iSMACONTROLLI EBV Smart Balancing Control Valve Instruction Manual

June 15, 2024
iSMACONTROLLI

EBV Smart Balancing Control Valve

Product Information

Specifications:

  • Product Name: EBV Smart Balancing Control Valve
  • Manufacturer: Isma Controlli
  • Model: DIM324en
  • Issue: 1st Revision 2
  • Release Date: 03/2024

Product Usage Instructions:

Valve Installation
Before installing the valve, ensure that the hydraulic connections follow the fluid directions as shown in the provided diagram. Make sure the pipes are clean and free from weld slag to prevent damage to the internal parts of the valve.

Q: What should I do if I notice irregular leakage from the valve?
A: In case of irregular leakage, check and replace O-rings and stem packing as necessary.
Q: Can the product specifications change without notice?
A: Yes, the performances stated in the product sheet can be modified without any prior notice.

Smart Balancing Control Valve

VALVE INSTALLATION

Hydraulic Connections:
Follow the fluid directions as shown in the diagram below.

Before installing the valve, make sure the pipes are clean and free from weld slag in order not to damage the internal parts of the valve itself.

Before the valve start-up, check if the flow correspond to the indication printed on the valve body.
The valve has the following specification according to stem position:

  • Stem down = fluid passing
  • Stem up = fluid intercepted

OPERATING CONDITIONS

Temperature, nominal pressure and differential pressure on the valve must be within the values specified in data sheets EBV_DBL603en.

PIPE FLUSHING

An anomalous valve leackage is caused, in almost all cases, by weld slag or foreign bodies entrapped between the valve seat and the plug, often causing damages.
To prevent such inconveniences, it is advisable to use filters upstream of the valve.
Moreover, the pipelines must be properly washed positioning the valve stem at half stroke; this operation must be performed before start-up and after a prolonged shutdown of the system.

The performances stated in this sheet can be modifi ed without any prior notice.

VALVE MAINTENANCE

Valves are equipped with a stuffing box with a double Oring and, therefore, they do not require any particular maintenance. In case of irregular leakage, O-Rings and stem packing have to be replaced.

PRESSURE SENSORS INSTALLATION

Make sure that the fluid is not present in the system and remove the closing caps on the valve flanges. Insert the MF extension and pressure transducers as indicated in the figure below.

ACTUATOR INSTALLATION

The actuators must not be installed in explosive atmosphere and must not be subjected to steam jets of water or dripping. Leave a space above the actuator sufficient to allow the uncoupling of the actuator from the valve body for any maintenance, at least 10-15 cm.

WIRING CONNECTION

Remove the cover screw with a screwdriver and then remove the cover as shown in the picture beside. The actuator is equipped with 3 removable terminal blocks:

  • a removable 8-pole terminal block (T1) with power supply, analog and digital command signal and feedback signal;
  • a removable 6-pole terminal block (T2) dedicated to the RS-485 bus connection (Modbus);
  • a removable 6-pole terminal block (T3) dedicated to the connections of the temperature sensors (only 4 poles are used).

TERMINAL BLOCK T1

Label Description Function Cable type Max wire length
L1 24Vac/dc Power supply AWG 16 (min 1mm2 – max 1,5mm2) 75 m
Ln 0V
Y 0-10Vdc Modulating control input AWG 20 (min 0,5mm2 – max 1,5mm2) 200 m
M 0V (common)
Y1 Not used

Y2
V+| 16Vdc| Power supply for pressure sensors| AWG 20 (min 0,5mm2 – max 1,5mm2)| 200 m
M| 0V (common)
U| 2-10Vdc| Feedback output signal| AWG 20 (min 0,5mm2 – max 1,5mm2)| 200 m
M| 0V (common)

TERMINAL BLOCK T2

Label Description Function Cable type Max wire length
M+ Tx

Modbus connection

|

Belden 8762

|

See chapter Modbus – RS485

M-| Rx
G| Shield
A1| 0-10 V from pressure sensor (inlet pressure)|

ΔP reading

|

Three-core cable supplied

|

75 cm

A2| 0-10 V from pressure sensor (outlet pressure)
G| 0 V (Common)| Pressure sensor common| 75 cm

TERMINAL BLOCK T3

Label Description Function Max wire length
T1 Supply temp. sensor ΔT limit function, energy monito- ring and power
control function 3 m
G Common
T2 Return temp. sensor
G Common

PRESSURE TRANSDUCERS CONNECTION

Label Description Function Cable type Max wire length
1 Power supply

Differential Pressure Reading

|

Three poles wire (sup- plied)

|

75 cm

2| 0-10V Signal
3| Common

P2 PRESSURE SENSOR (OUTLET) CONNECT TO PORT A OF THE VALVE
P1 PRESSURE SENSOR (INLET) CONNECT TO PORT AB OF THE VALVE

Modbus Control

Modulanting Control & Modbus Supervisory

Note: To avoid damages to electronic components caused by the PCB bending, do not press too much while fixing the terminal block.
Each pole of the terminal blocks is clearly marked and the same label is on the electronic board.
Before turning on the actuator make sure that the terminal blocks are correctly connected to the board and that the labels on the terminals and board match.

CABLE GLAND

The actuator is supplied with 2 cable glands with punched mem-branes for safe and tidy wiring.

  •  Cable gland 1 for 3 cables: 2-wire cable for power supply; 5- wire cable for control and feedback signals and 3-wire cable for Modbus;
  • Cable gland 2 for 4 cables: 2 cables with 2 wires for tempera-ture sensors (if present) and 2 cables with 3 wires for pressu-re trasmitters.

DIPSWITCH SETTING

DIAGNOSTIC – ALARM FUNCTIONS

DIAGNOSTIC – ALARM FUNCTIONS

N°| Error type| Actuator status| Actuator behavior| LEDs notification| Possible anomaly| Restore procedure

1

| Stroke less than 5 mm| Calibration / first installation| The actuator returns to its initial position and does not respond to the command. The actuator keeps the previous stroke or the default stroke| READ ON| alve with stroke less than 5 mm| Remove power and re-power again
Stroke greater than 60 mm| Calibration / first installation| The actuator leaves the ma ximum range of 60mm and moves to the new extreme. Once the new stroke limit is reached, it returns to the initial position signaling an anomaly.

The actuator does not learn the new stroke.

| RED fast blinking + GREEN ON| Valve with stroke greater than 60 mm or incorrect coupling| Remove power and re-power again

2

| Unexpected collision within the stroke| Normal operation| The actuator checks the stall condition 5 times. At the end of the attempts it signals an ano- maly. The actuator does NOT learn the new stroke, but after 60s repeats the attempts to check the blocking conditions.| RED fast blinking| Valve blocked| Reverse the con trol signal

3

| Stroke greater than expected| Normal operation| The actuator moves to the new crash position with low spe- ed signaling an anomaly. The actuator does NOT learn the

new stroke.

| RED fast blinking| damaged valve or incorrect coupling| Reverse the con- trol signal

4

| Low supply voltage| Normal operation| The actuator continues to operate but performance is not guaranteed. If the low voltage events persist (events greater than 10), the actuator stops working.| RED blinking alter- nately fast (5sec) and slow (5sec) + GREEN ON| 1. Wrong sizing of transformer| Check and restore power

2. Unstable power supply

5| High supply voltage|

Normal operation

| The actuator continues to operate but performance is not guaranteed. If the high voltage events persist (events greater than 10), the actuator stops working.|

RED slow blinking

| 1. Wrong sizing of transformer| Check and restore power

2. Unstable power supply

6

| temperature sensors error| Normal operation| Temperature or ΔT regulation loops not working.| RED blinking alter- nately fast (5sec) and slow (5sec) + GREEN ON| 1. Incorrect tem perature probe

connection

|

Check the connection and the condition of the temperature sensor

2. Temperature probes damaged
3. Temperature detected outside the range of use

7

| Pressure sensors error|

Normal operation

| Pressure or ΔP regulation Loops not working| Pressure detected outside the range of use or probes damaged

STANDARD LEDs BEHAVIOUR

LED 1 and LED 2 Actuator status
1 FIXED GREEN Actuator has arrived at the extreme end of the calibration

stroke
2| GREEN SLOW BLINKING| Actuator has arrived or is moving towards an intermediate point of the calibration stroke
3| RED and GREEN BLINKING AL- TERNATIVELY| Actuator is calibrating the stroke or performing the initial positioning
4| RED and GREEN FIXED| Manual control activated, the actuator ignores the control signal. WARNING!

The board is powered

LED 7 (RED) and LED 8 (RED) Actuator status
1 LED 7 RED ON; LED 8 RED ON Stable power supply of the actuator
2 LED 7 RED ON; LED 8 OFF Unstable actuator power supply; possible hardware

problem

DIMENSIONS [mm]

Pozzetti sonde di temperatura

Sonde di temperatura

Mod. DN L H h D b a f Holes Weight [kg]

EBV

| 65| 290| 320| 175| 185| 20| 145| 18| 4| 18
80| 310| 330| 186| 200| 22| 160| 18| 8| 28
100| 350| 341| 206| 220| 24| 180| 18| 8| 32
125| 400| 364| 255| 250| 26| 210| 22| 8| 45
150| 480| 382| 275| 285| 26| 240| 25| 8| 60

iSMA CONTROLLI S.p.A. – Via Carlo Levi 52, 16010 Sant’Olcese (GE) – Italy | [email protected]

www.ismacontrolli.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

iSMACONTROLLI User Manuals

Related Manuals