GIRA 5023 00 Switching Actuator Blind Actuator 16 A Standard and Komfort Instruction Manual
- June 24, 2024
- GIRA
Table of Contents
- GIRA 5023 00 Switching Actuator Blind Actuator 16 A Standard and Komfort
- Product Information
- Product Usage Instructions
- FAQ
- Safety instructions
- Device components
- Function
- Operation
- Switching off temporary manual operation mode
- Operating an output in manual mode
- Information for electrically skilled persons
- Technical data
- Accessories
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
GIRA 5023 00 Switching Actuator Blind Actuator 16 A Standard and Komfort
Specifications
- Product: Switching actuator / blind actuator 16 A Standard & Komfort
- Order numbers: 5023 00, 5033 00, 5028 00, 5038 00, 5030 00, 5040 00
- Product image: Non-binding
- Date: 04.06.2024
Product Information
Safety Instructions
Electrical devices should only be mounted and connected by electrically skilled persons to prevent serious injuries, fire, or property damage. Do not connect loads for mains voltage and SELV/PELV together to the device.
Device Components
Key components include a button field for manual operation, programming button and LED, KNX connection, status LEDs for outputs, and load connections (relay outputs).
Function
This device is part of the KNX system and requires technical knowledge obtained in KNX training courses. It can be updated with firmware easily using the Gira ETS Service App. The device is KNX Data Secure capable and must be planned, installed, and commissioned with ETS version 5.7.3 or higher.
Product Usage Instructions
Switch Operation
Use the button field for manual operation.
Venetian Blinds Operation
Ensure you use venetian blind motors with mechanical or electronic limit switches.
Logic Function Characteristics
The status LEDs indicate the relay output status: ON (closed), OFF (opened), Flashes slowly (manual mode selected), Flashes quickly (output disabled via continuous manual mode).
Operation Elements
Use the buttons and LEDs as follows: Button for manual operation, LED for continuous manual mode, LED for relay outputs status, Button for switch on/adjusting slats/stop/move hanging upwards.
FAQ
Q: Can I connect three-phase motors to this device?
A: No, connecting three-phase motors can damage the device.
Safety instructions
Electrical devices may be mounted and connected only by electrically skilled persons.
- Serious injuries, fire or property damage are possible. Please read and follow the manual fully.
- Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains voltage and SELV/PELV together to the device.
- For parallel connection of several motors to an output it is essential to observe the corresponding instructions of the manufacturers, and to use a cut-off relay if neces-sary. The motors may be destroyed.
- Use only venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct mastering. Observe the specifications of the motor man-ufacturers. Device can be damaged.
- Do not connect any three-phase motors. Device can be damaged.
- These instructions are an integral part of the product, and must remain with the end customer.
Device components
- Button field for manual operation
- Programming button and LED
- KNX connection
- Status LEDs for outputs
- Load connections (relay outputs)
Function
System information
- This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite for proper understanding.
- The function of the device depends on the software. Detailed information on software versions and the respective scope of functions as well as the software itself can be obtained from the manufacturer´s product database.
- The device can be updated. Firmware can be easily updated with the Gira ETS Ser-vice App (additional software).
- The device is KNX Data Secure capable. KNX Data Secure provides protection against manipulation in building automation and can be configured in the ETS pro-ject. Detailed technical knowledge is required. A device certificate, which is attached to the device, is required for safe commissioning. The device certificate must be re-moved from the device and stored securely during the mounting process.
- The device is planned, installed and commissioned with version 5.7.3 or higher of the ETS.
Intended use
- Switching of electrical loads with potential-free contacts
- Switching of electrically-driven Venetian blinds, roller shutters, awnings and similar hangings
- Installation in sub-distribution unit on DIN rail according to DIN EN 60715
- Operation in KNX System for Standard and Comfort devices.
- Operation in Gira One System for Standard devices only.
Product characteristics
- Outputs can be operated manually, construction site mode
- Manual switching between Venetian blind operation and switching operation without commissioning
- Feedback in manual mode and in bus mode
- Disabling of individual outputs manually or by bus
- Status feedback (e. g. wind alarm)
- KNX Data Secure compatible
- Updatable with Gira ETS Service App
Characteristics switch operation
- Operation as NO or NC contacts
- Feedback function
- Logic and restraint function
- Central switching functions with collective feedback
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
- Scene function
- Operating hours counter
Characteristics Venetian blinds operation
- Suitable for AC motors 110…230 V
- Operating modes “Venetian blind with slats”, “Roller shutter/awning”, “Venting louvre/roof window”
- Blind/shutter position directly controllable
- Slat position directly controllable
- Feedback of movement status, blind/shutter position and slat position
- Forced position through higher-level controller
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function with heating/cooling operation
- Disabling function (lock-out protection)
- Scene function
Logic function characteristics
- Logic gate
- Transformer (conversion)
- Disabling element
- Comparator
- Limit value switch
Operation
-
(4) Status LEDs for outputs
- ON: Relay output closed
- OFF: Relay output opened
- Flashes slowly: Output in manual mode selected
- Flashes quickly: Output disabled via continuous manual mode
-
(6) Button
Manual operation -
(7) LED
ON: Continuous manual mode active/Flashing: Temporary manual mode active -
(8) LED ON|
ON: Relay outputs closed, manual mode active -
(9) Button ON|
Short: Switch on, adjust slats or stop
Long: Move hanging upwards -
(10) Button OFF|
Short: Switch off, adjust slats or stop
Long: Move hanging downwards -
(11) LED OFF|
ON: Relay outputs opened, manual mode active -
(12) Button ALL OFF
Open all relay outputs, stop drives
In operation with the button field the device distinguishes between a short and a long press.
- Short: Pressing for less than 1 s
- Long: Pressing for between 1 and 5 s
- In switching operation, the device distinguishes between the “NO contact” and “NC contact” operating modes. The buttons (9 + 10) switch the switching state when actuated:
- NO contact: Switch on = close relay, Switch off = open relay
- NC contact: Switch on = open relay, Switch off = close relay
- The LED (4 + 8 + 11) always indicate the relay state.
- The LEDs (4) optionally indicate the states of the outputs only temporarily (parameter-dependent).
Operating modes
- Bus operation: operation via push-button sensors or other bus devices
- Temporary manual control: manual control locally with keypad, automatic re-turn to bus control
- Continuous manual mode: exclusively manual operation on the device No bus operation is possible in manual mode.
- After a bus failure and restoration the device switches to bus operation.
- The manual mode can be disabled in ongoing operation via a bus telegram.
Switching on temporary manual operation mode
Operation is not disabled.
- Press (6) button briefly.
- LED (7) flashes, LEDs A1… (4) of the first configured output or output pair flash.
Short-time manual operation is switched on.
After 5 s without a button actuation, the actuator returns automatically to bus operation.
Switching off temporary manual operation mode
The device is in short-term manual mode.
-
No button-press for 5 s.
– or – -
Press (6) button briefly as many time as necessary until the actuator leaves the short-time manual mode.
Status LEDs A1… (4) no longer flash, but rather indicate the relay status. Short-time manual operation is switched off.
Switching outputs: depending on the programming, the output relays switch to the position that is active after the manual mode is switched off, e.g. logic function.
Venetian blind outputs: depending on the programming, the blind moves to the position that is active after the manual mode is switched off, e.g. to safety or sun protection position.
Switching on permanent manual operation mode
Operation is not disabled.
Press the Ǖ (6) button for at least 5 s.
LED Ǖ (7) lights up, LEDs A1… (4) of the first configured output or output
pair flashes.
Continuous manual mode is switched on.\
Switching off permanent manual operation mode
The device is in permanent manual operation mode.
Press the (6) button for at least 5 s.
LED (7) is off.
- Continuous manual mode is switched off. Bus operation is switched on.
- Switching outputs: depending on the programming, the output relays switch to the position that is active after the manual mode is switched off, e.g. logic function.
- Venetian blind outputs: depending on the programming, the blind moves to the position that is active after the manual mode is switched off, e.g. to safety or sun protection position.
Operating an output in manual mode
- Activate short-term or permanent manual operation.
- Keep pressing the button (6) until the LED A1… (4) of the desired output or output pair flashes.
- Press the ON| (9) or OFF| (10) button.
Short: Switch on/off, drive stop.
Long: Move blind/shutter upwards/downwards.
LED ON| (8) ON: Relay output closed
LED OFF| (7) OFF: Relay output opened
Short-term manual mode: After running through all of the outputs the device exits manual mode after another brief actuation.
Switching off all outputs / Stopping all hangings
The device is in permanent manual operation mode.
Press the ALL OFF button (12).
Switching outputs: all outputs switch off (NO operating mode: relay output
opened/NC operating mode: relay output closed).
Venetian blind outputs: all blinds/shutters stop.
Disabling outputs
The device is in permanent manual operation mode. The bus control can be
disabled (ETS parameter).
- Keep pressing the button (6) until the LED A1… (4) of the desired output or output pair flashes.
- Press the ON| (9) and OFF| (10) buttons simultaneously for approx. 5 s. Selected output is disabled.
The status LED A1… (4) of the selected output or output pair flashes quickly. A disabled output can be operated in manual mode.
Re-enabling outputs
The device is in permanent manual operation mode. One or more outputs were
dis-abled in manual mode.
- Press button (6) repeatedly until the output to be unlocked or the output pair is selected.
- Press the ON| (9) and ǖ (10) buttons simultaneously for approx. 5 s. Disabling is deactivated.
The LED A1… (4) of the selected output or output pair flashes slowly.
Switching between Venetian blind and switching operation
Device is not in operation
-
Activate permanent manual operation.
-
Keep pressing the button (1) until the LED A1… (8) of the desired output or output pair flashes.
-
Press the (1) and ON| (4) and ǖ (5) buttons simultaneously for approx. 5 s.
Switching operation: Both status LEDs A1… (8) of the output pair light up. Venetian blind operation: Both status LEDs A1… (8) of the output pair flash al-ternately. -
Press the ON| (4) and ǖ (5) buttons simultaneously.
-
Outputs switch between switching operation and Venetian blind operation. Both status LEDs A1… (8) indicate the current operating mode.
-
Press the (1) and ON| (4) and OFF| (5) buttons simultaneously for approx. 5 s.
Operating mode switchover is terminated, permanent manual operation mode is activated. -
Press the button (1) for approx. 5 s.
Operating mode switchover is terminated, permanent manual operation mode is deactivated.
Information for electrically skilled persons
DANGER!
Mortal danger of electric shock. Disconnect the device. Cover up live parts.
Mounting and electrical connection
Mount device
- Enter or scan the device certificate and add it to the project. A high resolution camera should be used to scan the QR code.
- The device certificate should be removed from the device during mounting.
- Document all passwords and keep them safe.
Observe the ambient temperature. Ensure sufficient cooling.
Mount device on DIN rail.
Connect device
- Connect bus line with KNX device connection terminal observing the correct polarity.
- Attach the cover cap to the KNX connection as protection against hazardous voltages.
- Connect load as shown in the connection example. Two adjacent relay outputs form a Venetian blind output.
The total current capacity of neighbouring outputs is a maximum of 20 A.
Commissioning
Commissioning the device
NOTICE!
Incorrect load control due to undefined relay state at delivery.
Risk of destruction of connected drive motors.
During commissioning, before switching on the load, ensure that all relay
contacts are open by applying the KNX bus voltage. Observe the commissioning
sequence!
- Switch on the KNX bus voltage.
- Wait approx. 10 s.
- Switch on load circuits.
Delivery state: The outputs can be operated with manual control. Outputs are set as Venetian blind outputs.
Safe-state mode
The safe-state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis func-tions and programming of the device are possible. Manual operation is not possible.
Activating safe-state mode
- Switch off the bus voltage or remove the KNX device connection terminal.
- Wait approx. 15 s.
- Press and hold down the programming button.
- Switch on the bus voltage or attach the KNX device connection terminal. Re-lease the programming button only after the programming LED starts flashing slowly.
Safe-state mode is activated.
The programming mode can also be switched on and off in the safe-state mode as usual by briefly pressing the programming button again. The pro-gramming LED stops flashing if the programming mode is active.
Deactivating safe-state mode
Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.
Master reset
The master reset restores the default device settings (physical address
15.15.255, firmware is retained). The device must then be recommissioned with
the ETS. Manual operation is possible.
In secure operation: A master reset deactivates the device security. The
device can then be recommissioned with the device certificate.
Performing a master reset
Prerequisite: Safe-state mode is activated.
- Press and hold down the programming button for > 5 s.
The programming LED flashes quickly.
The device performs a master reset, restarts and is ready for operation again after approx. 5 s.
Restoring the device to factory settings
Devices can be reset to factory settings with the Gira ETS Service App. This
function uses the firmware contained in the device that was active at the time
of delivery (de-livered state). Restoring the factory settings causes the
devices to lose their physical address and configuration.
Optional: Installing the phase busbar (accessory)
- If necessary, cut the phase busbar at the notches using diagonal cutting pliers (see figure 5).
- Attach the end cap to the interface.
Ensure that the device connection terminals are open and the copper pins are
inserted in the device connection terminals.
- Align the phase busbar using the printed arrows and plug it into the device connection terminals (see figure 6).
- Screw the phase busbar to the device connection terminals.
Technical data
-
Ambient temperature -5 … +45 °C
-
Storage/transport temperature -25 … +70 °C
Switching current -
AC1 according to DIN EN IEC 60947-4-1 16 A
-
External ballasts 16 A, 140 μF
-
Switch-on current 200 μs Max. 800 A
-
Switch-on current 20 ms Max. 165 A
-
Switching voltage AC 250 V ~
Current carrying capacity -
Neighbouring outputs Ʃ 20 A
Loads per output -
Motors 1380 VA
-
HV halogen lamps 2300 W
-
HV-LED lamps Max. 400 W
-
LV halogen lamps with electronic transformers 1500 W
-
LV halogen lamps with inductive transformer 1200 VA
-
Fluorescent lamps, compensated 1160 VA
Terminals -
Connection mode Screw terminals
-
Stripping length 8 mm
-
Phillips screwdriver PZ1
-
Connection torque for screw terminals Max. 0.8 Nm
-
Clampable conductor cross-section
Single stranded 0.5 … 4 mm² -
Finely stranded without conductor sleeve 0.5 … 4 mm²
-
Finely stranded with conductor sleeve 0.5 … 2.5 mm²
Installation width -
Order no. 5023 00, 5033 00 72 mm / 4 HP
-
Order no. 5028 00, 5038 00 144 mm / 8 HP
-
Order no. 5030 00, 5040 00 216 mm / 12 HP
Weight -
Order no. 5023 00, 5033 00 approx. 230 g
-
Order no. 5028 00, 5038 00 approx. 500 g
-
Order no. 5030 00, 5040 00 approx. 740 g
KNX -
KNX medium TP256
-
Commissioning mode S mode
-
Rated voltage KNX DC 21 … 32 V SELV
-
KNX current consumption
-
Order no. 5023 00, 5028 00, 5033 00, 5038 00 5 … 18 mA
-
Order no. 5030 00, 5040 00 5 … 24 mA
Accessories
-
Set of 1-pole phase busbars for 16-gang switch actuator / 8-gang Venetian blind actuator, for Gira One and KNX
Order no. 8313 00 -
Set of 1-pole phase busbars for 24-gang switch actuator / 12- gang Venetian blind actuator, for Gira One and KNX
Order no. 8314 00 -
Set of end caps for phase busbar
Order no. 8315 00
Warranty
The warranty is provided by the specialist trade in accordance with statutory require-ments. Please submit or send faulty devices postage paid together with a fault de-scription to your responsible salesperson (specialist trade / installation company /electrical specialist trade). They will forward the devices to the Gira Service Center.
Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-
Systeme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 – 602-0 Fax +49(0)21 95 – 602-191
References
- Suche
- Gira Set Phasenschienen 1-polig für Schaltaktor 16fach / Jalousieaktor 8fach, für Gira One und KNX6 Stück Phasenschienen 1-polig, 4 Stück Endkappen /
- Gira Set Phasenschienen 1-polig für Schaltaktor 24fach / Jalousieaktor 12fach, für Gira One und KNX6 Stück Phasenschienen 1-polig, 4 Stück Endkappen /
- Gira Set Endkappen für Phasenschiene
- Schalter, Steckdosen & smarte Technik | Gira