Intesis DALI to KNX gateway Installation Guide
- June 7, 2024
- Intesis
Table of Contents
INKNXDAL0640200
DALI to KNX gateway
Order Code: INKNXDAL0640200
Installation Sheet rev.1.1
HMS Industrial Networks S.L.U ©
Owner’s Record
The serial number is located at the rear of the gateway. Record this
information in the space provided below. Refer to it whenever you contact upon
your gateway dealer or support team regarding this product.
Serial No. ____
SAFETY INSTRUCTIONS
WARNING
Follow carefully these safety and installation instructions. Improper work
may lead to serious harmful for your health and may damage seriously the
Intesis gateway and/or any other equipment connected to it too.
The Intesis gateway must be installed by accredited electrician or similar
technical personnel, following all the safety instructions given here and in
accordance always with the country legislation for installation of electric
equipment.
The Intesis gateway cannot be installed outdoors or exposed to direct solar
radiation, water, high relative humidity or dust.
The Intesis gateway must only be installed in a restricted access location.
In case of wall mount, fix firmly the Intesis device on a not vibrating
surface following the instructions next.
In case of DIN rail mount fix Intesis properly to the DIN rail following the
instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to earth is
recommended.
Disconnect always power of any wires before manipulating and connecting them
to the Intesis device.
A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV
rated is to be used.
Respect always the expected polarity of power and communication cables when
connecting them to the Intesis gateway.
Supply always a correct voltage to power the Intesis device, see details of
voltage range admitted by the device in the technical characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type.
Dispose of Used Batteries according to the instructions. Battery replacement
shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without routing
to the outside plant, all communication ports are considered for indoor only
and can be connected SELV circuits only.
This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels above 4
kV, precautions should be taken when the device is mounted outside an
enclosure. When working in an enclosure (ex. making adjustments, setting
switches etc.) typical anti-static precautions should be observed before
touching the unit.
Safety instructions in other languages can be found at :
https://intesis.com/docs/manuals/v6-safety
CONFIGURATION
Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at:
https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection or the Console Port (mini USB type B connector
included) for communication between the gateway and the configuration tool.
See CONNECTIONS below and follow instructions of user’s manual for more
details.
INSTALLATION
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the Intesis
device.
Disconnect power of any bus or communication cable before connecting it to the
Intesis gateway.
Mount the Intesis device on the wall or DIN rail following the instruction
given below, respecting the safety instructions given above. Connect a NEC
Class 2 or Limited Power Source (LPS) and SELV rated power supply to the
Intesis gateway, respect the polarity if DC power or Line and Neutral if AC
power. Apply always a voltage within the range admitted by the Intesis gateway
and of enough power (see technical characteristics).
Circuit-breaker must be used before the power supply. Rating 250V6A.
Connect the communication cables to the Intesis device, see details on the
user’s manual.
Power the Intesis gateway and the rest of devices connected to it.
NOTE: The device cannot be installed in air-handling space.
Wall Mount
- Separate the fixing clips in the bottom of the box, pushing them to the outside until hear the “click” which indicates that now the clips are in position for wall mount, see in the figure below.
- Use the holes of the to fix the box in the wall using screws. Use the template below for the wall wholes.
Clips in their original position (for DIN rail mount) Clips in position for wall mount
DIN Rail Mount
With the clips of the box in their original position, insert first the box in
the upper edge of the DIN rail and later insert the box in the down part of
the rail, using a small screwdriver and following the steps in the figure
below.
CONNECTIONS
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power
supply.
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied
is within the range admitted (check table below). The power supply can be
connected to earth but only through the negative terminal, never through the
positive terminal.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the
building, contact the network administrator and make sure traffic on the port
used is allowed through all the LAN path (check the gateway user manual for
more information). With factory settings, after powering up the gateway, DHCP
will be enabled for 30 seconds. After that time, if no IP is provided by a
DHCP server, the default IP 192.168.100.246 will be set.
PortA / KNX
Connect the KNX TP1 bus to connectors A3 (+) and A4 (-) of gateway’s PortA.
Respect the polarity.
PortB / DALI
Connect the DALI bus to connectors B1(-), B2 (+) of gateway’s PortB. The
Intesis device provides 16VDC (+/-2%) DALI voltage to the bus.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow
communication between the Configuration Software and the gateway. Remember
that Ethernet connection is also allowed. Check the user manual for more
information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual
for more information.
ELECTRICAL & MECHANICAL FEATURES
Enclosure| Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 90x88x56 mm
Recommended space for installation (dxwxh): 130x100x100mm
Color: Light Grey. RAL 7035
---|---
Mounting| Wall.
DIN rail EN60715 TH35.
Terminal Wiring (for power supply and low-voltage signals)| Per terminal:
solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm2 … 2.5mm2
2 cores: 0.5mm2… 1.5mm2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
Power| 1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC
Ethernet| 1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Port A| 1 x KNX TP-1 Plug-in screw terminal block orange (2 poles)
2500VDC isolation from other ports
KNX power consumption: 5mA
Voltage rating: 29VDC
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Switch A (SWA)| 1 x DIP-Switch for PORT A configuration: Reserved for future
use
PORT B| 1 x Serial EIA232 (SUB-D9 male connector)
Reserved for future use
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
B1, B2
1500VDC isolation from other ports
DALI guaranteed power: 235mA
Voltage rating: 16VDC (except PORT B: EIA232)
Switch B (SWB)| 1 x DIP-Switch for serial EIA485 configuration: Reserved for
future use
Battery| Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Console
Port
| Mini Type-B USB 2.0 compliant
1500VDC isolation
USB port| Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
Push Button| Button A: Check the user manual
Button B: Check the user manual
Operation Temperature| 0°C to +50°C
Operational Humidity| 5 to 95%, no condensation
Protection| IP20 (IEC60529)
LED Indicators| 10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
This marking on the product, accessories, packaging or literature (manual)
indicates that the product contains electronic parts and they must be properly
disposed of by following the instructions at https://intesis.com/weee-
regulation
Rev.1.0 © HMS Industrial Networks S.L.U – All rights reserved This information
is subject to change without notice
Rev.1.0
© HMS Industrial Networks S.L.U – All rights reserved
This information is subject to change without notice