TOSHIBA MMD-UP0121VHG-UL Vertical Air Handler Owner’s Manual

June 22, 2024
Toshiba

TOSHIBA MMD-UP0121VHG-UL Vertical Air Handler

TOSHIBA-MMD-UP0121VHG-UL-Vertical-Air-Handler-PRO

Specifications Model MMD-UP0121VHG-UL
Cooling Rated Capacity 12,000 Btu/h
Heating Rated Capacity 13,500 Btu/h
Airflow (H/M/L) 480/440/340 CFM
Sound Data (H, M, L) 41.4/38.2/36.8 dBA
External Static Pressure (ESP) 0.3 in. WG (Factory Default), 0.5 in. WG (Max)
Power Supply 208-230V/1Ph/60Hz
Net Weight 130 lbs

Product Usage Instructions

Installation

  1. Select a suitable location for the indoor unit with proper airflow and accessibility for maintenance.
  2. Follow the provided dimensional drawing to ensure correct placement and installation.

Operation

  1. Connect the unit to the power supply as per the specified requirements.
  2. Use the optional accessories like remote controls or central controllers for convenient operation.

Maintenance

  1. Regularly clean or replace filters as recommended to maintain optimal performance.
  2. Schedule professional maintenance checks annually to ensure efficient operation.

Frequently Asked Questions (FAQ)

  • Q: What should I do if the unit is not cooling/heating properly?
    A: Check the filters for blockages and ensure proper airflow. If the issue persists, contact a qualified technician for further inspection.

  • Q: Can I install the unit myself?
    A: Installation of the unit should be done by a certified HVAC professional to ensure safety and proper functioning.

  • Q: How often should I clean the filters?
    A: It is recommended to clean or replace the filters every 1-2 months depending on usage and air quality.

STANDARD FEATURES

  • Dual Drainage Spouts
  • Three Fan Speeds – High, Medium and Low
  • Unit Can Be Installed Standing Vertical or Laid Horizontally
  • Electronically Commutated Fan Motor (ECM)
  • Built In Pulse Modulating Valve For Installation Ease
  • Removable Front Panel Provides Easy Access
  • Filter MERV 3
INDOOR UNIT MODEL MMD-UP0121VHG-UL
PERFORMANCE
Cooling Rated Capacity Btu/h
Heating Rated Capacity Btu/h
Airflow (H / M / L) CFM
Sound Data (H, M, L) † dBA
External Static Pressure (ESP) in. WG

0.5 (Max)
ELECTRICAL|
Power Supply| V/Ph/Hz| 208-230/1/60
MCA| A| 1.9
MOCP
| A| 15
Full Load Amps (FLA)*| A| 1.5
PHYSICAL DATA|
---|---
Pipe Connection Size – Liquid| inches| 1/4 (brazed)
Pipe Connection Size – Suction| inches| 3/8 (brazed)
Refrigerant| R410A
DIMENSIONS (inches)| H (in)| 46-7/8
W (in)| 17-3/4
D (in)| 22-1/4
NET WEIGHT| lbs| 130

ACCESSORIES

  • Simple Wired Remote Control – RBC-ASCU11-UL
  • Wired Remote Controller (Local Controller) – RBC-AWSU52-UL
  • Touch Screen Central Controller – BMS-CT2560U-UL
  • Stand Alone Receiver with Wireless Remote TCB-AX32UL
  • Remote Sensor TCB-TC41U-UL
  • Wired Remote Controller – RBC-AMT32UL
  • Filter Box / 1” MERV3 (TCB-FB2F241VDGUL)
  • Plenum TCB-PL2S241VDGUL
  • Electrical Heater (240V/208V):
    1.0kW/0.8kW| TCB-HT101VDGUL
    ---|---
    3.0kW/2.3kW| TCB-HT301VDGUL
    5.0kW/3.8kW| TCB-HT501VDGUL

NOTES:

    • Does not include electric heater.
  • † Average / weighted sound values

Dimensional Drawing

Indoor Unit Vertical Air Handler MMD-UP0121VHG-UL:TOSHIBA-MMD-UP0121VHG-UL-
Vertical-Air-Handler-1

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>