Specifications:

  • NatureConnect link: Gateway for NatureConnect light experience
    with 5 lighting scenes

  • Control System: Interact

  • Features: Day Rhythm, Tunable White DALI DT8 DIA, Energize,
    Relax Present

  • Additional: Presence sensors for power consumption
    reduction

Product Usage Instructions:

Commissioning:

  1. Ensure you have a device with Interact commissioning app
    support (e.g. smartphone or tablet) with Bluetooth technology.

  2. Test the connection with the luminaires by pressing the service
    button, then check the luminaires.

  3. Configure the time using either a wired network with internet
    access or manually set the time using the Windows configuration
    app.

Commissioning with Interact PRF as Lighting Control

System:

  1. Download the interact office app and create an account.
  2. Create and structure a new project in the app.
  3. Create a Light Network within the app.
  4. Add a group to organize the connected luminaires.
  5. Reboot NatureConnect link if production date is before 23W48 by
    unplugging and reconnecting the connector after waiting 10
    seconds.

FAQ:

Q: How can I achieve the best NatureConnect experience?

A: Combine NatureConnect link with presence sensors and user
interfaces for optimal experience.

Q: What are the benefits of NatureConnect compared to

traditional lighting?

A: NatureConnect focuses on biological and emotional benefits,
in addition to visual benefits, by bringing elements of nature into
indoor spaces.

Q: How do presence sensors help in reducing power

consumption?

A: Presence sensors detect occupancy in a room and can signal
the NatureConnect link to activate specific scenes or turn off
luminaires when no occupancy is detected.

“`

Commissioning guide
NatureConnect link & Interact
1 NatureConnect_Commissioning guide_January 2024

Introduction
The NatureConnect system is based on biophilic design principles, which uses elements of nature and natural analogues in indoor spaces to make people feel happy and healthy. Unlike traditional lighting which focuses on visual benefits, NatureConnect additionally brings the biological and emotional benefits of lighting. It reconnects us with the constant cycles and variations of nature for comfortable, engaging and attractive indoor environments.
NatureConnect luminaires

NatureConnect link is the gateway that creates the NatureConnect light experience. It is programmed with 5 lighting scenes plus OFF status.
NatureConnect link
Control System (eg Interact)
Day Rhythm

Tunable White DALI DT8 DIA

Energize

Relax Present

All luminaires connected to the same NatureConnect link will behave in the same way.

OFF

Off

Day Rhythm low

The best NatureConnect experience is achieved combining NatureConnect link with presence sensors and user interfaces.

NatureConnect switch Wireless, battery free

Scene and Off buttons with icons and text for ease of use

Interact switch with NatureConnect icons (910505103545)

High quality engraving for long durability

Presence sensors helps to reduce the power consumption. They can be programmed in a way that when no occupancy is detected, inside the room, they send the signal to the NatureConnect link, to activate “Day Rhythm low” scene or to turn off the luminaires. When presence is detected it goes automatically to “Day rhythm”.

2 NatureConnect_Commissioning guide_January 2024

Commissioning
You will need a device that supports Interact commissioning app. (e.g. smartphone or a tablet) with Bluetooth technology. For more info check: https://sme.interact-lighting.com/web/help/prf- pra/2.3/install/commissioning.html
1 Test the connection with the luminaires by pressing the service button

Service

Color transition =

Service

1 Press the “service” button to start the test

2 Check luminaires

2 Time configuration – two methods

3 Press the “service” button to finish the test

1 Connect (temporarily) to a wired
network that has access to internet/NTP

2 Manually set the time with
Windows configuration app

NTP LED LED on time acquired
from NTP server
Connection to network

www.signify.com/natureconnect

Time is already configured from
! production date 23W48. Please
check on the box label.

Once the time is set, NatureConnect
!! link will keep the time without a perma-
nent internet connection.

3 NatureConnect_Commissioning guide_January 2024

Commissioning with interact PRF as Lighting Control System 1 Download the interact office app and create an account
2 Create and structure a new project
Create a project
Fill in the fields and open the new project just created.
4 NatureConnect_Commissioning guide_January 2024

Create a Light Network

1 2

5 NatureConnect_Commissioning guide_January 2024

Add a group
6 NatureConnect_Commissioning guide_January 2024

3 Reboot NatureConnect link before proceeding with commissioning ! Only needed if production date is before 23W48
Unplug the connector, wait 10 seconds and reconnect.

24V 0.875A

!

Wait for the device to start, before proceeding with the next steps. This will take minimum 5 minutes.

4 Find and assign the NatureConnect link connected with a SNS210
Stand close (2 m ca.) to the SNS210 connected to the NatureConnect link. (Bluetooth must be active on your device.)
Tab Light: click on Assign lights It will be found as e.g.: Philips luminaire – 6384 (number can vary)

*1

2

  • This number is different for each installation
    Once assigned, all luminaires connected to the NatureConnect link will appear as ON and will respond as whole.
    7 NatureConnect_Commissioning guide_January 2024

5 Configure the system with motion sensors
Tab Controls

Follow below steps:
1 Set CCT to 2700 K
Press “enter” or “OK”
2Set Background to 100%
Press “enter” or “OK”
3 Set Task to 100 %
Press “enter” or “OK”
4 Set Vacant to 0 %
Press “enter” or “OK”
5Set Hold time to 10 min
Press “enter” or “OK”
6Set Prolong time to 0 min
Press “enter” or “OK”

  • If color temperature slider is missing, follow the procedure indicated in the paragraph B in the Problem Solving chapter.

8 NatureConnect_Commissioning guide_January 2024

Optional: how to add battery power motion sensor
9 NatureConnect_Commissioning guide_January 2024

6 Configure the system without motion sensors

Follow below steps:
1 Set CCT to 2700 K
Press “enter” or “OK”
2Set Task level to 100%
Press “enter” or “OK”

*If color temperature slider is missing, follow the procedure indicated in the paragraph B in the Problem Solving chapter.

! If you are not using any user interface, skip to step 9.
10 NatureConnect_Commissioning guide_January 2024

7 Add one or more user interfaces
Day Rhythm
Off

When more than one

!

switch is used, all switches will behave in

the same way.

Tab Controls: click on Switches Click Show switch in the group

Select 4 button switch

Identify the switch following the instructions

Switch 1

11 NatureConnect_Commissioning guide_January 2024

Test if the switch is added by clicking ON/OFF button

Day Rhythm
Off

Lights turned off? If yes

In case luminires in the group do not turn off, follow below steps
Retry will restart the add switch flow from the beginning.
If the same error occurs again,
! follow the procedure indicated
in the paragraph A in the Problem Solving chapter.

12 NatureConnect_Commissioning guide_January 2024

8 Configure the four button switch

Configure the TOP LEFT button as the ENERGIZE scene
1 2 3

Follow below steps:
1 Type the name of the scene 2Set brightness to 100%
Press “enter” or “OK”
3 Set CCT to 2800 K
Press “enter” or “OK”
4 Wait 5 seconds 5 Click on “Create”

5

Configure the BOTTOM LEFT button as the RELAX scene
1 2 3

Follow below steps:
1 Type the name of the scene 2Set brightness to 100%
Press “enter” or “OK”
3 Set CCT to 2900 K
Press “enter” or “OK”
4 Wait 5 seconds 5 Click on “Create”

5

  • If color temperature slider is missing, follow the procedure indicated in the paragraph B in the Problem Solving chapter.
    13 NatureConnect_Commissioning guide_January 2024

9 Deploy settings and unlock the network

Deploy

Unlock

14 NatureConnect_Commissioning guide_January 2024

Additional scenes (optional)
! NOT REQUIRED if using only the user interface.

DAY RHYTHM scene
Day Rhythm
Follow below steps:

PRESENT scene

1
2 3

1 Type the name of the scene 2Set brightness to 100%
Press “enter” or “OK”
3 Set CCT to 2700 K
Press “enter” or “OK”

1
2 3

4 Wait 5 seconds 5 Click on “Create”

Follow below steps:
1 Type the name of the scene 2Set brightness to 100%
Press “enter” or “OK”
3 Set CCT to 3000 K
Press “enter” or “OK”
4 Wait 5 seconds 5 Click on “Create”

5

5

15 NatureConnect_Commissioning guide_January 2024

DEMO MODE
It is possible to program a scene that runs in cycle a faster mode of the dynamic scenes. Suitable for demo purposes controlled through the commissioning app.

DEMO DAY RHYTHM scene
Day Rhythm
Follow below steps:

DEMO ENERGIZE scene
Follow below steps:

1

1 Type the name of the scene

1

1 Type the name of the scene

2Set brightness to 100%

2

Press “enter” or “OK”

3 3 Set CCT to 4700 K

Press “enter” or “OK”

2Set brightness to 100%

2

Press “enter” or “OK”

3 3 Set CCT to 4800 K

Press “enter” or “OK”

4 Wait 5 seconds 5 Click on “Create”

4 Wait 5 seconds 5 Click on “Create”

5

5

DEMO RELAX scene
Follow below steps:

1

1 Type the name of the scene

2Set brightness to 100%

2

Press “enter” or “OK”

3 3 Set CCT to 4800 K

Press “enter” or “OK”

4 Wait 5 seconds 5 Click on “Create”

5

16 NatureConnect_Commissioning guide_January 2024

Problem solving
A Cannot add a switch to a group (PRF)
If it is impossible to make the luminaires react to the switch remove the switch from the configurator and restart the process from the beginning.
Go back to commissioning, step 7.
17 NatureConnect_Commissioning guide_January 2024

B What to do if the color temperature slider is missing
Under certain circumstances it is possible for the NatureConnect link to not be detected as a tunable white device. To fix this it is necessary to remove it from the system and add it again.
Remove NatureConnect link

Reboot NatureConnect link
24V 0.875A

1 Remove power for 10 seconds.
2 Wait 5 minutes until the NC link has fully started be-

  • fore continuing.
    3 Go back to step 4: “Find and assign the NatureCon-
    nect link connected with a SNS210”
  • During the NC link boot process, the SNS210 looses power temporarily. If this happens during the commissioning processes, you might have to reset the SNS210.

18 NatureConnect_Commissioning guide_January 2024

C What to do when system responds incorrectly to the inputs from the switch
It can happen that the scene is saved incorrectly and that the system does not respond or triggers the wrong light experience when pressing a scene button on the switch.
This typically happens when you do not wait for 5 seconds between changing the color temperature and pressing the create button.
Change the color temperature of the Energize scene to a wrong value on purpose (eg. 6600K) and save.

1 2 Wait 5 seconds, after setting CCT, before clicking on “Save”
3
Change the color temperature of the Energize scene back to correct value (2800K) and save.

Repeat the same steps for Relax scene
19 NatureConnect_Commissioning guide_January 2024

1
2 Wait 5 seconds, after setting CCT, before clicking on “Save”
3

© 2024 Signify Holding. All rights reserved. The information provided herein is subject to change, without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract, unless otherwise agreed by Signify. All trademarks are owned by Signify Holding or their respective owners