DANGER
Hazardous voltage. Will cause death or serious injury. Turn off and lock out
all power supplying this device before working on this device. Replace all
covers before power supplying this device is turned on.
CONTENTS:
Information
Order separately
Adapter Selection
Suitable for | |
---|---|
5ST3820- 1 | 5SY4/5/6/7/8 – 1/2pol, 5SP4 – 1pol |
5ST3820- 2 | 5SY4/5/6/7/8 – 3/4pol, 5SP4 – 2/3/4 pol |
5ST3820- 3 | 5SM2 |
5ST3820- 5 | 5SU1 (max. 3TE) |
5ST3820- 6 | 5SL6/4 – 1/2pol, 5SY…CC, 5TL1 – 1/2 pol |
5SL60, 5SV60
5ST3820- 7| 5SL6/4 – 3/4pol, 5SY…CC, 5TL1 – 3/4 pol|
Required tools
Assembly
MCB | RCD | SCD | |
---|---|---|---|
5ST3072- 0MC | 5SL6/4 | 5SY4/5/6/7/8 | 5S..0 |
5SV1/3/4/9 | 5SV60 | 5SU1(max. 3TE) | 5SM2 |
5ST3073- 0MC
Remote
Connection
Auxiliary Switch (AS) | Fault signal Contact (FC) | |
---|---|---|
N, L = Supply voltage | 21 = Normally Open (NO) | 11 = Normally Open (NO) |
COM = Common reference Terminal for ON/OFF | 22 = return conductor | 12 = return |
conductor
OFF = OFF command max. 10 V DC from the device| 23 = Normally Close (NC)| 13 =
Normally Close (NC)
ON = ON command max. 10 V DC from the device| |
Connection
N, L = Supply voltage| Test! = Initiate test routine (Test command max. 10 V
DC from the device)
---|---
COM = Common reference Terminal for ON/OFF/Test!| IRT1 = Combined Terminal L1
for IR measurement and RCD Test
OFF = OFF command max. 10 V DC from the device| IR2, IR3, IRN = Terminals L2,
L3, N for IR measurement
ON = ON command max. 10 V DC from the device|
COM, ON, OFF, Test!: 230V recommended rating voltage for switch and wires.
Information
| RCA| RC OFF| RC ON| OFF| O| I| ARD| IR
Measurement
| RCD Test
---|---|---|---|---|---|---|---|---|---
EN| Remote control auxiliary| Remote switching / test function is
switched off
| Remote switching / test function is
switched on
| Device combination is in the OFF position and protected against being
switched on| Device combination is switched off| Device combination is
switched on| Device with automatic reclosing| Measurement of Isolation
Resistance| Test of residual current device
| | | | | | | | |
Information
RC ON and RC OFF are only possible by manually switching the yellow slider on the remote control auxiliary.
Operation
RC ON
OFF Manual-OFF“ reset function
Assembly
Locking and sealing
Mountable accessories
5ST3072-0MC / 5ST3073-0MC + 5SM2… + 5SY… / 5SL…
- The RC-Unit/circuit breaker combination can be switched on using the 5ST3820-3 and adapters as well as those suitable for MCBs.
- It is not possible to switch off the RC unit via the remote control auxiliary; the circuit is switched off via the MCB contacts.
- The RC-Unit switched on asynchronously, in other words before the MCB.
- If the RC-Unit is switched off the RCA will switch twice.
- RC-Unit on: O -> I
- MCB on : O -> I
Information
- During first usage of RCA an initialization time of approx. 10-30 s is expected.
- The remote control differentiates between fault tripping and manual OFF. After a fault trip of the mounted protection device (MPD), the remote control can still be switched remotely. After manual OFF, remote switching is locked. This is for the safety of the operator and/or the plant. To release this lock, see: “manual-OFF” reset function. For on-site maintenance, an additional mechanical locking is recommended.
- The remote control can only be switched either wired or via the wireless interface. Switching via the wireless interface must be activated in SENTRON Powerconfig first.
- During firmware update, the AS/FC port functions (5ST3072-0MC) are temporarily unavailable. Avoid using these functions during the update.
- Test and switching commands are placed in a queue. Several commands must be sent at an interval of at least 15 s. The response time until a command is executed can take 1-3 s.
Status LED
If yellow slider is in RC ON and main protection device (MPD) is switched on manually during a fault trip is still present, the MPD performs a free tripping. The free tripping is handled as manual off. Please check installation and switch devices back on manually so that remote control is possible.
COM LED
Information
Automatic on = automatic reclosing function (ARD):
- When the main protection device is triggered by a fault, the automatic reclosing device (ARD) attempts to switch back on automatically three times (default setting: 10 sec / 1 min / 10 min).
- If all three reclosing attempts fail, this function (ARD) is locked. The LED indicates the status.
- While waiting for an ARD attempt, the RCA can be switched on manually or via remote. Max. 3 attempts are possible, including ARD function.
- ARD reset: To release the ARD from lock status after three failed reclosing attempts, the yellow slider must be manually set from “RC ON ” to “OFF ” and back again to “RC ON “, then the whole device combination must be switched on again with the handle.
- The ARD function can be parametrized via the wireless interface with SENTRON Powerconfig: On/Off, waiting times, second retry after the first three reclosing attempts.
RCD/IR Test: only for 5ST3073-0MC
- The RCD/IR test can be enabled /disabled and parametrized, depending on the configured main protection device (MPD) via the wireless interface with SENTRON Powerconfig. An IR (insulation resistance) test is always done after a trip acc. IEC63024, if enabled.
- after a successful test the RCA is automatically turned on again
- after an failed test, the installation must be checked for failures. No automatic ON in this case. Reset LED via yellow slider (RC ON → OFF → RC ON).
- After the removal of the failure another test is recommended.
- The handle must have following state before the tests can be executed, in case both are executed separately: RCD-Test: handle on: I; IR-Test: handle off: O
Information
License Information
The products contains third-party software. For further information, please
refer to: https://support.industry.siemens.com/cs/ww/en/view/109797242
Documents / Resources
|
SIEMENS 5ST3-COM Remote Control Auxiliary
Fernantrie
[pdf] User Guide
5ST3-COM Remote Control Auxiliary Fernantrie, Remote Control Auxiliary
Fernantrie, Control Auxiliary Fernantrie, Auxiliary Fernantrie, Fernantrie
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>