Carrier Edger Thermidistat Control Installation Guide
- June 7, 2024
- Carrier
Table of Contents
Edger Thermidistat Control
TP – PRH01 – B, TP – NRH01 – B PerformanceTM Series Edger ThermidistatTM
Control
Installation Instructions
A07049
Programmable Control
A07048
Non- Programmable Control
NOTE: Read the entire instruction manual before starting the installation.
US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1,
US6956463 B2.
TABLE OF CONTENTS
PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 2 INSTALLATION CONSIDERATIONS . . . . . . . .
. . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 SYSTEM START- UP
AND CHECKOUT . . . . . . . . . . . . . . . . . . . . . . 45 OPERATIONAL
INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 60 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 64 THERMIDISTAT CONTROL CONFIGURATION RECORD . . .
. . . . 84
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local
electrical codes during installation. All wiring must conform to local and
national electrical codes. Improper wiring or installation may damage
Thermidistat Control.
Recognize safety information. This is the safety- alert symbol . When you see
this symbol on the equipment and in the instruction manual, be alert to the
potential for personal injury. Understand the signal words DANGER, WARNING,
and CAUTION. These words are used with the safety- alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies a hazard which could result in personal
injury or death. CAUTION is used to identify unsafe practices which may result
in minor personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation, reliability,
or operation.
1
INTRODUCTION
Carrier’s 7- day, 5/2- day, 1- day programmable and non- programmable
Performance Series Thermidistat Control is a wall- mounted, low- voltage
control which combines temperature and humidity control in either a single
unit or a two- piece unit. In two- piece configuration, the relays are located
near the equipment and a two- wire connection is used between the Display
Module and the Equipment Control Module. Single- piece installation requires
more wiring and results in a higher profile. The Edger Thermidistat has no
need for batteries to store user- configured settings in memory. During power
loss its internal memory saves settings for unlimited time, and the clock
continues to run for at least 24 hours. An extension of Carrier’s proven line
of thermostats; it provides separate setpoints for heating and cooling in
addition to humidification and dehumidification. In the Edge Thermidistat
Control programmable configuration, different heating and cooling setpoints
and times are programmable for 4 periods per day or 2 periods per day.
Programming can be done for 7 days per week, 5/2 days per week, or 1 day. The
programmable Thermidistat Control can also be user configured as a non-
programmable Thermidistat Control. When operating as non- programmable, the
Edge Thermidistat Control will still have both temperature and humidity
control. The non- programmable Thermidistat Control features Touch ‘N’ Got
settings for quick and easy temperature change without complicated programming
schedules. The non- programmable Edge Thermidistat Control will still have
both temperature and humidity control. And, its Touch ‘N’ Go technology
enables the user to switch between three different user- configurable settings
through intuitive buttons located just below the display.
2
INSTALLATION CONSIDERATIONS
Power
This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C
terminals) of the low- voltage transformer to be connected to it for proper
operation. It will not operate without these 2 connections. Rh and Rc are
connected via PCB breakout jumper. See Fig. 1. For applications using two
24VAC transformers, one in the indoor unit and one in the outdoor unit,
connect the common from each to the C terminal. Connect R from the indoor unit
to the Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then,
break jumper on the circuit board. The W and HUM signals are taken from the Rh
power and the G signal is taken from the Rc power. If Thermidistat Control has
been installed in a two- transformer application that is later changed to a
single- transformer installation, installer must install a field supplied
jumper between Rc and Rh. Depending on the installation, up to 14 wires may be
required. Installation as two- piece unit is recommended. Only 2 wires are
required for connection between Display Module and Equipment Control Module.
These two wires (V+ and Vg) do not provide ordinary 24VAC. They carry a
combination of power and communications data that is unique to these products.
3
Fig. 1 – PCB Breakout Jumper
A07052
Models
There are programmable and non- programmable models for all applications. They
can be configured for AC or HP, 1- or 2- speed compressor, and for Hybrid
Heatt installations, allowing it to be used in place of all Carrier
thermostats. Programmable Thermidistat Controls may be configured as non-
programmable if user desires.
Humidify Equipment and Connections
The humidify output connects directly to 24VAC operated humidifiers. An isolation relay may be required when using powered humidifiers. No other connection or interlock is required. Any of several installer- selectable operating modes are available.
4
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
DO NOT connect furnace HUM terminal directly to Thermidistat Control HUM
terminal. This will bypass furnace safety controls. See Low Voltage Wiring
Diagrams and notes for proper connection.
Dehumidify Equipment and Connections
The dry contact output connects to the dehumidify input on variable- speed
furnaces and fan coils. Additional dehumidification is done by controlling the
compressor. A variety of operating modes are available. The dry contact must
be configured for dehumidification in setup Option 19. See Wiring Diagrams for
more information.
Outdoor Temperature Sensor (TSTATCCSEN01- B)
Outdoor air temperature sensor is included in the box with the Thermidistat
Control. Optimum performance is obtained when an outdoor temperature sensor is
used with the Thermidistat Control. Plan installation so that 2 wires can be
run from Equipment Control Module to an outdoor location, preferably on the
north side of the house or refer to Installation Instructions included with
the outdoor temperature sensor for simplified connection. Sensor can be
mounted to outdoor unit and existing control wires may be used for its
connection. Details are provided in sensor instructions.
5
Remote Indoor Temperature Sensor
A remote temperature sensor may be used with the programmable model, where it
is desirable to install the Thermidistat Control in a limited access location
while measuring the temperature in the living space. The remote room sensor
may be used as a stand alone or average with local sensor.
Two- Piece Thermidistat Control Configuration
The Performance Series Thermidistat Control can be installed in one of two
configurations. The control may be installed as a single- piece Thermidistat
Control or it may be split into two pieces and mounted in separate locations.
As a single- piece unit, all required wiring must be brought to the Equipment
Control Module for connection to the terminal strip. In two- piece
configuration, the Display Module can be mounted in the living space while the
Equipment Control Module may be mounted near the indoor furnace or fan coil.
Connection from the Display Module to the Equipment Control Module requires
only two wires. All other control wires are connected to the Equipment Control
Module from the HVAC equipment. This configuration results in a slimmer
display and locates the Equipment Control Module containing the switching
relays away from the main living space where relay clicking will not be heard.
The model numbers on the Display Module and the Equipment Control Module (ECM)
must match or unpredictable results may occur. Two- wire pigtail replacement
part number is TX- 2WR05.
Wiring
For all wiring applications, use 22 AWG or larger wire. Continuous wire
lengths over 100 ft. (30.5 m) should use 20 AWG or larger. Wire lengths are
not to exceed 250 ft. (76 m) per run.
6
INSTALLATION
! CAUTION
UNIT DAMAGE HAZARD Failure to follow the recommended wiring practices could
result in damage to the wall control and personal property. Improper wiring or
installation may damage Thermidistat Control. Check to make sure wiring is
correct before proceeding with installation or turning on power.
Installation Notes: S No part of the control should be installed directly
outdoors or in a cabinet outdoors. S Never remove the thermostat board from
the plastic housing. Doing so could warp and damage the components on the
board. S The control assembly should be mounted before wires are attached. S
During thermostat installation, provide sufficient excess wiring behind the
mounting plate. Coil the wiring, creating a service loop, and place in
mounting box or behind the wall to remove strain against the terminal strip.
See Fig. 2.
7
Fig. 2 – Coil Excess Wiring
A13295
Fig. 3 – TP- PRH01- B Carton Contents 8
A07685
Carton contains the following components. See Fig. 3 for TP- PRH01- B or Fig.
4 for TP- NRH01- B:
1. Display Module 2. Stand- off for Equipment Control Module 3. Outside Air
Temperature Sensor, screws and pigtail 4. Equipment Control Module
Fig. 4 – TP- NRH01- B Carton Contents 1. Display Module 2. Stand- off for
Equipment Control Module 3. Outside Air Temperature Sensor, screws and pigtail
4. Equipment Control Module
Thermidistat Control Location
Thermidistat Control should be mounted: S Approximately 5 ft (1.5m) from
floor.
9
A07686
S Close to or in a frequently used room, preferably on an inside partitioning
wall.
S On a section of wall without pipes or duct work.
Thermidistat Control should NOT be mounted:
S Close to a window, on an outside wall, or next to a door leading to the
outside.
S Exposed to direct light or heat from a lamp, sun, fireplace, or other
temperature- radiating objects which could cause a false reading.
S Close to or in direct airflow from supply registers and return- air
registers.
S In areas with poor air circulation, such as behind a door or in an alcove.
Installer should determine whether control will be installed as single- piece
or two- piece. In single- piece configuration, as many as 14 wires may need to
run to wall mounting location for connection to the control. In two- piece
configuration, the Display Module and Equipment Control Module are connected
by two wires.
Install Thermidistat Control
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing Thermidistat Control, turn off all power to equipment. There
may be more than 1 power disconnect.
10
! CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Improper wiring or installation may damage
Thermidistat Control. Check to make sure wiring is correct before proceeding
with installation or turning on power.
1. Turn off all power to equipment. 2. If an existing Thermidistat Control or
thermostat is being replaced:
a. Remove existing control from wall. b. Disconnect wires from existing
thermostat, 1 at a time. c. As each wire is disconnected, record wire color
and terminal marking. d. New or additional wires may be needed to accommodate
added humid-
ity outputs. e. Discard or recycle old control.
11
! CAUTION
ENVIRONMENTAL HAZARD Failure to follow this caution may result in
environmental damage. Mercury is a hazardous waste. Federal regulations
require that Mercury be disposed of properly.
Two- Piece Installation
The following steps should be followed for the installation of the two- piece
configuration. NOTE: The 2- wire pigtail is not intended to support the weight
of the Display Module. Do not hang the Display Module from the Equipment
Control Module screw terminals.
1. Remove mounting plate from back of Display Module by pressing the two tabs
on the bottom edge and pulling away. See Fig. 5 and 6.
12
Fig. 5 – Press Tabs to Remove Backplate
A07225
Fig. 6 – Take Apart 13
A07226
2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only–Display Module need not be leveled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. See Fig. 7.
Fig. 7 – Backplate Mounting
A07165
3. Drill four 3/16- in. mounting holes in wall where marked. Thermidistat Control may be mounted to a standard junction box, if desired. Hole pattern on Thermidistat Control mounting base matches junction box mounting holes.
4. Secure rear plastic mounting base to wall with 4 screws and anchors provided. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. Make sure all wires extend through hole in mounting base.
5. Adjust length and routing of each wire to reach proper connector block and terminal on mounting base with 1/4- in. (6 mm) extra wire.
14
6. Match and connect equipment wires to proper terminals of each connector block, being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base. If wires are connected incorrectly, the Display Module will not operate. See Fig. 8, 9 and 10.
Fig. 8 – Control Module Wiring Guide S Red is V+ S Black is Vg
15
A08072
Fig. 9 – Secure Wires to Terminal Strip
A07166
Fig. 10 – Connect Pigtail Wires to Display Module
A07167
16
NOTE: The 2- wire pigtail is not intended to support the weight of the Display
Module. Do not hang the Display Module from the Equipment Control Module screw
terminals.
S Red of the pigtail is V+
S Black of the pigtail is Vg
7. Push any excess wire into wall and against mounting base. Seal hole in
wall to prevent air leaks. Leaks can affect operation and cause incorrect
temperature and/or humidity measurement.
8. Make sure to attach 2- wire pigtail to Display Module mounting base. It is
packed loose in the box from the factory. Then attach 2- wire pigtail to the
back of the Display Module via 2 pin, keyed connector.
9. Reattach Display Module body to mounting base by first setting on at top
of mounting base and then push bottom corners of Display Module to snap into
place. See Fig. 11.
Fig. 11 – Attach Display to Backplate 17
A07168
10. Find suitable indoor mounting location for Equipment Control Module,
either near or on equipment. See Fig. 12.
IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or
below any other controls or equipment (i.e. humidistat, humidifier, etc.).
Fig. 12 – Equipment Control Module on Equipment
A07217
11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 13.
18
Fig. 13 – Standoff
A07227
NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall.
12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base. If wires are connected incorrectly, the Display Module will not operate. See Fig. 8, 9 and 10.
13. Snap cover over top of Equipment Control Module. See Fig. 14.
19
Fig. 14 – Cover on Equipment Control Module
A07218
14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2- digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33.
a. AC — 1- stage air conditioner with furnace or fan coil
b. HP — 1- stage heat pump with fan coil
c. A2 — 2- stage air conditioner with furnace or fan coil
d. H2 — 2- stage heat pump with fan coil
e. hh — Hybrid Heat system with 1- stage heat pump
f. h2 — Hybrid Heat system with 2- stage heat pump
g. H — heating only system
h. C — cooling only system
20
Single- Piece Installation
The following steps should be followed for the installation of the single-
piece configuration.
1. Remove cover from Equipment Control Module by pressing the two tabs on the
bottom edge and pulling away. Route wires through large hole in Equipment
Control Module. Level Equipment Control Module against wall (for aesthetic
value only – Equipment Control Module need not be leveled for proper
operation) and mark wall through 4 mounting holes.
2. Drill two 3/16- in. mounting holes in wall where marked. Thermidistat
Control may be mounted to a standard junction box if desired. Hole pattern on
Equipment Control Module matches junction box mounting holes.
3. Secure rear plastic Equipment Control Module to wall with 4 screws and
anchors provided. To avoid unintended bending of wall plate plastic, use all 4
screws and anchors. Make sure all wires extend through hole in Equipment
Control Module.
4. Adjust length and routing of each wire to reach proper connector block and
terminal on Equipment Control Module with 1/4- in. (6 mm) extra length. See
Fig. 15.
21
Fig. 15 – Equipment Control Module
A07219
5. Match and connect equipment wires to proper terminals of each connector block.
6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
7. Attach 2- wire pigtail to Equipment Control Module terminal block (terminals V+ and Vg). Attach 2- wire pigtail to the back of the Display Module via 2 pin, keyed connector.
8. Reattach Display Module body to Equipment Control Module by first setting on at top and then push bottom corners to snap into place. See Fig. 16.
22
Fig. 16 – Reattach Display Module
A07220
9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2- digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33.
a. AC — 1- stage air conditioner with furnace or fan coil
b. HP — 1- stage heat pump with fan coil
c. A2 — 2- stage air conditioner with furnace or fan coil
d. H2 — 2- stage heat pump with fan coil
e. hh — Hybrid Heat system with 1- stage heat pump
f. h2 — Hybrid Heat system with 2- stage heat pump
g. H — heating only system
h. C — cooling only system
23
Set Thermidistat Control Configuration
Configuration options enable the installer to configure the Thermidistat
Control for a particular installation. Most are not presented to the homeowner
and therefore must be properly set by the installer. (Only those marked with
an asterisk below are available to the homeowner.) The homeowner
configurations are described in the owner’s manual. A special procedure allows
entry into the configuration mode. Selections can be made while in
configuration mode. Description of each selection and how to use the
configuration mode follows. CONFIGURATION OPTIONS – SUMMARY Option 01 —
Equipment Type Option 02 — Clean Filter Timer Adjustment Option 03 —
Fahrenheit/Centigrade Selection Option 04 — Fan (G) on with W/W1 Selection
Option 05 — Room Air Temperature Sensing (programmable
models only) Option 06 — Cooling Lockout Below 55_F/13_C Selection (only
available if outdoor air sensor is present) Option 07 — Zoning Option 08 —
Auxiliary Heat Lockout Temperature Setting (only
available when heat pump is used and when outdoor air temperature sensor is
present) Option 09 — Heat Pump Lockout Temperature Balance Point (only
available when outdoor air temperature sensor is present) Option 10 —
Reversing Valve
24
Option 11 — Adjustable Setpoint Deadband (not available on heat only and cool
only systems)
Option 12 — Smart Recovery (programmable models only) Option 13 — Room
Temperature Offset Adjustment Option 14 — Humidity Offset Adjustment Option 15
— Enable Auto Mode Option 16 — Cycles Per Hour Option 17 — Time Between Stages
Option 18 — Backlight Configuration Option 19 — Dry Contact Option 20 —
Outdoor Air Temperature Offset Adjustment Option 21 — Keypad Lockout Option
22 — High Cool Latch Temperature Option 23 — High Heat Latch Temperature
Option 24 — Programmable/Non- Programmable
(programmable models only) Option 25 — Number of Programmable Periods per Day
(programmable models only) Option 26 — Minimum Cooling Setpoint Option 27 —
Maximum heating Setpoint Option 28 — UV Light Reminder Option 29 — Humidifier
Pad Reminder Option 30* — Programmable Fan (programmable models only)
25
Option 31* — Daylight Savings Time Configuration (programmable models only)
Option 32 — Furnace Heat Staging
Option 33 — Single or Two- Piece Installation
Option 34 — Hybrid Heat Furnace Latch Option 40 — Fan Humidify
Option 41 — Variable Speed Blower Option 42 — Variable Speed Super
Dehumidification
Option 43 — Intelligent Heat Staging Option 44 — Super Comfort Heat
Option 99 — Reset to Factory Defaults
TO ENTER CONFIGURATION MODE Press and hold FAN button for approximately 10
sec. The Display Module is now in configuration mode. It will automatically
exit this mode if no button is pressed for 3 minutes. Pressing the DONE button
will exit configuration mode immediately.
WHILE IN CONFIGURATION MODE
The option number is displayed in the heat setpoint location and the
configuration setting is displayed in the cool setpoint location. On the TP-
PRH01- B (programmable) model, a box will surround the option number. The mode
button is used to move the box between the two displayed values. The soft keys
below the listed values may also be used to move the box between selected
values. The value inside the box is changed by using the UP/DOWN buttons. On
the TP- NRH01- B (non- programmable) model, one of the values will be
flashing. The mode button is used to change which value is flashing or the
Home and Sleep buttons may also be used to select which value to flash. The
value that is flashing is changed by using the UP/DOWN buttons. All changes
made are saved at the time of selection and will be saved in the event of the
3 minute time- out or when installer exits from configuration menu.
26
Configuration Options –Selection
Option 01 — Equipment Type Range: H2, A2, HP, AC, hh, h2, H, C H2 — operates a
two- speed heat pump with a fan coil HP — operates a single- speed heat pump
with a fan coil A2 — operates a two- speed AC with a fan coil or furnace AC —
operates a single- speed AC with a fan coil or furnace hh — operates a single-
speed heat pump with a furnace h2 — operates a two- speed heat pump with a
furnace H — operates a heat- only system. Furnace or fan coil only;
no outdoor unit. C — operates a cool only- system. Outdoor AC unit with an
indoor fan coil with no strip heaters. Default is H2. Option 02 — Clean Filter
Timer Select hours of blower operation (heating, cooling, or fan) before CHECK
FILTER icon is displayed. With OF selected, icon will never come on, disabling
this feature. Time selection can range from 800 to 7200 hr by selecting
numbers 1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr).
Recommended selections are disposable filter- 800 to 2400 hr, media filter-
2400 to 3200 hr, or electronic air cleaner- 1600 to 2400 hr of blower
operation. For higher efficiency filter, please consult filter’s Installation
Instruction for details.
27
Option 03 — Fahrenheit/Centigrade
Select between Fahrenheit (F) and Centigrade (C) operation. Factory default is
Fahrenheit (F). Option 04 — Fan (G) On With W/W1
This selection determines whether fan (G) output is to be On or OFF when any
W/W1 (furnace or strip heat) output is On. Most furnaces and fan coils manage
their own blowers and do not require separate G signal. For these
applications, select OFF. Some auxiliary heaters require separate G signal to
turn on blower. In this case, select On. Select On for geothermal
applications.
Default is OF (off). Option 05 — Room Air Temperature Sensing (programmable
models only)
The remote room sensor may be installed as a single sensor or multiple sensors
may be installed for further averaging functionality. See Fig. 17.
RRS
SRTN
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Fig. 17 – Remote Room Sensor – Parallel Wiring
28
A09130
This selection determines which sensor the control will use for measuring room
air temperature. Room air temperature can be sensed in one of three ways; the
local sensor (L) located on the Display Module, the remote room air sensor
(r), or the average of local and remote sensors (Lr). Settings are L, r, Lr.
Default is L. Option 06 — Cooling Lockout Below 55_F/13_C
This selection disables cooling when outdoor temperature is below 55_F/13_C.
It requires an outdoor temperature sensor. Setting is not available if valid
outdoor sensor is not connected. Set to OF (off) to allow cooling below
55_F/13_C. Set to On to prevent cooling below 55_F/13_C.
Factory default is OF (off). Option 07 — Zoning
This selection should be set to On when the Thermidistat Control is to be used
as part of a zoning system. It is assumed that the zoning equipment will take
care of time guard and cycle timers. The minimum On time is still controlled
by the Thermidistat Control.
Default is OF (off). Option 08 — Auxiliary Heat Lockout Temperature
This selection is available on heat pump systems with a valid outdoor
temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25,
30, 35, 40, 45, 50, 55.
OF (off) – function is disabled. Auxiliary heat is allowed to operate whenever
sufficient demand for heat is available.
5 to 55_F (- 15 to 13_C) – Outdoor temperature above which the auxiliary heat
is not allowed to operate (unless MODE is set to Emergency Heat). If room
temperature falls below 45_F (7_C), the auxiliary heat will be allowed to turn
on and will continue to run until demand is satisfied. Default is OF (off).
29
Option 09 — Heat Pump Lockout Temperature Balance Point (only available when
heat pump is used and when outdoor air temperature sensor is present) This
selection is only available on Hybrid Heat systems. A Hybrid Heat system is
selected via the Option 1 Equipment Type configuration. Configurations
settings are: OF (off), 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55. OF (off) —
the heating cycle will always start with heat pump heating. 5 to 55_F (- 15 to
13_C) — the outdoor temperature below which heat pump operation is not
allowed. When emergency heat mode is selected, only auxiliary heat will
operate. Default is OF (off). Option 10 — Reversing Valve This selection is
only available on heat pump systems. “O” terminal can be configured to be
energized in either heating mode or in cooling mode, depending on heat pump
operation. “O” is used to describe a heat pump system that energizes its
reversing valve in cooling. “B” is used to describe a heat pump system that
energized its reversing valve in heating. H — Reversing valve output (O/W2/B)
is energized when HEAT mode is selected. C — Reversing valve output (O/W2/B)
is energized when COOL mode is selected. Default is C.
30
Option 11 — Deadband Setting Between Heat & Cool This option is not available
on Heat Only and Cool Only systems. The selection allows the installer to
choose how much differential exists between the heating and cooling setpoints.
Allowable selections are 1 thru 6. Default is 2. Option 12 — Smart Recovery
Smart Recovery OF (off) means setpoints change precisely at setback recovery
time. Thirty, 60, or 90 selects the number of minutes recovery starts before
programmed recovery time. Recovery takes place smoothly during the selected
recovery time, ending at the recovery time and temperature which is
programmed. Not available with non- programmable Thermidistat Controls or when
Thermidistat Control is configured as non- programmable. Default is 90. Option
13 — Room Air Temperature Offset Adjust The number of degrees to be added to
the displayed temperature to calibrate or deliberately miscalibrate the
measured room temperature ( – 5 to +5_). Default is 0. Option 14 — Humidity
Display Offset Adjust The percentage to be added to the displayed humidity to
calibrate or deliberately miscalibrate the measured room humidity (- 9% to +9%
RH). Default is 0. Option 15 — Enable Auto Mode This selection is not
available if the Thermidistat Control is configured as Heat Only or Cool Only
in Option 1. This allows the homeowner to select auto changeover mode in
addition to heat and cool. This allows the Thermidistat Control
31
to automatically change between heating mode and cooling mode when sufficient
demand for heating or cooling exists. On — Auto mode is available. OF — Auto
mode is not available. Default is On. Option 16 — Maximum Cycles Per Hour This
selection limits the number of cycles per hour that the Thermidistat Control
allows the system to operate. Selections are 2, 4, 6. 2 — The heating and
cooling outputs will be energized no more than 2 times per hour. When an
output is energized, it will not be energized again for 30 minutes. 4 — The
heating and cooling outputs will be energized no more than 4 times per hour.
When an output is energized, it will not be energized again for 15 minutes. 6
— The heating and cooling outputs will be energized no more than 6 times per
hour. When an output is energized, it will not be energized again for 10
minutes. Default is 4. Option 17 — Time Between Equipment Stages This
selection is only available for heat pump systems. This determines the minimum
number of minutes of equipment operation on the highest compressor stage
before allowing the transition to auxiliary heat. Available selections are 10,
15, 20, and 25. The time between stages of any individual piece of equipment,
such as low speed and high speed compressor or fan coil stages, will be fixed
at 10 minutes. Default is 15.
32
Option 18 — Backlight Configuration
When OF (off), the backlight will be lit for 10 seconds after a button is
pressed. After 10 seconds of no button presses, the backlight turns off. When
On, the backlight will normally be on and dim in appearance. The backlight
brightness becomes brighter when a button is pressed. After 10 seconds of no
button presses, the backlight will return to the dimmer level until another
button press occurs. The range of brightness is 1 through 5 with 5 being full
brightness.
Default is 3.
Option 19 — Dry Contact Configuration (programmable models only)
There are 3 available selections, OF, 1 and 2.
OF — The dry contact is always de- energized.
1 — The dry contact will be energized for the specified number of minutes per
hour. This selection is programmable by period. When this selection is changed
from OF to 1, the period icons are shown and the minute segments of the clock
display are shown. The triangle icon next to the WAKE period will be on and a
value between 0 and 60 will be shown in the minutes display. See Operational
Information and Wiring Diagrams for further explanation of dry contact
configuration and use. To change the period or minutes, press the soft key
below the period or minutes and then use the UP/DOWN buttons to change to the
desired value.
2 — The dry contact will operate as a DH relay. This relay is reverse logic.
When the humidity level is above the dehumidify setpoint, the dry contact D1-
D2 will be opened. When the humidity level is below the dehumidify setpoint,
D1- D2 will be closed. There is a +/- 2% hysteresis around the dehumidify
setpoint to prevent rapid on/off cycling of the DH output. When configured for
dehumidification, the Rc terminal must be connected to one of the dry contact
terminals. This provides power to energize the dehumidify terminal on the
cooling equipment when the dry contact is closed. See Wiring Diagrams for more
information.
Default is OF (off).
33
Option 19 — Dry Contact Configuration (non- programmable models only) OF — The
dry contact is always de- energized. ON — The dry contact will operate as a DH
relay. This relay is reverse logic. When the humidity level is above the
dehumidify setpoint, the dry contact D1- D2 will be opened. When the humidity
level is below the dehumidify setpoint, D1- D2 will be closed. There is a +/-
2% hysteresis around the dehumidify setpoint to prevent rapid on/off cycling
of the DH output. When configured for dehumidification, the Rc terminal must
be connected to one of the dry contact terminals. This provides power to
energize the dehumidify terminal on the cooling equipment when the dry contact
is closed. See Wiring Diagrams for more information. Default is OF (off).
Option 20 — Outdoor Air Temperature Offset Adjustment This selection allows
the calibration, or deliberate miscalibration of the outdoor air temperature
sensor reading. The selection ranges from – 5 to +5_. Default is 0. Option 21
— Keypad Lockout (programmable models only) This selection allows the
installer to limit access to the keypad. Selections are OF (off), 1, 2, 3.
These options are independent of Option 24, which allows the programmable
model to be configured as a non- programmable thermostat. OF (off) — The user
has full access to the keypad. 1 — The user has access to change the
setpoints, time of day and calendar.
34
2 — The user has access to change the setpoints only. 3 — The entire keypad is
locked. When a button is pressed, the backlight will turn on but none of the
operating parameters will be changed. When the keypad lock selection is turned
on, the padlock icon will be displayed. To unlock the keypad, press and hold
the UP/DOWN buttons simultaneously for five seconds. When the keypad is
unlocked, the padlock icon will turn off. The keypad will remain unlocked for
two minutes after the last button press. After two minutes with no button
presses, the keypad will lock again. The keypad will not lock in the software
configuration mode or in the installer test mode. Default is OF (off). Option
21 — Keypad Lockout (non- programmable models only) This selection allows the
installer to limit access to the keypad. Selections are OF (off), 1, 2. OF
(off) — The user has full access to the keypad. 1 — The user has access to
modify Home, Sleep, Away, and UP/DOWN setpoints. 2 — The entire keypad is
locked. When a button is pressed, the backlight will turn on but none of the
operating parameters will be changed. When the keypad lock selection is turned
on, the padlock icon will be displayed. To unlock the keypad, press and hold
the UP/DOWN buttons simultaneously for five seconds. When the keypad is
unlocked, the padlock icon will turn off. The keypad will remain unlocked for
two minutes after the last button press. After two minutes with no button
presses, the keypad will lock again. The keypad will not lock in the software
configuration mode or in the installer test mode. Default is OF (off).
35
Option 22 — High Cool Latch Temperature (only available if outdoor sensor is
present) An outdoor sensor is required for high cool latch feature. This
selection is only available when Option 1 is set to H2, A2, or h2 and when
Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 80,
85, 90, 95, 100, 105, 110, On. OF (off) — Cooling always starts in low stage
(Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and
staging timer constraints have been satisfied. 80 to 110_F (27 to 43_C) —
Outdoor temperature above which both first and second stages of the compressor
are energized to satisfy all cooling demands. When a cycle starts under a high
cool latch, it will finish the cooling cycle on high stage. If the cooling
equipment is energized to satisfy a dehumidify demand only (no cooling
demand), the latch will not be applied. On — The Y1 and Y/Y2 outputs are
simultaneously energized to satisfy all cooling demands. Default is OF (off).
Option 23 — High Heat Latch Temperature (only available if outdoor sensor is
present) This selection is only available when Option 1 is set to H2, or h2
and Option 7 (zoning) is set to OF (off). Configuration settings are OF (off),
20, 25, 30, 35, 40, 45, 50, On. OF (off) –Heating always starts in low stage
(Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and
staging timer constraints have been satisfied.
36
20 to 50_F (- 7 to 10_C) — Outdoor temperature below which both first and
second stages of the compressor are energized to satisfy all heating demands.
When a cycle starts under a high heat latch, it will finish the heating cycle
on high stage. On — The Y1 and Y/Y2 outputs are simultaneously energized to
satisfy all heating demands. Default is OF (off). Option 24 —
Programmable/Non- Programmable (programmable models only) This selection
allows the installer to configure the Thermidistat Control as either
programmable or non- programmable. Selections are P, nP. Default is P. Option
25 — Number of Programmable Periods (programmable models only) This selection
allows the installer to configure the Thermidistat Control for two or four
periods per day. Two periods is a common commercial application and four
periods is more common for residential. This selection is not available if
Option 24 has been set to nP to configure the Thermidistat Control for non-
programmable operation. 2 — Periods DAY and SLEEP are available 4 — Periods
WAKE, DAY, EVE, and SLEEP are available. Default is 4. Option 26 — Minimum
Cooling Setpoint This selection allows the installer to configure the minimum
cooling setpoint that the user is allowed to set. The range is based on the
value of the adjustable deadband Option 11, such that the minimum of the range
is 50_F/10_C plus the adjustable deadband and the maximum is 90_F/32_C.
37
Default is 52_F/11_C (based on the adjustable deadband default = 2). Option 27
— Maximum Heating Setpoint This selection allows the installer to configure
the maximum heating setpoint. The range is based on the adjustable deadband
value Option 11, such that the minimum of the range is 50_F/10_C and the
maximum is 90_F/32_C minus the deadband. Default is 88_F/31_C (based on the
adjustable deadband default = 2). Option 28 — UV Light Reminder This selection
allows the installer to select the number of months after which the UV Light
icon will be displayed to indicate to the homeowner that it is time to call
the dealer to have the UV Lights replaced. Selections available are OF (off),
6, 12, 18, 24, 30, 36, 42, 48. OF (off) — The UV Light reminder is turned off
and will never be displayed. 6- 48 — The number of months after which the UV
Light reminder will be displayed, “CHECK UV LIGHT”. Default is OF (off).
Option 29 — Humidifier Pad Reminder This selects the number of months after
which the Humidifier Pad Reminder icon will be displayed. This is not based on
run time. OF (off) — The Humidifier Pad Reminder is disabled and will never be
displayed. 1- 24 — The number of months after which the Humidifier Pad
Reminder icon will be displayed, “CHECK HUM PAD”. Default is OF (off).
38
Option 30 — Programmable Fan (programmable models only)
This selection allows the homeowner to program the fan selection to “Auto” or
“On” fan operation for each of the program schedule periods. This selection is
only available on programmable Thermidistat Controls. OF (off) — Programmable
fan is disabled and the homeowner must manually select “Auto” or “On” for fan
operation.
On — Programmable fan is enabled. The homeowner can program “Auto” or “On” fan
operation along with the heat and cool setpoints for each programmed period.
When the program schedule is running, the programmed heat setpoint, cool
setpoint, and fan selection for that period will be used. If the homeowner
“overrides” the programmed fan setting by pressing the fan button, the
override selection will remain in effect until the next programmed period
time. Default is OF (off).
Option 31 — Daylight Savings Time Configuration (programmable models only)
This selection allows the installer to set the Thermidistat Control to
automatically change by one hour on the specified day, month, and week
specified.
OF (off) — Daylight Savings Time Function disabled.
1,2 On — The first time the UP/DOWN button is pressed, the value of this
selection changes from OF (off) to 1. When 1 is displayed, the days of the
week and clock digits will be turned on. The installer will set the start date
(Spring) for Daylight Savings Time by setting the day of the week by selecting
the appropriate triangle icon next to the days of the week, the month of the
year will be set in the clock hours location (range 1- 12) and the week of the
month will be set in the clock minutes location. The week of the month
selections will be F, 2, 3, 4, and L for First, 2nd, 3rd, 4th, and Last. So
for the first Sunday in April, the display would show SUN, 4, F. When 2 is
displayed, the installer will then choose the end date for daylight savings
time (Fall). To activate the function, the installer changes the “2”
39
by pressing the up button and “On” is displayed. The setting shall be left
“On” to enable the Daylight Savings Time function. Default is On (on). Option
32 — Furnace Heat Staging Control (available only when the Thermidistat
Control is configured to operate AC or A2 equipment). 1 — Thermidistat Control
controls W1 output only and furnace controls the turn on and turn off of
higher stages of heat. 2 — Thermidistat Control will control the W1 and O/W2/B
outputs. Default is 1. Option 33 — Single or Two- Piece Installation This
configuration allows the Thermidistat Control to compensate for the amount of
heat generated by the Thermidistat Control electronics to allow more accurate
sensing of the temperature sensor. The amount of heat compensation will be
different between single installation and two- piece installation. Range: 1P
or 2P 1P — The installation is single piece. 2P — The installation is two
separate pieces. Default is 2P.
40
Option 34 – Hybrid Heat Furnace Latch This selection allows a Hybrid Heat
system to finish a heating cycle using the furnace. On – Once the furnace is
on, it will finish the heating cycle with the furnace. If a heat pump defrost
occurs, the heating cycle will finish with the furnace. OF – The system will
stage from furnace back to heat pump if heating demand dictates, or 2 minutes
after a defrost has ended. Default is On. Option 40 — Humidify Fan This
selection controls whether humidification can only be done when a heating
demand is present. If the homeowner turns humidification OFF, this
configuration operates as if the selection was set to OFF. OF – The humidity
output will only energize when there is a humidity demand and the heating
equipment is energized. On – The humidity output and the fan will energize
anytime humidification is needed during heating mode regardless of the state
of the heating equipment. Factory default is OF (Off) Option 41 — Variable
Speed Blower This selection allows the installer to select between a single
speed or variable motor. In a system with a two speed compressor (A2, h2, H2),
if a dehumidification demand exists and the compressor is energized for cool
to dehumidify, cooling, or both, and the system has a PSC blower (Option 41 =
OFF), then both Y/Y2 and Y1/W2 are energized.
41
Off – The system has a single speed (PSC) blower. On – The system has a
variable speed blower. Select Off for geothermal applications. Factory default
is OF (Off) Option 42 — Variable Speed Super Dehumidification This option will
only be available if the Variable Speed Blower setup (Option 41) has been set
to ON. OF – The fan output (G) is energized when the compressor is on for cool
to dehumidify functionality. On – The fan output (G) is de- energized when the
compressor is running for cool to dehumidify functionality. In this setup the
fan will run at very low speed because a Y/Y2 or Y1/W2 is present but the G
signal is not. The fan output (G) will be energized any time the compressor is
energized in response to a cooling demand. Factory default is OF (Off) Option
43 — Intelligent Heat Staging This function is only available if the equipment
configuration is a single speed heat pump (Option 01 = HP). Off – Electric
heat will not be staged. On – Three stages of electric heat will be staged.
This switch should be set to On if the HVAC equipment has two banks of strip
heaters. When electric heat is required, the thermostat will energize the
smallest bank first (W1 only), then the larger bank (turning the smaller bank
off – Y1/W2 only), and then both banks together (both W1 and Y1/W2). When
power is cycled to the thermostat, this unit configuration will be displayed
as HS. Factory defaults is OF (Off)
42
Option 44 — Super Comfort Heat This option is only available on heat pump
units HP (HP, H2, hh, and h2) when Option 41 (Variable Speed Blower) is set to
On and the system has a valid OAT sensor. OF (Off) – Comfort Heat is off On –
Comfort Heat feature is on. If the outdoor air temperature is between 12 to
40_F (- 11 to 4_C) and the compressor is running in heating, then the fan
output is turned off. This will signal the variable speed blower to reduce the
air speed. The fan output is turned off even if the user has the fan selection
set to continuous fan. The fan output will be turned back on in this
temperature range if the maximum capacity of auxiliary heat is on due to
system demand (auxiliary heat on in response to a defrost signal shouldn’t
cause the fan to turn back on). If the outdoor air temperature is below 12_F/-
11_C and there is sufficient demand for the equipment to be on, then the fan
output is turned back on and the W/W1 output is energized. In a two speed unit
the Y/Y2 output should be energized in addition to the W/W1 output. This logic
does not apply to a Hybrid Heat system. In the unlikely event that the
installer has selected a heat pump lockout temperature (Option 09) of 5_F/-
15_C in a Hybrid Heat system and the comfort heat feature is on, then the
comfort heat feature will turn the W/W1 on and the compressors off when the
outdoor air temperature drops below 12_F/- 11_C instead of at the lower
temperature of 5_F/- 15C. NOTE: All temperature boundaries have a +/- 2
hysteresis Factory default is OF (Off).
43
Option 99 — Reset to Factory Defaults Use this capability to reset the
Thermidistat Control to “out of the box” conditions. BEWARE! All configuration
settings, program settings, clock, and calendar which have been manually
entered will be lost! When this option is selected, the configuration number
(99), will appear on the left and 10 will appear on the right. To perform the
reset, first use the MODE key to move the box from the 99 to the 10
(programmable model) or to flash the 10 (non- programmable model). Then press
and hold the DOWN key. The 10 will start counting down toward zero. If the
DOWN key is kept pressed until the count reaches zero, the reset will be
performed. When the value reaches zero, the heat setpoint shall display – – .
The cool setpoint shall display – and the room air temperature shall display
Fd. When the factory defaults have been restored, the Thermidistat Control
will act as if power was cycled and return to normal operation. If the DOWN
key is released early, the number will return to 10 and the reset will not
occur.
44
SYSTEM START- UP AND CHECKOUT
The Thermidistat Control is designed with a built- in installer test
capability. It allows easy operation of equipment without delays or setpoint
adjustments to force heating or cooling. To enable installer test mode, press
and hold the fan button for 15 seconds. After 10 seconds, the Thermidistat
Control will enter Configuration Mode. Continuing to hold the Fan button
through 15 seconds will cause the Thermidistat Control to enter Installer Test
Mode. Pressing the Mode button will change the system operating mode to test
the heating and cooling equipment. Auto Mode is not available during Installer
Test Mode. If no buttons are pressed for 15 minutes, the installer test mode
will be terminated. Pressing DONE at any time will exit installer test mode.
Heat – The first stage of heating will be energized for three minutes, then
the first and second stages (if a second stage exists) will turn on for an
additional three minutes. During the first stage of heating, the HEAT ON icons
will be displayed. During the second stage of heating (if one exists), the “2”
next to the “On” will be displayed if the system has a two- stage compressor
(A2, h2, or H2 unit types). The “auxiliary heat on” icon will be displayed if
the second stage is electric heat (HP unit type). While the heating test is
active, the humidify output can be toggled. On the programmable models,
pressing the button below the humidify icon shall toggle the state of the
humidify output. On the non- programmable models, pressing the features button
shall toggle the state of the humidify output.
Installer test for cooling is the same as described for heating above. COOL ON
will be displayed during cooling in Installer Test Mode. While the cooling
test is active, the dehumidify icon shall be displayed if the dry contact has
been configured as a DH output. On the programmable models, pressing the
button below the dehumidify icon shall toggle the state of the dry contact
output. On the non- programmable models, pressing the features button shall
toggle the state of the dry contact.
45
In a heat pump application, when the mode is set to “em heat” the auxiliary
heat will turn on for 3 minutes. The clock display will count down from 180 to
0 during this test.
TO TEST FAN
Fan button switches FAN icon between AUTO and On. While On is displayed, G
output will be energized, turning fan on. On some fan coils, fan continues to
operate for 90 sec after G signal is removed.
Final Settings
Be sure to press DONE to exit installer setup mode. If the system is to be
left in operation after installation is complete, use MODE button to select
between HEAT, COOL, or AUTO to provide desired operation of heating, cooling,
or auto.
On the programmable models, the default setpoints and programmed schedule
conform to the Energy Starr requirements of the U.S. Department of Energy for
both heating and cooling. These provide energy saving temperature settings.
Refer to Table 1.
Table 1 Energy Star Default Schedule
SCHEDULE Wake 6:00 AM Day 8:00 AM Evening 5:00 PM Sleep 10:00 PM
HEAT
68_F/20_C 60_F/16_C 68_F/20_C 60_F/16_C
COOL
78_F/26_C 85_F/29_C 78_F/26_C 82_F/28_C
46
If the programmed schedule is to be used, make sure the triangle icon next to
the FOLLOW SCHEDULE icon is turned on. Pressing the Schedule button will cycle
the triangle icon through the FOLLOW SCHEDULE, HOLD and VACATION selections.
If fixed temperatures are desired, use SCHEDULE button to turn on arrow icon
next to HOLD. This will maintain setpoints, not allowing them to change with
programmed schedule. The FAN button may be used to select between AUTO (fan on
only with equipment) and On (fan on continuously) fan modes. For further
information on temperature selection and programming, refer to Homeowner’s
Guide.
Setting The Clock, Calendar, Daily Schedule, and Vacation Settings
(programmable models only)
To set the clock, press the SET button once. The Clock will be displayed at
the bottom center of the screen. Use the soft keys to move the box around the
digits to be set and the UP/DOWN buttons to change the setting. Concurrent
presses of the set button will cycle through the calendar, daily schedule, and
vacation settings. Calendar may be changed by using the soft keys to select
the Month, Day, or Year. The UP/DOWN buttons are used to change the Month,
Day, or Year setting when the box surrounds it. Day of the week (Mon- Sun) is
determined by calendar settings and is not directly adjustable. When changing
daily schedule settings, the soft keys are used to set the days, period times,
heating setpoints, and cooling setpoints. The UP/DOWN buttons are used to
change the setting with the box around it. ALL PROGRAM PERIODS (WAKE, DAY,
EVE, SLEEP) MUST OCCUR WITHIN THE SAME 24 HOUR PERIOD.
47
When changing Vacation settings, the soft keys are used to choose the
selection to be adjusted and the UP/DOWN buttons are used to change the
setting. Humidify setting may only be changed when heat mode is selected and
Dehumidify setting may only be changed when cool mode is selected.
Humidity Control Features
The various humidity control features of the Thermidistat Control are
explained below. They are grouped into 2 sections, humidification and
dehumidification. Instructions on how to select each feature are given at the
end of each section.
Humidification
The Thermidistat Control directly connects to a standard 24VAC humidifier to
control humidification in the home. A humidify setpoint between 10 and 44% in
2% increments relative humidity is selected by the homeowner, or all
humidification can be turned off. When humidity in home drops below setpoint,
humidifier will be turned on to raise humidity level. Humidification can only
occur while in heating mode. See Table 2 for reference.
Table 2 Humidification Selections
SELECTION
Normal Humidify Auto Humidify Humidify Off
FAN DISPLAY
Blank AUTO Blank
HUMIDIFY SETPOINT DISPLAY
10- 44 1
OF (Off)
1. Humidify In normal humidify, humidifier will be on if there is humidity demand and any heating equipment is on. This will include furnace, heat pump, or auxiliary heat.
48
2. Auto Humidify Thermidistat Control will automatically adjust the humidity
setpoint according to the outdoor temperature. As the outdoor temperature
decreases, the humidity setpoint also decreases. Settings ranging from 1 to 9,
1 being the lowest and 9 the highest, will be visible to the homeowner. See
Fig. 18 for outdoor temperature/indoor humidity relationship in auto humidify
mode. Outdoor Air Temperature Sensor must be connected.
3. Humidify Off The humidify function can be turned off completely. This does
not require changing existing setpoints.
To Select Humidification (programmable) Press the soft key below the humidify
icon to bring up humidity select screen. Humidify options are only available
when in Heating mode. When system is in AUTO mode, humidify options are
available if the last system operation was a call for heat. To Select
Humidification (non- programmable) Press the features button twice. The first
press displays the outdoor air temperature and the second press displays the
humidity value and humidify target. Pressing the mode button shall cycle
through the available humidification selections (Off, Humidify and Auto
Humidify). Additional Humidify Comments The humidifier is actually turned on
when humidity is 1% below setpoint and turned off when it reaches 1% above
setpoint. This built- in hysteresis prevents humidify output from toggling on
and off when humidity level is near setpoint.
49
Dehumidification
Dehumidification is done only during cooling. Depending on type of equipment
used, compressor speed, blower speed, setpoint adjustment, and equipment
cycling are modified to provide added dehumidification. A dehumidification
setpoint (separate from humidification setpoint) is available to the
homeowner. It can range from 46% to 66% relative humidity. When actual
humidity is higher than setpoint, a dehumidification demand exists. The
Thermidistat Control responds by activating the dry contact (when enabled in
Option 19). It may also control the compressor and blower, depending on
equipment type and dehumidify selection choice. The 3 available selections are
described below. A mandatory 5 minute blower off delay will be enforced if
there has been a call for dehumidification during a cooling call. The amount
of extra dehumidification available is very dependent on the type of equipment
in the home. Without a variable- speed blower, the system’s ability to adjust
dehumidification is very limited.
1. Normal Dehumidify Operation When normal dehumidify is selected, the
compressor will not turn on without a cooling demand. If dehumidify demand
exists while cooling, dry contact will also be active (24VAC removed). This
output commands variable- speed blowers to reduce their airflow, which
improves water removal from the cooled air.
2. Cool to Dehumidify The cool to dehumidify selection tells the system to
operate the compressor, within limits, when there is a dehumidify demand even
if there is no cooling demand. The limits are that the system may overcool up
to 3, but no more, while attempting to satisfy a dehumidify demand. Within
this 3 range, there is an additional balance between overcooling and humidity
satisfaction. When overcooling must occur, the dehumidify setpoint is adjusted
upward by 2% per degree of overcooling. For example, a cooling setpoint of
76_F/24_C and a dehumidify setpoint of 60% is equivalent to a cooling setpoint
of 75_F/24_C and a dehumidify setpoint of 62%. This dehumidify set-
50
point change is internal to the Thermidistat Control and is not shown on the display.
Fig. 18 – Auto Humidity
A06599
3. Dehumidify Off Dehumidification can be turned off completely. This can be done without changing existing setpoints.
51
To Select Dehumidification (programmable – between NORMAL, COOL TO, and OFF)
Press the soft key below the dehumidify icon button to bring up dehumidify
selections. Dehumidify options are only available when in Cooling mode. When
system is in AUTO mode, dehumidify options are available if the last system
operation was a call for cooling. To Select Dehumidification (non-
programmable – between NORMAL, COOL TO, and OFF) Press the features button
three times. The first press displays the outdoor air temperature, the second
press displays the humidify options and the third press will display the
current dehumidify selections. The mode button is used to cycle through the
dehumidify selections. Additional Dehumidify Comments Dehumidification can be
enhanced (with some efficiency loss) by turning blower off immediately at the
end of each cooling cycle (eliminating normal 90 sec blower off delay). Where
maximum humidity removal is desired, this should be done. Fan coils have the
capability of removing this off delay. On FK or FV Fan Coils, set delay tap to
0/0. On standard fan coils, a jumper can be cut to disable off delay. Refer to
fan coil Installation Instructions for details. If FAN is set for continuous
operation (fan On icon displayed), G output is turned off for 5 minutes at the
end of each cooling cycle as long as dehumidify demand exists. Like humidify,
dehumidify actions are initiated when humidity is 1% above setpoint and are
terminated when humidity drops to 1% below setpoint. This prevents unnecessary
toggling of dehumidify actions when humidity is near setpoint.
52
Dehumidify Output and Equipment Connections
When there is a dehumidify demand, dry contact is activated, meaning that a
24VAC signal is removed from the DHUM or DH output terminal. In other words,
dehumidify output logic is reversed – output is turned On when no dehumidify
demand exists and is turned OFF when demand exists. Carrier FK and FV series
variable- speed fan coils, all variable- speed furnaces, and select single and
multi- stage furnaces with the dehumidify connection have dehumidify inputs
which connect directly to Thermidistat Control dry contact. Refer to the
furnace literature for dehumidification options. The FK and FV series fan
coils have a terminal marked DH which should be connected to the Thermidistat
Control dry contact output. Jumper J1 on fan coil MUST be removed. It is
located behind the DH terminal. Additionally blower delay tap on fan coil
should be set to 0/0 (no On delay and no OFF delay) when using cool to
dehumidify. With this selection, the blower stops when G signal is removed,
preventing re- evaporation of water from the coil which would occur during the
normal 90 sec blower off delay. See fan coil installation instructions for
more information. The furnace dehumidify input acts differently depending on
which style of variable speed, select single- stage or multi- stage furnace
control you have.
Vacation (programmable models only)
A vacation selection is available specifically for times where the home will
not be occupied for an extended period. Vacation mode has an automatic hold,
meaning that setpoints are not affected by the programmed schedule. Vacation
mode is active for a specified period of time. While in vacation mode, the
system provides temperature and humidity protection for the home in the
selected mode, but not comfort. When vacation mode is active, an arrow will be
displayed beside “VACATION” in the upper left corner of the display.
53
Vacation Setpoints
A special set of temperature and humidity setpoints exist which are active in
vacation mode. They are adjustable by the homeowner, are exclusively for
vacation mode, and are remembered from one vacation selection to the next. See
Table 3 for default values.
Table 3 Vacation Setpoints Default Values
MODE Fan
Heat Setpoint Cool Setpoint Humidify Setpoint Dehumidify Setpoint
AUTO Auto 55_F/13_C 85_F/29_C 20_F/- 7_C 60_F/16_C
Vacation Humidification
Normal humidify is available using vacation setpoints. Auto humidification is
available, adjusting its setpoint with outdoor temperature the same as when
occupied. Vacation humidification can be turned off independently of occupied
humidification. While setting the Vacation setpoints, the Vacation humidify
setpoint is accessible by pressing the soft key below the humidify icon when
the box is around the heating setpoint.
Vacation Dehumidification
Normal Dehumidify, Cool to Dehumidify, and Dehumidify OFF are all available in
vacation mode, and selection of one of these can be different from that of
occupied. Vacation dehumidification selection and setpoints are remembered the
next time vacation is used. While setting Vacation setpoints, the Vacation
dehumidify setpoint is accessible by pressing the soft key below the
dehumidify icon when the box is around the cooling setpoint.
54
OPERATIONAL INFORMATION
Timers
Five- Minute Compressor Timeguard This timer prevents compressor from starting
unless it has been off for at least 5 minutes. It can be overridden for 1
cycle by simultaneously pressing FAN and UP buttons. Cycle Timer Based on the
selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10
minutes. This much time must elapse from the start of one cycle before another
cycle can start. It serves to impose the cycles per hour limits. It can be
defeated for one cycle by simultaneously pressing the FAN and UP buttons. Ten-
Minute Staging Timer In multistage heating or cooling, this timer prevents any
higher stage from turning on until preceding stage has been on for 10 minutes.
When staging between compressor and electric heat or between compressor and
furnace heat, the time is configurable. The timer is configurable via Option
17. This timer is overridden if temperature error is greater than 5_ (usually
due to a large change in desired temperature) and equipment stages up in 60
second intervals. The ten- minute staging timer does not require the
thermostat to change to a higher stage after 10 minutes. If the system is able
to meet the demand (maintain setpoint) it may not change stages after the 10
minute timer has expired. If there is sufficient demand for a higher stage at
the end of 10 minutes or at any time after the 10 minute timer has expired,
the thermostat will energize the next higher stage.
55
Defrost
When defrost occurs in a Hybrid Heat system, the furnace will operate during
the defrost cycle. At the end of the defrost cycle, the furnace and heat pump
will be de- energized while the fan is energized for 2 minutes allowing the
heat exchanger to cool down. If Option 34, Hybrid Heat Furnace Latch is set to
Off, at the end of the 2 minute time, the heat pump will be re- energized if a
call for heat still exists. If Option 34 is set to On (default), the furnace
will remain on until the end of the heating cycle. Defrost detection is not
available if the installer has configured the O/W2/B output to function as a B
output. During heat pump heating, a defrost signal shall be considered valid
if the compressor output is energized and the defrost signal has been active
for less than 15 consecutive minutes. Any defrost signal present for longer
than 15 minutes shall be considered invalid. Heat pump/fan coil and Hybrid
Heat systems shall use this input to:
S Detect that defrost is in progress and energize the auxiliary heat to
provide homeowner comfort during the defrost cycle
S Allow a defrost cycle to run to completion regardless of the system demand
Three- Minute Minimum on Time
In normal operation, when a stage turns on, it will not turn off for a minimum
of 3 minutes. In Hybrid Heat systems, the minimum on time for the furnace is 5
minutes. If the setpoint is changed, this timer is canceled, allowing the
equipment to turn off immediately when the demand is removed. The 3 minute
minimum on timer applies to all stages of heating and cooling, except Hybrid
Heat. A stage will run for a minimum of 3 minutes before the thermostat will
be allowed to stage to a lower stage.
56
Heat/Cool Setpoints (Desired Temperature)
A minimum difference of 1 and maximum of 6 is enforced between heating and
cooling desired temperatures. This is done by allowing 1 setting to “push” the
other, to maintain this difference. This difference is adjustable via
Configuration Option 11.
Equipment On Indicators
When cooling equipment is on, a COOL ON icon is displayed. While cooling
equipment operation is delayed by the time guard or cycle timer, COOL ON will
flash. The same is true for HEAT ON icon. During second stage compressor
operation a “2” will be displayed with the HEAT ON or COOL ON icon. This is
displayed when the Thermidistat Control is configured as H2, A2, or h2. When
the W is energized in a heat pump or Hybrid Heat system, the “auxiliary heat
on” icon will be displayed. Humidify and Dehumidify Indicators
When the Display Module door is closed, the humidify icon will be displayed
when humidification is active and the dehumidify icon will be displayed when
dehumidification is active. Auto Changeover When auto changeover mode is
selected, a change from heat to cool (or vice versa) will not occur until an
opposite mode demand has existed for 20 minutes. If setpoint is changed, 20-
minute requirement is deleted. Emergency Heat Mode When Thermidistat Control
is configured as a heat pump and emergency heat is selected, all Y signals are
locked out, and W becomes energized upon a call for heat.
57
Programmable Fan (programmable models only)
The fan output can be programmed based on period of the day. When programming
for each day and period the fan can be set to On or AUTO. If the fan button is
pressed to change from On to Auto or vice versa when programmable fan has been
enabled, the manual change will only remain in effect until the next program
period, when the programmable fan setting will be changed per the scheduled
setting. Dry Contact
On the programmable models, the dry contact that can be used for control of an
auxiliary device. The dry contact may be configured to be closed for a
specific number of minutes per hour for each period of the program schedule.
This can be used to operate a ventilator, damper, system blower, or other
auxiliary device. There are two terminals, D1 and D2. On both the programmable
and non- programmable models, when configured as a dehumidify output, it will
operate cooling equipment capable of dehumidify function. When configured for
dehumidification, the Rc terminal must be connected to one of the dry contact
terminals. The other dry contact terminal is connected to the dehumidify
terminal on the furnace or fan coil. This provides power to energize the
dehumidify terminal on the cooling equipment when the dry contact is closed.
If it is desired to operate a ventilator or other device, the D1 and D2
terminals can be connected directly to the equipment. This will provide a
closed contact for the specified number of minutes per hour. See Option 19. If
timed control of the system blower is required, the dry contact can be used
for this function. The G terminal can be connected to one of the dry contact
terminals with the other terminal being connected to Rc and/or Rh for timed
control of the fan. Note that this is not the same as programmable fan Option
30. See Wiring Diagrams for more information.
58
Relays This thermostat uses latching relays. When the thermostat loses power,
the relays will remain in their last position until power is restored and all
relays are reset to their correct position. Out of the box, the outputs may
appear to be On when the thermostat is not powered. This is normal. Output
states should only be checked when the thermostat is powered. Temperature
Offset After Power Cycle To compensate for internal heat build- up from the
electronics in the thermostat, the thermostat will add an offset to the actual
temperature that it measures. If the thermostat power is cycled quickly, one
can witness an immediate increase in the actual temperature displayed due to
this added offset. The thermostat display will return to the actual room
temperature after several minutes of operation.
59
TROUBLESHOOTING
If the display module doesn’t power up after power is applied, check the Rc/Rh
and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg
and V+. This voltage will be approximately 12- 20VDC. If voltage is present,
check the polarity to make sure it is wired correctly. The display will not
power up if polarity is reversed. If dashes appear for Option 01 in config and
during reboot, the problem could be the red pigtail being wired to Rc or Rh
and the black pigtail being wired to C. If so, remove the two- wire pigtail
and connect to the V+ and Vg terminals.
Error Codes
“- – ” – If Thermidistat Control cannot properly read room temperature,
display will indicate “- – ” and all outputs (except fan, if on) will turn
off. In the case where the installer has selected to average the local sensor
and the remote room sensor, the Thermidistat Control display will alternate
between “- – ” for the failed sensor and the temperature sensed by the working
sensor every 10 seconds. The control will operate from the temperature sensed
by the working sensor. E1 – If the Display Module and the Equipment Control
Module cannot communicate via two- wire connection, an E1 will be displayed.
E2 – There is no E2 error message. E3 – If Thermidistat Control cannot
properly read outdoor temperature, and it is needed for proper operation,
display will indicate “- – ” in the outdoor temperature location. If Option
06, 08, 09, 22, 23 or 44 is not set to OFF, display will indicate “- – ” in
the outdoor temperature location. E4 – If Thermidistat Control’s internal
memory fails, E4 will be displayed. Replace Thermidistat Control.
60
E5 – If Thermidistat Control cannot properly read humidity, E5 will be
displayed. Replace Thermidistat Control. If both Humidify and Dehumidify have
been set to OF, the humidity value will be shown as “- – ” when viewed from
the humidity menu, but no E5 will be shown in the display. Table 4 can be used
as a troubleshooting tool for determining which outputs will be active for a
particular configuration and each operating mode. When replacing a failed
component such as an equipment control module or a display module, the
installer should replace both parts as a matched set. It is very easy to
accidentally mix an A/C or HP display with a PRH equipment control module.
When this happens, some functions appear in the setup while others do not.
This can be very confusing to troubleshoot. Verify that both parts have the
same model and serial number when troubleshooting the thermostat.
61
Table 4 Equipment Configuration Outputs
Equip Config
Tstat Model
COOL STG 1
COOL STG 2
HEAT STG 1
HEAT STG 2
HEAT STG 3
HEAT STG 4
SS AC Opt 1 = AC
SS HP Opt 1 = HP RVS = O Opt
10 = C
SS HP Opt 1 = HP RVS = B Opt 10 = H
SS HP Opt 1 = HP RVS = O Opt 10 = C Opt. 43 = On
SS HP Opt 1 = HP RVS = B Opt 10 = H Opt. 43 = On
2SPD AC Opt 1 = A2
2SPD HP Opt 1 = H2 RVS = O Opt 10 = C
TPPRH01- B TP- NRH – A, – B
TPPRH01- B TP- NRH – A, – B
TPPRH01- B TP- NRH – A, – B
TPPRH01- B TP- NRH – A, – B
TPPRH01- B TP- NRH – A, – B
TPPRH01- B TP- NRH – A, – B
TPPRH01- B TP- NRH – A, – B
Y/Y2
Y/Y2, O/W2/B
Y/Y2
Y/Y2, O/W2/B
Y/Y2
Y1/W2
Y1/W2, O/W2/B
W/W1,
—
W/W1
O/W2/B
—
(if Opt 32 = 2)
—
Y/Y2
Y/Y2, W/W1
Y/Y2, W/W1, Y1/W2
—
Y/Y2, O/W2/B
Y/Y2, W/W1, O/W2/B
Y/Y2, W/W1, Y1/W2 O/W2/B
—
Y/Y2
Y/Y2, W/W1
Y/Y2, Y1/W2
—
Y/Y2, O/W2/B
Y/Y2, W/W1, O/W2/B
Y/Y2, Y1/W2, O/W2/B
Y/Y2, Y1/W2
W/W1
Y1/W2,Y /Y2,
O/W2/B
Y1/W2
W/W1, O/W2/B
Y1/W2, Y/Y2
—
Y1/W2, Y/Y2, W/W1
—
—
—
Y/Y2, W/W1, Y1/W2 Y/Y2, Y1/W2, W/W1, O/W2/B
—
—
EM HEAT STG 1
EM HEAT STG 2
—
—
W/W1
W/W1, Y1/W2
W/W1
W/W1, Y1/W2
W/W1
W/W1, Y1/W2
W/W1
W/W1, Y1/W2
—
—
W/W1
—
62
Equip Config
2SPD HP Opt 1 = H2 RVS = B Opt
10 = H
SS Hybrid Heat
Opt 1 = hh RVS= O Opt 10 = C
SS Hybrid Heat
Opt 1 = hh RVS = B Opt 10 = H
2S Hybrid Heat
Opt 1 = h2 RVS = O Opt 10 = C
2S Hybrid Heat
Opt 1 = h2 RVS = B Opt 10 = H
Heat Only Unit
Opt 1 = H
SS or 2SPD Cool Only
Unit Opt 1 = C
Table 4 – Equipment Configuration Outputs (cont.)
Tstat Model
COOL STG 1
COOL STG 2
HEAT STG 1
HEAT STG 2
HEAT STG 3
HEAT STG 4
EM HEAT STG 1
TP- PRH – A, – B TPNRH01- B
Y1/W2
Y1/W2, Y/Y2
Y1/W2, O/W2/B
Y1/W2, Y/Y2, O/W2/B
Y1/W2 Y/Y2 O/W2/B W/W1
—
W/W1
TP-
PRH01- B TP-
Y/Y2, O/W2/B
—
NRH01- B
Y/Y2
W/W1
W/W1, Y1/W2
—
W/W1
TP-
PRH01- B TP-
Y/Y2
—
Y/Y2 O/W2/B
W/W1
—
NRH01- B
—
W/W1
TPPRH01- B
TPNRH01- B
Y1/W2, O/W2/B
Y1/W2 Y/Y2, O/W2/B
Y1/W2
Y1/W2, Y/Y2
W/W1
—
W/W1
TP-
PRH01- B TP-
Y1/W2
Y1/W2, Y/Y2
Y1/W2, O/W2/B
Y1/W2, Y/Y2, O/W2/B
W/W1
—
W/W1
NRH01- B
TPPRH01- B
-TPNRH01- B
If HP or RH
board &
—
W/W1 Opt. 32 = 2
—
W/W1,
O/W2/B
—
—
TPPRH01- B
TPNRH01- B
Y1/W2
Y1/W2, Y/Y2 Ignore for SS
—
—
—
—
—
EM HEAT STG 2 -W/W1, Y1/W2
—
—
—
—
—
63
Display module V+ Vg
WIRING DIAGRAMS
Display module wall mount
V+ Vg V+ Vg
Equipment Control Module
V+
Vg
RVS/Heat Stage 2
O/B W2
Heat Stage 1
W/W1
Compressor
Y/Y2
Y1 / W2
Fan
G
24VAC Hot Heating
Rh
24VAC Hot Cooling
Rc
Dry Contact 1
D1
Dry Contact 2
D2
24VAC Common
C
Fan Coil O W3 W2 Y G R
C
Heat Pump O W2 Y
R
C
Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
OAT RRS SRTN
Outdoor Sensor
Remote Room Sensor
- Indicates connection may not be required/available.
Fig. 19 – Display to Equipment Control Module Connection
A09163
64
Equipment Control Module
RVS Cooling Heat Stage 3 Heat/Cool Stage 1 Heat/Cool Stage 2
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Fan Coil
O W1 W2 Y1 Y/Y2 G R
DH C
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Heat Pump
O W1
Y1 Y/Y2
R Remove J1 jumper for Dehumidify modes
C
- Indicates connection may not be required/available.
Fig. 20 – FV/FK Fan Coil with 2- Stage Heat Pump
A09657
65
Equipment Control Module
Typical Fan Coil
RVS Cooling Heat Stage 2 Heat Stage 3 Heat/Cool Stage 1
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
E W2 W3
G R
C Humidifier Solenoid
Valve Outdoor Sensor
Remote Room Sensor *
Single-Stage Heat Pump
O W2
Y R
C
- Indicates connection may not be required/available.
Fig. 21 – Typical Fan Coil with Heat Pump
A09165
66
Equipment Control Module
RVS/Heat Stage 2 Heat Stage 1
Compressor Low Compressor High
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
W3 W2
G R
C
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Aux. Connection
- Indicates connection may not be required/available.
Fig. 22 – Fan Coil Shown w/Aux. Connection #1 (Heat Pump/Air Conditioner removed for clarity.)
A09166
67
Equipment Control Module
Heat Stage 2 Heat Stage 1 Cool Stage 1 Cool Stage 2
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Fan Coil
O W2 W1 Y1 Y/Y2 G R
DH C
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Air Conditioner
Remove J2 Jumper for heat staging
Y1 Y2
R Remove J1 jumper for Dehumidify modes
C
- Indicates connection may not be required/available.
Fig. 23 – FV/FK Fan Coil w/2- Stage Air Conditioner
A09167
68
Equipment Control Module
Heat Stage 2 Heat Stage 1
N/A Cool Stage 1
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Typical Fan Coil
O E W3 W2 Y G R
Single-Stage Air Conditioner
Y R*
C
C
Humidifier Solenoid Valve
Outdoor Sensor
Remote Room Sensor *
- Indicates connection may not be required/available.
Fig. 24 – Typical Fan Coil with Air Conditioner
A09658
69
Equipment Control Module
Fan Coil
RVS/Heat Stage 2 Heat Stage 1
Compressor Low Compressor High
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
W3 W2
G R
C
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Aux. Connection
- Indicates connection may not be required/available.
Fig. 25 – Fan Coil Shown with Aux. Connection #2 (Heat Pump/Air Conditioner removed for clarity.)
A09169
70
Equipment Control Module
RVS Cooling Heat Stage 2 Heat Stage 3 Heat/Cool Stage 1
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Fan Coil
O
W1 W2 Y/Y2 G R Y1
DH C
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Heat Pump
O W2 Remove J2 Jumper for heat staging Y
R Remove J1 Jumper for Dehumidify modes
C
- Indicates connection may not be required/available.
Fig. 26 – FV/FK Fan Coil with 1- Stage Heat Pump
A12237
71
Equipment Control Module
Typical Fan Coil
RVS/Heat Stage 2 Heat Stage 1
Compressor Low Compressor High
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
E W2
G R
C Humidifier Solenoid
Valve Outdoor Sensor
Remote Room Sensor *
- Indicates connection may not be required/available.
Fig. 27 – Typical Fan Coil Heating Only 72
A09171
Equipment Control Module
RVS/Heat Stage 2
O/B W2
Heat Stage 1
W/W1
Compressor Low
Y1 / W2
Compressor High
Y/Y2
Fan
G
G
24VAC Hot Heating
Rh
R
24VAC Hot Cooling
Rc
Dry Contact 1
D1
Dry Contact 2
D2
24VAC Common
C
C
Humidify
HUM
Outdoor Air Temp
OAT
Remote Room Sensor
RRS
OAT/RRS Com
SRTN
A09172
Fig. 28 – Thermidistat Control w/Dry Contact Control for Fan Run Time
73
Equipment Control Module
Heat Stage 2 Heat Stage 1
N/A Heat/Cool Stage 1
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Fan Coil
O W2 W1 Y1 Y/Y2 G R
DH C
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Air Conditioner
Remove J2 Jumper for heat staging
Y
R* Remove J1 Jumper for Dehumidify modes
C
- Indicates connection may not be required/available.
Fig. 29 – FV/FK Fan Coil with 1- Stage Air Conditioner
A09659
74
Equipment Control Module
Typical Fan Coil
Single-Stage Air Conditioner
RVS/Heat Stage 2 Heat Stage 1
Compressor Low Compressor High
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
G R
C Humidifier Solenoid
Valve Outdoor Sensor
Remote Room Sensor *
- Indicates connection may not be required/available.
Fig. 30 – Typical Fan Coil Cooling Only
75
Y R* C
A09660
Equipment Control Module
Furnace
RVS Cooling Heat Stage 3 (furnace)
Heat/Cool Stage 1 Heat/Cool Stage 2
Fan 24VAC Hot Heating 24VAC Hot Cooling ***Dry Contact 1
Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
W2 W/W1
Y1 Y/Y2
G R
DHUM COM
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Heat Pump O W2** Y1
Y/Y2 R
C
- Indicates connection may not be required/available. ** Some heat pumps may designate W1. ***Option 19 set to 2.
A09121
Fig. 31 – Variable Speed, Multi- Stage, Stage Modulating and Single- Stage Furnace with 2- Stage Heat Pump
76
Equipment Control Module
RVS Cooling Heat Stage 2 (furnace)
Heat Stage 2 Heat/Cool Stage 1
Fan 24VAC Hot Heating 24VAC Hot Cooling ***Dry Contact 1
Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Furnace
Y1 W
Y/Y2 G R
HUM DHUM COM Humidifier Solenoid Valve Outdoor Sensor Remote Room Sensor *
Single-Stage Heat Pump
O W2**
Y R
C
- Indicates connection may not be required/available. ** Some heat pumps may designate W1. ***Option 19 set to 2.
Fig. 32 – Single- Stage Furnace with Heat Pump (Hybrid Heat)
77
A09618
Equipment Control Module
Furnace
Air Conditioner
Heat Stage 2 Heat Stage 1 Cool Stage 1 Cool Stage 2
Fan 24VAC Hot Heating 24VAC Hot Cooling
Dry Contact 1 Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
W2 W/W1
Y1 Y/Y2
G R
DHUM COM
Humidifier Solenoid Valve
Outdoor Sensor Remote Room Sensor *
Y1 Y/Y2
R
C
- Indicates connection may not be required/available. A09123
Fig. 33 – Variable Speed, Step Modulating, Multi- Stage and Single- Stage Furnace with Two- Stage Air Conditioner
78
Equipment Control Module
N/A Heat Stage 1
N/A Cool Stage 1
Fan 24VAC Hot Heating 24VAC Hot Cooling **Dry Contact 1
Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
Furnace
Y1 W
Y/Y2 G R
Single-Stage Air Conditioner
Y R*
DHUM
COM
C
Humidifier Solenoid Valve
Outdoor Sensor
Remote Room Sensor *
- Indicates connection may not be required/available. ** Option 19 set to 2.
A09661
Fig. 34 – Single- Stage Furnace with Single- Speed Air Conditioner
79
Equipment Control Module
RVS Cooling Heat Stage 3 (furnace) Heat Stage 2 (furnace)
Heat/Cool Stage 1 Fan
24VAC Hot Heating 24VAC Hot Cooling *** Dry Contact 1
Dry Contact 2 24VAC Common
Humidify Outdoor Air Temp Remote Room Sensor
OAT/RRS Com
O/B W2 Y1 / W2 W/W1
Y/Y2 G Rh Rc D1 D2 C
HUM OAT RRS SRTN
Furnace
W2 W/W1
Y1 Y/Y2
G R
DHUM COM Humidifier Solenoid Valve Outdoor Sensor Remote Room Sensor *
Heat Pump O
W2**
Y R
C
- Indicates connection may not be required/available. ** Some heat pumps may designate W1. ***Option 19 set to 2.
A09125
Fig. 35 – Variable Speed, Multi- Stage and Step Modulating Furnace with Single- Stage Heat Pump
80
Equipment Control Module
Furnace
N/A Heat Stage 1
N/A N/A Fan 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2
24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com
O/B W2 W/W1 Y1 / W2 Y/Y2
G Rh Rc D1 D2 C HUM OAT RRS SRTN
W
G R
DHUM COM Humidifier Solenoid Valve Outdoor Sensor Remote Room Sensor *
- Indicates connection may not be required/available.
Fig. 36 – Single- Stage Furnace Heating Only 81
A09126
Equipment Control Module
Furnace
Air Conditioner
Heat Stage 2
O/B W2
W2
Heat Stage 1
W/W1
W/W1
N/A
Y1 / W2
Y1
Cool Stage 1
Y/Y2
Y/Y2
Y
Fan
G
G
24VAC Hot Heating
Rh
R
R*
24VAC Hot Cooling
Rc
**Dry Contact 1
D1
Dry Contact 2
D2
DHUM
24VAC Common
C
COM
C
Humidify Outdoor Air Temp
HUM OAT
Humidifier Solenoid Valve *
Remote Room Sensor OAT/RRS Com
RRS SRTN
Outdoor Sensor
Remote Room Sensor
- Indicates connection may not be required/available. ** Option 19 set to 2.
A09662
Fig. 37 – Variable Speed, Multi- Stage, Step Modulating and Single- Stage Furnace with Single- Stage Air Conditioner
82
Equipment Control Module
Furnace
Air Conditioner
Heat Stage 2
O/B W2
Heat Stage 1
W/W1
W1
N/A
Y1 / W2
Y1
Cool Stage 1
Y/Y2
Y/Y2
Y
Fan
G
G
24VAC Hot Heating
Rh
R
24VAC Hot Cooling
Rc
R
** Dry Contact 1
D1
Dry Contact 2
D2
DHUM
24VAC Common
C
COM
C
Humidify Outdoor Air Temp
HUM OAT
Humidifier Solenoid Valve *
Remote Room Sensor OAT/RRS Com
RRS SRTN
Outdoor Sensor Remote Room Sensor
- Indicates connection may not be required/available. ** Option 19 set to 2.
A09152
Fig. 38 – Single- stage Furnace with Air Conditioner and Split Power
83
THERMIDISTAT CONTROL CONFIGURATION RECORD
Installer _____
Model Number __
A. Hardware Configuration
Seal Hole In Wall
B. Mode Settings
Mode (Off, Heat, Cool, Auto, Em Heat)
Heating Setpoint Value
Cooling Setpoint Value
Fan (Auto or On)
C. Home, Away, Sleep Settings Heat Cool
Date ____
Home
Away
Sleep
D. Schedule (For Programmable Thermidistat Controls)
Period 1
Period 2
Period 3
Period 4
Time Heat Cool Time Heat Cool Time Heat Cool Time Heat Cool
All Days
Weekdays
Weekend
84
E Configuration Options
Option 01 ____ Equipment Type
Option 02 ____ Clean Filter Timer Adjustment
Option 03* ____ Fahrenheit/Centigrade Selection
Option 04 ____ Fan (G) on with W/W1 Selection
Option 05 ____ Room Air Temperature Sensing (programmable models only)
Option 06 ____ Cooling Lockout Below 55_F/13_C Selection (only available if outdoor air sensor is present)
Option 07 ____ Zoning
Option 08
Auxiliary Heat Lockout Temperature Setting (only available when heat pump is used and when outdoor air temperature sensor is present)
Option 09 ____ Heat Pump Lockout Temperature
Option 10 ____ Reversing Valve
Option 11 ____ Adjustable Setpoint Deadband (not available on Heat Only and Cool Only systems)
Option 12 ____ Smart Recovery (programmable models only)
Option 13 ____ Room Air Temperature Offset Adjustment
Option 14 ____ Humidity Offset Adjustment
Option 15 ____ Enable Auto Mode
Option 16 ____ Cycles Per Hour
Option 17 ____ Time Between Stages
Option 18* ____ Backlight Configuration
85
E Configuration Options (cont) Option 19 Dry Contact (programmable models
only) Option 20 Outdoor Air Temperature Offset Adjustment Option 21
Keypad Lockout Option 22 High Cool Latch Temperature Option 23 ____ High
Heat Latch Temperature Option 24 Programmable/Non- Programmable
(programmable models only) Option 25* Number of Programmable Periods Per
Day (programmable models only) Option 26 Minimum Cooling Setpoint Option
27 Maximum Heating Setpoint Option 28 UV Light Reminder Option 29
Humidifier Pad Reminder Option 30 ____ Programmable Fan (programmable
models only) Option 31 Daylight Savings Time Configuration (programmable
models only) Option 32 Furnace Heat Staging Option 33 Single or Two-
Piece Installation Option 34 Hybrid Heat Furnace Latch Option 40 Fan
Humidity Option 41 Variable Speed Blower Option 42 Variable Speed
Super Dehumidification Option 43 Intelligent Heat Staging Option 44
Super Comfort Heat Option 99 Reset to Factory Defaults * Options with an
asterisk can also be set/changed by the homeowner.
86
NOTES 87
NOTES 88
997- 060360- 11- R
Copyright 2017 Carrier Corporation 7310 W Morris St. Indianapolis, IN 46231
TP- PRHB- 02SI
Replaces: TP- PRHB- 01SI
Edition Date: 04/17
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>