resideo Braukmann AM-1 Series Thermostatic Mixing and Diverting Valve Standard and C Temperature Range Installation Guide
- June 7, 2024
- resideo
Table of Contents
Braukmann
AM-1 Series
PROPORTIONAL THERMOSTATIC MIXING AND DIVERTING VALVE STANDARD AND “C”
TEMPERATURE RANGE MODEL
INSTALLATION INSTRUCTIONS
APPLICATION
The AM-1 Series family of quality valves in a variety of temperature ranges and connections, for master mixing or diverting applications.
SPECIFICATIONS
Media Temperature Ranges:
Cold Inlet: 39°F-80°F (4°C-27°C)
Hot Inlet: 120°F-180°F (49°C-82°C)
Mixed Outlet:
C Model: 70°F-120°F (21°C-49°C)
Standard Model: 70°F-145°F (21°C-63°C)
Connections:
Straight-through design (HOT and COLD at the same level).
Construction:
Nickel-plated brass construction. EPDM o-rings. Made in USA.
Lead-Free Plumbing Code Compliance: The wettable surfaces of lead-free
models contain less than .25% of lead by the weighted average
Operating Pressure: 150 psi (1034 kPa) maximum.
Patent Information: U.S. Patent No. 6,079,625.
Temperature Gauge Adapter: Lead-free brass,
EPDM o-ring
INSTALLATION
IMPORTANT
Mounting must comply with all local codes.
NOTE TO INSTALLER: This product should be installed by a qualified individual,
in accordance with local codes and ordinances. It is the responsibility of the
installer to properly select, install and adjust these devices as specified in
these instructions. For installations that require compliance with
Building/Mechanical/Plumbing Codes, the appropriate AM-1 Series valve must be
chosen and installed, and the discharge temperature set and locked according
to these instructions. AM-1 “C” Series models with the temperature range,
70°F– 120°F (21°C–49°C) and “Standard” models with temperature range
70°F–145°F (21°C–63°C) are ASSE 1017 (point of source application) certified,
and CSA ® ®a ® and IAPMOlisted.These models shall be used to supply water to
tubs, showers, bathing facilities, and other outlets. These valves should be
installed where they will be accessible for cleaning, servicing or adjustment.
ASSE 1017 Applications—Point of Source
These AM-1 Series models can be installed in any position consistent with the
intended use. For domestic hot water supply, the valve must be installed as
shown in Fig. 1. There shall be no shut-off valves installed between the cold
water line and the cold water connection on the AM-1 Series valve. Check
valves shall be installed as indicated for NPT models; all AM-1 model with
union fittings are supplied with integral check valves on both the hot and
cold ports. A cold water service valve may be installed, as indicated,
between the cold water supply line to the distribution system and the cold
water line supplying both the water heater and the AM-1 Series valve.
Installation of Union Sweat, CPVC, neon Propress, Push Connect, and PEX
Connections
— Union sweat connections, if used, should be soldered prior to assembly to
the valve, or without the sealing gasket or optional check valve present.
After the joint has cooled, the sealing gasket and/or check valves may be
installed.
— CPVC fittings are limited to a system maximum temperature of 180° F (82° C)
and 100psi (689 a).
— PEX fitting and crimp ring (provided by Installer) are designed to meet ASTM
F1807 requirements.
— PEX tubing used with PEX fittings must meet ASTM F876 requirements.
— Press connections, using press tools, and installation practices compatible
with Viega systems.
— Push connect fittings can be used with both copper and LDPE (plastic).
Utilize the included tube liners for non-copper applications.
Installation of Temperature Gauge Adapter
IMPORTANT
Union sweat connections must be soldered before the thermowell with O-ring and
sealing gasket are installed. Install the thermowell with O-ring and sealing
gasket after the joint has cooled.
- Install thermowell with O-ring to the thermometer adapter body.
- Tighten to 75 LB-IN ± 10 LB-IN. DO NOT OVERTIGHTEN.
- Install the thermometer into the thermowell until seated and tighten the set screw to secure it in place.
VALVE ADJUST CEMENT
To adjust the temperature setting of the mixing valve, attach the mo strip
(supplied with the valve) to the piping connected to the Mix port of the
valve. Loosen handwheel screw, lift handwheel and turn to the desired
temperature as indicated on the most rip. Reposition the handwheel and
retighten the screw.
Temperature Setting Procedure
It is possible to limit the temperature range. To use this feature:
M27487A
- LOOSEN SCREW, LIFT HANDWHEEL.
- TURN THE HANDWHEEL CLOCKWISE OR COUNTERCLOCKWISE TO ADJUST TEMPERATURE.
- REPOSITION HANDWHEEL TO LOCK POSITION.
- RETIGHTEN SCREW.
Thermostrip Installation
Clean pipe and firmly apply Thermostrip on mix outlet of the valve. Flow water
and adjust mixed outlet temperature for desired setting range. Actual mixed
water temperature is indicated in green with 2° F (1° C) increments. Blue
means slightly lower and brown means slightly higher.
WARNING
Water Temperature above 120°F (49° C) can cause serious injury. Mixing
valve temperature setting should be done by licensed contractor per local code
requirement. To ensure correct temperature control, use a water thermometer at
the faucet outlet.
The thermostrip is ONE TIME USE ONLY for the initial system temperature
setting. Check the expiration date printed on the temperature strip to ensure
temperature reading accuracy. If necessary, contact your Resideo distributor
to obtain a replacement thermostrip, part number TS205-064.
Thermostrip is only included in models without the temperature gauge.
Post Installation Procedure
1. Write temperature setting on CAUTION label and sign in space provided.
2. Attach CAUTION label to AM-1 valve.
3. Explain the CAUTION label to the owner.
4. Deposit this instruction sheet with the owner.
OPERATION
The AM-1 series valve provides for automatic operation through the use of a thermostatic element in the product. The element will control the mixing of the hot and cold supply to provide mixed tempered water to connected fixtures. This provides constant water temperature under different working conditions.
MAINTENANCE PROCEDURES
Hard water conditions may result in scale deposits, causing binding of internal parts in extreme cases. Cleaning the internal parts will usually restore the valve to proper operating conditions. In some cases, it may be necessary to replace the lower assembly.
To clean and/or replace the lower assembly, shut off water and:
- With a screwdriver, remove the screw and handwheel.
- Loosen upper nut (do not remove) to allow engaging an adjustable wrench on the lower nut. Unscrew lower nut (counterclockwise). This removes top assembly.
- Brass top assembly will pop up. Remove lower assembly, diffuser, and spring.
- Carefully remove any scaling (calcium deposit) or foreign particles from the valve seat and other internal parts. Use vinegar to remove calcium. Soak parts until calcium becomes soft and can be scrubbed and washed off. Do not use solvents or scratch metallic / Teflon® coated surfaces.
- Replace cleaned spring, diffuser, and lower assembly following the instructions below or use a new replacement kit assembly. For the correct kit number, see Table 1.
Install spring, diffuser, and lower assembly:
- Insert spring onto the diffuser.
- Insert diffuser with spring end first into the body.
- Fit valve top assembly into lower assembly and insert into the valve.
- Tighten lower nut.
- Reposition the handwheel and insert the screw. Turn the handwheel to the desired temperature setting.
Table 1. AM-1 Series Replacement Kits
Part No. | Model | Description |
---|---|---|
AM-1-020RP | C | 70 °F-120 °F (21 °C-49 °C) Thermostatic Element Replacement Kit |
AM-1-025RP | STD | 70 °F-145 °F (21 °C-63 °C) Thermostatic Element Replacement |
Kit
AM1-TG100-US-LF/U| ALL| 1/2″ (12.7 mm) AM1 Temp Gauge Tail PC w/Sweat
AM1-TG101-US-LF/U| ALL| 3/4″ (19 mm) AM1 Temp Gauge Tail PC w/Sweat
AM1-TG102-US-LF/U| ALL| 1″ (25.4 mm) AM1 Temp Gauge Tail PC w/Sweat
TG200-UT/U| ALL| Thermometer, 2″ (50.8 mm) Dial w/ Threaded Well
TG250-UT/U| ALL| Thermometer, 2.5″ (63.5 mm) Dial w/ Threaded Well
ASSE® is a registered trademark of the American Society of Sanitary
Engineering.
CSA® is a registered trademark of the Canadian Standards Association.
IAPMO® is a registered trademark of the International Association of Plumbing
and Mechanical Officials.
ASTM® is a registered trademark of the American Society for Testing and
Materials.
Teflon® is a registered trademark of E.I. du Pont de Nemours and Company.
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
62-3075EFS—09 M.S. Rev. 03-20 | Printed in the United States
www.resideo.com
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>