Intesis DALI to BACnet Server gateway User Manual

June 7, 2024
Intesis

Intesis DALI to BACnet Server gateway

Order Codes:
INBACDAL0640200 (64 ballasts, 1 DALI channel)
INBACDAL1280200 (128 ballasts, 2 DALI channels)

HOW IT WORKS

The Intesis INBACDAL***0200 Gateway has been specially designed to work as a translator between a DALI installation and BACnet IP or BACnet MSTP based control and monitoring systems.

Intesis acts as a master in the DALI bus, allowing both BACnet IP and BACnet MSTP client/master devices to read and write on all configured DALI signals.

BACnet MSTP devices are connected to the serial port of the gateway, while BACnet IP devices are connected to the Ethernet port. On the DALI side, the gateway simulates a DALI-2 master device allowing other DALI/DALI-2 devices to be present in the DALI channels.

Configuration project and DALI commissioning is done through Intesis MAPS.
graphical user interface, application, table, Excel

FEATURES

  • Handles conversion between BACnet (IP & MSTP) and DALI/DALI2 ballasts and DALI-2 sensors (occupancy and light instances)
  • Support for BACnet IP or BACnet MSTP, not both simultaneously*
  • Designed following DALI IEC 62386 standard and certified by DiiA
  • Supports parts 201, 202 y 207 for ECGs
  • Supports parts 303 and 304 for Sensors
  • DALI line scan (ballast detection) and commissioning
  • Configuration through IP or USB (Console) port
  • Front cover LED indicators to provide easy to check communication status on both the Ethernet and serial ports
  • Includes Intesis MAPS with automatic updates for both Intesis MAPS and Gateway’s firmware
  • INBACDAL1280200 does not offer BACnet MSTP communication

INTEGRATION EXAMPLE

VERSION SUPPORT 1 DALI CHANNEL

diagram

VERSION SUPPORT 2 DALI CHANNELS

CONNECTIONS

PROTOCOLS

a close up of a sign

DALI is an industry-standardized protocol, for digital lighting control, and is specified in the multi-part international standard IEC 62386

The digital nature of DALI allows two-way communication between devices, so that a device can report a failure, or answer a query about its status or other information.

Wiring is relatively simple; DALI power and data is carried by the same pair of wires, without the need for a separate bus cable

For further information, please visit https://www.digitalilluminationinterface.org


BACnet is the Data Communication Protocol for Building Automation and Control Networks. Developed under the auspices of the American Society of Heating, Refrigerating and AirConditioning Engineers (ASHRAE).

BACnet is an American national standard, a European standard, a national standard in more than 30 countries and an ISO global standard. The protocol is supported and maintained by ASHRAE Standing Standard Project committee 135.

For further information, please visit www.bacnet.org


COMMUNICATION

 |

BACnet

| DALI
---|---|---
MSTP|

IP

Connection| EIA485 (3 wire isolated)
9.6, 19.2, 38.4, 57.6, 76.8, 115.2kbps| 10BASE-T
100BASE-TX
10 Mbps
100 Mbps| DALI
Data rate| 1.2 kbps
Data Types
&
Functions supported
| Object types
0-AO (Analog Output) 1-AI (Analog Input)
2-AV (Analog Value)
3-BO (Binary Output)
4-BI (Binary Input)
5-BV (Binary Value)
13-MI (Multistate Input)
14-MO (Multistate Output)
15-MV (Multistate Value)| Functions

Trend Logs

Calendars

Schedules

| Part 201: Fluorescent lights (DALI type 0)
Part 202: Emergency lights (DALI type 1)
Part 207: LED modules (DALI type 6)
Part 103: Control devices Part 303: Occupancy sensors
Part 304: Light sensors

ELECTRICAL & MECHANICAL FEATURES

Enclosure| Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 90x88x56 mm
Recommended space for installation (dxwxh): 130x100x100mm
Color: Light Grey. RAL 7035
---|---
Mounting| Wall.
DIN rail EN60715 TH35.
Terminal Wiring (for power supply and low-voltage signals)| Per terminal: solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm2… 2.5mm2
2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required
Power| 1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC +/-10%
Ethernet| 1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Port A| 1 x DALI port (Plug-in screw terminal block orange 2 poles)
1500VDC isolation from other ports
DALI guaranteed power: 235mA
Voltage rating: 16VDC
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Switch A
(SWA)| 1 x DIP-Switch for serial EIA485 configuration: Reserved for future use
PORT B| INBACDAL0640200
1 x Serial EIA232 (SUB-D9 male connector)
Reserved for future use
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
A, B, SG (Reference ground or shield)
1500VDC isolation from other ports
(except PORT B: EIA232)
INBACDAL1280200
1 x Serial EIA232 (SUB-D9 male connector) Reserved for future use
1 x DALI port (Plug-in screw terminal block green 2 poles) 1500VDC isolation from other ports
DALI guaranteed power: 235mA
Voltage rating: 16VDC
Switch B
(SWB)| 1 x DIP-Switch for serial EIA485 configuration: Position 1:
ON: 120 Ω termination active
Off: 120 Ω termination inactive
Position 2-3:
ON: Polarization active
Off: Polarization inactive
Battery| Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Console Port| Mini Type-B USB 2.0 compliant
1500VDC isolation
USB port| Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Push Button| Button A: Check the user manual
Button B: Check the user manual
Operation Temperature| 0°C to +50°C
Operational Humidity| 5 to 95%, no condensation
Protection| IP20 (IEC60529)
LED Indicators| 10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator 1 x Button B indicator

Web: www.intesis.com
logo

© HMS Industrial Networks S.L.U – All rights reserved
This information is subject to change without notice

Documents / Resources

| Intesis DALI to BACnet Server gateway [pdf] User Manual
DALI to BACnet Server gateway, INBACDAL 0200
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Intesis User Manuals

Related Manuals