the earth fault occurs, the Yellow
LED Alarm indicator will light up and a notification email will be sent to the
customer.
57
Technical Information
7cTechnical Information
Model Occasionally Max. Voltage
Table 7-1A: Specifications M30A_230 DC Input 1100 V *1
M30A_230 (Korea) 1000 V
Operating Voltage Range
200 – 1000 V
MPP Voltage Range @ AC400V
480 – 900 V
480 – 800 V
Start Voltage
250 V
Nominal DC Voltage
600 V
Max. Input Current
Each MPPT: 30 A, Total: 72 A
Max. Input Power
Each MPPT: 20.4 kW
Max. Allowable Array Isc
50A per MPPT
MPP Tracker
3
Connection Type
2 strings / MPPT, Amphenol H4 Connector
DC Switch
Built-in
String Monitoring
Built-in
Arc Fault Detection
Built-in
Surge Protection
Type II SPD
AC Output
Rated Output Power
30 kW
Max. Apparent Power
33 kVA
Max. Output Power
30 kW @ 40°C ; 33 kW @ 35°C
Max. Output Current
50 A
Nominal AC Voltage Operating Voltage Range
3 Ph 220 / 380, 230 / 400V Y or 80% to 130% of Nominal AC Voltage
Operating Frequency Range
50 / 60Hz ± 5Hz
Power Factor
0.8 ind – 0.8 cap (Adjustable)
Surge Protection
Type II SPD
T.H.D Night Time Consumption *2
< 3% < 2 W
Inrush Current Max. Output Fault Current (rms)
110 A / 50 s 60 A
Max. Output Over Current Protection (peak)
116 A
1 The max withstand voltage is 1100Vdc. (Inverter stops output when the PV voltage is over 1000Vdc) 2 Night time consumption with standby communication.
58
Model
Peak Efficiency Euro Efficiency
Communication Port
Grid support
Operating Temp. Range Protection Level Operating Elevation Cooling Noise
Dimension (W x H x D) Weight Relative Humidity Pollution Degree Overvoltage
Category Back-Feed Current to the Array Galvanic Isolation
Technical Information
Table 7-1B: Specifications M30A_230 Efficiency
M30A_230 (Korea)
98.6 %
Information
98.2 %
RS-485 (built-in) / Wi-Fi (built-in) / SUB_1G (optional)
Regulation
IEC 62109-1/-2 IEC 62920 CNS 15382
CNS 15426-1/-2 VDE-AR-N 4105 VDE-AR-N 4110 EN/IEC 61000-6-1/-2 EN/IEC
61000-6-3/-4 AS4777.2 : 2020
General Data
KN 62920 KS C 8567 KS C 8565
-25 to +60°C (Derating Above 40°C)
IP66
< 4000 m
Natural cooling
45.9 dBA @1m, Amb 25°C
651 x 520 x 220 mm
42 kg
0%-100% non-condensing
II
AC Output: III, DC Input: II
0
No
59
Technical Information
Efficiency(%)
100 % 99 % 98 % 97 % 96% 95% 94% 93% 92% 91% 90% 0%
Efficiency
Output voltage at 230Vac / 400Vac
Pn=30kW
480 V 600 V 800 V
20%
40%
60%
80%
Output Power (%)
Figure 7-1: Efficiency Curve
100%
60
Technical Information
P/Pn(%)
Power Derating Curve with Ambient Temprature
Output voltage at 230Vac / 400Vac PF=1
Pn=30kW
110 %
100 %
90 %
80 %
70 % 60 %
480V 600V 800V 900V
50 % 0
10
20
30
40
50
60
Ambient Temperature (°C)
Figure 7-2: Power Derating Curve with Ambient Temprature (PF=1)
P/Pn(%)
Power Derating Curve with Ambient Temprature
Output voltage at 230Vac / 400Vac PF=0.9
Pn=30kW
110 %
100 %
90 %
80 %
70 % 60 %
480V 600V 800V 900V
50 % 0
10
20
30
40
50
60
Ambient Temperature (°C)
Figure 7-3: Power Derating Curve with Ambient Temprature (PF=0.9)
61
Technical Information
P/Pn(%)
120 %
Power De-rating Curves with PV Voltage
Output voltage at 230Vac / 400Vac PF=1
Pn=30kW
100 %
80 %
60 %
40 %
20 %
0% 200
35 C 40 C 50 C 60 C
300
400
500
600
700
800
900
1000
PV Voltage (V)
Figure 7-4: Power De-rating Curves with PV Voltage
62
Appendix: Assembly Note
Technical Information
Appendix-1: Assembly Note-1
NO
Location
1
Wi-Fi module cover
2
Communication cover
Screw torque 8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm)
63
Technical Information
H4CFC4D-MS
H4CMC4D-MS
Appendix-2: Assembly Note-2
NO
Location
Screw torque
1
Internal fan 2
8.0 kgf-cm (0.8Nhm)
2
Internal fan 2 cover
6.0 kgf-cm (0.6Nhm)
3
Internal fan 1
8.0 kgf-cm (0.8Nhm)
4
Internal fan 1 cover
6.0 kgf-cm (0.6Nhm)
5
H4 wire
–
Conductor cross-section 12/10 AWG (4/6mm²)
64
Technical Information
NO Location 1 AC SPD cover 2 AC SPD board 3 DC SPD board 4 Communication port 5 AC wire
Appendix-3: Assembly Note-3
Screw torque 8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm)
Conductor cross-section –
25.5 kgf-cm (2.5Nhm)
20 AWG (0.5mm²) 6 AWG (13.3 mm²)~4 AWG (25 mm²)
65
The power behind competitiveness
M30A_230
English
1
67
www.deltaww.com
Contents
1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 74 1.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 74 1.1.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 74 1.1.2 . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 74 1.2 . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 75 1.2.1 . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 75 1.2.2 . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 76 2 . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 2.1 . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 2.2 . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 3 . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 82 3.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 83 3.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
85 3.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
88 3.3.1 AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
3.3.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
89 3.3.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 90 3.3.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 91 3.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 93 3.4.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 94 3.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 96 3.6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 97 3.6.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 98 3.6.2 RS-485 . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 99 3.6.3 EPO . . . . . . . . . . . . . . . . . . . . . . .
. . . .101 3.6.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .102 3.7 Wi-Fi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .103
69
4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 104 4.1 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 104 4.2 ID . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 105 4.2.1 DSS . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 105 4.2.2 . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 106 4.2.3 ID . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 107 4.2.4 . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 108 4.2.5 . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 108 4.3 Delta . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 109 5 . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 5.1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 5.1.1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
5.1.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 111 5.2 (SPD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
5.2.1 AC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
113 5.2.2 DC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 115 5.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 116 5.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 117 5.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 119 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 120 6.1 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 120 6.2 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
6.3 () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 6.4
() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 7 . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
124 : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 129
70
Figure
2-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
2-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
2-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
3-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
3-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
3-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
3-4: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
3-5: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
3-6: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
3-7: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
3-8: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
3-9:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
3-10: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
3-11: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
3-12: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
3-13: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
3-14: H4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
3-15: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
3-16: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
3-17: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
3-18: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
3-19: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
3-20: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
3-21: Wi-Fi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
4-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
4-2: DSS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
4-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
4-4: ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
4-5: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
4-6: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
71
5-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
110 5-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
5-3: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 5-4: . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 112 5-5: AC SPD . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 5-6: AC
SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 5-7:
DC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115 5-8: DC SPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 116 5-9: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
5-10: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
118 7-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 126 7-2: (PF=1) . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 127 7-3: (PF=0.9) . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . 127 7-4: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
72
Table
2-1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 79 2-2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 80 2-3: . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 81 3-1: . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 90 3-2: RS-485 . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 99 3-3: . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 100 3-4: EPO. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 101 4-1: LED . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 104 4-2: LED . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 6-1A: () . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 6-2A: () . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 6-2B: () . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 6-2C: () . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 6-3A: () . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 6-4A: () . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 7-1A: . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
7-1B: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 125 -1: -1 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 129 -2: -2 . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 130 -3: -3 . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 131
73
1
1.1
1.1.1
~ DELTA ELECTRONICS, INC. – All rights reserved. DELTA ELECTRONICS, INC. DELTA
ELECTRONICS, INC.
1.1.2
74
1.2
–
DELTA
– , – () – L1, L2, L3, N
1.2.1
– M30A_230 3 MPP
– – 10F – DELTA
75
1.2.2
–
–
–
–
76
–
!!
–
– –
– –
77
2
M30A_230 EMI
– , – () – L1, L2, L3, N
2.1
: · M30A_230 DELTA
78
2.2
2-1
1 DELTA
2
3
4
5
H4
6
H4
7
()
8
Wi-Fi
9
2-1 :
2-1 :
M30A_230
1
1
: / : 3mm
1
1
6
2
H4
1
1
Wi-Fi
6
79
2-2 :
2-2 :
NO.
1 4 * 7
NO.
2 LED 5 8 (H4) x 6 strings
NO.
3 6 Wi-Fi
80
2-32-3
2-3 :
2-3 :
60 seconds
60
,
, WEEE marking ,
81
3
– –
– –
Wi-Fi -70 dBm
1. 2. 3.
82
3.1
3-1 3-2
3-1: 83
3-2: 651 mm
220 mm
556 mm 520 mm 490 mm
3-3: 84
3.2
3-43-7
1. 2. ()3-4 3. 12M6(3-5) 4. 5. 2M53-5
3.5
– 6M6 – –
(, …) /,
85
unit: mm
460
400
30
6.5
82
82
82
82
82 25
410.6 17 27 31
500
3-4:
8.5 5.5
or
-
: M6
-
: M5
3-5 : 86
300mm
200mm >300mm
200mm
300mm
500mm *
500mm *
- 3-6:
90 3-7:
87
3.3
!!
–
–
– – –
– –
88
3.3.1
3Ø-4W 3Ø-3W N
TNC system 220/380V, 230/400V
L1 L2 L3 PE/N
M30A_230
TNS system 220/380V, 230/400V
L1 L2 L3 N PE M30A_230
TNC-S system 220/380V, 230/400V
L1 L2 L3 N PE M30A_230
TT system 220/380V, 230/400V
L1 L2 L3 N
M30A_230
IT system 220/380V, 230/400V
L1 L2 L3
M30A_230
3.3.2
89
3.3.3
3-1
13.3~25 mm² (6~4 AWG)
3-1: 20~26 mm
2.0~4.0 Nhm
70 mm 22±2 mm
70 mm (MAX) 22±2 mm
PE N L1 L2 L3
Outer Jacket
3-8 :
– –
90
3.3.4
1. 3-9AB 2. A()2~4 Nhm
4mmB ( 3-11) 3. AB3-12
B
A
3-9 :
140 (REF)
F
32.2 ± 0.8
Part A D1
Cable range: 20~26 mm
Cable range
D1
20 ~ 26 mm
Part A fastening torque 3 ~ 5 Nm
Part B fastening torque 1.5 ~ 1.7 Nm
3-10 :
91
B
A
Part B 13.3~25 mm² (6~4 AWG) Tightening torque: M8/ 2.0~4.0 Nhm
3P4W : (L1L2L3N) + PE
L2
L3
L1
N
PE
3P3W : (L1L2L3) + PE
L2
L3
L1 PE
3-11 :
B
A
3-12 :
92
3.4
:!!
– – – – MPPT
!
– – 1100V – “” – 1100V
– –
– DC
–
H4+
H4-
XX: Fuse rating 20A / 25A / 30A
93
3.4.1
: · NEC · 6.5-7.5mm · 12/10 AWG (4/6mm2)
3-13~3-14
M30A_230 H4 (2-1, 5)
6.5 d7.5 mm
H4CFC4D-MS H4CMC4D-MS
“CLICK” 3-13:
94
3-14 : H4
– 95
3.5
O 3-15
A
A
B
B
- A-: M6 / : 3.9 Nhm B-: M5
3-15 :
96
3.6
3-16 12VVCCRS-485EPO SUB_1G
VCC & RS-485
V1 x1 & EPO x1 x6
+ 12V
ON 11
3-16 :
()
97
3.6.1
3-17
- : 0.8 Nm
7.2mm* 10mm
7.2mm 10mm 7.2 mm 8.7 mm 3-17:
(2-1 9)
98
3.6.2 RS-485
RS-4853-2 -1212V
(12VON) -35 RS-485DATA+ -46 RS-485DATA- 120 3-3 RS-485 · 3-18 · RS-
485610mBelden 3105A
–
3-2: RS-485
Pin
Function
1
VCC (+12V)
2
GND ()
123456
3
DATA+
4
DATA-
5
DATA+
6
DATA-
VCC GND D+ D- D+ D-
RS-485 1. (: 0.5~1.5 mm²) 2. Y(: SNYBL1-4)
SNYBL1-4
A
(: 0.5~1.5 mm²)
99
- : 0.8 Nhm
120(1/2W) DATA+ to DATA-
RS485/USB or
RS485/RS232
3-18 :
3-3 :
ON
ON
1
OFF
100
3.6.3 EPO
(EPO) APPDelta Solar System (DSS)
V1 K0 K1 K2 K3 K4 K5 K6
3-19 :
V1K0EPO 3-4
3-4: EPO
V1 & K0
(EPO)
V1 & K1
0 %
V1 & K2
30 %
V1 & K3
60 %
V1 & K4
100 %
V1 & K5
V1 & K6
101
3.6.4
M30A_230 3-20 APPDSS
3-20 :
102
3.7 Wi-Fi
Wi-Fi(WPA2-PSK) APPDSSWi-Fi (8, 2-1)Wi-Fi 1. 2.
3-21 : Wi-Fi
–
– Wi-FiAPPQR-code https://mydeltasolar.deltaww.com/index.php?p=manual
– Wi-FiWi-Fi(Wi-Fi, , DC1…) -70dbm<-70dbm
103
4
– –
4.1 LED
M30A_230 3LED4-1 LED4-14-2
LED ()
LED (/)
LED ()
Countdown
On Grid Inverter Fault / Remote off
Inverter Warning Field Fault
Field Warning NO DC
FW Upgrade Standby
Check PV Power System Lock
*FLASH: ON 1s / OFF 1s FLASH FAST: ON 0.25s / OFF 0.25s FLASH SLOW: ON 5s / OFF 10s
4-1 :
4-1: LED Grid () FLASH ON OFF
ON (or OFF) OFF ON OFF
FLASH FLASH FLASH FAST
OFF
Alarm (/) OFF / OFF OFF / OFF ON / OFF
FLASH / OFF OFF / ON
OFF / FLASH OFF / FLASH SLOW
FLASH / OFF OFF / FLASH OFF / FLASH FAST FLASH / FLASH
4-2:
Offline
COMM. () OFF
Wi-Fi
FLASH (ON 1s / OFF 2s)
104
4.2 ID
IDID – DSS (Delta Solar System) RS485Wi-FiDSS – DeltaSolar APP Wi-Fi()APP
4.2.1 DSS
“RS485” ()
4-2 : DSS 105
4.2.2
“Auto ID
”
“Scan”
4-3 : 106
4.2.3 ID
IDID ID”Set ID”
4-4 : ID 107
4.2.4
“Set ”
4.2.5
4-5 :
“Sync Clock
”
4-6 : 108
4.3 Delta
Delta : DSS (Delta Solar System Software) APP(MyDeltasSolar)
Active power control
Q(U) control (volt-var control)
P-F control (watt-frequecy control)
Q by night(Q setting 24/7)
P(U) control (volt-watt control)
Anti-PID
Fixed cos Fixed Q(%)
Dry contact ARC fault detection
Auto ID
Wi-fi
DSS : https://mydeltasolar.deltaww.com/manual/eng/SUB_1G/DSS.pdf
APP (DeltaSolar) : https://mydeltasolar.deltaww.com/index.php?p=manual
109
5
!!
– LED
5.1
5.1.1
!
– – 1. ( 5-1) 2. ( 5-1) 3. ( 5-2)
5-1 : 110
5-2 :
5.1.2
–
– IP66
1. 2. 3. 4. (2-1 9) 5. 6.
–
()
111
5.2 (SPD)
M30A_230
AC SPD
DC SPD
5-3 :
5-4 : APPDSSW18- AC Surge W17- DC Surge
112
5.2.1 AC SPD
1. LED 2. 5.1.1 3. 4. 3AC SPD 5. AC SPD0.8 Nm3 6. 0.8 Nm 7. 5.1.2
-
: 0.8 Nhm
-
: 0.8 Nhm
5-5 : AC SPD 113 -
: 0.8 Nhm
5-6 : AC SPD
114
5.2.2 DC SPD
1. LED 2. 5.1.1 3. 5-7 4. 3DC SPD 5. DC SPD0.8 Nm3 6. 7. 5.1.2
- : 0.8 Nhm
5-7 : DC SPD 115
- : 0.8 Nhm
5-8 : DC SPD
5.3
H4+
H4-
XX: Fuse rating 20A / 25A / 30A 116
5.4
1. LED 2. 5.1.1 3. DC SPD 4. 5. 6. 7. 5-10 8. 5.1.2
FAN 2
FAN 1
DC SPD
5-9 : 117
FAN 1
-
: 0.8 Nhm FAN 2
-
: 0.6 Nhm
-
: 0.8 Nhm
-
: 0.6 Nhm
5-10 :
118
5.5
:!!
–
: !
– –
: !
– 42
– AC – DC – H4H4 – Wi-Fi RS-485 1. 2. 3.
119
6
(6-1~6-4)
6.1 ()
6-1A: ()
AC Freq High (E01)
AC Freq Low (E02)
1. 2.
Island (E03,E04,E05)
AC
AC phase jump (E06)
Grid Quality
(E07)
AC phase abnormal
(E08)
No Grid (E09)
AC 1. AC 2. AC
AC 1. AC 2. AC
AC Volt Low (E10)
AC Volt High (E11)
1. 2. 3. AC 1. 2.
1. 2. 3. AC
EPO (E25)
EPO
DC Volt High (E30)
1000Vdc
Insulation Fault (E34)
solar arrayVoc1000Vdc 1. 2. 3.
Remote OFF (E36)
Remote OFF
120
6.2 ()
6-2A: ()
DC Injection (F01,F02,F03,F04)
Temperature High
(F05)
Amb Temp Fault (F06)
Temperature Low
(F07)
Boost Temp Fault (F08)
Bidir. Temp Fault (F09)
Inveter Temp Fault (F10)
AC RLY Fault (F13)
1. 2.
FW Unmatch (F14)
AC Sensor Fault (F15)
Vdc Sensor Fault (F16)
Idc Sensor Fault (F17)
AC Sensor Fault (F18)
Idc Sensor Fault (F19)
Red COMM Fault (F22)
DSP COMM Fault (F23)
1. (W08) 2. 1. (W08) 2. 1. (W08) 2.
121
6-2B: ()
Ground Cur. High
(F24)
Iac Unbalance 1.
(F26)
RCMU Fault (F27)
RCMU
AC RLY Short (F28)
AC
AC RLY Open (F29)
AC
Bus Unbalance (F30)
Bus Voltage High (F31, F32, F33, Bus
F34, F35)
AC Current High (F36,F37,F38,
F39,F40,F41)
AC CT Fault (F42)
R
AC CT Fault (F43)
S
AC CT Fault (F44)
T
AC Current High (F45)
ZC Circut Fault (F50)
Inv Circut Fault (F51)
Boost Circuit Fault (F52)
Arc Circut Fault 1.
(F58)
Arc Fault (F59)
1. 2. AC DC 1. DC 2. , Voc
1000Vdc (E30)
DC 1. 2. DSSARC
3.
122
6-2C: ()
DC Current High (F60,F61,F70,F71)
DC
Ext COMM. Fault (F74)
1. 2.
6.3 ()
De-rating (W07)
String fault (W08)
String Current Low (W23)
6-3A: ()
1. 2. 3. P-F 4. P(V) 5. 6. 7. 8.
1. 2. 3.
DC
1. 2. 3. 4. 5-1. 5-2. 6. PV panel 7. PV panel 8.
1. 2. PV panel 3. 4.
1. 2.
6.4 ()
Fan Fail (W11)
6-4A: ()
1. 2. 3.
DC SPD Fault (W17)
AC SPD Fault (W18)
Boost Circuit Fault (W30)
DC/AC SPD
1. DC/AC SPD 2. DC/AC SPD
123
7
Model
MPP @ AC400V MPP
() T.H.D *2 (rms) (peak)
7-1A: M30A_230 1100 V *1
M30A_230 (Korea) 1000 V
200 – 1000 V
480 – 900 V
480 – 800 V
250 V
600 V
Each MPPT: 30 A, Total: 72 A
Each MPPT: 20.4 kW
50 A per MPPT
3
2 strings / MPPT, Amphenol H4 Connector
Type II SPD 33 kVA
30 kW @ 40°C ; 33 kW @ 35°C
50 A
220 / 380V, 230 / 400V (3Ø3W or 3Ø4W) 80% to 130% of Nominal AC Voltage
50 / 60Hz ± 5Hz
0.8 ind – 0.8 cap
Type II SPD
< 3%
< 2 W 110 A / 50 s
60 A
116 A
1 1100 Vdc (1000 Vdc) 2
124
Model
(W x H x D)
7-1B: M30A_230
98.6 %
M30A_230 (Korea)
98.2 %
RS-485 / Wi-Fi
IEC 62109-1/-2 IEC 62920 CNS 15382
CNS 15426-1/-2 VDE-AR-N 4105 VDE-AR-N 4110 EN/IEC 61000-6-1/-2 EN/IEC
61000-6-3/-4 AS4777.2 : 2020
KN 62920 KS C 8567 KS C 8565
-25 to +60°C (Derating Above 40°C)
IP66
< 4000 m
45.9 dBA @1m, Amb 25°C 651 x 520 x 220 mm 42 kg
0%-100% non-condensing II
AC Output: III, DC Input: II 0 No
125
(%) 100 % 99 % 98 % 97 % 96% 95% 94% 93% 92% 91% 90%
0%
230Vac / 400 Vac
480 V 600 V 800 V
20%
40%
60%
(%)
7-1:
Pn=30kW
80%
100%
126
P/Pn(%)
110 % 100 % 90 % 80 % 70 % 60 % 50 %
0
230 Vac / 400 Vac PF=1
480V 600V 800V 900V
10
20
30
40
(°C)
7-2: (PF=1)
P/Pn(%)
110 % 100 % 90 % 80 % 70 % 60 % 50 %
0
230 Vac / 400 Vac PF=0.9
480V 600V 800V 900V
10
20
30
40
(°C)
7-3: (PF=0.9)
127
Pn=30kW
50
60
Pn=30kW
50
60
P/Pn(%)
120 %
230 Vac / 400 Vac PF=1
Pn=30kW
100 %
80 %
60 %
40 %
20 %
0% 200
35 C 40 C 50 C 60 C
300
400
500
600
700
800
(V)
7-4:
900
1000
128
:
-1: -1
NO
1
Wi-Fi
2
8.0 kgf-cm (0.8Nhm) 8.0 kgf-cm (0.8Nhm)
129
H4CFC4D-MS
H4CMC4D-MS
NO
1
2
2
2
3
1
4
1
5
H4
-2: -2 8.0 kgf-cm (0.8Nhm) 6.0 kgf-cm (0.6Nhm) 8.0 kgf-cm (0.8Nhm) 6.0 kgf-cm (0.6Nhm) –
130
12/10 AWG (4/6mm²)
NO 1 2 3 4 5 AC
-3: -3
8.0 kgf-cm (0.8Nhm)
–
8.0 kgf-cm (0.8Nhm)
–
8.0 kgf-cm (0.8Nhm)
–
–
20 AWG (0.5mm²)
25.5 kgf-cm (2.5Nhm)
6 AWG (13.3 mm²)~4 AWG (25 mm²)
131
Version 07240426
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>