RUSKIN TS150 Firestat for Reopenable Fire and Smoke Dampers Instruction Manual
- June 9, 2024
- RUSKIN
Table of Contents
RUSKIN TS150 Fire stat for Reopenable Fire and Smoke Dampers
APPLICATION
The TS150 is a UL Classified heat responsive device which is used in conjunction with Ruskin fire/smoke dampers. The TS150 is an optional device which can be ordered with electric actuators or pneumatic actuators and EP (electro/pneumatic) switches. The TS150 allows the dampers to be reopened after the initial closure for dynamic smoke control. The TS150 must be installed at the factory and cannot be added in the field. Replacement TS150’s may be field installed with the approval of the local authority.
SMOKE DETECTION/TEST/POWER FAILURE OPERATION
If smoke is detected, or during testing, or if power failure occurs, the damper will close and lock. When the smoke signal ceases (or smoke detector resets) , the test is complete or power is restored the SYSTEM will automatically REMOTE RESET the damper to the open position. The damper automatically resets if nuisance alarms occur and the SYSTEM is reset. The damper may be closed at any time by placing the MCP1 (optional) or other control switch (by others) in the CLOSED position.
FIRE OPERATION
When the switch of a control panel (MCP) is in the NORMAL position and
temperatures in excess of 165°F/74°C (212°F/100°C optional) are detected, the
damper will close and lock and the damper CLOSED indicator light on the
control panel will light. The damper remains closed until the override signal
for smoke management from a remote command station is present and the duct
temperature has not exceeded the high limit. The high limit temperature sensor
prevents the damper from reopening when duct temperature is above the damper’s
UL555S degradation test temperature of 250°F/121°C or 350°F/177°C. Upon
cessation of the fire condition, the damper can be reopened by pressing the
RESET button on the TS150 assembly. At no time will the damper disengage from
the actuator. The integral SP100 will positively communicate to the fire
commander via the control panel the position of the damper for smoke
management purposes. Refer to the appropriate damper installation instructions
for details on damper installation. All electrical wiring and connections to
the Fire-Stat must be in accordance with the standards of the authorities
having jurisdiction.
S1 and S2 Switch AMP Ratings: 15 AMPS, @ 24, 125 or 250 VAC 1/2 AMP, @ 125
VDC, 1/4 AMP, @ 250 VDC
SEE COMPLETE MARKING ON PRODUCT
ITEM | DESCRIPTION |
---|---|
1 | TS-150 Fire Stat |
2 | Adjustable Connecting Rod |
3 | Flex Conduit |
4 | Damper Frame |
5 | Actuator or EP Switch |
6 | Over-Center Lock |
7 | Damper Sleeve |
8 | FAST, PFMA or conventional mounting angles |
9 | Sleeve to Duct Connection (by others) |
AVAILABLE TEMPERATURE SETTINGS
Primary | Hi-Limit |
---|---|
165°F/74°C | 250°F/121°C |
165°F/74°C | 350°F/177°C |
212°F/100°C | 250°F/121°C |
212°F/100°C | 350°F/177°C |
250°F/121°C | 350°F/177°C |
WIRING DIAGRAM 3900 Doctor Greaves Road
Grandview, MO 64030
Website: www.ruskin.com
Phone: 816-761-7476