GREE 68 Series Coil Unit Fan User Manual
- June 8, 2024
- Gree
Table of Contents
GREE 68 Series Coil Unit Fan
FAQ
Frequently Asked Questions
- Q: How often should I clean the filters?
- A: It is recommended to clean the filters every 2-3 months to maintain optimal performance.
- Q: Can I use this unit for both cooling and heating?
- A: Yes, the GREE G Series Fan Coil Unit is designed to function for both cooling and heating purposes.
Nomenclature
-
Fan coil unit
-
Motor
- Default: AC motor; E: EC motor
-
Model
- Default: standard cooling; D: district cooling
-
Unit size: 51,68,85,102,136,170,204,238
-
Installation: horizontal-concealed
-
Static pressure
- U: 50Pa
-
Coil
- S: 3-row; F: 4-row
-
Design number: as per the alphabetic order A, B, C…Z
-
Return air plenum
- Default: without the plenum
- H: with the rear return air plenum only
- X: with the bottom return air plenum only
- HL: rear withdrawal with aluminum filter
- XL: bottom withdrawal with aluminum filter
- HN: rear withdrawal with nylon filter
- XN: bottom withdrawal with nylon filter
-
Type of the fan
- T: metallic fan
-
Type of the drain pan
- Default: galvanized steel with PE insulation
- A: stainless steel with PE insulation
- A+digit: stainless steel with PE insulation and extended
- B: galvanized steel with fireproof fiber insulation
- B+digit: galvanized steel with fireproof fiber and extended
- C+digit: galvanized steel with PE insulation and extended
- D: stainless steel with fireproof fiber insulation
- D+digit: stainless steel with fireproof fiber insulation and extended
( Note: the “digit” indicates the extended length/100, like C3 indicates the extended length is 3*100mm.)
-
Power supply
- K: 220~240V 50Hz 1-phase
Product Introduction
The GREE G series fan coil unit is a new generation of the ultra-thin horizontal concealed product, functioning for both cooling and heating, with a compact structure, 235mm in height and 490mm in depth. As it can be installed in a quite simple way and requires small installation space, it is widely applicable to public places. On request, either the FP/FPE series for standing cooling or the FPD/FPED series for district cooling is available.
Casing
The standard casing of the main unit is made of high-quality hot-dip galvanized sheets. It is fabricated with high-accuracy and shaped in a whole piece. The machine-made stamping process will reduce the possibility of injuries caused by sharp edges of the metal sheet during transport. It is good-looking and is of excellent insulation performance with the flexible foaming rubber inside.
Option: hot-dip galvanized sheet (oil coated) + weather-proof power coated, 1500h moisture-proof and heat-proof, applicable to high-temperature and high-humidity applications.
Motor
Capacitor-starting three-speed AC motor, the motor casing is designed for water-proof and dust-proof performance and improved reliability. The T-shaped speed control design will enhance its anti-harmonic capacity. The maintenance- free and enclosed structure for the bearing can provide more than 30,000 hours service life. For guaranteeing its safety and reliability, the motor will undergo multiple tests on the harmonic, the frequency sweep, and temperature rise of the windings before delivery. Besides, the motor support is of the high-strength structure which will be approved through the drop-off and stacking tests.
A permanent magnetic brushless EC motor increases the efficiency of over 30%, compared to an AC motor. We develop a constant torque technology to adaptively make up the airflow, stabilising the entire cooling capacity. The motor resistable loss percentage at over 10% indicates that it will boost heat exchange and system stability prominently.
Fan
The case is made of high-quality hot-dip galvanized steel plate. The side plate has an aerodynamic shape. The air inlet ring is integrally stretched and formed. The cochlear plate is integrated with the side plate by self-tapping screws in the form of undercut. At the vent, the cochlear plate is designed to conform to the aerodynamic special tongue to prevent vortex formation in the exit stream.
The forward multi-blade impeller is made of high-quality galvanized sheet for precision progressive die stamping. Crimping molding, reasonable design makes the aerodynamic performance of the fan to the best. All impellers are tested in accordance with ANSI/AMCA-204 using a precision electronic balancing machine for two-stage dynamic balancing with internal control accuracy up to G2.5.
Cooling Coil
The coils are made of the high-efficiency 3/8 seamless copper tubes with aluminum fins. It can work with high efficiency. Beside the connectors for the supply and return water lines, the air exhaust valve is also available. The inlet and outlet pipes are equipped with specially sealed connectors which has undergone 3.2Mpa pressure test and high-precision helium leak detection.
Filter
- The metal filter is either 10mm or 21mm and it is made of multi-layer aluminum or stainless steel screens.
- It is washable and economical. Moreover, it is safe, secure, and resistant to high temperature, acid and alkali. The PVC filter is 8mm thick.
Drain Pan
Stamped as a whole piece, there is no welding joint for the drain pan and leakage will be avoided. The insulation material is pressed against the whole, the combination is compact, the appearance is exquisite, the insulation performance is good, and there is no worry about condensation. The fixing position of the drain pan has a height difference to ensure that the drain pan is inclined at a certain angle after the unit is hoisted, and the condensed water is discharged smoothly.
Technical Information
Technical Information: Specification and Dimensions
FP series standard cooling performance parameters (4-row)
Size | 51 | 68 | 85 | 102 | 136 | 170 | 204 | 238 |
---|
Performance
|
Airflow
|
H
| CFM| 312| 406| 524| 600| 824| 1029| 1200| 1400
m³/h| 530| 690| 890| 1020| 1400| 1750| 2040| 2380
M
| CFM| 276| 350| 485| 541| 618| 694| 835| 1171
m³/h| 470| 595| 825| 920| 1050| 1180| 1420| 1990
L
| CFM| 218| 279| 368| 306| 471| 506| 656| 794
m³/h| 370| 475| 625| 520| 800| 860| 1 5| 1350
Total Cooling Capacity|
H
| kW| 3.3| 4.25| 5.7| 6.5| 8.9| 10.8| 12.6| 15
MBh| 11.3| 14.5| 19.4| 22.2| 30.4| 36.8| 43.0| 51.2
Sensible Cooling Capacity|
H
| kW| 2.33| 3.18| 3.8| 4.4| 6| 7.25| 8.6| 10.9
MBh| 7.9| 10.9| 13.0| 15.0| 20.5| 24.7| 29.3| 37.2
Total Heating Capacity|
H
| kW| 5.6| 7.05| 9.6| 10.7| 14.7| 18.2| 21| 25
MBh| 19.1| 24.1| 32.8| 36.5| 50.2| 62.1| 71.7| 85.3
Water Flow Rate
|
H
| L/s| 0.14| 0.18| 0.24| 0.28| 0.38| 0.46| 0.54| 0.68
GPM| 2.22| 2.85| 3.80| 4.44| 6.02| 7.29| 8.56| 10.78
Water Pressure Drop
|
H
| kPa| 10.7| 18.8| 36.8| 24.8| 27.8| 26.4| 40.49| 49.99
Ft.WG| 3.5| 6.2| 12.1| 8.1| 9.1| 8.7| 13.3| 16.4
Sound Pressure Level
| H|
dB(A)
| 41.5| 43.5| 45| 47.5| 47| 48.5| 52| 51
M| 39| 38| 41.5| 45| 42| 41| 45| 48
L| 27| 33| 40| 31| 33.5| 31| 35| 39
Coil
| Type| Copper tube, high-efficiency aluminum louvered fins
Pressure| ≤2MPa(300psig)
Motor
| Type| Class B insulation, capacitor start
Quantity| 1| 1| 1| 1| 2| 2| 2| 2
Power Supply| 220-240V AC 50Hz
Fan
| Type| Front-curved multi-vane low-noise centrifugal fan
Quantity| 2| 2| 2| 2| 3| 4| 4| 4
Connection pipe
| Inlet Pipe| Rc3/4 (female thread)
Outlet Pipe| Rc3/4 (female thread)
Condensate Pipe| R23/4 (female thread)
Unit Weight
| Standing concealed type fan coil unit| kg| 17| 19| 20.5| 23| 32| 35.5| 38|
46
Horizontal concealed type fan coil unit| kg| 20| 22| 24| 27| 38| 40| 43| 52.5
Notes
- Nominal conditions for cooling: 26.7/19.4°C indoor dry/wet bulb temperature, 7.2/12.8°C entering and leaving water temperature
- Nominal conditions for heating: 21.1°C indoor dry bulb temperature, 60°C entering water temperature, the same water flow as that for cooling
- The sound pressure level above is tested at three speed settings in a semi-anechoic chamber 1m away from both the bottom side of the unit and the air outlet. It may differ with the actual noise as the operation environment varies.
- Parameters listed at the nameplate always prevail.
- On request of the clients, the return air plenum is optional. Parameters listed above are for the unit without the return air plenum.
Dimensions / Horizontal concealed type fan coil unit without the return air plenum
Dimension | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
---|---|---|---|---|---|---|---|---|
A | 800 | 900 | 1000 | 1190 | 1520 | 1620 | 1770 | 1820 |
B | 460 | 490 | 490 | 490 | 490 | 490 | 490 | 485 |
C | 235 | 235 | 235 | 235 | 235 | 235 | 235 | 278 |
D | 632 | 732 | 832 | 1022 | 1352 | 1452 | 1602 | 1652 |
E | 132 | 132 | 132 | 132 | 132 | 132 | 132 | 194 |
F | 632 | 732 | 832 | 1022 | 1352 | 1452 | 1602 | 1652 |
G | 235 | 235 | 235 | 235 | 235 | 235 | 235 | 278 |
H | 606 | 706 | 806 | 996 | 1326 | 1426 | 1576 | 1626 |
Horizontal concealed type fan coil unit with return air plenum
Dimension | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
---|---|---|---|---|---|---|---|---|
A | 800 | 900 | 1000 | 1190 | 1520 | 1620 | 1770 | 1820 |
B | 520 | 520 | 520 | 520 | 520 | 520 | 520 | 540 |
C | 235 | 235 | 235 | 235 | 235 | 235 | 235 | 276 |
D | 632 | 732 | 832 | 1022 | 1352 | 1452 | 1602 | 1652 |
E | 132 | 132 | 132 | 132 | 132 | 132 | 132 | 194 |
F | 657 | 757 | 857 | 1047 | 1377 | 1477 | 1627 | 1678 |
G | 235 | 235 | 235 | 235 | 235 | 235 | 235 | 276 |
H | 606 | 706 | 806 | 996 | 1326 | 1426 | 1576 | 1626 |
I | 632 | 732 | 832 | 1022 | 1352 | 1452 | 1602 | 1652 |
J | 214 | 214 | 214 | 214 | 214 | 214 | 214 | 255 |
Performance Correction
FP series standard cooling performance correction table
Size
|
Speed
|
ESP
| Air Flow Dry| Capacity Total Sensible| Air Off FCU DB WB| Water Flow| Water Pressure| Power Input| Heating Capacity|
LDBT
| Water Flow| Water Pressure
---|---|---|---|---|---|---|---|---|---|---|---|---
Pa| m³/h| kW| kW| °C| °C| L/s| kPa| W| kW| °C| L/s| kPa
51
|
H
| 0| 794| 4.21| 3.10| 14.37| 13.49| 0.179| 21.20| 75.4| 7.07| 48.87| 0.179|
10.54
25| 685| 3.81| 2.79| 13.86| 13.16| 0.162| 17.79| 70.0| 6.41| 50.32| 0.162|
8.96
50| 530| 3.30| 2.33| 13.08| 12.64| 0.140| 13.79| 63.0| 5.60| 52.64| 0.140|
6.82
75| 328| 2.25| 1.57| 11.69| 11.53| 0.095| 6.99| 54.3| 3.66| 55.76| 0.095| 3.13
M
| 0| 720| 3.94| 2.89| 14.03| 13.26| 0.167| 18.77| 68.3| 6.62| 49.86| 0.167|
9.44
25| 618| 3.54| 2.58| 13.50| 12.93| 0.151| 15.74| 63.5| 5.95| 51.24| 0.151|
7.82
50| 470| 3.00| 2.16| 12.69| 12.35| 0.128| 11.79| 57.0| 4.97| 54.18| 0.128|
7.81
75| 275| 1.96| 1.35| 11.29| 11.17| 0.083| 5.52| 48.7| 3.27| 58.06| 0.083| 7.77
L
| 0| 426| 2.72| 1.94| 12.41| 12.12| 0.116| 9.91| 46.3| 4.52| 54.12| 0.116|
4.76
25| 399| 2.58| 1.83| 12.19| 11.95| 0.110| 9.04| 41.5| 4.29| 54.82| 0.110| 4.77
50| 370| 2.54| 1.80| 12.00| 11.79| 0.108| 8.75| 35.0| 4.04| 55.07| 0.108| 3.86
75| 240| 2.30| 1.61| 11.78| 11.60| 0.098| 7.39| 26.7| 3.76| 55.55| 0.098| 3.29
68
|
H
| 0| 955| 5.16| 3.74| 14.30| 13.35| 0.219| 31.93| 88.4| 8.71| 49.61| 0.219|
16.83
25| 846| 4.78| 3.44| 13.82| 13.03| 0.203| 27.95| 83.0| 8.03| 50.79| 0.203|
14.85
50| 690| 4.25| 3.18| 13.09| 12.53| 0.181| 22.87| 76.0| 7.05| 52.62| 0.181|
12.05
75| 488| 3.20| 2.25| 12.18| 11.89| 0.136| 13.87| 61.2| 5.31| 55.04| 0.136|
7.47
M
| 0| 845| 4.78| 3.44| 13.82| 13.03| 0.203| 27.96| 82.3| 8.03| 50.79| 0.203|
14.85
25| 743| 4.39| 3.14| 13.35| 12.71| 0.187| 24.22| 77.5| 7.33| 51.94| 0.187|
12.85
50| 595| 3.89| 2.76| 12.66| 12.23| 0.165| 19.45| 71.0| 6.21| 53.72| 0.165|
9.78
75| 401| 2.77| 1.92| 11.60| 11.42| 0.118| 10.82| 62.7| 4.51| 56.20| 0.118|
5.81
L
| 0| 531| 3.41| 2.40| 12.38| 12.04| 0.145| 15.52| 56.3| 5.67| 54.51| 0.145|
8.35
25| 504| 3.27| 2.30| 12.26| 11.95| 0.139| 14.41| 53.3| 5.44| 54.84| 0.139|
7.76
50| 475| 3.25| 2.30| 12.10| 11.83| 0.138| 14.23| 45.0| 5.17| 55.24| 0.138|
7.19
75| 345| 3.00| 2.09| 11.90| 11.67| 0.128| 12.48| 36.7| 4.94| 55.61| 0.128|
6.72
85
|
H
| 0| 1195| 6.58| 4.73| 14.22| 13.24| 0.280| 51.78| 110.5| 11.05| 49.95| 0.280|
28.14
25| 1185| 6.54| 4.70| 14.18| 13.21| 0.278| 51.14| 105.1| 10.99| 50.06| 0.278|
28.13
50| 890| 5.70| 3.80| 13.08| 12.45| 0.242| 40.13| 100.0| 9.60| 52.75| 0.242|
21.82
75| 721| 4.71| 3.28| 12.32| 11.89| 0.200| 28.74| 89.1| 7.65| 54.32| 0.200|
16.30
M
| 0| 1 8| 6.29| 4.50| 13.97| 13.07| 0.267| 47.65| 101.0| 10.54| 50.57|
0.267| 26.19
25| 1015| 5.92| 4.21| 13.59| 12.81| 0.252| 43.06| 96.3| 9.86| 51.46| 0.252|
23.68
50| 825| 5.30| 3.75| 12.80| 12.24| 0.225| 35.32| 94.0| 8.50| 53.26| 0.225|
19.07
75| 663| 4.43| 3.07| 12.06| 11.70| 0.189| 26.03| 80.9| 7.17| 54.89| 0.189|
14.72
L
| 0| 724| 4.72| 3.29| 12.34| 11.91| 0.201| 28.99| 68.3| 7.68| 54.27| 0.201|
16.30
25| 696| 4.65| 3.23| 12.22| 11.81| 0.198| 28.24| 63.5| 7.46| 54.55| 0.198|
15.64
50| 625| 4.60| 3.00| 11.89| 11.56| 0.196| 27.74| 57.0| 6.84| 55.28| 0.196|
13.69
75| 600| 4.11| 2.83| 11.77| 11.47| 0.175| 22.75| 48.7| 6.60| 55.50| 0.175|
12.94
102
|
H
| 0| 1284| 7.40| 5.28| 13.72| 12.90| 0.315| 27.10| 137.4| 12.31| 51.07| 0.315|
19.57
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
25| 1175| 7.00| 4.96| 13.36| 12.65| 0.297| 24.46| 132.0| 11.58| 51.90| 0.297|
17.86
50| 1020| 6.50| 4.40| 12.83| 12.27| 0.276| 21.52| 125.0| 10.70| 53.25| 0.276|
16.10
75| 818| 5.45| 3.78| 12.10| 11.73| 0.232| 15.88| 116.3| 8.83| 54.82| 0.232|
11.77
M
| 0| 1170| 6.98| 4.95| 13.35| 12.64| 0.297| 24.46| 127.3| 11.55| 51.93| 0.297|
17.76
25| 1068| 6.58| 4.63| 13.00| 12.39| 0.280| 22.06| 122.5| 10.82| 52.74| 0.280|
16.11
50| 920| 6.05| 4.25| 12.48| 12.01| 0.257| 18.99| 116.0| 9.68| 53.96| 0.257|
13.61
75| 726| 4.98| 3.44| 11.78| 11.48| 0.212| 13.56| 107.7| 8.03| 55.60| 0.212|
10.11
L
| 0| 576| 4.12| 2.82| 11.25| 11.07| 0.175| 9.69| 75.3| 6.59| 56.88| 0.175|
7.32
25| 549| 3.97| 2.71| 11.13| 10.96| 0.169| 9.11| 70.5| 6.33| 57.09| 0.169| 6.81
50| 520| 3.90| 2.67| 10.98| 10.83| 0.166| 8.84| 64.0| 6.02| 57.35| 0.166| 6.31
75| 490| 3.63| 2.46| 10.84| 10.70| 0.154| 7.75| 55.7| 5.71| 57.61| 0.154| 5.82
136
|
H
| 0| 1671| 9.74| 6.91| 13.62| 12.81| 0.414| 37.21| 225.7| 16.09| 51.20| 0.414|
21.90
25| 1589| 9.43| 6.68| 13.41| 12.67| 0.401| 35.19| 206.6| 15.54| 51.69| 0.401|
20.79
50| 1400| 8.90| 6.00| 12.91| 12.31| 0.378| 31.73| 183.0| 14.70| 52.92| 0.378|
18.94
75| 1103| 7.38| 5.10| 12.08| 11.69| 0.314| 22.94| 154.9| 11.86| 54.73| 0.314|
13.84
M
| 0| 1260| 8.11| 5.65| 12.53| 12.03| 0.345| 26.72| 162.6| 13.16| 53.70| 0.345|
16.25
25| 1179| 7.74| 5.37| 12.30| 11.86| 0.329| 24.88| 152.2| 12.49| 54.24| 0.329|
15.03
50| 1050| 7.32| 5.10| 11.93| 11.57| 0.311| 22.55| 137.0| 11.41| 55.08| 0.311|
13.05
75| 871| 6.16| 4.21| 11.43| 11.19| 0.262| 16.71| 117.1| 9.80| 56.25| 0.262|
10.23
L
| 0| 874| 6.16| 4.21| 11.43| 11.19| 0.262| 16.71| 102.2| 9.80| 56.25| 0.262|
10.23
25| 837| 6.06| 4.14| 11.35| 11.12| 0.258| 16.26| 96.5| 9.48| 56.47| 0.258|
9.70
50| 800| 6.00| 4.10| 11.25| 11.05| 0.255| 15.93| 88.0| 9.11| 56.71| 0.255|
9.06
75| 764| 5.53| 3.77| 11.16| 10.98| 0.235| 13.81| 76.5| 8.77| 56.94| 0.235|
8.55
170
|
H
| 0| 2104| 11.51| 8.32| 14.18| 13.26| 0.490| 28.58| 274.8| 19.69| 50.37|
0.490| 19.13
25| 2010| 11.18| 8.06| 14.03| 13.15| 0.476| 27.15| 256.1| 19.08| 50.75| 0.476|
18.11
50| 1750| 10.80| 7.25| 13.49| 12.78| 0.459| 25.48| 225.0| 18.20| 52.25| 0.459|
17.14
75| 1538| 9.42| 6.67| 13.00| 12.43| 0.400| 20.03| 202.2| 15.80| 53.20| 0.400|
13.65
M
| 0| 1465| 9.12| 6.44| 12.83| 12.31| 0.388| 18.99| 201.2| 15.24| 53.60| 0.388|
12.92
25| 1368| 8.69| 6.11| 12.60| 12.14| 0.369| 17.40| 191.1| 14.46| 54.15| 0.369|
11.92
50| 1180| 7.99| 5.70| 12.17| 11.82| 0.340| 15.07| 210.0| 12.86| 55.22| 0.340|
9.85
75| 1073| 7.21| 5.01| 11.93| 11.65| 0.307| 12.61| 154.8| 11.91| 55.82| 0.307|
8.64
L
| 0| 1007| 6.89| 4.78| 11.74| 11.49| 0.293| 11.90| 133.2| 11.32| 56.19| 0.293|
7.96
25| 960| 6.64| 4.58| 11.60| 11.38| 0.282| 10.86| 127.7| 10.85| 56.49| 0.282|
7.48
50| 860| 6.00| 4.10| 11.34| 11.16| 0.255| 9.11| 131.0| 9.89| 57.05| 0.255|
6.41
75| 800| 5.76| 3.93| 11.16| 11.00| 0.245| 8.49| 107.6| 9.28| 57.38| 0.245|
5.74
204
|
H
| 0| 2311| 13.26| 9.45| 13.77| 12.93| 0.564| 43.60| 295.7| 21.69| 50.43|
0.564| 26.43
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
25| 2229| 12.94| 9.20| 13.64| 12.84| 0.550| 41.93| 276.6| 21.14| 50.76| 0.550|
25.37
50| 2040| 12.60| 8.60| 13.29| 12.59| 0.536| 40.31| 253.0| 21.00| 51.72| 0.536|
24.51
75| 1743| 11.07| 7.74| 12.68| 12.14| 0.470| 33.05| 224.9| 17.80| 53.02| 0.470|
19.60
M
| 0| 1630| 10.58| 7.36| 12.43| 11.95| 0.450| 31.00| 255.6| 16.94| 53.60|
0.450| 18.24
25| 1549| 10.22| 7.09| 12.25| 11.82| 0.435| 29.50| 245.2| 16.31| 54.00| 0.435|
17.18
50| 1420| 9.82| 6.82| 11.95| 11.59| 0.418| 27.85| 230.0| 15.26| 54.67| 0.418|
15.56
75| 1241| 8.71| 5.97| 11.54| 11.26| 0.370| 23.46| 210.1| 13.72| 55.60| 0.370|
13.15
L
| 0| 1194| 8.45| 5.77| 11.43| 11.17| 0.359| 22.51| 150.2| 13.27| 55.86| 0.359|
12.50
25| 1154| 8.34| 5.69| 11.34| 11.10| 0.355| 22.17| 144.5| 12.93| 56.06| 0.355|
11.97
50| 1 5| 8.30| 5.70| 11.26| 11.04| 0.353| 22.00| 136.0| 12.54| 56.28|
0.353| 11.40
75| 1077| 7.77| 5.29| 11.18| 10.98| 0.331| 20.19| 124.5| 12.18| 56.47| 0.331|
10.83
238
|
H
| 0| 2817| 16.11| 11.45| 13.85| 12.95| 0.685| 52.15| 325.9| 26.93| 51.00|
0.685| 31.29
25| 2630| 15.46| 10.93| 13.56| 12.75| 0.657| 49.17| 309.9| 25.71| 51.67|
0.657| 29.31
50| 2380| 15.00| 10.90| 13.14| 12.45| 0.638| 47.22| 301.0| 25.00| 52.88|
0.638| 30.73
75| 2218| 13.90| 9.71| 12.86| 12.25| 0.591| 42.55| 277.8| 22.77| 53.21| 0.591|
24.60
M
| 0| 2355| 14.45| 10.14| 13.11| 12.42| 0.614| 44.80| 261.5| 23.81| 52.68|
0.614| 26.25
25| 2183| 13.76| 9.60| 12.80| 12.20| 0.585| 41.97| 251.7| 22.51| 53.35| 0.585|
24.19
50| 1990| 12.94| 8.98| 12.45| 11.94| 0.550| 38.71| 237.3| 21.01| 54.11| 0.550|
21.86
75| 1736| 11.77| 8.10| 11.96| 11.57| 0.501| 34.38| 217.7| 18.90| 55.14| 0.501|
18.78
L
| 0| 1567| 10.94| 7.49| 11.63| 11.31| 0.465| 31.40| 154.5| 17.42| 55.82|
0.465| 16.58
25| 1475| 10.45| 7.12| 11.45| 11.16| 0.444| 27.84| 149.3| 16.55| 56.20| 0.444|
15.35
50| 1350| 9.76| 6.63| 11.20| 10.96| 0.415| 29.73| 140.7| 15.37| 56.71| 0.415|
13.71
75| 896| 6.98| 4.65| 10.29| 10.18| 0.297| 19.77| 126.7| 10.67| 58.41| 0.297|
7.65
Note:
- Nominal conditions for cooling: 26.7/19.4°C indoor dry/wet bulb temperature, 7.2/12.8°C entering and leaving water temperature
- Nominal conditions for heating: 21.1°C indoor dry bulb temperature, 60°C entering water temperature, the same water flow as that for cooling.
- The noise listed above is tested at the high speed in a semi-anechoic chamber 1m away from both the bottom side of the unit and the air outlet. It may differ with the actual noise as the operation environment varies.
- Parameters listed at the nameplate always prevail.
- On request of the clients, the return air plenum is optional. Parameters listed above are for the unit without the return air plenum.
Installation
Installation Instructions and Precautions
Installation Location and Environment
- Do not install the unit where there is heavy smog, otherwise the plastic components would age, break off or leak.
- Do not install the unit where there is corrosive or inflammable gas.
- Do use the lifting rod for installation and make sure the installation location is capable of bearing 4 times weight of the unit. If not, it should be reinforced before installation.
- The FCU should be kept level during hoisting. The lifting fitting is only allowed to bear the weight of the unit other than air ducts, water tubes, and other.
Electric Wiring
- All wiring should be performed by qualified technicians in accordance with national or local laws and regulations.
- The wiring diagram stuck to the body of the main unit always prevails.
- Note: The wiring diagram as shown below is just for reference. Those struck to the main body of the unit always prevail for repair and maintenance.
FP/FPD series FCU
FPE/FPED series FCU (single motor)
FP/FPD series FCU (dual motors)
Selection requirements
- Application type (standard / district cooling);
- Ventilation, drainage and power supply;
- Fresh air and ventilation requirements;
- Noise level or part required during peak period;
- The required control system, especially if winter heating is require;
- Give the unit enough space, including the floor-to-ceiling height, and take care of the maintenance.
- Ensure that there is enough installation and maintenance space around the unit, and keep away from obstacles at the air inlet and outlet to ensure that the airflow can blow through the entire room, so that the unit is ventilated smoothly and reliably. The condensation pipe should be kept clear and the drainage gradient should be >5%.
- Horizontal concealed type fan coil unit.
Optional Parts
Thermostat
- It is applicable to fan coil units manufactured not only by GREE but also others.
- It can be used matching with a standard #86 mounting case. As electric wiring is concealed inside it, it makes the whole indoor decoration looks better.
Z54352A1 Thermostat
Outline Dimensions (Unit: mm)
Electric Wiring
WK-011PM Thermostat
It is intended for indoor temperature control for the fan coil unit or ducted unit of the central air conditioning system. Based on difference of the actual indoor temperature and the set point, it will do control to the fan coil unit so as for desired indoor temperature, comfort and energy saving benefits.
With the micro-computer control technologies and large-sized LCD, it will control the electronic valve and the three-speed motor through push buttons (buttons for operation of ON/OFF, mode, fan speed and temperature). When the indoor temperature reaches the desired point, it will stop the electronic valve and let the motor run with the speed set point. There are additional functions, including timing ON/OFF, child lock, energy saving, and dehumidification. Manual setting are allowed to the fan operation after reaching the desired set point, hold-on temperature range and memory upon ON/OFF.
Image
Features
Outline Dimensions (Unit: mm)
Electric Wiring
WK-010PW Thermostat for the Fan Coil Unit
It is intended for indoor temperature control for the fan coil unit or ducted unit of the central air conditioning system. Based on difference of the actual indoor temperature and the set point, it will do control to the fan coil unit so as for desired indoor temperature, comfort and energy saving benefits.
With the micro-computer control technologies and large-sized LCD, it will control the electronic valve and the three-speed motor through push buttons (buttons for operation of ON/OFF, mode, fan speed and temperature). When the indoor temperature reaches the desired point, it will stop the electronic valve and let the motor run with the speed set point. Manual setting are allowed to the fan operation after reaching the desired set point, hold-on temperature range and memory upon ON/OFF. The thermostat offers BMS functions.
Image
Features
Installation Dimensions (Unit: mm) / Electric Wiring
WK-011PA Thermostat
It is intended for indoor temperature control for the fan coil unit or ducted unit of the central air conditioning system. Based on difference of the actual indoor temperature and the set point, it will do control to the fan coil unit so as for desired indoor temperature, comfort and energy saving benefits.
With the micro-computer control technologies and large-sized LCD, it will control the electronic valve and the three-speed motor through push buttons (buttons for operation of ON/OFF, mode, fan speed and temperature). When the indoor temperature reaches the desired point, it will stop the electronic valve and let the motor run with the speed set point. There are additional functions, including timing ON/OFF, child lock, energy saving, and dehumidification. Manual setting are allowed to the fan operation after reaching the desired set point, hold-on temperature range and memory upon ON/OFF.
Water Valve
General
T41-V41 series electric heating constant-temperature water valve is intended to control the open and closed status of the pipes for the heating or cooling system so as to control the indoor temperature. There are both 2-way and three-way valves. On request, the extended coils and connection pipes as well as the water valve kit can be delivered all together. As installation of the water valve is quite simple, it can be installed by the contractor as shown in the figure below.
Technical parameters
Model| Type| Coefficient of flow (Kv) straight| Coefficient of
flow (Kv) angular| Closing pressure (MPa)| Connector| Centre-to-
centre distance (mm)
---|---|---|---|---|---|---
V41D20S(O)250| 2-way| 2.5| ―| 0.15| G3/4(DN20)|
V41D20T250| 3-way| 2.5| 1.6| 0.15| G3/4 (DN20)| 50
Assembly and Usages
- Pay attention to the allowable water flow direction of the valve during installation. The control or drive device should be located above the valve. It would be better to use the three-way valve for mixed fluids.
- Before powering the unit on, check the power source required for the drive, otherwise the motor would be damaged.
- See the installation guides for the water valve for more details.
Gree Electric Appliances, Inc. of Zhuhai, founded in 1991, is the world’s largest air conditioner enterprise integrating R&D, manufacturing, marketing and services. Technology Innovation and quality are always our priority. With efforts of thousands of Gree’s engineers, we own more than 3500 patents for our products.
Nowadays, we have 7 production bases in Zhuhai, Chongqing, Hefei and Zhengzhou(China), as well as Brazil, Pakistan and Vietnam, with annual production capacity of 30 million sets of residential air conditioners and 4 million sets of commercial air conditioners.
With the installation of Gree commercial air conditioners in important projects at home and abroad like Media Village for 2008 Beijing Olympic Games, Stadiums for 2010 World Cup in South Africa, as well as India Telecom base station, Gree commercial air conditioners are ready to develop steadily to every corner in the world, to present a more comfortable and harmonious working environment and family atmosphere.
Contact
- Add: West Jinji Rd, Qianshan Zhuhai, Guangdong, China 519070
- Tel: +86-756)8614883
- Fax: +86-756)8614998
- http://www.gree.com
- Email: global@cn.gree.com
For continous improvement in the products, Gree reserves the right to modify the product specification and appearence in this manual without notice and without incurring and obligations.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>