Braeburn Non-Programmable Thermostat 1025NC User Guide
- June 6, 2024
- Braeburn
Table of Contents
Braeburn Non-Programmable Thermostat 1025NC User Guide
View all Braeburn thermostat manual
NOTE: The reset button should be pressed after making any changes to the installer switches
Warning Turn off power to the heating equipment before installation.
Attention For installation by experienced service technicians only.
Read all instructions before proceeding.
This thermostat requires 24 Volt AC Power or two (2) properly installed “AA”
Alkaline batteries for proper operation. When connecting 24 Volt AC Power the
batteries may be installed as a backup. For use only as described in this
manual. Any other use will void warranty.
Specifications
This thermostat is compatible with:
- Single stage heat only systems
- 250 – 750 millivolt heat only systems
- 2 or 3 wire hydronic zone systems
Electrical and control specifications:
- Electrical Rating: 24 Volt AC
- 1 amp maximum load per terminal
- AC Power: 18 – 30 Volts AC
- DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included)
- Control Range: 45° – 90° F (7° – 32° C)
- Temperature Accuracy: +/- 1° F (+/- .5° C)
Terminations
- 1025NC – R, G, W1, V3, C
About Your Thermostat
1
| Room Temperature| Displays the current room temperature
---|---|---
2| Reset Button.|
Resets thermostat back to factory defaults
3
| Low Battery Indicator| Indicates when the batteries need to be
replaced
4| System Switch|
Selects heat on or off
5
| Quick Reference Instructions| Stored in slot at top of thermostat
6| Fan Indicator|
.Indicates when the system fan is running
7
| System Status Indicator| .Displays information about the status of
the system
8| Arrow Buttons|
Used to increase or decrease settings
9
| Set Temperature| .Displays the current set point temperature
10| Fan Switch
|
Selects the system fan mode
| Battery Compartment|
.Located in the back of the thermostat
Warning Disconnect power before beginning installation.
Installation
Thermostat Location
Install the thermostat approximately 5 feet (1.5m) above the floor in an area
that has a good amount of air circulation and maintains an average room
temperature.
Avoid installation in locations where the thermostat can be affected by
drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed
pipes, chimneys and outside walls.
Install your new Braeburn thermostat in 5 basic steps:
- Install the Sub-Base
- Provide Power
- Connect Your Wires
- Set Installer Switches
- Attach Thermostat to Sub-Base
Install the Sub-Base
-
Remove the sub-base from the body of the thermostat.
-
Mount the sub-base as shown below:
Drill 3/16” pilot holes in your desired location. Use supplied anchors for drywall or plaster.
NOTE: After sub-base installation, you may insert the quick reference card into the slot on the top of the base.
Provide Power
- For 24 Volt AC power, you must connect the common side of the transformer to the C terminal on the thermostat sub-base.
- For primary or back-up power, insert the 2 supplied “AA” type alkaline batteries into the battery compartment located in the rear housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the batteries correctly with the +/- symbols in the battery compartment.
Connect Your Wires
Wiring Terminations
Terminal
| Function| Description
---|---|---
R| Input|
Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source)
G
| Output| Fan Control
W1| Output|
Conventional Heat Control
V3
| Output| Zone Valve Power Close
C| Input|
24 Volt AC Transformer Common
Conventional Systems
Typical Wiring Configurations
Heat Only or Millivolt
R
| Power Connection
---|---
W1|
Heat Relay
G
| Fan Control [note 3]
C|
24 Volt AC Transformer Common [note 2]
Wire Hydronic Zone Valve
R
| Power Connection
---|---
W1|
Zone Valve Power Open
V3
| Zone Valve Power Close [note 1]
G|
Fan Control [note 3]
C
|
24 Volt AC Transformer Common [note 2]
NOTES – Conventional Systems
- For a 2-wire zone valve you will not connect V3
- If batteries are installed, the 24 Volt AC common connection is optional
- If needed for system
Provide disconnect and overload protection as required.
Set Installer Switches
Switch F / C| Factory
Default
F| Setting Options
F| Comments
Select for fahrenheit temperature scale
---|---|---|---
C| Select for celsius temperature scale
HE / HG| HG| HG| Select for gas heat or hydronic systems
without fan
HE| Select for electric heat or hydronic systems with fan
NOTE: The reset button should be pressed after making any changes to the installer switches.
Attach Thermostat to Sub-Base
- Line up the thermostat body with the sub-base.
- Carefully push the thermostat body against the sub-base until it snaps into place.
- Insert quick reference card into slot on top of thermostat.
System Testing
Warning Read Before Testing
- Do not short (or jumper) across terminals on the gas valve or at the system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
- Move the SYSTEM switch to ON mode.
- Press to raise the set temperature a minimum of 3 degrees above the current room temperature. The system should start within a few seconds. With a gas heating system, the fan may not start right away.
- Move the SYSTEM switch to the OFF mode. Allow the heating system to fully shut down.
- Move the FAN switch to the ON mode. The system fan should start (on systems where a fan is installed) within a few seconds.
- Move the FAN switch to the AUTO mode. Allow the system fan to turn off.
Setting User Options
Advanced User Options
User options allow you to customize some of your thermostats features.
The default user options are compatible with most applications, therefore it
is not required that you adjust them.
To access the User Options menu, hold down both the and buttons for approximately 3 seconds until the screen changes and displays the User Option.
Press the or button to change the setting for the displayed User Option. After you have made your desired setting, press and together to return to the normal mode.
The thermostat will also return to normal mode after your last user option is made or after no keys have been pressed for 15 seconds.
Table of User Options
No.
| User Options| Factory Default| Setting Options| ****
Comments
---|---|---|---|---
1| 1st stage differential| 0.5| 0.5, 1.0
or 2.0
|
Select a 1st stage temperature differential of .5˚, 1˚ or 2˚F (.25˚, 5˚ or 2˚C)
Detailed Explanation of User Options:
Temperature Differential
The differential setting is the temperature control range that your thermostat
will provide. The smaller the setting, the tighter your range of temperature
control and comfort will be.
Operating Your Thermostat
Setting the System Control Mode
- OFF Heating system is off..
- HEAT Your heating system will operate.
Setting the Fan Control Mode
The Fan Control has 2 modes of operation – AUTO
and ON. The mode can be selected by moving the
FAN switch to the appropriate position.
- AUTO The fan will run when required by the system.
- ON The fan will run continually.
NOTE: Some system types do not have a fan control mode.
Temperature Adjustment
Press the or button to adjust the current set point temperature.
Status Indicators
Status indicators appear in the display to let you know if your system is on
or off.
- HEAT ON Indicates your heating system is running.
Resetting the Thermostat
This thermostat provides you with a reset button that will erase all of your
user settings.
To reset the thermostat, use a small object such as a tooth pick or paperclip
and gently press the button located inside the small hole on the front of the
thermostat housing labeled “reset”.
Thermostat Maintenance
Changing the Batteries
Depending on your particular installation, this
thermostat may be equipped with two (2) “AA”
type alkaline batteries.
If batteries are installed and they become low, a low battery indicator will
appear in the display.
You should change your batteries immediately when you see the low battery
signal by following these instructions.
NOTE: We recommend replacing the thermostat batteries annually or if the thermostat will be unattended for an extended period of time.
- Remove thermostat body by gently pulling it from base.
- Remove old batteries and replace with new batteries.
- Make sure to correctly position the (+) and (-) symbols.
- Gently push thermostat body back onto base.
Thermostat Cleaning
Never spray any liquid directly on the thermostat. Using a soft damp cloth
wipe the outer body of the thermostat. Never use any abrasive cleansers to
clean your thermostat.
For troubleshooting tips, visitbraeburnonline.com.
Limited Warranty
When installed by a professional contractor, this product is backed by a 5 year limited warranty. Limitations apply. For limitations, terms and conditions, you may obtain a full copy of this warranty:
- Visit us online: www.braeburnonline.com/warranty
- Phone us: 866.268.5599
- Write us: Braeburn Systems LLC
2215 Cornell Avenue
Montgomery, IL 60538
Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599
(U.S.)
630-844-1968 (Outside the U.S.)
©2020 Braeburn Systems LLC • All Rights Reserved.