Altronix AL600UL3X Triple Output Power Supply-Charger Installation Guide

June 4, 2024
Altronix

Altronix-logo

Altronix AL600UL3X Triple Output Power Supply-Charger

Overview:
Altronix AL600UL3/AL600UL3X Triple Output Power Supply/Charger is specifically designed for use with access control and fire-protective signaling systems and accessories. AL600UL3/AL600UL3X converts a 115VAC 60Hz input into three (3) outputs (see specifications).

Features:

Agency Listings:

  • UL Listed:
    UL294 Access Control Systems
    UL1481 Power Supplies for Fire
    Protective Signaling Systems.

  • cUL Listed:
    CSA Standard C22.2 No.205-M1983,
    Signal Equipment.

  • MEA – NYC Department of Buildings Approved.

  • CSFM – California State Fire Marshal Approved.

  • NFPA 72 Compliant
    (Fire-Protective Signaling Service).
    Input:

  • Input 115VAC, 60Hz, 3.5A.

  • Input fuse rated @ 5A/250V.
    Output:

  • Class 2 Rated power-limited outputs
    (5VDC and 12VDC only).

  • 1.75A continuous supply current at 5VDC.

  • 1.75A continuous supply current at 12VDC.

  • 3A continuous supply current at 24VDC.

  • 100 mV p/p output ripple.

  • Filtered and electronically regulated output(s).

  • Short circuit and thermal overload protection.
    LED Indicators:

  • AC input, DC output and Battery LED indicators.
    Battery Backup:

  • Built-in charger for sealed lead acid or gel type batteries.

  • Automatic switch over to stand-by battery when AC fails.

  • Maximum charge current 0.7A.

  • Zero voltage drop when switched over to battery backup.
    Supervision:

  • AC fail supervision (form “C” contacts).

  • Low battery and battery presence supervision (form “C” contacts).
    Additional Features:

  • Power supply, enclosure, cam lock and battery leads.
    Enclosure Dimensions (H x W x D):
    AL600UL3:
    13.5” x 13” x 3.25”
    (342.9mm x 330.2mm x 82.6mm).
    Accommodates up to two (2)
    12VDC/7AH batteries.
    AL600UL3X:
    15.5” x 12” x 4.5”
    (393.7mm x 304.8mm x 114.3mm).
    Accommodates up to two (2)
    12VDC/12AH batteries.

*Access Control Performance Levels: Destructive Attack – I; Endurance – IV; Line Security – I; Stand-by Power – IV.

Stand-by Specifications

(Current is specified on AL3XB input):

Output| 4 hr. of Stand-by and 5 Minutes of Alarm| 24 hr. of Stand-by and 5 Minutes of Alarm| 60 hr. of Stand-by and 5 Minutes of Alarm
---|---|---|---


24VDC / 40AH Battery

| 5VDC – 1.75A| 5VDC – 0.3A| 5VDC – 0.1A
12VDC – 1.75A| 12VDC – 0.3A| 12VDC – 0.1A
24VDC – 3A| 24VDC – 0.3A| 24VDC – 0.1A

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

  1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 7-8). Secure enclosure to earth ground.
    It is recommended to first review the following tables for screw terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up.
    Carefully review:

    • Stand-by Specifications (pg. 2)
    • LED Diagnostics (pg. 4)
    • Terminal Identification Table (pg. 4)
  2. Connect AC power (115VAC 60Hz) to the terminals marked [L, N] (Fig. 1, pg. 5). Green “AC” LED on power supply board will turn on. This light can be seen through the LED lens on the door of the enclosure. Secure green wire lead to earth ground.
    Use 18 AWG or larger for all power connections (Battery, DC output).
    Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
    Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
    For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 6).

  3. Measure output voltage before connecting devices. This helps avoiding potential damage.

  4. Connect devices to be powered at 5VDC to the terminals marked [+ 5VDC –].

  5. Connect devices to be powered at 12VDC to the terminals marked [+ 12VDC –].

  6. Connect devices to be powered at 24VDC to the terminals marked [+ 24VDC –].

  7. Connect two (2) 12V Stand-by batteries.
    Note: For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type if used. Use two (2) 12V stand-by batteries connected in series to the terminals marked [+ BAT –] (Fig. 1 , pg. 5).

  8. It is required to connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] (Fig. 1b, pg. 5).
    Use 22 AWG to 18 AWG for AC Fail and Low Battery reporting. AC Failure will report in 5 minutes.
    Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper (Fig. 1a, pg. 5).

  9. Please ensure that the cover is secured with the provided key lock.

Wiring: Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

  • Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper
    voltage level (refer to Power Supply Voltage Output Specifications chart).

  • Battery Test: Under normal load conditions check that the battery is fully charged, check specified
    voltage both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires.
    Note: Maximum charging current under discharge is 0.7A.
    Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

AL600ULXB – Power Supply

Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat) Battery Status
--- ---
ON Normal operating condition.
OFF Battery fail/low battery.

Terminal Identification:

AL600ULXB – Power Supply

Terminal Legend Function/Description
L, N 115VAC, 60Hz
+ DC – 24VDC @ 6A total continuous output (supplies power to ALX3B).
AC Fail NC, C, NO Indicates loss of AC power, e.g. connect to audible device

or alarm panel.

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.

Bat Fail NC, C, NO| Indicates low battery condition, e.g. no battery presence.

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. Low battery threshold: 24VDC. Output threshold is set approximately @ 21VDC

+ BAT –| Stand-by battery connections. Maximum charge current 0.7A.

ALX3B – Power Output Module

Terminal Legend Function/Description
+ INPUT – 24VDC from power supply (AL600ULXB).
+ 24VDC – 24VDC @ 3A continuous power-limited output
+ 12VDC – 12VDC @ 1.75A continuous power-limited output.
+ 5VDC – 5VDC @ 1.75A continuous power-limited output.

Fig. 1 – AL600UL3
CAUTION: De-energize unit prior to servicing.
For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating.
Do not expose to rain or moisture. Altronix-AL600UL3X-Triple-Output-Power-
Supply-Charger-fig-1

Appendix A – UL Listed Compatible Devices

A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with AL600UL3/AL600UL3X output.

System Sensor Smoke Detector/Base| Detector Type| Max Stand-by Current (mA)| Alarm Current (mA)
---|---|---|---
B112LP| Base| 0.12| 36
B114LP| Base| |
B404B| Base| |
DH100ACDC| Photoelectric| 0.15| 0.70
DH100ACDCLP| Photoelectric| 0.15| 0.70
DH100ACDCLPW| Photoelectric| 0.15| 0.70
DH400ACDCI| Ionization Duct| 25| 95
DH400ACDCP| Photoelectric Duct| 25| 95
1112/24/D| Ionization| 0.05| 50
1424| Ionization| 0.10| 41
1451 (w/B402B Base)| Ionization| 0.10| 39
2112/24ATR| Photoelectric| 0.50| 60/70
2112/24AITR| Photoelectric| 0.50| 60/70
2112/24/D| Photoelectric| 0.05| 50
2112/24T/D| Photoelectric w/135o Thermal| 0.05| 50
2112/24TSRB| Photoelectric w/135o Thermal Supervisory Relay| 15| 45
2312/24TB| Photoelectric| 0.12| 50
2412 (12 volt)| Photoelectric| 0.12| 77
2424| Photoelectric| 0.10| 41
2451| Photoelectric| 0.10| 39
2451TH (with/B402B Base)| Photoelectric| 0.10| 39
2W-MOD| Loop Test/Maintenance Mod.| 30| 50
4W-B (12/24 volt)| Photoelectric I3| 0.05| 23
4WT-B (12/24 volt)| Photoelectric I3 w/Therm| 0.05| 23
4WTA-B (12/24 volt)| I3 Photo w/Therm/Sounder| 0.05| 35
4WTR-B (12/24 volt)| I3 Photo w/Therm/Relay| 0.05| 35
4WITAR-B (12/24 volt)| I3 Photo w/Isolated Therm/Sounder/Relay| 0.05| 50
2W-MOD2| I3 Loop Test/Maintenance Mod.| 0.05|
RRS-MOD| I3 Reversing Relay/Sync Module| 0.05|

6424| Projected Beam| 10| 28.4
Beam 1224(S)| Projected Beam| 17| 38.5

A.2 Relays
Table A-2 below lists relays compatible with AL600UL3/AL600UL3X output.

Manufacturer Model Current (mA)
  PR-1 15
  PR-2 30
System Sensor PR-3 EOLR-1 30

30

 | R-10T| 23
 | R-14T| 23
Manufacturer| Model| Current (mA)
---|---|---
 | R-20T| 40
 | R-24T| 40
System Sensor| R-10E R-14E| 23

23

 | R-20E| 40
 | R-24E| 40

Enclosure Dimensions (BC300): AL600UL3Altronix-AL600UL3X-Triple-Output-
Power-Supply-Charger-fig-2

Enclosure Dimensions (BC400): AL600UL3X Altronix-AL600UL3X-Triple-
Output-Power-Supply-Charger-fig-3

Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIAL600UL3/AL600UL3X

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Altronix User Manuals

Related Manuals