Helmholz 700-860-WAL01 Wall IE Industrial NAT Gateway and Firewall User Guide
- June 5, 2024
- Helmholz
Table of Contents
Quick Start Guide
WALL IE, Industrial NAT Gateway/Firewall
Order number: 700-860-WAL01
As of firmware V1.10
Version 14
Safety instructions
Target audience
CAUTION
This description is only intended for trained personnel qualified in control
and automation engineering who are familiar with the applicable national
standards.
For installation, commissioning, and operation of the components, compliance
with the instructions and explanations in this operating manual is essential.
The specialist personnel is to ensure that the application or the use of the
products described fulfills all safety requirements, including all applicable
laws, regulations, provisions, and standards.
Intended use
WARNING
The device has a protection rating of IP 20 (open type) and must be installed
in an electrical operating room or a control box/cabinet in order to protect
it against environmental influences. To prevent unauthorized operation, the
doors of control boxes/cabinets must be closed and possibly locked during
operation.
The consequences of improper use may include personal injury to the user or
third parties, as well as property damage to the control system, the product,
or the environment. Use the device only as intended!.
Operation
ATTENTION
Successful and safe operation of the device requires proper transport,
storage, set up, assembly, installation, commissioning, operation, and
maintenance. Operate the device only in flawless condition. The permissible
operating conditions and performance limits (technical data) must be adhered
to. Retrofits, changes, or modifications to the device are strictly forbidden.
Security
ATTENTION
The device is a network infrastructure component and therefore an important
element in the security consideration of a plant. When using the device,
therefore, observe the relevant recommendations to prevent unauthorized access
to installations and systems. Further information on this can be found in the
device manual.
Introduction
WALL IE, the Industrial NAT Gateway and Firewall, simply integrate machine
networks into the high-level production or company network using network
segmentation, packet, and MAC address filtering.
The NAT operating mod e serves the forwarding of the data traffic between
various IPv4 networks. It enables the address translation via NAT and uses
packet filters for the limitation of access to the automation network located
below.
In the Bridge operating mode, the WALL IE acts as a network bridge in an IPv4
subnetwork. In contrast to normal switches, packet filtering is possible in
this operating mode. This means that the restriction of access to individual
areas of your network can be achieved without having to use different networks
for this purpose. This document explains the initial commissioning of the WALL
IE using the “NAT” and “Bridge” application examples. Only the most important
settings are explained.
For a detailed description of all functions and important safety instructions, please refer to the WALL IE manual. This can be found at www.helmholz.de or scan the QR code directly.
https://www.helmholz.de/goto/700-860-WAL01#tab-documentation
Connecting the WALL IE
The WALL IE must be supplied with DC 24 V at the wide range input 18-30 V DC
via the supplied connector plug. The connection (FE) is for the functional
earth. Connect it properly to the reference potential.
The WALL IE is designed exclusively for operation with safety extra-low
voltage (SELV/PELV).
The RJ45 socket “P1 WAN” is used to connect the external network. The RJ45
sockets “P2 LAN-P4 LAN” are switched and are used to connect the internal
network.
The inputs IN1 and IN2 have no function in the current firmware version but
will be available for external switching of firewall rules in a later firmware
version.
The housing of the WALL IE is not grounded. Please connect the functional
earth connection (FE) of the WALL IE properly to the reference potential.
The device may only be operated with power supplies that meet the
specifications of EN/IEC 60950- 1 for power sources of limited capacity.
Otherwise, the device must be operated in an enclosure that meets the
requirements of a fire protection enclosure according to EN/IEC 60950-1.
Initial access to the web interface
The WALL IE is delivered from the factory with the IP address 192.168.0.100
and the subnet mask 255.255.255.0 on the LAN side. Access to the web interface
is only possible via the P2 – P4 LAN ports.
The IP address of your network adapter must first be set in accordance with
the IP subnet of the WALL IE: Start → Settings → Network and Internet → Change
Adapter settings → Properties → Internet protocol version 4 Now connect a
patch cable with the LAN connection of your PC and one of the LAN ports P2- P4
of the
WALL IE.
The web interface can be reached in the delivery condition by entering the URL
“https://192.168.0.100” on the browser page.
For security reasons, the web interface can only be reached through a secured HTTPS connection. An exception rule must be confirmed in the browser once to reach the website. A certificate for the connection backup can be stored in the “Device/HTTPS” menu.
With the first login, you will be requested to set a password for the “admin”
user.
The password must contain at least 8 characters and can be up to 128
characters long, it can contain special characters and numbers. With the
button “Continue” the password will be saved in the device and you will be
redirected to the “Overview” page of the WALL IE.
The main user is always “admin”.
In addition to the main user, the “it-user” and “machine-user” can also be
used with limited rights.
The users can be activated and the affiliated passwords set in the
“Device/Password” menu.
Please memorize the password carefully! For security reasons, there is no way to reset the password without setting the device to factory settings.
Main view
The “Overview” website of the WALL IE always opens after the login. The
“Overview” main view contains an overview of the most important settings and
information of the WALL IE.
The topmost line contains the menu with the functions for configuration.
Please check the WALL IE website for a newer firmware version. The firmware
update is described on page 18.
Firmware link: http://www.helmholz.de/goto/700-860-WAL01#tab-software
http://www.helmholz.de/goto/700-860-WAL01#tab-software
Choosing the operating mode
Depending on the application for the WALL IE, the operating mode must be
defined at the beginning.
WALL IE supports two basic modes of operation: NAT and Bridge.
6.1 The NAT operating mode
When an automation cell with preset IP addresses is to be incorporated into a
company network with other IP addresses, the IP addresses of the machine must
normally all be set again.
When using Network Address Translation (NAT), WALL IE offers the possibility
to leave the IP addresses of the machine as they are, but to enable
communication with
the machine network with its own IP addresses from the company network.
In the NAT operating mode, WALL IE forwards the data transfer between various
IPv4 networks (Layer 3) and exchanges the IP addresses with the help of NAT.
Packet filters and MAC address filters can also be configured to control the
data transfer permitted.
Broadcast traffic is generally filtered at the WALL IE, which means that the time behavior of the machine network is not impaired by the company network.
Basic NAT, also known as “1:1 NAT” or “Static NAT”, is the translation of
individual IP addresses or of complete IP address ranges.
With the help of port forwarding, it is possible as an alternative to
configuring those packets to be forwarded to a particular TCP/UDP port of the
WALL IE to a certain participant in the machine network (LAN).
The NAT operating mode thus also allows the integration of several automation
cells that use an identical IP address range into the same Company network.
Each automation cell can be assigned different free IP addresses from the
company network.
If “NAT” is your planned application case, please continue reading on page 8.
6.2 The Bridge operating mode
In the Bridge operating mode, WALL IE behaves like a layer 2 switch between
the machine network (automation cell) and the company network. The IP
addresses in the company network are in this case in the same IP address space
(subnet) as the addresses in the machine network.
Access between the two network areas can be limited or secured with packet
filters and MAC address filters.
This allows the separation of parts of the company network without using
different network addresses.
If “bridge” is your planned application case, please continue reading on page
15.
Application „NAT“
To activate the NAT operating mode, select the “Operating Mode” menu point in the “Device” menu and set this to “NAT”.
7.1 Adjustment of the IP addresses in the NAT operating mode
Click on the “Network” menu and select the submenu “Interface”. The IP
addresses of the WALL IE in the WAN and in the LAN (“WAN IP”/”LAN IP”), as
well as the affiliated subnet masks (“WAN netmask”/”LAN netmask”) can be
defined here. A DNS server and a default gateway can also be indicated. This
is necessary when devices from the LAN should reach the Internet via the WALL
IE.
If these are not indicated (“0.0.0.0”), then communication of devices in the
LAN with the Internet is prevented. It is necessary to indicate a DNS server
for the SNTP service.
Optionally, the WAN-IP settings, the DNS server, and the default gateway can
also be obtained using DHCP.
The entry is saved with the “Submit” button and the IP settings are then
activated immediately. The current entry is rejected without acceptance with
“Decline”.
If you change the LAN IP address, you may need to reopen the WALL IE web page on the browser under the new IP address and log in again.
7.2 Setting up “Basic NAT” rules
To use Basic NAT functionalities, the operating mode of the WALL IE must be
set to “NAT”. Select the “NAT” menu and the “Basic NAT” submenu. Enter the
first rule and save it using the button.
The “External IP” is a free IP address from the WAN IP address range. This must not have been assigned to any other Ethernet station (in the WAN) yet! The “Internal IP” is the existing IP address of the network node in the machine (LAN). As “Comment” any text can be entered. With this ‘additional WAN interface,’ the address conversion (“natting”) to the entered LAN IP (the target device) is then realized in the WALL IE.
Status: = Rule is active, a click on the lamp symbol changes the rule status
to inactive
= Rule is inactive, a click on the lamp symbol changes the rule status to
active
Possible actions: delete a rule edit a rule copy a rule
In the case of a “Basic NAT” rule, all ports for “WAN to LAN” data transfer are initially blocked for this rule for security reasons! In order to enable access, packet filter rules must be created or the default action for the packet filters be set to “Accept”. The “LAN to WAN” data transfer is initially always enabled but can also be limited by packet filter rules or the default action.
7.3 Packet filter “WAN to LAN”
The packet filters can be used to restrict access between the company network
(WAN) and the machine network (LAN). For example, it can be configured that
only certain subscribers from the company network are allowed to exchange data
with defined subscribers from the automation cell.
The following filter criteria on layers 3 and 4 are available: IPv4 addresses,
protocol (TCP/UDP/ICMP), and ports.
Click on the “Packet Filter” menu and select the sub-menu “WAN to LAN”.
With the “Default Option,” you can set whether all frames are generally
allowed (“Accept”) and only special packets are filtered (“Blacklisting”), or
whether all frames are generally prohibited (“Reject” / “Drop”) and only those
frames are allowed to pass through that correspond with the filter rules
(“Whitelisting”).
If you initially do not wish to filter, set the default action to“Accept”.
In order to limit access to the machine network to certain participants in the WAN, set the default action to “Reject” or “Drop”. In the case of prohibited frames from the WAN, “Reject” sends an error message in response, while “Drop” rejects the frame without sending an error message.
Example: A PC in the company network (WAN) has the IP address 10.10.1.11 (e.g.
a visualization).
This PC should be able to access the CPU with the IP address 192.168.10.1
within the LAN via port 102 with the help of the TCP protocol.
Now enter the following rule and save it with the button.
Source IP indicates the IP address of the active device in the company network
(WAN).
Destination IP specifies the addressed device in the machine network (LAN).
The filter rules can be defined for one protocol type with protocol “TCP”,
“UPD” or “ICMP”.
Destination Ports indicate the ports to which the filter rules apply.
If a filter rule applies to several or even all ports, this can be simply defined in the “Destination Ports” field. A list of ports is indicated separated by commas: “80,443,1194”. A port range can be indicated with a colon “4000:5000” or “1:65535” for all ports. Combinations are also possible: “80,443,4000:5000”.
It is also possible to configure the access of several participants with one another. An IP range can be defined with a dash: “10.10.1.10-10.10.1.20“. A list of IP addresses is indicated with commas: “10.10.1.10,10.10.1.15,10.10.1.20”. IP subnet can be also declared using CIDR notation: “10.10.1.10/24”.
Action defines whether this rule allows communication (“Accept”), rejects with an error message (“Reject”), or simply rejects (“Drop”). The appropriate method here should always be chosen in interaction with the “Default Action”. If the Default Action is, for example, “Reject” or “Drop”, the filter rules should all be set to “Accept” (Whitelisting). If the Default Action is “Accept”, a block can be defined in the filter rules with “Reject” or “Drop” for certain devices (Blacklisting).
7.4 Packet filter “LAN to WAN”
By default data traffic is permitted for devices from the machine network
(LAN) to the company network (WAN) without limitations (“Default Action”:
“Accept”).
The general rule can be changed by setting the “Default Action” to “Reject” or
“Drop”. In addition to the general rule, filtering can be further customized
using specific packet filter rules.”
The entry of the filter rules corresponds to the “WAN to LAN” packet filter
rules, the source IP now indicates the IP address of the active device in the
machine network (LAN), and the destination address represents the device in
the company network (WAN).
7.5 SEAT
The function “SNAT (Source NAT)” transparently forwards incoming traffic from
the WAN side to the LAN network. To all packets, forwarded on the LAN side by
WALL IE, the source IP address is replaced with the WALL IE LAN IP address.
Therefore, none of the LAN participants needs the WALLIE LAN-IP as a
„gateway“. This is a considerable advantage when integrating into existing
network structures since the parameters no longer have to be changed here.
7.6 NAPT
“NAPT for LAN to WAN traffic” replaces the sender addresses of queries from
the LAN with the WALL IE WAN IP address.
The option “NAPT: Active” thus enables communication of devices from the LAN with devices in the WAN. WALL IE thereby acts as a gateway to administer the implementation to the IP addresses of the WAN network and looks after the assignment of the response.
In order for the communication from LAN to WAN to work when NAPT is activated, the WALL IE LAN IP address must be entered as a gateway in all devices on the LAN!
If the NAPT option is deactivated, the query packets from the LAN are forwarded from the LAN to the WAN with their original sender IP and sender port.
7.7 Port forwarding
With the help of port forwarding (“Port forwarding for WAN to LAN traffic”),
it can be configured that packets at a certain TCP/UDP port of the WALL IE
(WAN) can be
forwarded to a participant in the LAN (e.g. 10.10.1.1:81 to 192.168.10.5:80).
In the following example, the website (Port 80) of the CPU with the IP
192.168.10.5 via WAN can be reached through access to the WALL IE-own IP
address 10.10.1.1 with Port 81.
Protocol: “TCP” or “UDP”
External port: Port number through which the device on the LAN side is
accessed. On the LAN side, the device is accessed using an internal IP address
and internal port number.
Internal IP: IP address of a device connected to LAN.
Internal Port: Port used to access device connected to LAN.
Comment: Freely definable comment.
“Port forwarding” and “Basic NAT” can be used simultaneously in NAT operating mode. If the default action for the “WAN to LAN” packet filters is set to “Reject” or “Drop”, corresponding filter rules for access must also be created for each port forwarding entry.
Application “Bridge”
To activate the bridge operating mode, select the “Operating Mode” menu item in the “Device” menu and set it to “Bridge”.
8.1 Adjustment of the IP addresses in the bridge operating mode
Click on the “Network” menu and select the sub-menu “Interface”. The IP
addresses of the WALL IE (“LAN IP”) and affiliated subnet mask (“LAN netmask”)
can be defined here. A DNS server and a default gateway can also be indicated.
This is necessary when devices from the LAN should reach the Internet via the
WALL IE. If these are not indicated, then communication of devices on the LAN
with the Internet is prevented.
The entry is saved with the “Submit” button and the IP settings are thus
activated immediately. The current entry is rejected without acceptance with
“Decline”.
If you change the LAN IP address, you may need to reopen the WALL IE web page on the browser under the new IP address and log in again.
In bridge mode, all ports are initially blocked for “WAN-to-LAN” data traffic
for security reasons! To allow access, packet filter rules must be created or
the “Default Action” for the packet filters must be set to “Accept”. LAN to
WAN traffic is always enabled by default but can also be restricted by packet
filters or the default action.
A DHCP client or a DHCP server is not available in the bridge operating mode.
8.2 Packet filter “WAN to LAN”
The packet filters enable the limitation of access between the company network
(WAN) and the machine network (LAN). For example, it can be configured that
only certain participants from the company network may exchange data with
defined participants in the automation cell. The following filter criteria on
layers 3 and 4 are available: IPv4 addresses, protocol (TCP/UDP/ICMP), and
ports.
Select the “WAN to LAN” menu point in the “Packet Filter” menu.
With the “Default Option,” you can set whether all frames are generally
allowed (“Accept”) and only special packets are filtered (“Blacklisting”), or
whether all frames are generally prohibited (“Reject” / “Drop”) and only those
frames are allowed to pass through that correspond with the filter rules
(“Whitelisting”).
If you initially don’t wish to filter, set the default action to“Accept”.
In order to limit access to the machine network to certain participants in the
WAN, set the default action to “Reject” or “Drop”. In the case of prohibited
frames from the
WAN, “Reject” sends an error message in response, while “Drop” rejects the
frame without sending an error message.
Example: A PC in the company network (WAN) has the IP address 10.10.1.11 (e.g.
a visualization).
This PC should be able to access the CPU with the IP address 10.10.1.30 within
the LAN via port 102 with the help of the TCP protocol. Now enter the
following rule and save it with the button.
Source IP indicates the IP address of the active device in the company network
(WAN).
Destination IP is the addressed device in the machine network (LAN).
The filter rules can be defined for one protocol type with protocol “TCP”,
“UPD” or “ICMP”.
Destination Ports indicate the ports to which the filter rules apply.
If a filter rule applies to several or even all ports, this can be simply
defined in the “Destination Ports” field. A list of ports is indicated
separated by commas: “80,443,1194”. A port range can be indicated with a
colon: “4000:5000” or “1:65535” for all ports. Combinations are also possible:
“80,443,4000:5000.” It is also possible to configure the access of several
participants with one another. An IP range can be defined with a dash:
“10.10.1.10-10.10.1.20“. A list of IP addresses is indicated with commas:
“10.10.1.10,10.10.1.15,10.10.1.20”. IP subnet can be also declared using CIDR
notation: “10.10.1.10/24”. Action defines whether this rule allows
communication (“Accept”), rejects with an error message (“Reject”), or simply
rejects (“Drop”). The appropriate method here should always be chosen in
interaction with the “Default Action”. If the Default Action is, for example,
“Reject” or “Drop”, the filter rules should all be set to “Accept”
(Whitelisting). If the Default Action is “Accept”, a block can be defined in
the filter rules with “Reject” or “Drop” for certain devices (Blacklisting).
8.3 Packet filter “LAN to WAN”
By default data traffic is permitted for devices from the machine network
(LAN) to the company network (WAN) without limitations (“Default Action”:
“Accept”). The general rule can be changed by setting the “Default Action” to
“Reject” or “Drop”. In addition to the general rules, filtering can be further
customized using specific packet filter rules.
Firmware update
The firmware of the WALL IE can be very simply updated via the website.
Please download the firmware update file in advance.
Link to firmware: http://www.helmholz.de/goto/700-860-WAL01#tab-software or
scan the QR code.
http://www.helmholz.de/goto/700-860-WAL01#tab-software
The firmware file can be recognized by the “.HUF” extension (Helmholz Update
File) and is also encoded to protect it from being changed.
Save the firmware file on your PC and select the location with “Browse” in the
“Device” menu under “Firmware Upgrade”.
The firmware file is then transferred to the WALL IE. This can take up to 1
minute.
The firmware file is decrypted and checked in WALL IE. If the content is
correct, the firmware is transferred retentively to the program memory and
then an automatic restart is performed.
During the update process, the operation of the WALL IE is interrupted. Do not
switch off the device during the update process..
The configuration of the WALL IE is retained when updating to a higher
version, as far as this is technically possible. However, a “downgrade” to an
older firmware version can lead to configuration errors. It is recommended to
perform a factory reset after a downgrade.
After a firmware update, it may be necessary to clear the browser cache once
to update outdated JavaScript elements of the WALL IE website.
LEDs status information
PWR | Off | No power supply or device defective |
---|---|---|
On | The device is correctly supplied with voltage | |
RUDY | On | The device is ready to operate |
ACT | Flashing light or on | Data transfer permitted between WAN and LAN |
USER | Flashing light | Reset to works setting activated |
RJ45 LEDs | Green (Link) | Connected |
Orange (Act) | Data transfer at the port |
The function of the buttons
The “FCN” button can be used to reset the WALL IE to factory settings. The “FCN” button must be held down during the startup phase of the WALL IE. The successful resetting of the parameters and settings is acknowledged by the “USR” LED lighting up during the boot process. The “FCN” button can then be released.
The “RST” button triggers an immediate restart of the WALL IE in which all saved settings are retained.
Technical data
Order no. | 700-860-WAL01 |
---|---|
Name | WALL IE |
Dimensions (D x W x H) | 32,5 x 58,5 x 76,5 mm |
Weight | Approx. 130 g |
WAN interface | |
Number | 1 |
Type | 10Base-T/100Base-T |
Connection | RJ45 socket |
Transmission rate | 10/100 Mbps |
LAN interface | |
Number | 3, switched |
Type | 10 Base-T/100 Base-T |
Connection | RJ45 socket |
Transmission rate | 10/100 Mbps |
Operating modes | Bridge, NAT (Basic NAT, NAPT) |
Packet filter | IPV4 addresses, protocol (TCP/UDP), ports (“WAN to LAN” and |
“LAN to
WAN” separate), MAC addresses (black & whitelisting)
Status indicator| 4 LEDs function status, 8 LEDs Ethernet status
Voltage supply| 24 V DC, 18–30 V DC
Current draw| Max. 250 mA at 24 V DC
Power dissipation| Max. 2,4 W
Ambient conditions|
Installation position| Any
Ambient temperature| -40 °C … +75°C
Transport and storage temperature| -40 °C … +85°C
Relative air humidity| 95 % r H without condensation
Pollution degree| 2
Protection rating| IP20
Certifications| CE, UL
UL| UL 61010-1/UL61010-2-201
Voltage supply| DC 24 V (18 … 30 V DC, SELV, and limited energy circuit)
Pollution degree| 2
Altitude| Up to 2000m
Temperature cable rating| 87°C
RoHS| Yes
REACH| Yes
The contents of this Quick Start Guide have been checked by us so as to ensure
that they match the hardware and software described.
However, we assume no liability for any existing differences, as these cannot
be fully ruled out. The information in this Quick Start Guide is, however,
updated on a regular basis. When using your purchased products, please make
sure to use the latest version of this Quick Start Guide, which can be viewed
and downloaded on the Internet from www.helmholz.de.
Our products contain open source software, among others. This software is
subject to the respectively relevant license conditions. We can send you the
corresponding license conditions, including a copy of the complete license
text together with the product. They are also provided in our download area of
the respective products under
www.helmholz.de. We also offer to send you or any
third party the complete corresponding source text of the respective open
source software for an at-cost fee of 10.00 Euro as a DVD upon request. This
offer is valid for a period of three years, starting from the date of product
delivery.
Our customers are important to us, we are happy to receive suggestions and
ideas for improvement. If you have any questions regarding the use of the
product, please contact Helmholz Support by phone or send an e-mail to
support@helmholz.de.
All trademarks shown or mentioned in this document are the property of their
respective owners or manufacturers.
The representation and naming serve exclusively to explain the use and setting
options of the products documented here.
Quickstart Guide WALL IE
Version 14
18.07.2022
Documents / Resources
|
Helmholz 700-860-WAL01 Wall IE Industrial NAT Gateway and
Firewall
[pdf] User Guide
700-860-WAL01, Wall IE Industrial NAT Gateway and Firewall, 700-860-WAL01 Wall
IE Industrial NAT Gateway and Firewall
---|---
References
- Helmholz – Compatible with you | Automatisierungstechnik
- WALL IE - Industrial NAT Gateway/Firewall | NAT-Gateway / Firewall | Industrial Ethernet | Produkte | Helmholz – Compatible with you | Automatisierungstechnik
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>