Helmholz 700-875-WAN01 PLC Control Systems User Guide

June 9, 2024
Helmholz

Table of Contents

700-875-WAN01 PLC Control Systems

Quick Start Guide

REX 100 Router

Order numbers: 700-875-WAN01
700-875-LTE01 | 700-875-LTE11
700-875-LTE51 | 700-875-LTE61
700-875-WIF01 | 700-875-WIF51
from firmware V 2.2.11

Helmholz GmbH & Co. KG | Hannberger Weg 2 | 91091 Großenseebach | Germany 10.01.2024 Phone +49 9135 7380-0 | Fax +49 9135 7380-110 | info@helmholz.de | www.helmholz.de

1 Safety instructions

Target audience

This description is only intended for trained personnel qualified in control and automation  engineering who are familiar with the applicable national standards. For installation, commissioning, and operation of the components, compliance with the instructions and explanations  in this operating manual is essential. The specialist personnel is to ensure that the application or the use of the products described fulfills all safety requirements, including all applicable laws, regulations, provisions, and standards.

Intended use

The device has a protection rating of IP 20 (open type) and must be installed in an electrical  operating room or a control box/cabinet in order to protect it against environmental influences. To prevent unauthorized operation, the doors of control boxes/cabinets must be closed  and possibly locked during operation. The consequences of improper use may include personal injury to the user or third parties, as well as property damage to the control system, the product, or  the environment. Always use the device as intended, so that, for example, it can never be used as the sole  means of averting dangerous conditions on machines and systems.

Operation

Successful and safe operation of the device requires proper transport, storage, setup, assembly, installation, commissioning, operation, and maintenance. Operate the device only in flaw less condition. The permissible operating conditions and performance limits (technical data)  must be adhered to. Retrofits, changes, or modifications to the device are strictly forbidden.

The devices contain components that can be damaged or destroyed by electrostatic discharge. When handling the devices, observe the necessary safety measures against electrostatic discharge (ESD) in accordance  with EN 61340-5-1 and EN 61340-5-2.

Security

The device is a network infrastructure component and therefore an important element in the  security consideration of a plant. When using the device, therefore, observe the relevant rec ommendations to prevent unauthorized access to installations and systems.

RF radiation

Device variants with an integrated modem should be installed and operated with a minimum  distance of 20 cm between the radiator / antenna and your body.

Information

This document explains the initial commissioning of the REX 100 Router. The latest version of  the document and a detailed manual can be found at www.helmholz.de or scan the QR code  directly.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 4

2 Introduction to the function of the REX 100

The REX 100 is an industrial router suitable for worldwide remote access (depending on the REX variant)  to IPv4-capable end devices (PLC, HMI, IP cameras, etc.). This Quick Start Guide explains the basic set tings in the myREX24 V2 portal and shows how to transfer the configuration made there to the REX 100  unit.

No integration into a PLC engineering tool by means of a GSDML file is necessary and system states can  be viewed and diagnoses can be carried out on the password-protected website of the device.

Internet access and a valid account for the myREX24 portal are required for the configuration. The free of  charge software shDIALUP for Windows operating systems is available to you by downloading from  www.helmholz.de.

We recommend using the current version (from V3.7R1.0) of the “shDIALUP” client software for  commissioning. For a successful and secure connection to the myREX24 V2 portal, the firmware  status of all REX 100 routers should be checked regularly and, if necessary, updated with the help of  the system settings in your myREX24 account.

3 Prepare and Connection

Depending on the REX variant, the LAN ports P1 to P4 or P2 to P4 are available for connection to the  machine network. Internal switch functions are active even if the REX 100 router is not connected to the  Internet.

For devices with a modem, antennas available as accessories and a mini-SIM card (except for Wi-Fi vari ants) are required for access to a GSM network. This serves the purpose of identification for the network operator. The insert is found on the left housing side. In order to unlock and remove the insert, please press the recessed yellow button next to the card reader. Please use the supplied tool (SIM card ejector) for this.

When selecting a mobile phone contract, please use a standard mobile phone data tariff. Please  avoid IoT tariffs, because these are often only designed for small amounts of data or low transmission speeds.

3.1 Power supply

The REX 100 is designed exclusively for operation with safety extra-low voltage (SELV / PELV) and is sup plied with 24 V DC via the supplied connector.

The housing of the REX 100 is not earthed. Please make sure to connect the functional earthing connection (FE) of the device to the reference potential of your control cabinet or system structure in order  to ensure correct ESD derivation of the antenna and network sockets.

The device is intended to be supplied by an isolated Limited Energy Source according to UL61010-1 (3rd ed cl. 9.4)  or according to UL60950-1/UL62368-1 or Class 2 according to NEC. Please use Cu power supply wires, AWG 28- 12. Maximum length of removed insulation is 10 mm. Temperature cable rating is 87 °C.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 5

3.2 Power source requirement

This device may only be operated with power supplies that meet the requirements of EN 62368-1 for  power sources of limited power. Otherwise, the device must be operated in a housing that meets the requirements of fire protection according to EN 62368-1.

3.3 Terminals and Interfaces

Rigid copper wires with a max. diameter of 1.5 mm² can be clamped onto the provided connector plug.  Network cables corresponding to at least category 5/5e (CAT-5) should be connected to the RJ-45 sockets.

3.4 Installation position/minimum clearances

The router was designed to be mounted on DIN rails (as per DIN EN 50 022) and intended for installation  in switch cabinets. Installation and mounting must take place in accordance with VDE 0100/IEC 364.  The router can be installed in any position.

It is recommended that minimum clearances to neighboring assemblies are observed during assembly. If  the distances 30 mm on the top and on bottom and 10 mm on each side are maintained, easy access to  the connections and contact options on the router is possible without having to remove other system parts. In addition, there should always be enough space for the necessary cable routing.

3.5 Digital inputs/outputs IO1 and IO2

The bidirectional connections IO 1 and IO2 can – independently of one another – be configured as digital  inputs (standard setting) or as digital outputs.

3.5.1 Inputs

The alarm inputs can be activated with potential-free switches, buttons or relay contacts. IN1 can, for example, be used for the VPN establishing  of connection with the myREX24 portal. An alarm can be triggered with the IN2.

**Example wiring of the inputs:

**

3.5.2 Outputs

When selecting for the output circuit, the REX can provide the status of an active Internet, VPN or user portal connection as a signal. Each output can have a max. 0.5A (@ 24 V).

Example wiring of the outputs:


QuickStart Guide REX 100 | Version 10 | 10.01.2024 6

The parameterization is carried out via the alarm management in the myREX24 V2 portal. Alternatively,  the input and output functions could also be displayed in a dashboard using the data point functions.

When using outputs O1 and O2, the corresponding input signals I1 and I2 assume the respective  output status and can themselves no longer be used externally for other alarm input signals.

3.6 REX 100 WAN

Connect the WAN interface of the REX 100 (P1 WAN) with a patch cable with the higher level (compa ny) network/router. 3 LAN ports are available for connection to the machine network and for commis sioning via PC.

3.7 Antenna connection

Only connect antennas that are included in the Helmholz accessories and ensure prior to installation  that the antenna is positioned in such a way that the modems receive a permanent radio signal to a  WLAN access point or can connect to an adequate 4G mobile network. Also be sure to follow the instruc tions from the technical data sheets of the antenna manufacturer and do not install these into metal  housings (e.g., control cabinet).

3.7.1 REX 100 WiFi

The WLAN radio module only works in the 2.4 GHz range and it must be ensured that the required inter net connection can be established via an existing access point in the (company) network. The required  WLAN antenna is connected to the RP-SMA socket. The 4 LAN ports are then available for connection to the machine network and for commissioning/diagnosis via PC.

3.7.2 REX 100 LTE (4G)

For radio reception, a suitable antenna must at least be screwed  onto the SMA socket “MAIN”.

In order to improve the data throughput, a second antenna terminal is available on the REX 100 LTE router with the SMA socket “Rx” that can be used as an option. This functionality is called antenna diversity in the “WCDMA mode” and Downlink-MIMO in the “LTE mode”.

The second receiver antenna should not be located in the immediate vicinity of the main antenna. In order to improve the diversity gain and reduce other reciprocal interactions (interference effects), the two antennas should be (taking the space available in the application into account) installed with the greatest possible distance between them.

For the same reason, the second antenna should be mounted cross-polarized (rotated by 90° in relation to  the main antenna).

QuickStart Guide REX 100 | Version 10 | 10.01.2024 7

3.8 REX 100 LTE + WAN und REX 100 WiFi + WAN

With this device variant, a failover can be parameterized in the configuration if required (see chapter 5.5).

For this application, connect the WAN interface (P1 WAN) of the REX 100 with a patch cable to the higher-level (company) network/router. 3 LAN ports are available for connection to the machine network and for commissioning via PC.

Furthermore, the requirements from points 3 and 3.6 must be met. The VPN connection is primarily implemented via the WAN interface. If the connection is not established or is interrupted, the REX 100 automatically switches to the appropriate wireless connection. As soon as WAN is available again, it switches back.

Connection examples REX 100:

3.9 Boot process

The PWR LED lights up when the 24-volt supply voltage is applied. The boot process starts following the  internal system check, which is indicated by the blinking RDY LED. The REX 100 is ready for operation as  soon as the PWR LED and RDY LED light up continuously (duration: approx. 90 sec.).

The 4G products 700-875-LTE01 and 700-875-LTE51 are intended for use in Europe and Asia. For  use in North America, please use the “NAG” variants 700-875-LTE11 or 700-875-LTE61. Before  using an LTE router, please compare the LTE frequency bands of the selected device with the support ed frequency bands of the provider in the country of use.

If you have any further questions on this issue, our technical sales team will be happy to help you.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 8

4 Access to the myREX24 V2 portal

The complete configuration of the REX 100 takes place via the myREX24 V2 portal. A secure connection  to the portal is required for this:

The shDIALUP remote client software enables you to administrate the myREX24 V2 portal and realize a  VPN tunnel to a REX router. The software (shDIALUP) can be found in the download area at  www.helmholz.de. There you can also download more documents with additional information at any  time.

Alternatively, you can create the REX configuration with an HTTPS-secured direct call from your  browser. The call is possible via the following URL: https://v2.myREX24.net. However, it is not possible  to realize a VPN remote maintenance via the browser.

Always use your myREX24 V2 account data to log in.

4.1 Registration

You should only register at www.myREX24.net if you do not yet have a myREX24 V2 portal account or  have not received user access from a myREX24 account administrator.

Fill out the required fields there. After your data is checked by our service team (Mon. to Fri., 8 a.m. to 5  p.m. CET), you will receive two separate e-mails with the access data.

One e-mail contains the username, and the second the password.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 9

4.2 Login to the myREX24 V2 portal server

Install the shDIALUP software with administrative rights under a Windows operating system. After open ing the program, select the “V2.myREX24.net” server in the top menu bar and then log in to the  myREX24 V2 portal with your access data.

Your login name can be comprised of your username and company name separated by the @ symbol,  for example: admin@helmholz

Following the initial login, you will be prompted to register a new, individual password for your account.  As the account administrator, you can create and administer additional users after logging in to the  myREX24 V2 portal if necessary.

4.3 Navigation in the portal

Once a user has logged in for the first time, he or she is guided through a tutorial. Navigation, basic settings and switching from the simple view to the extended view are shown.

4.4 Simple and extended views

You can choose between the two views in the menu interface of the myREX24 V2 portal. The “simple  view” is active the first time you log in. You can switch to the “extended view” at any time without changes being lost or losing their validity.

The simple view is mainly used throughout the rest of this Quick Start Guide. The extended view is also  presented in some places for purposes of illustration.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 10

5 Initial router-configuration via the myREX24 V2 portal

 The following information describes the basic configuration steps required to set up a REX router for a  VPN connection. A description of the extended functions can be found in the online help or in the man uals/white papers.

You can go to the online help in the myREX24 V2 portal using the question mark symbol in the lower  left-hand area of the screen.

When you log in for the first time, the myREX24 portal guides you through a brief tutorial. It is recom mended to re-issue the password for your myREX24 account once in accordance with the tutorial.

5.1 Creating a new project

A project is the highest level for carrying out the following tasks:

– – Device administration

– – Remote maintenance

– – Monitoring and alarms

– – Data logging

– – Visualizations

Initially, at least one new project must be created in which a router is assigned. Navigate to the Admin istration section by using the marked symbol (the tutorial also brings you to this point).

QuickStart Guide REX 100 | Version 10 | 10.01.2024 11

A unique project name is now issued in this menu. Additional account users, if created, can be assigned  to this project on the “Access” tab.

5.2 Creating a new device

A router can be added to the tree structure using the green plus symbol or with a right-click of the mouse.

If a project does not yet have a router, the same function is made available in the main view by way of the  green button “Create new device”.

Clicking the respective button starts the configuration assistant, which guides the user through the set tings.

5.3 Configure REX 100 (connection data)

Three simple steps are enough for minimal configuration of the router.

– Selection of the device type

– Network settings

– Transfer of the configuration to the REX router

QuickStart Guide REX 100 | Version 10 | 10.01.2024 12

5.4 Step 1 “Device” – Selection of the type and name

In the first step, the correct device type (matching the device order number) must be selected. A unique,  freely selectable name should be assigned to this router.

Only numbers and letters may be used (0 to 9, A to Z, a to z and no spaces or special characters).

5.5 Step 2 “Internet” – Network settings

In Step 2, the network configuration for the LAN, WAN and, depending on the version, the LTE cellular  or the WiFi settings must be defined.

LAN All REX 100 routers come with the IP address 192.168.0.100/24 as a default. If necessary, mod ify the IP address and subnet mask according to the specifications from the machine network  to be maintained remotely.

WAN The required information for the DHCP or static IP settings is provided by the respective net work administrator. DHCP is preset at the factory.

Modem The parameters for the APN access point (Access Point Name) of the card provider and the  correct SIM PIN must be available to you and be stored here. There are already several provid ers available for selection (sorted by country). In the event that the correct provider is not pre sent, this can also be entered manually.

WLAN Enter the Wi-Fi-specific access data. The corresponding data provides you with the responsible  network administrator.

If you use DHCP, make sure that the DHCP server does not assign an IP address the WAN interface  that is already active on the LAN side. IP addresses from two different subnets must be assigned to  each router’s LAN and WAN interfaces.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 13

Examples: LAN network settings, WLAN or APN access data and download

5.6 Step 3 “Configuration” – Coupling/pairing the router with the portal

In step 3, the basic settings of a minimum configuration for the REX 100 are now stored in your portal  account and must now be transferred to the device. By clicking on the download button (here marked in  red), the configuration file is downloaded from the portal server and can then be transferred to the REX  router using a FAT-formatted USB stick.

We recommend the “Download configuration to PC” variant for the initial configuration.

6 Router configuration transfer options

Newly created or subsequently modified device configurations can be transferred to the REX 100 in a  variety of ways.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 14

1. Download configuration to PC (via USB flash drive). The configuration file is saved on the PC and  can subsequently be transferred to the REX 100 using a USB stick (subsequent procedure described  in chapter 6.1).

2. Synchronize (recommended for subsequent modifications). If the router has already been config ured and a connection with the portal is established, each subsequent change to the configuration  can be carried out via the existing VPN remote connection (further procedure described in Section  6.2).

3. Transfer configuration to the device (with LAN connection, only possible via shDIALUP). For this  configuration option, the REX 100 must be accessible directly in the LAN from the PC. The PC  must also be logged in on the Internet via the shDIALUP dial-up client using your myREX24 ac count at the same time.

The transfer via USB stick (point 1) is explained in this Quick Start Guide, and how retroactive changes  can be transferred via the function “Synchronization” (Point 2).

6.1 Transferring the configuration using a USB flash drive

Ensure that the power supply is connected to the REX 100. Download the configuration file provided  through the myREX24 portal to the FAT-formatted USB flash drive connected to your PC using the  download symbol.

The myrex24.mbn(x) configuration file must be stored in the root directory of your USB flash drive  and may not be renamed.

Now carry out the steps described in chapter 12 “Load configuration/ firmware update from the USB  stick”.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 15

6.2 Synchronization

As soon as the REX 100 has logged into your account in the portal, you can transfer subsequent changes  at any time with “Synchronize”. Where there is an existing myREX24-V2 portal connection, the REX 100  checks cyclically whether there is a new configuration available for its serial number and then loads it automatically.

As soon as you have modified and saved one or more parameters, a gray exclamation mark symbol ap pears next to the in green animated online LED with the tooltip: “Device configuration not up to date”.  Click this symbol (or the “Synchronize” button) to start the process.

Synchronization in the simplified view:

Synchronization in the extended view:

QuickStart Guide REX 100 | Version 10 | 10.01.2024 16

The synchronization function is confirmed through the following dialog:

In this menu, you can select optional user-defined settings, such as the sending of infor mation/confirmation mails.

The REX router now accepts the new settings and restarts automatically. As soon as the boot process has  concluded, the REX router logs into the portal again.

7 Connection to the machine network

The following steps presume that the REX 100 has already been configured and that you have suc cessfully logged into your account with shDIALUP. A secure VPN connection to the end device can not be implemented via the browser view (https://v2.myREX24.net).

Logged-in REX 100 routers are identified with a green circle in the dashboard. The secure VPN connec tion between the PC and REX router is not established until the connection button is clicked.

Effective immediately, you can view the setup of your REX router and the functional  overview of the myREX24 V2 portal very easily online.

https://youtu.be/r4KxlV-VgdY

Video tutorial (3:22 min.)

QuickStart Guide REX 100 | Version 10 | 10.01.2024 17

The active connection status to the REX 100 is represented by an animated orange connection button.  The number of active connections made using this account is shown with details in the menu bar.

Once the VPN connection to the REX 100 has been established, all the IPv4 packets valid for the applica ble LAN network on the system side will be forwarded. The parameters (port, VPN IP, LAN IP etc.) used  for this connection are also shown with details in the status bar at the bottom.

To end the remote access connection, click the Disconnect button and accept the final security query. 8 Tips and tricks

8.1 Checking the device status

The device status website of the REX 100 shows the connection status and the active configuration data  of the router. To this purpose, the REX 100 must be accessible in the LAN, meaning that the TCP/IP ad dress of a PC must be in the same IP subnet. To this purpose, enter the LAN IP address of the REX 100 into the address bar of a browser.

Authenticate yourself with the standard

user: helmholz and the
password: router

QuickStart Guide REX 100 | Version 10 | 10.01.2024 18

By clicking on one of the green info symbols in the status fields, you can view further information on  each step of the connection.

If the website of the REX 100 is not accessible, please check the corresponding setting in the  myREX24 portal. Make sure that there are no address space conflicts with any other network inter faces (do not assign the same IP address more than once) in order to be able to communicate with the REX 100.

8.2 VPN port and China gateway

By default, the REX 100 tries to establish an outgoing VPN connection via port 1194 (TCP) to the address  https://vpn-v2.myrex24.net (5.39.123.21).

If necessary, the alternative ports 80 or 443 can be set (device management: “Services” -> “VPN” -> “VPN  Port”).

Please clarify all details about the settings in advance with your local IT department. In order to be able to  establish a secure connection to the myREX24 V2 server with shDIALUP or the REX 100, at least one of  the following TCP ports (80, 1194 or 443) must be enabled for the VPN tunnel in the customer firewall.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 19

China gateway: By default, No Gateway is set.

If the REX Router is used in China, the Gateway “China –Shenzhen Datacenter” can be selected. URL: vpncn-v2.myrex24.net

IPv4 Adresse: 43.247.70.163 ((if name resolution does not work).

Do not use the China Gateway outside China!

8.3 Diagnostics page

In the event of irregularities or interruptions when establishing the connection, the diagnostics page can  provide troubleshooting assistance. In the event of an error, Helmholz technical support requires the  respective result from the individual and autonomous test functions.

8.4 Is a MAC address filter activated in the firewall?

It may be necessary to approve the MAC address of the REX 100 in the higher- level DSL modem or the  firewall. Should it not be possible to establish a connection, please ask the responsible network adminis trator whether such a MAC address filter has been activated.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 20

8.5 Is the connection established over a proxy?

If a connection is not established on the customer network, the required proxy settings may not have  been stored or may be faulty. These settings may be adjusted on the configuration page of the REX 100 in  the Internet settings.

8.6 Device configuration: Services – NTP server

For the internal system time of the REX 100, this carries out a comparison using a time server on the In ternet at regular intervals. Where necessary, you can individually set the preset NTP server entry and the  interval.

Various functions in the myREX24 portal require a current time setting in the REX 100.

8.7 Device configuration: Services – Mail settings

If you would like to use the REX 100 function for the automatic sending of e-mails, port 25 (SMTP) may  not be blocked in the firewall of the customer network. You can also use alternative e-mail servers to send  e-mails.

8.8 Mobile connection is interrupted

If the provider for mobile communication remote maintenance interrupts the connection of your REX  100 router, this may have occurred for the following reasons, among others:

– Wrong username/ password

– Ports blocked by the provider

– Credit of prepaid SIM cards used up

QuickStart Guide REX 100 | Version 10 | 10.01.2024 21

9 Remote maintenance of Ethernet CPUs

The LAN ports are suitable for 100 Mbps and full duplex operation and support auto- crossover and  auto-negotiation. No special PROFINET functions are supported. When connecting additional  Ethernet participants (PLC/panel) on the REX 100, it must be ensured that the IP addresses of the  devices lie within the address range of the LAN interface of the REX 100.

9.1 Device settings: Services – Firewall – SNAT

With a REX 100, the SNAT function is activated as a default. With this setting, participants for which no  gateway/router has been entered are accessed via the VPN tunnel. For the CPUs and panels of some  manufacturers, it can be the case that you need to explicitly enter the gateway and deactivate the SNAT  function in order that a remote connection with the end device is possible.

*Gateway: This refers to the configured LAN IP address of the REX 100.

To access a PLC or panel via the VPN tunnel, the OpenVPN adapter must be selected in the correspond ing engineering tool as the interface. The virtual network connection responsible for this is the TAP  Windows Adapter V9.

The excerpt shown here shows the setting to be selected in the PG / PC interface module from the SIMAT IC STEP 7/TIA software.

9.2 Search over IP

With the SEARCHoverIP function activated, unparameterized network components (PLCs with IP ad dress: 0.0.0.0) can be found and configured remotely. However, this search function is not supported by  all control manufacturers!

When SEARCHoverIP is activated, the “remote maintenance network” (remote client) is connected  one-to-one with the LAN network on the device (router) via Layer2. These broadcasts and multicasts  on the remote maintenance side generate additional data traffic through the VPN tunnel. Under  certain circumstances this can lead to IP address conflicts and network disruptions on the router LAN  side. It is therefore recommended to deactivate this function in normal remote maintenance mode!

In the delivery state, SEARCHoverIP is not activated.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 22

10 Description of LEDs and buttons

10.1 Function and status LEDs in normal operation

PWR

|

Indicator light for the power supply

---|---

RDY

|

Readiness indicator (this LED must show a solid light after a max. of 110 sec.)

CON

|

Off: There is no active Internet or VPN connection

Solid light: Internet connection active or possible, but VPN connection inactive

Flashing (1.5 Hz): VPN connection is active.

Rapid flashing (3 Hz): The router is attempting to establish a VPN connection

USR

|

Solid light: When loading default settings, firmware files, or device configurations

Flashing (1.5 Hz): A portal configuration was recognized on the USB stick (see FCN button)

Rapid flashing (3 Hz): A firmware file was recognized on the USB stick (see FCN button)

10.2 RJ45 network LEDs

LED

|

LED-color

|

LED-status

|

Description

---|---|---|---

WAN & LAN

|

Orange

|

LED on

|

Network connection present

Green

|

LED flashing

|

Network data traffic active

10.3 Buttons

FCN

|

1. Function key for manually establishing the connection with the portal server.

2. If the USR LED starts flashing, this means that you have ten seconds to press this button in order to load data from an  inserted USB stick.

---|---

RST

|

Reset button for restarting the router

Use the provided tool to activate the buttons (SIM card ejector).

QuickStart Guide REX 100 | Version 10 | 10.01.2024 23

10.4 myREX24 V2 portal LEDs

|

The device is not connected with the portal.

---|---

|

The device has logged in at the portal and is thus online.

|

Depending on the device type, the router is connected to:

– a machine (PLC) connected on the REX

– the website of a connected machine

– the integrated web server of the device (router)

|

The device configuration is not up to date.

This means: the configuration of a newly created device has not yet been transferred to the device or the changed  configuration of an existing device has not yet been transferred to the device/no synchronization has been carried out. This symbol can be displayed in connection with any of the symbols named above.

Example of the visual representation of the information points on the status of the interfaces in the  “simple view”.

11 Restoring the REX 100 router to its default settings

In order to reset the REX 100 to the factory settings, the following steps are necessary:

  • Apply a supply voltage (or press “RST”) until the PWR LED lights up.
  • Wait until the RDY LED flashes.
  • Press the FCN button for approx. 10–15 seconds until the USR LED flashes orange.
  • After you release the FCN button, the REX 100 reboots and once again has the factory settings.

The IP address of the REX 100 LAN interface is reset to 192.168.0.100/24.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 24

12 Load configuration/firmware update from USB stick

To provide the REX 100 with a configuration or perform a firmware update from a USB stick, please carry  out the following steps:

  • The start process of the device must be completed (PWR & RDY LEDs light up continuously).
  • Save the file in the root directory of a standard FAT-formatted USB stick. Important! Do not  change the file name.
  • Insert the USB stick into the USB interface of the REX 100.
  • Once the USR LED starts flashing, you will have ten seconds to press the FCN button. Then hold  it pressed until the USR LED lights steadily.
  • During the operation, the voltage supply should not be interrupted.
  • Once the USR LED lights up continuously, you can release the FCN button, at which point the data will be loaded from the USB stick.
  • The process is complete once the PWR and RDY LEDs light up again permanently.

Ensure that either only the firmware file or only the configuration file is found in the root directory of  the USB stick. If you wish to update both the firmware and the configuration, carry out the following  steps consecutively for each file.

Once the configuration file has been successfully transferred, the file will automatically be renamed  “Xmyrex24.mbn(x)”, making it impossible to accidentally reuse it a second time.

The firmware and the client software „shDIALUP“ of the REX 100 can be easily updated via the website. Please download the desired file from www.helmholz.com or scan the QR code.

REX 100 firmware and „shDIALUP“ dial-up client

QuickStart Guide REX 100 | Version 10 | 10.01.2024 25

13 Technical data

13.1 REX 100 WAN

Order no.

|

700-875-WAN01

---|---

Article designation

|

REX 100 WAN

Dimensions (D x W x H)

|

32,5 x 58,5 x 76,5 mm

Weight

|

Approx. 130 g

Number of inputs | type

|

2 | DC 24 V, as per DIN EN 61131-2 Type 2

Number of outputs | type

|

2 | DIN EN 61131-2 Type 3

WAN-interface

|

1x

Type

|

10-Base-T/100-Base-T

Connection

|

RJ45 socket

Transmission rate

|

10/100 Mbit/s

LAN-interface

|

3x

Type

|

10-Base-T/100-Base-T

Connection

|

RJ45 socket

Transmission rate

|

10/100 Mbit/s

USB-interface

|

1x

Protocol

|

USB 2.0 Host

Connection

|

USB-A-socket

Status indicator

|

4 LEDs, functional status, 8 LEDs, Ethernet-status

Voltage supply

|

DC 24 V, 18 … 30 V DC

Current draw

|

max. 100 mA with DC 24 V

Power dissipation

|

max. 2,4 W

Environment requirements

|

Ambient temperature

|

-40 °C … +75°C

Transport and storage temperature

|

-40 °C … +85 °C

Relative humidity

|

95 % r. H. without condensation

Pollution degree

|

2

Protection rating

|

IP20

VPN

|

Protocol

|

OpenVPN, 1 tunnel

Encryption method

|

Control Channel: TLSv1.2, cipher ECDHE-RSA-AES256-GCM-SHA384 Data Channel: Cipher ‘AES-256-GCM’ initialized with 256 bit key

Authentication

|

Pre-Shared-Key, X.509

Certifications

|

UL

UL

|

UL 61010-1/UL 61010-2-201

Voltage supply

|

DC 24 V (18 … 30 V DC, SELV and limited energy circuit)

Pollution degree

|

2

Altitude

|

Up to 2,000 m

Temperature cable rating

|

87°C

QuickStart Guide REX 100 | Version 10 | 10.01.2024 26

13.2 REX 100 WiFi

Order no.

|

700-875-WIF01/700-875-WIF51

---|---

Article designation

|

REX 100 WiFi

Dimensions (D x W x H)

|

32,5 x 58,5 x 76,5 mm

Weight

|

Approx. 130 g

Number of inputs | type

|

2 | DC 24 V, as per DIN EN 61131-2 Type 2

Number of outputs | type

|

2 | DIN EN 61131-2 Type 3

WLAN-interface

|

RP-SMA socket

Type

|

IEEE802.11b/g/n

Frequency range

|

EU (2.412 GHz – 2.472 GHz, 1-13 Channel)

Maximum output power

|

19 dBm EIRP, RF power including maximum antenna gain (3 dBi)

Transmission speed

|

802.11b: 1, 2, 5.5, 11 Mbps

802.11g: 6, 9, 12, 18, 24, 36, 48, 54 Mbps

802.11n: MCS0-MCS7 (max 72.2Mbps)

Wireless security methods

|

AES/CCMP, WEP/TKIP

Network-interfaces (device-dependent)

|

4x LAN (700-875-WIF01); 3x LAN + 1x WAN (700-875-WIF51)

Type

|

10-Base-T/100-Base-T

Connection

|

RJ45 socket

Transmission rate

|

10/100 Mbit/s

USB-interface

|

1x

Protocol

|

USB 2.0 Host

Connection

|

USB-A-socket

Status indicator

|

4 LEDs, functional status, 8 LEDs, Ethernet-status

Voltage supply

|

DC 24 V, 18 … 30 V DC

Current draw

|

max. 120 mA with DC 24 V

Power dissipation

|

max. 2,9 W

Environment requirements

|

Ambient temperature

|

0 °C … +60°C

Transport and storage temperature

|

-40 °C … +60 °C

Relative humidity

|

95 % r. H. without condensation

Pollution degree

|

2

Protection rating

|

IP20

VPN

|

Protocol

|

OpenVPN, 1 tunnel

Encryption method

|

Control Channel: TLSv1.2, cipher ECDHE-RSA-AES256-GCM-SHA384 Data Channel: Cipher ‘AES-256-GCM’ initialized with 256 bit key

Authentication

|

Pre-Shared-Key, X.509

Certifications

|

UL

UL (only 700-875-WIF01)

|

UL 61010-1/UL 61010-2-201

Voltage supply

|

DC 24 V (18 … 30 V DC, SELV and limited energy circuit)

Pollution degree

|

2

Altitude

|

Up to 2,000 m

Temperature cable rating

|

87°C

FCC

|

FCC ID: XPYLILYW1 IC: 8595A-LILYW1

QuickStart Guide REX 100 | Version 10 | 10.01.2024 27

13.3 REX 100 LTE Europe/Asia

Order no.

|

700-875-LTE01/700-875-LTE51

---|---

Article designation

|

REX 100 LTE

Dimensions (D x W x H)

|

32,5 x 58,5 x 76,5 mm

Weight

|

Approx. 130 g

Number of inputs | type

|

2 | DC 24 V, as per DIN EN 61131-2 Type 2

Number of outputs | type

|

2 | DIN EN 61131-2 Type 3

GSM modem

|

Multiband 2G/3G/4G Data Interface

Antenna terminal

|

SMA socket (exterior thread)

SIM-Card type

|

Mini SIM(2FF), 1,8 V/3 V

GSM frequency bands

|

B3, B8

UMTS frequency bands

|

B1, B3, B8

LTE frequency bands (MHz)

|

B1, B3, B7, B8, B20 [from HW 5-3A], B28A [from HW 5-3C]

Output power

|

Class 1 (1W) DCS 1800, Class 4 (2W) GSM 900,

Class 3 (0,25W, 23dBm) 3G, Class 3 (0,2W, 23 dBm) LTE

Data transmission rate

|

LTE Cat.4 – Uplink max. 50 Mbps | Downlink max. 150 Mbps

Network-interfaces

|

4x LAN (700-875-LTE01); 3x LAN/1x WAN (700-875-LTE51)

Type

|

10-Base-T/100-Base-T

Connection

|

RJ45 socket

Transmission rate

|

10/100 Mbit/s

USB-interface

|

1x

Protocol

|

USB 2.0 Host

Connection

|

USB-A-socket

Status indicator

|

4 LEDs, functional status, 8 LEDs, Ethernet-status

Voltage supply

|

DC 24 V, 18 … 30 V DC

Current draw

|

max. 200 mA with DC 24 V

Power dissipation

|

max. 4,8 W

Environment requirements

|

Ambient temperature

|

-40 °C … +75°C

Transport and storage temperature

|

-40 °C … +85 °C

Relative humidity

|

95 % r. H. without condensation

Pollution degree

|

2

Protection rating

|

IP20

VPN

|

Protocol

|

OpenVPN, 1 tunnel

Encryption method

|

Control Channel: TLSv1.2, cipher ECDHE-RSA-AES256-GCM-SHA384 Data Channel: Cipher ‘AES-256-GCM’ initialized with 256 bit key

Authentication

|

Pre-Shared-Key, X.509

UL Certification (only700-875-LTE01)

|

UL 61010-1/UL 61010-2-201

Voltage supply

|

DC 24 V (18 … 30 V DC, SELV and limited energy circuit)

Pollution degree

|

2

Altitude

|

Up to 2,000 m

Temperature cable rating

|

87°C

QuickStart Guide REX 100 | Version 10 | 10.01.2024 28

13.4 REX 100 LTE north America versions / „NAG“

Order no.

|

700-875-LTE11/700-875-LTE61

---|---

Article designation

|

REX 100 LTE (NAG)

Dimensions (D x W x H)

|

32,5 x 58,5 x 76,5 mm

Weight

|

Approx. 130 g

Number of inputs | type

|

2 | DC 24 V, as per DIN EN 61131-2 Type 2

Number of outputs | type

|

2 | DIN EN 61131-2 Type 3

GSM modem (4G)

|

Multiband GSM/GPRS/WCDMA/LTE data interface

Antenna terminal

|

SMA socket (exterior thread)

SIM-Card type

|

Mini SIM(2FF), 1,8 V/3 V

GSM/GPRS/EDGE frequency bands

|

850, 1900 MHz; max. 236kbps

HSxPA frequency bands

|

1900 (B2), 850 (B5) MHz; Downlink max. 21 Mbps, Uplink max. 5,76  Mbps

LTE frequency bands (MHz)

|

700 (B17), 850 (B5), AWS 1700 (B4), 1900 (B2) for AT&T and T-Mobile,  not suitable for Verizon!

Network-interfaces

|

4x LAN (700-875-LTE11); 3x LAN/1x WAN (700-875-LTE61)

Type

|

10-Base-T/100-Base-T

Connection

|

RJ45 socket

Transmission rate

|

10/100 Mbit/s

USB-interface

|

1x

Protocol

|

USB 2.0 Host

Connection

|

USB-A-socket

Status indicator

|

4 LEDs, functional status, 8 LEDs, Ethernet-status

Voltage supply

|

DC 24 V, 18 … 30 V DC

Current draw

|

max. 200 mA with DC 24 V

Power dissipation

|

max. 4,8 W

Environment requirements

|

Ambient temperature

|

-40 °C … +75°C

Transport and storage temperature

|

-40 °C … +85 °C

Relative humidity

|

95 % r. H. without condensation

Pollution degree

|

2

Protection rating

|

IP20

VPN

|

Protocol

|

OpenVPN, 1 tunnel

Encryption method

|

Control Channel: TLSv1.2, cipher ECDHE-RSA-AES256-GCM-SHA384 Data Channel: Cipher ‘AES-256-GCM’ initialized with 256 bit key

Authentication

|

Pre-Shared-Key, X.509

FCC modem

|

FCC ID: R17LE910NA

This device variant is not suitable for operation in the European Economic Area (EEA)! We recommend  using an AT&T SIM card to use the 700-875-LTE11/61 in the United States. The required frequencies are  supported for the network operator Verizon, but this operator refuses to establish the connection because  only approved devices are accepted in the Verizon GSM network.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 29

The contents of this Quick Start Guide have been checked by us so as to ensure that they match the hardware  and software described. However, we assume no liability for any existing differences, as these cannot be fully  ruled out. The information in this Quick Start Guide is, however, updated on a regular basis. When using your  purchased products, please make sure to use the latest version of this Quick Start Guide, which can be viewed  and downloaded on the Internet from www.helmholz.de.

Our products contain open-source software, among others. This software is subject to the respectively relevant license condi tions. We can send you the corresponding license conditions, including a copy of the complete license text together with the  product. They are also provided in our download area of the respective products under www.helmholz.de. We also offer to send  you or any third party the complete corresponding source text of the respective open-source software for an at-cost fee of 10.00  Euro as a DVD upon request. This offer is valid for a period of three years, starting from the date of product delivery.

Our customers are important to us, we are happy to receive suggestions and ideas for improvement. If you have any questions  regarding the use of the product, please contact Helmholz Support by phone or send an e-mail to support@helmholz.de.

All trademarks shown or mentioned in this document are the property of their respective owners or manufacturers. The repre sentation and naming serve exclusively to explain the use and setting options of the products documented here.

QuickStart Guide REX 100 | Version 10 | 10.01.2024 30