Emerson Programmable Touchscreen Thermostat 810-1600 User Manual
- June 7, 2024
- Emerson
Table of Contents
Programmable Touchscreen Thermostat 810-1600
Emerson Programmable Touchscreen Thermostat Installation and Operation Manual
026-1739 Rev 2
Emerson Digital Solutions Commercial and Residential Solutions 1065 Big Shanty
Road NW, Suite 100
Kennesaw, GA 30144 770-425-2724 ·
1-800-829-2724
www.climate.emerson.com Email: ColdChain.TechnicalServices@Emerson.com
Contents
1 OVERVIEW ……………………………………………………………………………………………………………………… 1
1.1. SPECIFICATIONS ……………………………………………………………………………………………………………….. 1 1.1.1.
Technical Specifications…………………………………………………………………………………………….. 1
1.2. TERMINAL IDENTIFICATION AND ELECTRICAL RATINGS………………………………………………………… 3
2 INSTALLATION ………………………………………………………………………………………………………………. 4
2.1. ENCLOSURE……………………………………………………………………………………………………………………… 4 2.2. THERMOSTAT
LOCATION …………………………………………………………………………………………………… 4 2.3. THERMOSTAT INSTALLATION
…………………………………………………………………………………………….. 5
2.3.1. Opening and Closing the Thermostat Enclosure ………………………………………………………….. 5
2.3.2. Mounting the Baseplate on the Wall ……………………………………………………………………………. 5
2.3.3. Wires and Electrical Connection ………………………………………………………………………………… 6 2.4.
WIRING AND CONNECTIONS ………………………………………………………………………………………………. 7 2.4.1. Wiring
Guide – Conventional Systems (24VAC) ……………………………………………………………. 7 2.4.2. Wiring
Guide – Heat Pump Systems (24VAC)……………………………………………………………….. 8 2.4.3.
Thermostat Power Terminals …………………………………………………………………………………… 9 2.4.4.
Thermostat Communication Terminals……………………………………………………………………… 9 2.4.5.
Thermostat Input Terminals …………………………………………………………………………………….. 9 2.4.6.
Thermostat Output Terminals ………………………………………………………………………………… 10
3 OPERATION…………………………………………………………………………………………………………………… 11
3.1. GRAPHICAL USER INTERFACE (GUI)…………………………………………………………………………………. 11 3.2.
CONFIGURATION MENU …………………………………………………………………………………………………… 11
3.2.1. Configuration Menu Modbus Device Address ………………………………………………………….. 13
3.2.2. Configuration Menu Modbus Device Baud Rate ………………………………………………………. 13
3.2.3. Configuration Menu Thermostat System Configuration
…………………………………………….. 14 3.2.4. Configuration Menu – Number of Heating
Stages………………………………………………………… 16 3.2.5. Configuration Menu – Number of Cooling
Stages………………………………………………………… 17 3.2.6. Configuration Menu Full Segments
Display Test ……………………………………………………… 19 3.2.7. Configuration Menu System
Revision Display………………………………………………………….. 19 3.3. TEMPERATURE UNIT SELECTION
………………………………………………………………………………………. 21 3.4. TIME AND DATE
SETTING………………………………………………………………………………………………… 21 3.5. MENUS & INTERFACE
……………………………………………………………………………………………………… 23 3.5.1. Temperature
Setpoints……………………………………………………………………………………………… 24 3.5.2. Thermostat
Mode…………………………………………………………………………………………………….. 25 3.5.3. Fan Mode
………………………………………………………………………………………………………………. 25 3.5.4. Fan Mode Display – Fan
Status ………………………………………………………………………………… 26 3.5.5. Active Stage(s) Indicator
………………………………………………………………………………………….. 27 3.5.6. Schedule Mode
……………………………………………………………………………………………………….. 28 3.5.7. Occupancy Mode (Energy
Saving Mode)……………………………………………………………………. 30 3.5.8. Manual Override
…………………………………………………………………………………………………….. 31 3.5.9. Screen Lock
……………………………………………………………………………………………………………. 32
Table of Contents · v
3.6. COMMUNICATION NETWORK …………………………………………………………………………………………… 33 3.6.1.
RS-485 Serial Link ………………………………………………………………………………………………….. 33
3.7. POWER OUTAGE …………………………………………………………………………………………………………….. 34 3.8. ADVANCED
SETTINGS …………………………………………………………………………………………………….. 35
3.8.1. Thermostat System Configuration …………………………………………………………………………….. 35
3.8.2. Thermostat Stage(s) Behavior ………………………………………………………………………………….. 36
3.8.3. Input Settings …………………………………………………………………………………………………………. 36 3.8.4.
Dehumidification Mode …………………………………………………………………………………………… 37 3.8.5. Economizer
Mode …………………………………………………………………………………………………… 37 3.8.6. Hold Mode
…………………………………………………………………………………………………………….. 38 3.8.7. Internal Temperature
Offset …………………………………………………………………………………….. 40 3.8.8. Delay Fan
……………………………………………………………………………………………………………… 40 3.8.9. Temperature Filter Time
(Sampling Rate)………………………………………………………………….. 40 3.8.10. Temperature Hysteresis
…………………………………………………………………………………………. 40 3.8.11. Minimum Temperature Deadband
(Read-Only)……………………………………………………….. 40 3.8.12. Temperature Minimum Setpoint
…………………………………………………………………………….. 40 3.8.13. Temperature Maximum
Setpoint…………………………………………………………………………….. 40 3.8.14. Temperature Stage
Difference ……………………………………………………………………………….. 40 3.8.15. Compressor Min ON time
……………………………………………………………………………………… 41 3.8.16. Compressor Min OFF
time……………………………………………………………………………………. 41
4 PROGRAMMABLE TOUCHSCREEN THERMOSTAT SETUP FOR E2 AND SITE
SUPERVISOR……………………………………………………………………………………………………………………… 42
4.1. NEW INSTALLATION OF DESCRIPTION FILE TO E2………………………………………………………………. 42
4.1.1. Uploading the Touch_TStat Description File to E2 ……………………………………………………..
42
4.2. DEVICE AND COM PORT SETUP IN E2 ……………………………………………………………………………… 44 4.2.1.
Modbus Device Setup………………………………………………………………………………………………. 44 4.2.2. E2 COM Port
Setup ………………………………………………………………………………………………… 44
4.3. INSTALLING THE THERMOSTAT IN E2 ……………………………………………………………………………….. 46
4.3.1. Installing the Thermostat Application ……………………………………………………………………….. 46
4.3.2. Commissioning the Thermostat ………………………………………………………………………………… 46
4.4. DEVICE AND COM PORT SETUP IN SITE SUPERVISOR…………………………………………………………. 47
4.4.1. Modbus Device Setup………………………………………………………………………………………………. 47 4.4.2. Site
Supervisor COM Port Setup ………………………………………………………………………………. 48 4.4.3. Adding the
Touchscreen Thermostat Application in Site Supervisor ……………………………… 49 4.4.4.
Installing and Commissioning the Touchscreen Thermostat…………………………………………. 49
5 TROUBLESHOOTING …………………………………………………………………………………………………… 51
6 REGULATORY INFORMATION …………………………………………………………………………………… 52
vi · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
1 Overview
The Emerson Programmable Touchscreen Thermostat (P/N 810-1600) is a configurable device intended for light commercial applications. The thermostat is a communicating, intelligent sensor and controller combination with built- in temperature and humidity sensors used to control systems such as conventional Rooftop Units (RTU) and Heat Pumps (HP). The thermostat communicates over a Modbus RTU network that easily integrates with a building management system (BMS).
1.1. Specifications
1.1.1. Technical Specifications
Power Requirements
18VAC to 30VAC, 50-60Hz, less than 3.6 VA at 24VAC nominal, Class 2
Wire Size Relay Contact Rating Binary Input Analog Input
18AWG maximum, 22AWG recommended Max 1.0A per Relay, Max Total 2.0A (R, Rc and
C terminal) Fan Proof switch input (floating or GND)
Designed for 10K NTC thermistor
Serial Data Link Relay Output Temperature Sensor Type Supported Configurations Temperature Setting Range Temperature Accuracy Minimum Temperature Deadband Operating Temperature Storage Temperature Humidity Accuracy Humidity Display Range
Modbus RTU on RS-485, 9600 or 19200 bps (default) 2C, 2H, Fan, ECO, AUX, O/B
Local integrated temperature sensor, digital output (I2C) Conventional
systems, Heat-pump systems 32°F to 122°F (0°C to 50°C) +/- 0.6°C, +/- 1.1°F,
within operating temperature range
Default value is 4°F / 2°C, between cooling and heating
32°F to 122°F (0°C to 50°C) -4°F to 140°F (-20°C to 60°C) +/- 5% @ 50% RH @
77°F (25°C) 0% to 95%
Table 1-1 – Technical Specifications
Specifications
Overview · 1
RTC Battery
Compliance (USA)
Compliance (Canada) Dimensions Software
CR1220 Designed to comply to UL60730, FCC CFR 47 Part 15 Subpart B Class B Designed to comply to E60730, Industry Canada ICES-003 Issue 6 H 4.72″ x W 5.47″ x T 1.32″ V107
Table 1-1 – Technical Specifications
2 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
1.2. Terminal Identification and Electrical Ratings
Signal Name C R W1 W2 AUX O/B Rc Y1 Y2 ECO G GND B+ AIN1 IN2 IN3 IN4 IN5 GND
Description
24AVAC Power Supply Common 24AVAC Power Supply Heat Stage 1, relay output Heat
Stage 2, relay output Dehumidification, relay output Reversing Valve, relay
output 24VAC Power Supply for Y1, Y2 Cool Stage 1, relay output Cool Stage 2,
relay output Economizer, relay output Fan Control, relay output Reference for
DC Signals RS-485 B+ Signal RS-485 A- Signal Remote 10K thermistor (Indoor)
Remote 10K thermistor (Outdoor) Remote 10K thermistor (Supply) Remote Humidity
sensor (0-5V) Fan proof input Reference for DC Signals
Voltage 18-30VAC 50/60Hz 18-30VAC 50/60Hz 18-30VAC 50/60Hz 18-30VAC 50/60Hz
18-30VAC 50/60Hz 18-30VAC 50/60Hz 18-30VAC 50/60Hz 18-30VAC 50/60Hz 18-30VAC
50/60Hz 18-30VAC 50/60Hz 18-30VAC 50/60Hz
0-3.3VDC (10K NTC) 0-3.3VDC (10K NTC) 0-3.3VDC (10K NTC) 0-5VDC 0VDC or
floating
Table 1-2 – Terminal Identification and Electrical Ratings
Maximum Current Rating
2.0A 2.0A 1.0A 1.0A 1.0A 1.0A 2.0A 1.0A 1.0A 1.0A 1.0A
Terminal Identification and Electrical Ratings
Overview · 3
2 Installation
2.1. Enclosure
Figure 2-1 – Emerson Programmable Thermostat Enclosure
2.2. Thermostat Location
The thermostat should be mounted: > About 5 ft (1.5 m) from the floor. > On a
part of wall without hidden pipes or ductwork. > In a room that operating
limits are within 32°F to 122°F (0°C to 50°C). > In a room that humidity
operating range is within 0% to 95% relative humidity, non-condensing.
The thermostat should not be mounted: > Nearby a window, on an outside wall,
or next to a door leading to the outside. > Where exposed to direct light and
heat from any heat source, such as a lamp, the sun, a fireplace, or any
heating element which may cause a false reading (temperature measurement
offset). > Nearby a direct airflow from supply registers (air vent or duct
outlet). > In areas and locations with poor air circulation such as behind a
door.
4 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
2.3. Thermostat Installation
2.3.1. Opening and Closing the Thermostat Enclosure
Figure 2-2 – Exploded View of Thermostat
To open the thermostat enclosure, grip the top and the bottom edge of the
front part of the device and pull straight. A certain physical resistance is
normal from the 24x contacts pins (terminal strips and terminal blocks) that
have to be separated during the operation. To close the thermostat enclosure,
make sure to align the top and the bottom tabs between the front part and the
baseplate, and then push the front part firmly toward the wall. Again, some
force is required to mate both parts.
NOTE: Both top and bottom securing screws are optional and normally not
installed on the units.
2.3.2. Mounting the Baseplate on the Wall
Figure 2-3 – Baseplate (Back view) Thermostat Installation
Installation · 5
To fix the baseplate on a wall, pass the wires through the opening of the
baseplate, and use either 2x self-taping screws and dry-wall anchors, or
regular 6-32 machine screws to attach on a standard single-gang electrical
junction box (2″ x 4″).
CAUTION! Do not over-tighten the screws when attaching the baseplate on a wall
as physical damage may occur.
CAUTION! Keep the thermostat housing and vents clean and free of any debris to
avoid malfunction of the device.
2.3.3. Wires and Electrical Connection Once the baseplate is affixed on the
wall, proceed with the wiring connections to the terminal block. Please refer
to Section 2.4., Wiring and Connections for configuration and signals
definition.
Figure 2-4 – Baseplate with Terminal Blocks Labels
6 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
2.4. Wiring and Connections
WARNING! Turn off power of the HVAC system at the main power panel or on the
controlled-system itself to avoid any electrical shock or damage to the
system.
2.4.1. Wiring Guide – Conventional Systems (24VAC)
Single Transformer System:
Shorting Jumper
2H / 2C System with 1 Transformer
R
24VAC Power Supply
Rc
24VAC Power Supply for Y1, Y2
C
24VAC Power Supply Common
Y1
Cool Stage 1, relay output
Y2
Cool Stage 2, relay output
W1
Heat Stage 1, relay output
W2
Heat Stage 2, relay output
G
Fan Control, relay output
Table 2-5 – Single Transformer System
Dual Transformer System:
2H / 2C System with 2 Transformers
R
24VAC Power Supply
Rc
24VAC Power Supply for Y1, Y2
C
24VAC Power Supply Common
Y1
Cool Stage 1, relay output
Y2
Cool Stage 2, relay output
W1
Heat Stage 1, relay output
W2
Heat Stage 2, relay output
G
Fan Control, relay output
Table 2-6 – Dual Transformer System
For systems with only one stage, second stage terminals (Y2, W2) can be left
floating (open).
Wiring and Connections
Installation · 7
2.4.2. Wiring Guide – Heat Pump Systems (24VAC)
Shorting Jumper
2H / 2C System
R
24VAC Power Supply
Rc
24VAC Power Supply for Y1, Y2
C
24VAC Power Supply Common
Y1
*Cool Stage 1, relay output
Y2
*Cool Stage 2, relay output
O/B
Reversing Valve, relay output
G
Fan Control, relay output
Table 2-7 – Heat Pump Systems
For systems with only one stage, second stage terminal (Y2) can be left
floating (open).
*NOTE: Stage 1 and Stage 2 for Heat Pumps are Compressor Stages (Heat/Cool) and not
only Cool Stages.
8 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
2.4.3. Thermostat Power Terminals
Thermostat Power
R
24VAC Power Supply
Rc
24VAC Power Supply for Y1, Y2
C
24VAC Power Supply Common
Table 2-1 – Power Terminals
2.4.4. Thermostat Communication Terminals
AB+ GND
Modbus Connections RS-485 A- Signal RS-485 B+ Signal Reference for DC Signals
Table 2-2 – Comm Connections
2.4.5. Thermostat Input Terminals
IN1 IN2 IN3 IN4 IN5 GND
Thermostat Inputs Remote 10K thermistor (Indoor) Remote 10K thermistor (Outdoor) Remote 10K thermistor (Supply) Remote Humidity sensor (0-5V) Fan proof input Reference for DC Signals
Table 2-3 – Input Terminals
Wiring and Connections
Installation · 9
2.4.6. Thermostat Output Terminals RTU System Output Terminals:
Y1 Y2 W1 W2 G O/B ECO AUX
Thermostat Outputs Cool Stage 1, relay output Cool Stage 2, relay output Heat Stage 1, relay output Heat Stage 2, relay output Fan Control, relay output Reversing valve, relay output Economizer, relay output Dehumidification, relay output
Table 2-4 – Output Terminals
10 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3 Operation
3.1. Graphical User Interface (GUI)
The display of the device is used as the Graphical User Interface to show some
of the status, setpoints and actual measurements such as room temperature and
relative humidity. The display is a resistive touch-type that allows users to
navigate and to change values that are shown on the display (see Figure 3-1).
Figure 3-1 – Display With All Segments Shown
3.2. Configuration Menu
On the first start-up of the thermostat, the default System Configuration is
idle. This means that the first step to get the device started is to configure
the appropriate system configuration. The following menu will appear by
default upon the first startup (Figure 3-2).
Graphical User Interface (GUI)
Operation · 11
Figure 3-2 – Thermostat Display In Idle Configuration
To access the Configuration Menu (see Figure 3-3), press the technician
icon
for 10 seconds. If the thermostat has been previously configured, to access the configuration menu from the main display, a technician icon should be displayed on the right bottom corner of the screen. The technician icon is not displayed automatically (Figure 3-3). To display the technician icon, touch on the
right-bottom corner of the screen, and then press the technician icon seconds.
for 10
Figure 3-3 – Configuration Menu Access 12 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.2.1. Configuration Menu Modbus Device Address The first configuration menu (see Figure 3-4) allows users to change the Modbus device address. Ad is shown on the right side of the display to indicate which parameter is being changed (Ad stands for Address). To change the value, press either the up or down arrow, and then press the check icon to go to the next parameter. Press CA to cancel and exit the configuration menu without saving any changes.To change values, touch either the up or down arrow, and then touch the check icon to go to the next parameter.
Figure 3-4 – Modbus Address Configuration Menu
Address Number 1 to 247
Modbus Device Address Range from 1 to 247
Table 3-1 – Modbus Device Address Range
3.2.2. Configuration Menu Modbus Device Baud Rate The second configuration menu (see Figure 3-5) allows users to change the Modbus device baud rate. “br” is shown on the right side of the display to indicate which parameter is being changed (br stands for Baud Rate). To change the value, press either the up or down arrow, and then press the check icon to go to the next parameter. Press CA to cancel and exit the configuration menu without saving any changes.
Configuration Menu
Operation · 13
Figure 3-5 – Modbus Baud Rate Configuration Menu
Menu Option Number 0 1
Corresponding Baud Rate 9600 bps 19200 bps (default)
Table 3-2 – Modbus Baud Rate
3.2.3. Configuration Menu Thermostat System Configuration The third configuration menu (see Figure 3-9) allows users to set the thermostat system configuration. SC is shown on the right side of the display to indicate which parameter is being changed (SC stands for System Configuration). The current revision of the Emerson Programmable Touchscreen Thermostat supports Conventional HVAC Systems such as RTU and Heat-pump Systems using a reversing valve. There are 4x possible configurations: IDLE, RTU, HP_O and finally HP_B. The first system configuration is IDLE. In this configuration, all the outputs of the thermostats are open and the thermostat controls are inactive. This is to prevent any issues within the current configuration compared to the equipment connected to the thermostat. To change the value, press either the up or down arrow, and then press the check icon to go to the next parameter. Press CA to cancel and return to the normal display without saving any changes.
14 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Figure 3-6 – Thermostat System Configuration Menu NOTE: By default, the thermostat is configured as 2 heat-stages and 2 cool-stages thermostat. The number of heating/cooling stages can be changed in the subsequent menus.
· When the system is not configured, for example, configured in IDLE, all other configurations are accessible through the menu as below:
Menu Option Number 0 1 2 3
System Configuration IDLE RTU (Conventional Systems) HP_O (Heat-pump with O as reversing signal) HP_B (Heat-pump with B as reversing signal)
Table 3-3 – Thermostat System Configuration
Configuration Menu
Operation · 15
Figure 3-7 – Thermostat System Configuration Menu With Options: 0-IDLE. 1-RTU,
2-HP-O, 3-HP-B
· When the system is already configured in RTU, HP_O or HP_B, only the IDLE
and the current configuration are accessible through the menu:
Menu Option Number 0 (1, 2, or 3)
System Configuration IDLE Current Configuration
Table 3-4 – Thermostat System Configuration
IMPORTANT! In order to change the thermostat’s configuration from a functional configuration (not IDLE) to another one, the thermostat must be set to IDLE configuration first, then all configuration options will be displayed on the screen and the new desired configuration can be chosen.
IMPORTANT! A factory reset of all parameters will occur when the system is set
to the IDLE configuration, except current date and time that are kept with the
use of a Real-Time Clock (RTC).
3.2.4. Configuration Menu – Number of Heating Stages For all systems, the
number of heating stages can be modified inside this menu. On the screen, the
letters “HS” stands for Heating Stages. Possible values are 1 heating stage, 2
heating stages (see Figure 3-8 and Figure 3-9). Press the “Done” icon to move
on to the next menu. Values will not be saved until the last configuration
menu is reached.
16 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Figure 3-8 – Number of Heating Stages is Set to 2 (unsaved)
Figure 3-9 – Number of Heating Stages is Set to 1 (unsaved)
3.2.5. Configuration Menu – Number of Cooling Stages
For all systems, the number of cooling stages can be modified inside this
menu. On the screen, the letters “CS” stands for Cooling Stages. Possible
values are 1 cooling stages, 2 cooling stages (see Figure 3-10 and Figure
3-10). Press the “Done” icon to move on to the next menu. Values will not be
saved until the last configuration menu is reached.
Configuration Menu
Operation · 17
Figure 3-10 – Thermostat Display When Restarting to Occur (Rebooting)
Figure 3-11 – Thermostat System Configuration Menu (New System Configuration
Mode after IDLE)
18 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.2.6. Configuration Menu Full Segments Display Test The fourth configuration menu (see Figure 3-12) allows users to test the full display segments. This allows a complete review of the display segments and to inform the user of all possible segments in the current Emerson Programmable Touchscreen Thermostat revision. Press the check icon to go to the next parameter.
Figure 3-12 – Full Segments Display Test
3.2.7. Configuration Menu System Revision Display The fifth and last
configuration menu (see Figure 3-13) provides the current system revision
number. This number is shown with three digits. Note that there is no decimal
after the first digit, but the revision number contains a decimal. For
example, revision number 100 on the display = 1.00. The software revision will
be updated for the latest official release, and will likely be higher than
1.00. Touch the letters “CA” to cancel any previous changes and go back to the
normal display without saving. Press the check icon to terminate the
configuration menus.
Figure 3-13 – System Revision Display (For revision 1.00) Configuration Menu
Operation · 19
IMPORTANT! If at least one of those parameters has been changed, the
thermostat will reboot: Thermostat system configuration, number of Heating
stages or number of Cooling stages.
Prior to device restart, the display will show “- -” to indicate that the
device is about to reboot. (See Figure 3-15). When the device is rebooting,
the display will turn off for approximately a few seconds until reboot
operation has completed.
Figure 3-14 – Thermostat Display Before Reboot
20 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.3. Temperature Unit Selection
The temperature unit can be changed to either °F unit or °C unit. To select
one or the other, press the unit indicator on the display (see Figure 3-15),
either °F or °C. The temperature unit will toggle from one to the other each
time the unit is pressed.
Figure 3-15 – Temperature Unit Selection
3.4. Time and Date Setting
· On the main display, the clock at top right shows the actual time. To change
or update the time, press the clock on the display (see Figure 3-16):
Figure 3-16 – Clock Settings
· The first step in time settings is to set the time format between 12 hours
AM/PM or 24 hours. Select between H12 for 12-hours AM/PM and H24 for 24-hours
format, and then press the check icon to go to the next parameter (see Figure
3-17). Press CA to cancel and return to the normal display without saving any
changes.
Temperature Unit Selection
Operation · 21
IMPORTANT! If time is set through the Modbus network, the format to use for the time parameter should be 24-hours (0-23). The actual time display on the thermostat will be according to the selected time setting (12H or 24H).
Figure 3-17 – Time Format Setting with Check Icon
· The second step (see Figure 3-18) is the hour field that will be flashing on
the top right of the screen. To change the hours, press either the up or down
arrow to the desired value, and then press the check icon to go to the next
parameter.
· The third step (see Figure 3-18) is the minutes field that will be flashing
on the top right of the screen. To change the minutes, press either the up or
down arrow to the desired value, and then press the check icon to go to the
next parameter.
· The last step (see Figure 3-18) is the day of the week that will be flashing
at the top of the screen. To change the day of the week, press either the up
or down arrow to the desired value, and then press the check icon to save the
changes. Press CA to cancel and return to the normal display without saving
any changes.
Figure 3-18 – Time and Day Settings 22 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.5. Menus & Interface
· The main user interface menu is shown in Figure 3-19:
Figure 3-19 – Main User Interface (Backlight Off)
· To access or wake-up the display, press anywhere on the screen (Figure
3-20). Control icons will appear on both right and left side of the display.
The display will return to backlight off after about 30 seconds of inactivity
on the touch display. This backlight off state is essential to avoid important
temperature measurement shifts due to thermostat self-heating.
Figure 3-20 – Wake-up Display Menus & Interface
Operation · 23
3.5.1. Temperature Setpoints
· To change either the heating or cooling setpoint, press the desired setpoint
on the right side of the display (either COOL or HEAT, see Figure 3-21) and
the corresponding setpoint configuration menu will appear with arrows (see
Figure 3-22).
Figure 3-21 – Temperature Setpoint Access
Figure 3-22 – Temperature Setpoint Menu (either COOL or HEAT)
24 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.5.2. Thermostat Mode
To change the Thermostat Mode, press the
icon (see Figure 3-23). Text on the
right side of the icon will display OFF, COOL, HEAT and AUTO. The active mode will be displayed on the right side of the screen as COOL or HEAT, with the number of stages activated right above the mode (stages indicator marks, see Section 3.5.5., Active Stage(s) Indicator. Stages indicator marks will be displayed for the HEAT Mode, the COOL Mode, and the Fan Mode as well.
Figure 3-23 – Changing Thermostat Mode
Thermostat Mode OFF COOL HEAT
AUTO
Description Thermostat will be in OFF mode. Thermostat will be in cooling mode only. Thermostat will be in heating mode only. Thermostat will be in automatic switchover mode between cooling and heating mode.
Table 3-5 – Thermostat Mode
3.5.3. Fan Mode Fan mode can be either AUTO or ON. To change the Fan Mode, press (touch) the
icon
(Figure 3-24). When the FAN_MODE is AUTO, the fan will be active
only when heating or cooling call is active. While when FAN_MODE is ON, the fan stays active (ON) independently of “Thermostat mode” or heating and cooling conditions.
Menus & Interface
Operation · 25
Figure 3-24 – Fan Mode Selection
3.5.4. Fan Mode Display – Fan Status When FAN_MODE is AUTO: · Fan icon is
displayed. · The text AUTO is displayed. · The fan indicator (four dashes over
the fan) is displayed according to heating or cooling status.
When FAN_MODE is ON: · Fan icon is displayed. · No text is displayed. · The
fan indicator (four dashes over the fan) will be displayed
as long as the FAN_MODE is ON.
26 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Fan Mode
Description
AUTO
Fan will be activated when either cooling or heating call is active.
Output Activation
Output Display on GUI
0% (OFF)
100% (ON)
Fan stays active (ON) independently of
ON
“Thermostat mode” or heating and
100% (ON)
cooling conditions.
Table 3-6 – Thermostat Mode
3.5.5. Active Stage(s) Indicator The thermostat will show the mode is active
with the number of activated output stages (see Figure 3-25), as well as the
target temperature setpoint under the given active mode.
Figure 3-25 – Active Stage(s) Indicator Menus & Interface
Operation · 27
According to the number of output stages configured and available into the thermostat (1 to 2 stages for Cooling and Heating), the display will show output activation status according to the following table:
Stages Configuration
Output Activation 0% OFF
Output Display (on GUI)
2-stage Configuration (Cooling, Heating)
50% (1-stage ON) 100% (2-stages ON)
1-stage Configuration (Cooling, Heating)
0% OFF 100% (1-stage ON)
Table 3-7 – Active Stage Output Activation Status
3.5.6. Schedule Mode The thermostat can operate on either a schedule or
unscheduled operation.
Schedule Mode Inactive (Unscheduled Operation) The Schedule Mode set to Inactive is the most basic mode of the thermostat. The user can change the temperature setpoints on the display, see Section 3.1., Graphical User Interface (GUI). The setpoints will remain unchanged until the next manual update on the display or by Modbus.
Schedule Mode Active (Scheduled Operation) The Schedule Mode set to Active describes the thermostat behavior against a programmed schedule. To set the Schedule Mode to Active, send a request from the BMS to enable or disable the schedule. The scheduled operation (Active) can only be activated by the Modbus network. Scheduled operation can be done via the BMS schedule or the back-up schedule. A) BMS schedule If a Modbus communication to the thermostat occurs, then it is assumed that the Building Management System (BMS) controls the thermostat with its own schedule. B) Back-up schedule If the thermostat detects a Modbus communication loss (no communication addressed to the thermostat during 10 minutes or more), the internal schedule takes over to control the thermostat. When the internal schedule is running, the icon “Follow schedule” will be visible on the display (Figure 3-26). The text “Follow schedule” is not displayed in case the BMS schedule is active.
28 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Figure 3-26 – Follow Mode Activated
The internal schedule is based on four events/periods for each day, which can
be programmed on a 5 & 2 day schedule (weekdays and weekends). For each
period, the Start Time, the Thermostat Mode and the Occupancy Mode are set. As
described in Section 3.5.2., Thermostat Mode, the Thermostat Mode can be set
to either OFF, COOL, HEAT or AUTO. The Occupancy Mode can be set to either
Occupied or Unoccupied through the scheduler parameters (see Section 3.5.7.,
Occupancy Mode (Energy Saving Mode). The Backup schedule is programmed
(default values) as follows:
Period
1 2 3 4
Monday to Friday (Weekdays)
Start Time
Thermostat Mode
Occupancy Mode
6:00 AM AUTO
OCCUPIED
12:00 PM AUTO
OCCUPIED
6:000 PM HEAT
UNOCCUPIED
12:00 AM HEAT
UNOCCUPIED
Table 3-8 – Default Programmed Schedule
Saturday and Sunday (Weekend)
Start Time
Thermost at Mode
Occupancy Mode
6:00 AM HEAT
UNOCCUPIED
12:00 PM HEAT
UNOCCUPIED
6:00 PM HEAT
UNOCCUPIED
12:00 AM HEAT
UNOCCIUPIED
Menus & Interface
Operation · 29
3.5.7. Occupancy Mode (Energy Saving Mode) When the Schedule Mode is set to
Follow, there are two groups of temperature setpoints, each one related to the
occupancy status of the room. A given room can be either configured to
Occupied or Unoccupied for a certain period of time. Normally, the Occupied
Mode has setpoints that are more comfortable for the occupants, while the
Unoccupied Mode brings energy savings with more conservative setpoints.
Figure 3-27 – Thermostat Occupancy Mode
When the thermostat is in Occupied Mode, a person-shaped icon will appear on
the display (see Figure 3-28):
Figure 3-28 – Occupied Mode Icon on Display
30 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.5.8. Manual Override
Generating an override: When the thermostat is under scheduled operation, the user can make a manual override (by the GUI) by modifying one of the following parameters: 1. Setpoint heat (occupied or unoccupied according to the active occupancy mode). 2. Setpoint cool (occupied or unoccupied according to the active occupancy mode). 3. Thermostat mode The word “override” appears on the left-lower corner of the screen. See Figure 3-29:
Figure 3-29 – Manual Override on Display
When at least one parameter is overridden, the following parameters cannot be
modified by the BMS: 1. Setpoint heat occupied. 2. Setpoint heat unoccupied.
3. Setpoint cool occupied. 4. Setpoint cool unoccupied. 5. Thermostat mode. 6.
Occupancy mode.
Resetting the override: 1) For both BMS schedule and Backup schedule, users can reset the override by pressing the text “override” on the GUI. 2) BMS can reset the override through the thermostat application. The thermostat executes the command and resets the override. 3) Deactivating the schedule resets the override. Note that resetting the override is not possible if the HOLD mode is active (this applies for GUI and BMS).
Menus & Interface
Operation · 31
When the Backup schedule is active, override resets when the next event/period is reached (for example, the programmed schedule resumes).
Current values vs scheduled values: Scheduled values are those values that application reads from the memory and will be used according to the schedule. Override values are not stored in memory, and are used for certain periods according to the needs of the user. In all times, the Modbus registers hold the current values that are used by the thermostat.
Override status: BMS can read the OVERRIDE STATUS to verify if override is taking place or not. (This applies only for the BMS schedule). Intuitively, if BMS communicates with the thermostat, the Backup schedule is automatically inactive.
NOTE: When an override is taking place, it stays in the following conditions: 1) Override stays if BMS schedule becomes inactive and Backup schedule becomes active due to loss of communication between thermostat and BMS. 2) Override stays if Backup schedule becomes inactive and BMS schedule becomes active due to re-establishment of communication between thermostat and BMS. 3) In case of Backup schedule, override stays as long as Hold mode is active and the next event/period is reached (HOLD mode has been activated while override is taking place). 3.5.9. Screen Lock The touchscreen of the thermostat can be locked. Screen can be locked completely or partially. When the screen is completely locked, the user cannot modify any parameter on the screen. When the screen is partially locked, the user can only modify the setpoints and nothing else. The Screen Lock function can only be accessed remotely through the Modbus network interface. The Screen Lock options are: · Lock the screen completely · Lock the screen partially (can adjust temperature setpoints) · Unlock the screen
When the screen is completely locked, a lock icon will appear on the screen (see Figure 3-30). While the screen is partially locked, if something other than setpoints is touched or pressed, the lock icon will appear for short time (approximately one second) to indicate that the touched button is locked.
If communication with the BMS is lost while the screen is locked, the thermostat waits up to 10 minutes before auto-unlocking the screen (users have all-access). If communication between BMS and the thermostat is re- established, the BMS needs to send the lock request in order to lock the screen again.
32 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Figure 3-30 – Locked Screen with Lock Icon
3.6. Communication Network
3.6.1. RS-485 Serial Link The thermostat is equipped with a RS-485 serial data
link to communicate with the BMS. Communication with the Emerson Programmable
Touchscreen Thermostat is performed via the Modbus RTU protocol over the
RS-485 link. The Modbus network is used to read the status of the thermostat
and/or apply new settings to modify its operation. There are three (3)
switches (DIP switch) that allow enabling or disabling some termination and
bias resistors for the proper function of the RS-485 network (see Figure
3-31). These switches are located on top-right corner when the thermostat
enclosure is open.
Communication Network
Operation · 33
Figure 3-31 – Modbus RS-485 Network Configuration Switches
Switch #1: Pull-up resistor enable (PU+) This switch provides the ability to
add a pull-up resistor (510 Ohms) on the RS-485 network for bias purposes.
Normally, this switch is in the OFF position (no pull-up resistor on the
network). Switch #2: End of Line resistor enable (EOL) This switch provides
the ability to add a termination resistor (120 Ohms) on the RS-485 network for
termination purposes. If you do have a termination resistor elsewhere on your
network setup, put this switch in the OFF position. If you do not need a
termination resistor from the thermostat, put this switch in the ON position.
Switch #3: Pull-down resistor enable (PD-) This switch provides the ability to
add a pull-down resistor (510 Ohms) on the RS-485 network for bias purposes.
Normally, this switch is in the OFF position (no pull-down resistor on the
network.)
3.7. Power Outage
In case of a power outage, the last settings of the thermostat are kept in
volatile memory and retrieved upon power restore. The only exception not
stored in non-volatile memory is the Manual Override Mode (see Section 3.5.8.,
Manual Override). The thermostat is equipped with an RTC (Real-Time Clock)
device that is connected to a backup battery. This lithium coil cell battery
only maintains time and date in the unlikely event of a power outage. The
expected lifetime of the battery is seven (7) years.
34 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
3.8. Advanced Settings
3.8.1. Thermostat System Configuration
Default Value: IDLE The thermostat can control different types of HVAC
equipment, and is configured accordingly by the thermostat control
configuration. The supported types are Conventional Systems such as Rooftop
Units (RTU) and Heat-pump Systems (HP). To prevent any damage to the system
upon first boot-up sequence of the thermostat, once installed, the default
control configuration is IDLE, which means that all outputs are set in
floating state to prevent any equipment issue.
Stage
IDLE (Default)
Heat
1
–
Activated 2
–
Cool
1
–
Activated 2
–
Table 3-9 – Thermostat Configuration
RTU (Roof-Top Unit) Conventional
System W1 W1+W2 Y1 Y1+Y2
HP_O (Heat-pump)
Y1 Y1+Y2 Y1+O Y1+Y2+O
HP_B (Heat-pump)
Y1+B Y1+Y2+B Y1 Y1+Y2
Advanced Settings
Operation · 35
3.8.2. Thermostat Stage(s) Behavior Figure 3-32 below briefly describes the behavior of the thermostat according to the room temperature, setpoints, and stage(s) that is or are activated.
Figure 3-32 – Thermostat Behavior
CAUTION! The DEAD BAND MINIMUM, HYSTERESIS and STAGE DIFF parameters have
write access. A special precaution must be taken in this case because these
parameters are often linked together and some interference could occur if
those parameters are not set properly.
3.8.3. Input Settings There are 5 inputs terminal (IN1 to IN5) that can be
configured. Each input terminal has MODE, STATE and OFFSET Modbus parameters.
Also, IN1 has a supplementary WEIGHT Modbus parameter. These configuration
registers will affect the INPUT VALUE and CONTROL TEMPERATURE Modbus
registers.
Digital Thermistor 0-10V
INPUT INx MODES Local terminal connected to a digital switch. Local terminal connected to a thermistor. Local terminal connected to 0-10V voltage.
Table 3-10 – Input In Modes
Input modes are configured to the following settings and are read only.
IN1 = Thermistor (used for the Indoor temperature) IN2 = Thermistor (used for the Outdoor temperature) IN3 = Thermistor (used for the Supply Air temperature)
36 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
IN4 = 0-10V (Used for a Remote Humidity sensor) IN5 = Digital (used for a Fan proof input) Although the input can accept up to 10V voltage, the IN4 has been adapted for a 0-5V sensor. So, = 0%RH and 5V = 100%RH.
OFF LOCAL REMOTE
INPUT INx STATE The input is not used. The thermostat updates the INPUT VALUE (INx) with the value provided by the corresponding local INx terminal. The network updates the INPUT VALUE (INx) with the value provided by Modbus.
Table 3-11 – Input In State
INPUT INx OFFSET INPUT VALUE (INx)
CONTROL TEMPERATURE INPUT WEIGHT IN1 Table 3-12 – Input In State
INPUT INx STATE Offset added to the input terminal when the INx STATE is LOCAL. When the INx STATE is REMOTE, the OFFSET is not used. In LOCAL state, this is the corresponding terminal INx value with the applied offset. In REMOTE state, this is the value written by the Modbus network. CONTROL TEMPERATURE is updated according to a relationship between the thermostat internal temperature and the INPUT VALUE (IN1). The formula used to get the value is WEIGHT x IN1 + (1-WEIGHT) x Internal Temperature. This is used by the thermostat algorithm (stage, economizer, display). Value used in the CONTROL TEMPERATURE calculation.
3.8.4. Dehumidification Mode When DEHUMIDIFICATION MODE is set to ON, if the current humidity measure is equal or higher than the DEHUMIDIFICATION RH SETPOINT, the AUX output relay is activated. If the current humidity measure is lower than the DEHUMIDIFICATION RH SETPOINT, the AUX output relay is deactivated.
When the DEHUMIDIFICATION MODE is set to OFF, the AUX output relay is always deactivated.
NOTE: Note that there is no information on the status of the dehumidification
on the display. 3.8.5. Economizer Mode
The ECONOMIZER mode is used to cool the room with fresh outdoor air instead of
air cooled by the compressor when possible to save energy.
Advanced Settings
Operation · 37
To allow the Economizer mode to be activated, the following conditions must be
reached: · The ECONOMIZER ENABLE must be enabled. · The thermostat mode must
be AUTO or COOL. · The outdoor temperature (IN2) must be below the ECONOMIZER
CHANGEOVER SETPOINT value. · The outdoor temperature (IN2) must be below the
room temperature. · The Supply Air temperature (IN3) must be above the
ECONOMIZER
SUPPLY AIR TEMPERATURE SETPOINT value.
When the Economizer mode is activated, the FAN and ECO output relays are
energized until SET POINT COOL is reached.
Pre-occupancy Purge The pre-occupancy purge is used only when the schedule is
active. The thermostat energizes the FAN and ECO relay outputs a period of
time before a transition from unoccupied to occupied. This period is
determined by the ECO PRE-OCCUPANCY PURGE_PERIOD.
To allow the pre-occupancy purge to be activated, the following conditions
must be reached: · The ECONOMIZER ENABLE must be enabled. · The scheduler must
be enabled. · The ECO PRE-OCCUPANCY PURGE_PERIOD must be different than OFF.
NOTE: Note that there is no information on the status of the economizer on the
display. 3.8.6. Hold Mode Users can hold the following parameters and prevent
them from being changed on the screen or by the BMS:
Setpoint heat (occupied and unoccupied), set point cool (occupied and
unoccupied), thermostat mode, occupancy mode and fan mode. The HOLD function
can be activated only when the schedule is active. When HOLD function is
active, BMS cannot disable the schedule itself nor reset the override. The
HOLD function can be fixed for 1,2,3, or 4 hours.
To activate the HOLD mode:
1. Press the room temperature digits and the menu will be displayed. 2. Use
the arrows UP and DOWN to set the time of HOLD (Figure 3-33). 3. Press the
“Done” icon to confirm and exit.
38 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
4. In the main display, the word “HOLd” will be displayed on the upper-right
corner of the screen (replaces the time digits).
Figure 3-33 – Setting the Hold Function
Figure 3-34 – Hold Function When Activated
To deactivate the HOLD mode: 1. Press the room temperature digits, the Hold
menu will be displayed. 2. Use the DOWN arrow to set the time of HOLD to zero.
3. Press the “Done” icon to confirm and exit. 4. In the main display, the word
“HOLD” will disappear. The BMS can verify if HOLD mode is active or inactive.
Advanced Settings
Operation · 39
3.8.7. Internal Temperature Offset Default Value: 30.74°F (-0.7°C) Temperature
offset applied to the internal temperature measurement. 3.8.8. Delay Fan
Default Value: 60 seconds Time delay before stopping the fan after heating or
cooling stages turn off. 3.8.9. Temperature Filter Time (Sampling Rate)
Default Value: 60 seconds Temperature Filter Time is the time constant on the
temperature measurement. (Time base for the software sampling, with four (4)
samples required to get the filtered value).
3.8.10.Temperature Hysteresis Default Value: 33.8°F (1°C) Temperature
hysteresis is the temperature difference between activation and deactivation
of an output stage (either the cooling or heating) during normal operation.
3.8.11. Minimum Temperature Deadband (Read-Only) Default Value: 35.6°F (2°C)
Minimum temperature deadband between heat and cool setpoints. This deadband
feature prevents the thermostat to send heat and cool activation
simultaneously. When the temperature measurement of the room is within this
zone (between heat and cool setpoints), then no output stage is activated.
3.8.12. Temperature Minimum Setpoint Default Value: 59°F (15°C) Minimum
allowable temperature setpoint for a user.
NOTE: This parameter is set through network and is not accessible on the
display of the thermostat.
3.8.13. Temperature Maximum Setpoint Default Value: 77°F (25°C) Maximum
allowable temperature setpoint for a user.* 3.8.14. Temperature Stage
Difference Default Value: 33.8°F (1°C)
40 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Temperature difference between engagement of stage 1 and stage 2, for both
heating and cooling mode. 3.8.15. Compressor Min ON time
Default Value: 0 seconds Once activated by the thermostat algorithm, the
compressor output (Yx) will be kept activated for a minimum period equivalent
to Min ON time parameter. 3.8.16. Compressor Min OFF time
Default Value: 0 seconds Once deactivated by the thermostat algorithm, the
compressor output (Yx) will be kept deactivated for a minimum period
equivalent to Min OFF time parameter.
Advanced Settings
Operation · 41
4 Programmable Touchscreen Thermostat Setup for E2 and Site Supervisor
E2
4.1. New Installation of Description File to E2
4.1.1. Uploading the Touch_TStat Description File to E2 The Touchscreen
Thermostat requires adding a description file (P/N 527-0729) to E2. Contact
Customer Service to obtain this information:
Solutions.CustomerService@Emerson.com
NOTE: Ultrasite32 Software must be installed to perform a description file
upload.
1. Connect to E2 using UltraSite32 (refer to the UltraSite32 Manual P/N
026-1002).
2. Expand UltraSite to view Directory Level and Site Level see Figure 4-1. 3.
Right-click Site Level and click Connect. 4. Expand Site Level and locate the
E2 Unit where the Touch T-Stat.dsc will be
installed. 5. Right-click on the unit and select Upload Description File
Figure 4-1 – Upload Description File 42 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
6. Click Browse and select the appropriate description (.dsc) file for Touch
T-Stat.dsc from the computer and click Open
Figure 4-2 – E2 Description File Upload
7. Click Upload. A window will display that the description file was
successfully imported. Click OK. The description (dsc) file should appear in
the list.
8. Once completed, disconnect from the E2 and reboot the E2 controller –
either manually with the toggle switch or remotely through Terminal Mode.
NOTE: DO NOT omit the step of rebooting the controller.
New Installation of Description File to E2 Programmable Touchscreen Thermostat
Setup for E2 and Site Supervisor · 43
4.2. Device and COM Port Setup in E2
4.2.1. Modbus Device Setup
Figure 4-3 – E2 Network Connections
4.2.2. E2 COM Port Setup
1. Log into the E2 by pressing . 2. Press then , and to access General
controller Info. 3. Press twice to move to C3: Serial tab (Figure 4-4).
44 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
Figure 4-4 – C3: Serial Tab
4. Press the to select the Com Port that the device is wired to (COM2, COM4
or COM6).
5. Press for LOOK UP and select MODBUS-1, MODBUS-2 or MODBUS-3.
6. Press to set configuration.
7. Set the MODBUS connection as follows:
· Press to select options and press e to set the configuration.
Com Baud: 19.2 Kbaud > Com Data Size: 8 > Com Parity: None > Com Port Stop Bits: 1
· Press to set the configuration. 8. Press to save changes. 9. Press to return to the Home screen.
Device and COM Port Setup in E2Programmable Touchscreen Thermostat Setup for E2 and Site Supervisor · 45
4.3. Installing the Thermostat in E2
4.3.1. Installing the Thermostat Application
1. Press , , , to enter Connected I/O Boards and Controllers. 2. Press once
to move to C3: ECT tab. Highlight the application Tch T-Stat and
enter the desired number of devices under Quantity up to 6.
Figure 4-5 – C3: ECT Tab
4.3.2. Commissioning the Thermostat
1. Press , , , to enter the Network Summary screen.
2. Highlight the Tch T-Stat001 to be commissioned by pressing the down arrow
and then
3. A window with Select Network appears on the screen, select the Modbus
number
where you configured the device and press 4. Select the address for the device
and press . Default for the device is 1.
46 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
5. A window will appear. Press and a confirmation will show MODBUS Device
Address is set.
Figure 4-6 – Modbus Device Address is Set
NOTE: Refer to Section 3.2.1. to set the Device Address on the thermostat.
Site Supervisor
4.4. Device and COM Port Setup in Site Supervisor
4.4.1. Modbus Device Setup
Figure 4-7 – Modbus Device Setup for Site Supervisor
NOTE: The polarity of the MODBUS connection between Site Supervisor and
Touchscreen Thermostat is reversed.
Device and COM Port Setup in Site SupervisorProgrammable Touchscreen
Thermostat Setup for E2 and Site Supervisor · 47
4.4.2. Site Supervisor COM Port Setup 1. Click the Settings icon (the gear)
and select General System Properties.
Figure 4-8 – General System Properties
2. Select the Com Port the device is wired to (Com Port 1 – 4). 3. Select the
available Modbus (Modbus-01 – Modbus-04). 4. Set the Modbus connection as
follows:
Com Port Baud: 19.2 Kbaud > Com Port data size: 8 > Com Port Parity: None > Com Port Stop Bits: 1 5. Click Save to save the changes.
Figure 4-9 – Set Com Port Parameters 48 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
4.4.3. Adding the Touchscreen Thermostat Application in Site Supervisor 1.
Click the Control Inventory icon (the box) 2. Expand the HVAC category and go
to the Add Control drop-down list and select
Touch T-Stat.
Figure 4-10 – Add Controls
4.4.4. Installing and Commissioning the Touchscreen Thermostat 1. Click the
Port ID drop-down list to select Modbus assigned to the Com Port selected in
Section 4.4.3. 2. Click the Address drop-down list to select the Modbus
Address (default address is 1). 3. Click the Association drop-down list to
select the HVACZone to associate with the
thermostat. 4. Click Update to save settings.
Figure 4-11 – Setting Up the Thermostat Update
Device and COM Port Setup in Site SupervisorProgrammable Touchscreen
Thermostat Setup for E2 and Site Supervisor · 49
5. Wait a few seconds and the device should appear Online.
Figure 4-12 – Device is Online
50 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
5 Troubleshooting
In the unlikely occurrence of a problem with the thermostat, please try the
following suggestions. Most problems can usually be corrected promptly and
easily.
Problems Display is blank, corrupted or shows “E01” or “- -” Display shows
“Lo” Display shows “HI” Heating or cooling system does not respond
Modbus network does not respond
Suggestions
Make sure the operating conditions are within the specifications (temperature range and humidity range). > Open the thermostat enclosure as per Section 2.3., Thermostat Installation and wait 30 seconds prior to closing the enclosure. > Check the circuit breaker for 24VAC and reset if necessary. > Check the power switch at HVAC system and make sure it is ON.
Check that the room temperature is not under 0°C or 32°F.
Check that the room temperature is not above 50°C or 122°F.
Set Thermostat Mode to HEAT, and make sure the HEAT temperature setpoint is higher than the current room temperature. > Set Thermostat Mode to COOL, and make sure the COOL temperature setpoint is lower than the current room temperature. > Open the thermostat enclosure as per Section 2.3., Thermostat Installation and wait 30 seconds prior to closing the enclosure. > Check circuit breaker for 24VAC and reset if necessary. > Check the power switch at HVAC system and make sure it is ON. > Check that Rc terminal is properly connected to R terminal with shorting jumper wire.
Open the thermostat enclosure as per Section 2.3., Thermostat Installation and wait 30 seconds prior to closing the enclosure. > Check circuit breaker for 24VAC and reset if necessary. > Check the power switch at HVAC system and make sure it is ON. > Make sure that wirings are intact and properly connected to the terminal blocks. > Make sure that A- and B+ signal are properly connected and not inverted. > Check the configuration of DIP switches to match your network (PU+, EOL and PD-).
Table 5-1 – Thermostat Troubleshooting
If a problem is still present after the above suggestions, please contact Emerson Electronics and Solutions Technical Support 770-425-2724 or email ColdChain.TechnicalServices@Emerson.com.
Device and COM Port Setup in Site Supervisor
Troubleshooting · 51
6 Regulatory Information
· Non-safety Declaration: The thermostat does not exhibit any safety risk to
the user if the usage guidelines are followed. No safety function is present
in the thermostat.
· Power Supply Guidelines: The thermostat must be power supplied by an NEC
(National Electrical Code) Class II limited power 24VAC transformer
· FCC Compliant to CFR47, Part 15, Subpart B, Class B · Industry Canada (IC)
Compliant to ICES-003, Issue 6
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions: 1. This device may not cause harmful
interference, and 2. This device must accept any interference received,
including interference that may
cause undesired operation
CAUTION! Any changes or modifications not approved by Emerson can void the
user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures: · Reorient or relocate the receiving antenna. ·
Increase the separation between the equipment and receiver. · Connect the
equipment into an outlet on a circuit different from that to which
the receiver is connected. · Consult the dealer or an experienced radio/TV
technician for help. This Class B digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment regulations.
52 · Emerson Programmable Touchscreen Thermostat I&O Manual
026-1739 Rev 2
CALIFORNIA PROPOSITION 65 This product can expose you to chemicals including
lead, which are known by the State of California to cause cancer and birth
defects or other reproductive harm.
For more information, go to www.P65Warnings.ca.gov Failure to follow these
instructions can result in birth defects or other
reproductive harm.
For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>