Adjusment principle of KV

The adjustment of the desired flow should be using the embedded tool that displays the 12 adjustment positions. Turn the tool with a screwdriver as shown in the diagram below. Place the number corresponding to the desired forfeit opposite the indentation on this hat

Nominal level setting

COMAP Autobalancing Thermostatic Radiator Valve Autosar
3

  • Close the valve completely and mark it with one position.
  • Open and count 6 marks. The valve is now open at nominal opening.
  • To install thermostatic head, remove the plastic cap.
  • Put the thermostatic head in position 5, firmly push the head on the faucet and screw in hand tight.