NatureConnect W120L120 Sky Light Installation Guide

June 1, 2024
NatureConnect

NatureConnect

by

Nature Connect

skylight W120L120

4x 4x   4x

1x

|

Power

| Current| Dimensions LxWxH|
---|---|---|---|---
NatureConnect skylight W120L120| 150 W| 0.7 A| 1195x1195x150 mm|

30 kg

NatureConnect W120L120 Sky Light 1 NatureConnect W120L120 Sky Light 3

Three installation methods:

a. Suspended recessed

b. Suspended surface mounted

c. Suspended open ceiling

  Always use gloves when installing luminaire.

2023/02/14 – 442710705710
© Signify Holding. All rights reserved

Data subject to change without notice
www.signify.com/natureconnect

Determine orientation of the Skylight in the ceiling according to the lighting plan

NatureConnect W120L120 Sky Light 8a
[1]

  1. Sun sides
  2. 4x Fixation points

Fix the four steel cables to the ceiling according to the orientation of the luminaire
[2]

Insert the suspension cables in the four cable grippers on the luminaire

[3]

Suspended recessed in system ceiling

2×2 tiles opening in the ceiling

[4a]

Suspended surface mounted in system ceiling

[4b]

  1. Empty space for driver
  2. Empty space for suspension cables

Suspended open ceiling

NatureConnect W120L120 Sky Light 17

[4c]

Insert the luminaire through the opening

No mechanical load on the ceiling

[5a]

Insert the middle part of the luminaire in the opening.

NatureConnect W120L120 Sky Light 16

[5b]

Connection to mains

NatureConnect W120L120 Sky Light 18

connector GST18i5, male

Inrush current

Electrical characteristics

I max (A) 50
T ref (Us)  330
MCB Max n. of lumin.
B-10 A 3
B-16 A 6
C-10 A 6
C-16 A 10

ATTENTION OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES

  • The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.

  • The external flexible cable contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.

  • The product is partially IPX0 & as such is not protected against water ingress & as such we strongly recommend that the environment in which the luminaire is to be installed is suitably checked.

  • If the above advice is not taken and the luminaires are subject to water ingress, Signify cannot guarantee safe failure & product warranty will become void.

  • During installation or maintaining the luminaire please use gloves to avoid spots on the cover.

  • To remove dust and spots use the following:
    – Dust: use micro fiber cloths only
    – Fingerprints, etc.: use a cleaner for synthetic materials with antistatic properties.

  • Luminaire has basic insulation between Low Voltage supply and control conductors.

  • The luminaire shall, under no circumstance, be covered with thermal insulation matting or similar material.

INFORMATION ON MINIMUM CLEARANCE DISTANCES (for Australia and New Zealand)

NatureConnect LP911P NC2 SKYLIGHT A W120L120 is a Do-Not-Cover luminaire type.

Please note the following warnings for recessed application:

  • Australia and New Zealand

WARNING — RISK OF OVERHEATING OR FIRE IF THE CLEARANCE DISTANCES ARE COMPROMISED.

Abbreviations (clearances):

  1. HCB (Height clearance to building element)
    Minimum distance as specified by the luminaire manufacturer between the top of the recessed luminaire and any building element above it.

  2. MIC (Minimum insulation clearance)
    Minimum distance as specified by the luminaire manufacturer between the top of the recessed luminaire and the building insulation above it.

  3. SCB (Side clearance to building element)
    Minimum distance between the side of the recessed luminaire and any building element as specified in AS/NZS 3000, or as specified by the luminaire manufacturer.

  4. SCI (Side clearance to insulation)
    Minimum distance as specified by the luminaire manufacturer between the recessed luminaire and any building insulation.

Minimum clearances requirements for LP911P NC2 SKYLIGHT A W120L120 luminaire:

RISK OF FIRE – BUILDING INSULATION MUST NOT COVER THIS LUMINAIRE
HCB = 0 mm MIC = 10 mm SCB = 0 mm SCI = 0 mm

  • New Zealand (additional)

WARNING — THIS LUMINAIRE IS NOT SUITABLE FOR INSTALLATION IN LOCATIONS WHERE THERMAL INSULATION IS PRESENT, OR MAY REASONABLY BE EXPECTED TO BE INSTALLED IN THE FUTURE, OR WHERE THERE IS A LIKELIHOOD OF OTHER COMBUSTIBLE MATERIAL, E.G. LEAVES OR VERMIN DEBRIS, ETC. COLLECTING ON OR AROUND THE LUMINAIRE. IT IS NOT SUITABLE FOR DOMESTIC INSTALLATIONS OR INSTALLATION IN RESIDENTIAL AREAS OF NON-DOMESTIC INSTALLATIONS (RESIDENTIAL INSTITUTIONS, HOTELS, BOARDING HOUSES, HOSPITALS, ACCOMMODATION HOUSES, MOTELS, HOSTELS AND THE LIKE).

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals