GIRA one 16 Gang Blind Actuator Instruction Manual
Product Information
Product Name: Switching actuator / blind actuator 16 A Standard &
Komfort
Order Numbers: 5023 00, 5033 00, 5028 00, 5038 00, 5030 00, 5040 00
Safety Instructions:
- Electrical devices may only be mounted and connected by electrically skilled persons.
- Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains voltage and SELV/PELV together to the device.
- For parallel connection of several motors to an output, it is essential to observe the corresponding instructions of the manufacturers and to use a cut-off relay if necessary.
- Use only Venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct mastering.
- Do not connect any three-phase motors.
Device Components:
- Button field for manual operation
- Programming button and LED
- KNX connection
- Status LEDs for outputs
- Load connections (relay outputs)
Function:
This device is a product of the KNX system and complies with the KNX directives. It can be updated with firmware using the Gira ETS Service App. It is also KNX Data Secure capable, offering protection against manipulation in building automation. The device certificate must be removed from the device and stored securely during mounting.
Intended Use:
The device is designed for switching actuation and blind actuation. It can be used for various applications with appropriate motor connections.
Product Usage Instructions
Switch Operation Characteristics:
The device has relay outputs that can be controlled to switch on or off. The status LEDs indicate whether the relay outputs are closed or opened. The LEDs can also indicate if the output is in manual mode or disabled via continuous manual mode.
Blinds Operation Characteristics:
The device can be used for controlling blinds. The buttons and LEDs on the device allow for manual operation, adjusting slats, stopping, and moving the blinds upwards or downwards.
Operating Elements
- Status LEDs for outputs:
-
* **ON:** Relay output closed
-
- OFF: Relay output opened
- Flashes slowly: Output in manual mode selected
- Flashes quickly: Output disabled via continuous manual mode
-
- Button for manual operation
- LED:
- ON: Continuous manual mode active
- Flashing: Temporary manual mode active
- LED:
- ON: Relay outputs closed, manual mode active
- Button:
- Short: Switch on, adjust slats or stop
- Long: Move hanging upwards
- Button:
- Short: Switch off, adjust slats or stop
- Long: Move hanging downwards
Safety instructions
- Electrical devices may only be mounted and connected by electrically skilled persons.
- Serious injuries, fire or property damage possible. Please read and follow manual fully.
- Danger of electric shock on the SELV/PELV installation. Do not connect loads for mains voltage and SELV/PELV together to the device.
- For parallel connection of several motors to an output it is essential to observe the corresponding instructions of the manufacturers, and to use a cut-off relay if neces-sary. The motors may be destroyed.
- Use only Venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct mastering. Observe the specifications of the motor man-ufacturers. Device can be damaged.
- Do not connect any three-phase motors. Device can be damaged.
- This manual is an integral part of the product, and must remain with the end cus-tomer.
Device components
- Button field for manual operation
- Programming button and LED
- KNX connection
- Status LEDs for outputs
- Load connections (relay outputs)
Function
System information
- This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
- The function of this device depends upon the software. Detailed information on load-able software and attainable functionality as well as the software itself can be ob-tained from the manufacturer´s product database.
- The device can be updated. Firmware can be easily updated with the Gira ETS Ser-vice App (additional software).
- The device is KNX Data Secure capable. KNX Data Secure offers protection against manipulation in building automation and can be configured in the ETS project. De-tailed specialist knowledge is required. A device certificate, which is attached to the device, is required for safe commissioning. During mounting, the device certificate must be removed from the device and stored securely.
- Planning, installation and commissioning of the device are carried out with the aid of the ETS, version 5.7.3 and above.
Intended use
- Switching of electrical loads with potential-free contacts
- Switching of electrically-driven Venetian blinds, roller shutters, awnings and similar hangings
- Installation in sub-distribution unit on DIN rail according to DIN EN 60715
- Operation in KNX system for Standard and Comfort devices.
- Operation in Gira One system for Standard devices only.
Product characteristics
- Outputs can be operated manually, construction site mode
- Manual switching between Venetian blind operation and switching operation without commissioning
- Feedback in manual mode and in bus mode
- DisabStatus feedback (e. g. wind alarm)
- KNX Data Secure compatible
- Updatable with Gira ETS Service App
Characteristics switch operation
- Operation as NO or NC contacts
- Feedback function
- Logc and restraint function
- Central switching functions with collective feedback
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
- Scene function
- Operating hours counter
Characteristics blinds operation
- Suitable for AC motors 110…230 V
- Operating modes “Venetian blind with slats”, “Roller shutter/awning”, “Venting louvre/roof window”
- Blind/shutter position directly controllable
- Slat position directly controllable
- Feedback of movement status, blind/shutter position and slat position
- Forced position through higher-level controller
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function with heating/cooling operation
- Disabling function (lock-out protection)
- Scene function
Logic function characteristics
- Logic gate
- Transformer (conversion)
- Disabling element
- Comparator
- Limit value switch
Operation
Status LEDs for outputs
- ON: Relay output closed
- OFF: Relay output opened
- Flashes slowly: Output in manual mode selected
- Flashes quickly: Output disabled via continuous manual mode
- Button
- Manual operation
- LED
- ON: Continuous manual mode active/Flashing: Temporary manual mode active
- LED
- ON: Relay outputs closed, manual mode active
- Button
- Short: Switch on, adjust slats or stop
- Long: Move hanging upwards
- Button
- Short: Switch off, adjust slats or stop
- Long: Move hanging downwards
- LED
- ON: Relay outputs opened, manual mode active
- Button ALL OFF
- Open all relay outputs, stop drives
- In operation with the button field the device distinguishes between a short and a long press.
- Short: Pressing for less than 1 s
- Long: Pressing for between 1 and 5 s
- In switching operation, the device distinguishes between the “NO contact” and “NC contact” operating modes. The buttons (9 + 10) switch the switching state when actuated:
- NO contact: Switch on = close relay, Switch off = open relay
- NC contact: Switch on = open relay, Switch off = close relay
- The LED (4 + 8 + 11) always indicate the relay state.
- The LEDs (4) optionally indicate the states of the outputs only temporarily (parameter-dependent).
Operating modes
- Bus operation: operation via push-button sensors or other bus devices
- Temporary manual control: manual control locally with keypad, automatic re-turn to bus control
- Continuous manual mode: Exclusively manual operation on the device
- No bus operation is possible in manual mode.
- After a bus failure and restoration the device switches to bus operation.
- The manual mode can be disabled in ongoing operation via a bus telegram.
- Switching on temporary manual operation mode
Operation is not disabled.
- Press button (6) briefly.
- LED (7) flashes, LEDs A1… (4) of the first configured output or output pair flash.
- Short-time manual operation is switched on.
- After 5 s without a button actuation, the actuator returns automatically to bus operation.
Switching off temporary manual operation mode
- The device is in short-term manual mode.
No button-press for 5 s. – or –
- Press (6) button briefly as many time as necessary until the actuator leaves the short-time manual mode.
- Status LEDs A1… (4) no longer flash, but rather indicate the relay status. Short-time manual operation is switched off.
- Switching outputs: depending on the programming, the output relays switch to the position that is active after the manual mode is switched off, e.g. logic function.
- Blind/shutter outputs : depending on the programming, the hangings move to the position that is active after the manual mode is switched off, e.g. to safety or sun protection position.
- Switching on permanent manual operation mode
- Operation is not disabled.
- Press the (6) button for at least 5 s.
- LED (7) lights up, LEDs A1… (4) of the first configured output or output pair flash.
- Continuous manual mode is switched on.
- Switching off permanent manual operation mod
- The device is in continuous manual mode.
- Press the (6) button for at least 5 s.
- LED (7) is off.
- Continuous manual mode is switched off. Bus operation is switched on.
- Switching outputs: depending on the programming, the output relays switch to the position that is active after the manual mode is switched off, e.g. logic function.
- Blind/shutter outputs: depending on the programming, the hangings move to the position that is active after the manual mode is switched off, e.g. to safety or sun protection position.
Operating an output in manual mode
- Activate short-term or permanent manual operation.
- Press button (6) repeatedly until LED A1… (4) of the desired output or output pair flashes.
- Press button (9) or (10).
- Short: Switch on/off, drive stop.
- Long: Move blind/shutter upwards/downwards.
- LED (8) ON: Relay output closed
- LED (7) OFF: Relay output opened
- Short-term manual mode: After running through all of the outputs the device exits manual mode after another brief actuation.
Switching off all outputs / Stopping all hangings
- The device is in permanent manual operation mode.
- Press the ALL OFF button (12).
- Switching outputs: all outputs switch off (NO operating mode: relay output opened/NC operating mode: relay output closed).
- Venetian blind outputs: all blinds/shutters stop.
Disabling outputs
- The device is in continuous manual mode. The bus control can be disabled (ETS parameter).
- Press button (6) repeatedly until LED A1… (4) of the desired output or output pair flashes.
- Press the (9) and Dž (10) buttons simultaneously for approx. 5 s. Selected output is disabled.
- The status LED A1… (4) of the selected output or output pair flashes quickly. A disabled output can be operated in manual mode.
Re-enabling outputs
- The device is in continuous manual mode. One or more outputs were disabled in manual mode.
- Press button (6) repeatedly until the output to be unlocked or the output pair is selected.
- Press the (9) and (10) buttons simultaneously for approx. 5 s. Disabling is deactivated.
- The LED A1… (4) of the selected output or output pair flashes slowly.
- Switching between Venetian blind and switching operation
- Device is not in operation
Activate permanent manual operation.
- Press button (1) repeatedly until LED A1… (8) of the desired output or output pair flashes.
- Press the (1) and (4) and (5) buttons simultaneously for approx. 5 s.
- Switching operation: Both status LEDs A1… (8) of the output pair light up. Venetian blind operation: Both status LEDs A1… (8) of the output pair flash al-ternately.
- Press the (4) and (5) buttons simultaneously.
- Outputs switch between switching operation and Venetian blind operation. Both status LEDs A1… (8) indicate the current operating mode.
- Press the (1) and 4) and (5) buttons simultaneously for approx. 5 s.
- Operating mode switchover is terminated, permanent manual operation mode is activated.
- Press the button (1) for approx. 5 s.
- Operating mode switchover is terminated, permanent manual operation mode is deactivated.
Information for electrically skilled persons
DANGER!
- Mortal danger of electric shock.
- Disconnect the device. Cover up live parts.
Mounting and electrical connection
Commissioning
- Commissioning the device
NOTICE!
- Incorrect load control due to undefined relay state at delivery.
- Risk of destruction of connected drive motors.
- During commissioning, before switching on the load, ensure that all relay contacts are open by applying the KNX bus voltage. Observe commissioning sequence!
- Switch on the KNX bus voltage.
- Wait about 10 s.
- Switch on load circuits.
- Delivery state: The outputs can be operated with manual control. Outputs are set as Venetian blind outputs.
Safe-state mode
- The safe-state mode stops the execution of the loaded application program.
- Only the system software of the device is still functional. ETS diagnosis func-tions and programming of the device are possible. Manual operation is not possible.
Activating safe-state mode
- Switch off the bus voltage or remove the KNX device connection terminal.
- Wait about 15 s.
- Press and hold down the programming button.
- Switch on the bus voltage or attach the KNX device connection terminal. Re-lease the programming button only after the programming LED starts flashing slowly.
- The safe-state mode is activated.
- By briefly pressing the programming button again, the programming mode can also be switched on and off in the safe-state mode as usual. If the program-ming mode is active, the programming LED stops flashing.
Deactivating safe-state mode
- Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.
Master reset
- The master reset restores the basic device settings (physical address 15.15.255, firmware remains in place). The device must then be recommissioned with the ETS. Manual operation is possible.
- In secure operation: A master reset deactivates device security. The device can then be recommissioned with the device certificate.
Performing a master reset
- Precondition: The safe-state mode is activated.
- Press and hold down the programming button for > 5 s.
- The programming LED flashes quickly.
- The device performs a master reset, restarts and is ready for operation again after approx. 5 s.
- Restoring the device to factory settings
- Devices can be reset to factory settings with the Gira ETS Service App. This function uses the firmware contained in the device that was active at the time of delivery (de-livered state). Restoring the factory settings causes the devices to lose their physical address and configuration.
Technical data
- KNX
- KNX medium TP256
- Commissioning mode S-mode
- Rated voltage KNX DC 21 … 32 V SELV
- Current consumption KNX
- Order no. 5023 00, 5028 00,
- 5033 00, 5038 00
- 5 … 18 mA
- Order no. 5030 00, 5040 00 5 … 24 mA
Outputs
- Switching voltage AC 250 V ~
- Switching current AC1 16 A
- Fluorescent lamps 16 AX
- Current carrying capacity
- Neighbouring outputs Ʃ 20 A
- Loads per output
- Ohmic load 3000 W
- Capacitive load max. 16 A (140 μF)
- Motors 1380 VA
- Switch-on current 200 μs max. 800 A
- Switch-on current 20 ms max. 165 A
- Lamp loads
- Incandescent lamps 2300 W
- HV halogen lamps 2300 W
- HV-LED lamps max. 400 W
- LV halogen lamps with electronic
- transformers 1500 W
- LV halogen lamps with inductive
- transformer 1200 VA
- Compact fluorescent lamps uncompensated 1000 W
- parallel compensated 1160 W (140 μF)
Installation width
- Order no. 5023 00, 5033 00 72 mm / 4 HP
- Order no. 5028 00, 5038 00 144 mm / 8 HP
- Order no. 5030 00, 5040 00 216 mm / 12 HP
Weight
- Order no. 5023 00, 5033 00 approx. 230 g
- Order no. 5028 00, 5038 00 approx. 500 g
- Order no. 5030 00, 5040 00 approx. 740 g
- Clampable conductor cross-section
- Single stranded 0.5 … 4 mm²
- Finely stranded without conductor sleeve 0.5 … 4 mm²
- Finely stranded with conductor sleeve 0.5 … 2.5 mm²
- Ambient conditions
- Ambient temperature -5 … +45 °C
- Storage/transport temperature -25 … +70 °C
- Connection torque, screw terminals max. 0.8 Nm
Warranty
- The warranty is provided in accordance with statutory requirements via the specialist trade.
- Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade).
- They will forward the devices to the Gira Service Center.
Systeme
- Industriegebiet Mermbach
- Dahlienstraße
- 42477 Radevormwald
- Postfach 12 20
- 42461 Radevormwald
- Deutschland
- Tel +49(0)21 95 – 602-0
- Fax +49(0)21 95 – 602-191
- www.gira.de
- info@gira.de
Read More About This Manual & Download PDF:
References
- Suche
- Gira Set Phasenschienen 1-polig für Schaltaktor 16fach / Jalousieaktor 8fach, für Gira One und KNX6 Stück Phasenschienen 1-polig, 4 Stück Endkappen /
- Gira Set Phasenschienen 1-polig für Schaltaktor 24fach / Jalousieaktor 12fach, für Gira One und KNX6 Stück Phasenschienen 1-polig, 4 Stück Endkappen /
- Gira Set Endkappen für Phasenschiene
- Schalter, Steckdosen & smarte Technik | Gira