Automatic Centre AQS-KAM-RH-V CO2 Temperature Humidity Transmitters Instruction Manual
- June 8, 2024
- Automatic Centre
Table of Contents
AQS-KAM-xx, AQS 71-KAM-T, AQS-KAM-RH-V
CO2 TEMPERATURE HUMIDITY TRANSMITTERS
Instruction Manual
GENERAL
The AQS Temperature Transmitters set new standards in CO2 measurements in HVAC
applications. Operation is based on the infrared principle. A calibration-free
procedure compensates for aging of the infrared source and ensures outstanding
long-term stability. The AQS provide 0…10 V analog output for CO2 and
temperature and are designed for HVAC applications (contact Honeywell for
special applications). They are suitable for direct wiring with universal and
voltagecontrolled inputs. Additionally, the AQS-KAM-xx Temperature
Transmitters feature a built-in passive temperature sensor. The AQS-KAM-RH-V
Temperature Sensor is equipped with a relative humidity sensor. See also
following table.
Table 1. List of devices
OS number| CO2 + temp.
output| temp. output (passive)| rel. humidity output
---|---|---|---
AQS-KAM-00| 0…10 V| Pt1000| —
AQS-KAM-01| Ni1000| —
AQS-KAM-10| NTC101Ω| —
AQS-KAM-20| NTC20kΩ| —
AQS 71-KAM-T| | —
AQS-KAM-RH-V| | 0…10 V
NOTE: Avoid strong mechanical stress and improper handling. The cable
gland and housing cover must be screwed tightly against gas penetration, to
avoid incorrect measurements.
PRODUCT DATA & INSTALLATION INSTRUCTIONS
FEATURES
- Calibration-free technology
- Outstanding long-term stability
- Maintenance free
- universal mounting flange
SPECIFICATION
Power supply | 24 Vac, ±20% (SELV) 15…35 Vdc |
---|---|
Power consumption | 0.6 W |
Max. current consumption | 0.35 A (0.3 sec / 15 sec) |
Ambient Limits
Operating temperature | -20…+60 °C (-4…+140 °F) |
---|---|
Transport and storage | -20…+60 °C (-4…+140 °F) |
Humidity | 0…95% rh, non-condensing |
Safety
Protection class | III as per EN 60730-1 |
---|---|
Protection standard | Housing IP65 as per EN60529 |
Probe IP20
Housing material| Flame retardant V0 as per UL94
Housing| plastic (PC)
Dimensions| see Fig. 1 on page 3
Mounting| duct, M16x1,5 cable inlet
CO2 Sensor
Output signal | 0…10 V |
---|---|
Output current | -1 mA < IL < 1 mA |
Output scaling | 0…10 V = 0…2000 ppm CO2 |
Accuracy (CO2 at | 0…2000 ppm < ± (50 ppm |
25°C [77°F], 1013 mbar) | +2% of measured value) |
Temperature stability: | typ. ± (1 + CO2 conc. [ppm] / 1000) |
ppm / K (-20 … +45 °C)
Response time| t63 < 100 sec at 3 m/s
Warm-up time| < 5 min
Temperature
Output signal | 0…10 V |
---|---|
Output Current | -1 mA < IL < 1 mA |
Output scaling | 0…10 V = 0…50 °C |
Accuracy (20 °C [68 °F]) | ± 0.3 K |
Response time | t63 < 50 sec. at 3 m/s |
AQS-KAM-RH-V | t63 < 60 sec. at 3 m/s |
Table 2. Troubleshooting
Error | Possible cause | Remedies |
---|---|---|
Unrealistic results | Skewed installation | Air inlet and probe tip must be |
perpendicular to air flow.
Low air velocity| Air velocity must be > 1 m/sec (200 ft/min).
Housing not tight| Seal cover and gland tightly.
Long response time| Contamination of sensor or probe| Check sensor and probe
for soiling and clean, as necessary.
Passive Temp. Sensors (AQS-KAM-xx)
Output | 2-wire |
---|---|
Wire resistance (typ.) | 0.4 Ω (terminal-sensor) |
NTC10kΩ
Nominal value | 10kΩ ±0.5% at 25 °C |
---|---|
Accuracy | ±0.2 °C at 25 °C |
Response time (typ.) | t63 < 120 s at 3 m/s air velocity |
Sensitivity (typ.) | -440 Ω / K at 25 °C (non-linear) |
NTC20kΩ
Nominal value | 20kΩ ±0.5% at 25 °C |
---|---|
Accuracy | ±0.2 °C at 25 °C |
Characteristic | NTC20kΩ (see EN0B-0476GE51) |
Response time (typ.) | t63 < 120 s at 3 m/s air velocity |
Sensitivity (typ.) | ≈ -934.5 Ω / K at 25 °C (non-linear) |
Ni1000
Nominal value | 1000 W at 0 °C |
---|---|
Accuracy | ±0.4 °C at 0 °C |
Characteristic | DIN 43760 |
Sensitivity (typ.) | ≈ 6.18 W / K |
Pt1000
Nominal value | 1000 W at 0 °C |
---|---|
Accuracy (IEC751 Cl. B) | 0.3 + 0.005*│t│ at 0 °C |
Characteristic | see EN0B-0476GE51 |
Sensitivity (typ.) | ≈ 3.85 W / K |
Relative humidity (AQS-KAM-RH-V)
Working range | 0…95% RH, non-condensing |
---|---|
Output | 0…10 V prop. to 0…100% RH |
Accuracy at 20 °C | typ. ±2% RH, max. ±3% RH in range of 20…80% RH |
NOTE: Temperature / relative humidity / CO2 accuracy may differ,
depending on various environmental conditions (e.g., air velocity or
temperature difference between the air temperature and the ambient
temperature).
WIRING
wiring run | maximum length |
---|---|
sensor to controller | 200 m (660 ft) |
NOTE: Installation of the sensor near high EMI-emitting devices may lead
to faulty measurements.
Use shielded wiring in areas with high EMI.
Keep 15 cm (5.9’’) min. distance between sensor lines and 230 Vac power lines.
Use two transformers: one for sensors and actuators and one for the
controller.
DIMENSIONS
Fig. 1. Housing dimensions (mm)
MOUNTING
Screw with torque of 1.5 Nm for break-through. Recommended tightening torque:
3.5 Nm.
Fig. 2. Assembly of conduit / cable gland
WIRING
*IMPORTANT
For failure-free operation and performance according to specifications, it is
essential that the supply GND and the measurement GND be wired separately!
Manufactured for and on behalf of the Environmental & Energy Solutions
Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland
by its Authorized Representative:
Home and Building Technologies
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 01
Fax +49 (0) 7031 637 740
http://ecc.emea.honeywell.com
EN1B-0377GE51 R0518F
Subject to change without notice