APPLICATION
The Z11S automatic reverse rinsing actuator provides fully automatic cleaning
for all Resideo reverse rinsing filters, filter combinations, water supply
units and water distributor units. The reverse rinsing intervals are
adjustable in sixteen steps between four minutes and three months. The Z11Shas
an emergency running function in the event of power failure (only when
batteries are fitted) and offers the possibility of manual operation of the
reverse rinsing function. Connection options are available for differential
pressure switching, remote control and remote monitoring.
SPECIAL FEATURES
- Push buttons give easy setting of intervals.
- Push button for manual operation of reverse rinsing.
- Digital indicator of time interval set.
- Digital indicator of number of reverse rinsing cycles carried out
- Facility to indicate time remaining before next programmed reverse rinsing cycle
- Reset button enables resetting of counter
- Settings are maintained even when electrical power fails
- Set during manufacture to 45 day interval Can be set to 16 different reverse rinsing intervals Automatic battery 1) run-on if mains supply fails
- Manufactured with integral electrical suppression
- Additional PG 9 cable entry for connection of remote operation, remote monitoring or differential pressure control Can be connected for differential pressure switch, remote operation or remote monitoring.
- Bayonet connection enables fitting without tools.
TECHNICAL DATA
Operating temperatures
Max. water temperature:| 70 °C
Specifications
Mains cable:| 1.5 metres
Batteries:| Four LR6-1.5 V-Mignon/AA size alkali-manganese
batteries 1)
Battery life:| Approximately 3 years
Time intervals:| 4 minutes to 3 months
Ambient conditions:| 5 – 90 % relative humidity,
0 – 60 °C
Protection class:| 1 DIN VDE 0700-T1/
EN 60335-1
Protection type:| IP 55 sprayed water
CONSTRUCTION
Overview
Components | Materials | ||
---|---|---|---|
1 | Bayonet connection | – | |
2 | Housing | High-quality synthetic |
material
3| Mains cable| –
METHOD OF OPERATION
The Z11Sopens or closes the ball valve according to the set time interval. The
opening of the ball valve causes a differential pressure within the filter
which activates the reverse rinsing function. The ball valve closes again at
the end of the reverse rinsing period. Four batteries (not supplied) provide
back-up protection. The batteries close the ball valve if power fails during
reverse rinsing function, thus preventing unwanted water loss.
REVERSE RINSING
Reverse rinsing duration when mains electrical operation approximately 25 sec.
Reverse rinsing quantity at 4.0 bar operating pressure.
Filter size| Drain connection| Reverse rinsing
quantity (litres)
---|---|---
1/2” + 3/4“| DN50| 12
1″ + 11/4“| DN70| 15
11/2” + 2″| DN70| 18
TRANSPORTATION AND STORAGE
Keep parts in their original packaging and unpack them shortly before use. The
following parameters apply during transportation and storage:
Parameter | Value |
---|---|
Environment: | clean, dry and dust free |
Min. ambient temperature: | 0 °C |
Max. ambient temperature: | 60 °C |
Min. ambient relative humidity: | 5 % * |
Max. ambient relative humidity: | 90 % * |
INSTALLATION GUIDELINES
Setup requirements
- In case the mains supply fails during the backwash the batteries (if they are fitted) provide the energy for closing the backwash ball valve. The battery charge should be checked regularly. At the latest after two years exchange the batteries with new ones.
- In order to avoid flooding, it is recommended to arrange a permanent, professionally dimensioned wastewater connection.
Installation Example
Fig. 1 Remote control analogous.
Fig. 2 Remote control digital.
Fig. 3 Differential pressure switch.
Fig. 4 Remote monitoring.
Additional connection options The Z11S can be remotely actuated by:
- A volt-free switching circuit
- Via an open-collector output In both cases the minimum holding period is one second. Reverse rinsing occurs when the inputs “Start” and “U+” have been separated. The reverse rinsing function can be actuated according to demand using the DDS76 differential pressure switch with voltage free switching. It is recommended that the differential pressure be set to 1.0 bar. Operation occurs when the inputs “Start” and “U+” have been separated, that is, after the differential pressure has fallen below the set value. Through this it is guaranteed that a maximum quantity of water is available for reverse rinsing. If reverse rinsing starts immediately irrespective of the duration of the differential pressure signal, then the inputs should be connected instead to “U+” and “SIGN”. The DDS76 differential pressure switch can only be used where Z11S and F76S fine filters are also installed. For remote monitoring of the open/closed position of the ball valve the installation of a building management system with 0 to 10 V input is recommended. The maximum current is 10 mA. With a current of 0.5 V the ball valve is open and with a value between 5 V and 6 V the ball valve is closed.
DIMENSIONS
Overview
ORDERING INFORMATION
The following tables contain all the information you need to make an order of
an item of your choice. When ordering, please always state the type, the
ordering or the part number.
Options
The actuator is available in the following sizes: 1/2″, 3/4″, 1″, 11/4″, 11/2″
and 2″. standard- not available.
Z11S-A | Z11S-B | Z11S-Z | ||
---|---|---|---|---|
Connection type: | 230 V, 50/60 Hz, 10 W with moulded Schuko |
electrical plug
| •| –| –
24 V, 50/60 Hz, 10 W without electrical plug| –| •| –
230 V, 50/60 Hz, 10 W with moulded Type 12
electrical plug for Switzerland
| –| –| •
Manufactured for and on behalf of
Pittway Sàrl, Z.A., La Pièce 4, 1180 Rolle, Switzerland by its authorised
representative Ademco 1 GmbH.
For more information
homecomfort.resideo.com/europe
Ademco 1 GmbH, Hardhofweg 40, 74821 MOSBACH, GERMANY
Phone : +49 6261 810
Fax : +49 6261 81309
© 2020 Resideo Technologies, Inc. All rights reserved. Subject to change. EN0H-1119GE23 R0420.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>