Honeywell PWTA Series Conduit Wet Pressure Transmitters Installation Guide
- June 7, 2024
- Honeywell
Table of Contents
Honeywell PWTA Series Conduit Wet Pressure Transmitters Installation Guide
WARNING
This product can expose you to chemicals including 1,3 Butadiene, which is known to the State of California to cause cancer and reproductive harm. For more information, go to www.P65Warnings.ca.gov
APPLICATION
The PWTA Series wet/wet differential pressure sensors provide reliable, accurate measurement and control of proper applications, including the monitor and control of pump differential pressure, chiller/boiler differential pressure drop, and CW/HW system differential pressure. The PWTA Series is ideal for measuring pressure across pumps, filters, heat exchangers, compressors and other non-corrosive wet media applications. he PWTA Series of pressure sensors feature three field selectable pressure ranges, bi/uni- directional modes with configurable output: 4-20 mA, 0-5 Vdc, or 0-10 Vdc output.
IMPORTANT
- Only qualified trade installers should install this product
- This product is not intended for life-safety applications
- Do not install in hazardous or classified locations
- The installer is responsible for all applicable codes
- De-energize power supply prior to installation or service
Product Application Limitation:
Honeywell products are not designed for life or safety applications. Honeywell products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Honeywell is not liable, in whole or in part, for any claims or damages arising from such uses.
IMPORTANT
- Do NOT exceed gauge pressure rating of sensor.
- Use ONLY Honeywell gauge pressure sensors provided with your PWTA transmitter to obtain the specified transmitter accuracy.
- Follow instructions step by step to ensure proper setup
DIMENSIONS
CONNECTION WIRING
Honeywell recommends 22 AWG stranded, 4 conductor shielded cable to wire between the PWTA transmitter and pressure sensors.
Terminals are rated for 24-14 AWG, 3.5 lb-in of torque.
INSTALLATION
-
Identify PWTA sensors A & B and their respective PSIG rating.
If the expected system gauge pressure exceeds the PSIG rating on the PWTA sensors call factory and DO NOT proceed with install.- PWTA40-X = 100 PSIG (50/75/100 PSID)
- PWTA100-X = 100 PSIG (10/20/40 PSID)
- PWTA250-X = 250 PSIG (75/150/250 PSID)
-
Plumb sensors to media. Sensor A is intended for supply pressure and sensor B is intended for return pressure of the system. Plumb sensors to the side or top of pipe, as plumbing to the bottom will cause sediment to settle and could clog or affect sensor accuracy.
It is advisable to use a single wrap of PTFE tape on the sensor thread sealing alternative, to improve sensor accuracy.
No bypass valve manifold is necessary. Use only Honeywell gauge pressure sensor elements provided with your transmitter.
Optional shutoff valves are available:
Honeywell recommends closing service valves when flushing system to prevent contaminants and water hammer from damaging sensing elements. -
Mount the PWTA transmitter and run conduit (if required) between the transmitter and the sensors.
-
Run the appropriate length cables between the PWTA transmitter and sensors.
Honeywell recommends 22 AWG stranded, 4 conductor shielded cable to wire between the PWTA transmitter and the sensors. -
Loosen the top screw on each sensor and remove the terminal block for wiring as shown below.
-
Conduit Adapter
-
Terminal Block
-
* **Rubber Cover**
* **Pressure Sensing Element**
-
Run the cable through the conduit adapter and connect the wires to the sensor terminal block. Note that the conduit terminal block is numbered and color coded to match the terminal label colors on the PWTA transmitter
Reassemble the sensor conduit adapter and terminal block. Place the rubber cover back on the conduit adapter and plug the adapter onto the sensor. Tighten the assembly screw.
DO NOT attempt to plumb or tighten the sensors while wires are attached, as you run the risk of pulling wires from cable attachments
-
Wire sensors A & B to the PWTA Transmitter terminals labeled A & B respectively. For strain relief, use the cable clamps as shown below:
IMPORTANT
Cable shielding should ONLY be connected to the GROUND terminal at the PWTA transmitter. DO NOT connect cable shielding at the pressure sensor.
Picture above shows the 5 wires connected properly from the sensor to the PWTA transmitter (+/- voltage supply (terminals 1 and GROUND), +/- feedback from transducer (terminals 2 and 3) and shield wire (GROUND terminal). -
Connect conduit fittings to the sensors and PWTA transmitter. Use water tight fittings if required by your installation conditions.
-
Wire PWTA transmitter for voltage or current output as shown (Remote zero wiring is optional)
-
. Use the following diagram for the remaining configuration of your PWTA system.
-
Select 20 mA, 5 V or 10 V output using OUTPUT switch based on wiring configuration.
-
Verify the PSIG jumper matches the PSIG rating on the sensors.
Sensor Identification:- PWTA40-X = 100 PSIG
- PWTA100-X = 100 PSIG
- PWTA250-X = 250 PSIG
PWTA Transmitter Jumper Configuration
-
Select differential pressure range using RANGE switch. Identify if your PWTA transmitter is labeled a PWTA40, PWTA100, or PWTA250 model. Each Transmitter provides three PSID ranges based on the PSIG rating on sensors A and B. Use the appropriate PSID range selection chart below based on the transmitter label. Selected range will scale the PWTA transmitter output
Transmitter PSID Range Selection:
-
Inspect LCD for readings. LCD toggles between sensor A reading, sensor B reading, and PSID reading.
Sensor A reading is indicated by a tick mark on the top left of LCD. Sensor B reading is indicated by a tick mark at the bottom left of LCD. PSID reading is displayed without any mark at the left of the LCD.
O/R symbol will flash in bottom center of LCD if differential pressure reading is over range. If this occurs, select larger PSID range to avoid clipping of readings. -
. Check remaining jumper configurations for additional setup options:
Display Units: LCD will display readings in PSI or kPa. LCD will indicate PSI or kPa at top of screen.
Test Mode: In “Test Mode” sensor forces outputs to fullscale for testing wiring and panel setup.
Direction Mode: PWTA transmitter can be set up in Uni or Bi directional mode.
Table 1. Bi-Directional Mode Example range set at 100
Response Time: In “Slow Mode” the output returns a reading averaged over
64 samples. In ‘Fast Mode’ the output returns the most recently calculated
reading for PSI.
Port Swap: If Sensor A was plumbed to the return (low) side and Sensor B
was plumbed to the supply (high) side instead of re-plumbing the sensors, the
Port Swap can be utilized without a physical reconfiguration. If this jumper
is removed, transmitter is in Absolute Mode, where values will always be
reported positive.
- To custom zero the device (optional), hold down the zero button for 5 seconds (until the LCD blinks once). Hold down for 10 seconds (until LCD blinks twice) to reset/clear the zero value.
- Seal remaining conduit knockouts on PWTA transmitter.
CALIBRATION
Honeywell wet pressure sensors are factory calibrated as a set to each PWTA transmitter.
RECYCLING
Product should not be thrown away in regular trash. Instead, it should be recycled according to local municipality.
TROUBLESHOOTING
Symptom | Solution |
---|---|
No output | Check wiring. Ensure power supply meets requirements. |
Pressure reading error | Verify control panel software is configured for |
correct output scaling.
Verify switch and jumper settings.
Device will not zero| Hold ZERO button for full 5-seconds until LCD blinks
once.
Continue holding ZERO button for 10-15 seconds, until LCD blinks twice, to
restore to factory settings.
SPECIFICATIONS
Power supply
| Voltage output (0-5V)| 12-30 VDC/24 VAC1,
20 mA max.
---|---|---
Voltage output (0-10V) Current (4-20 mA) output| 15-30 VDC/24 VAC
12-30 VDC, 20 mA max.
Outputs| Switch selectable| 2-wire 4-20 mA, 3-wire 0-5V/10V
Pressure Ranges (Switch selectable)| PWTA40-X PWTA100-X
PWTA250-X| 10/20/40 PSID
50/75/100 PSID
75/150/250 PSID
Operating Temperature| Transmitter| 32 to 140°F (0-60°C)
Media Compatibility| Type| Water, other 17-4 SS compatible media
Temperature| -40 to 248°F (-40-120°C)
Zero adjustment
|
Automatic
| Pushbutton, terminal block switch input
Press button for 5 seconds to re-zero
Hold for 10 seconds to restore to factory settings
Sensor type| | Micro-machined silicon strain gauge
PWTA40
Transmitter
| Accuracy2| Range A: +/-4% FS Range B/C: +/- 2% FS
PWTA100/250
Transmitter
| Accuracy2| Range A: +/-2% FS Range B/C: +/- 1% FS
Sensor Performance
| Accuracy| < +/-0.5% BFSL
---|---|---
Zero Offset| < +/-2% FS
Span Tolerance| < +/-2% FS
Stability (1 year)| +/-2.5% FS, typ
Over-range protection| 2x rated pressure
Burst pressure| 5x or 20,000 PSI
(whichever is less)
Pressure Cycles| > 100 million
Compensated Range| 30 to 130°F (0-55°C)
Temperature Compensation| Zero, < +/-1.5% of FS Span, < +/-1.5% of FS
Shock| 100G, 11 msec, 1/2 sine
Vibration| 10G peak, 20 to 2000 Hz
EMI/RFI Protection| Yes
Enclosure, Transmitter| Construction| Powder coated steel
Sealing| IP65 (Installed with water- tight fittings)
Enclosure, Sensor| Construction| Stainless Steel, 17-4, 1/4” MNPT, 1/2”
Conduit Fitting
One side of transformer secondary is connected to signal common. Dedicated transformer is recommended
For PWTA Transmitter performance accuracy, FS is defined as the full scale of the selected range in bi-directional mode
SPECIFICATION BY PRODUCT
Product Number | Max PSIG | Selectable PSID Range |
---|---|---|
PWTA40-X | 100 PSIG | 10/20/40 PSID |
PWTA100-X | 100 PSIG | 50/75/100 PSID |
PWTA250-X | 250 PSIG | 75/150/250 PSID |
Honeywell Building Technologies
In the U.S.: Honeywell
715 Peachtree Street NE Atlanta, GA 30308
customer.honeywell.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>