victron energy Skylla-IP65 24/35(3) 120-240V | Battle Born Batteries
Safety Instructions
General
-
Please read the documentation supplied with this product first, so that you are familiar with the safety signs and directions before using the product.
-
This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only.
danger of electric shock -
The product is used in combination with a permanent energy source (battery). Even if the equipment is switched off, a dangerous electrical voltage may still be present at the input and/or output terminals. Always disconnect the AC power and the battery before performing maintenance.
-
The product contains no internal user-serviceable parts. Do not remove the front panel unless the mains and the battery are disconnected. Do not put the product into operation unless all panels are fitted. All maintenance should be performed by qualified personnel.
-
Never use the product at sites where gas or dust explosions could occur. Refer to the specifications provided by the manufacturer of the battery to ensure that the battery is suitable for use with this product. The battery manufacturer’s safety instructions should always be observed.
do not lift heavy objects unassisted
Installation
- Read the installation instructions before commencing installation activities.
- This product is a safety class I device (supplied with a ground terminal for safety purposes). Its AC input and/or output terminals must be provided with uninterruptible grounding for safety purposes. An additional grounding point is located on the outside of the product. If it can be assumed that the grounding protection is damaged, the product should be taken out of operation and prevented from accidentally being put into operation again; contact qualified maintenance personnel.
- Ensure that the connection cables are provided with fuses and circuit breakers. Never replace a protective device by a component of a different type. Refer to the manual for the correct part.
- Check before switching the device on whether the available voltage source conforms to the configuration settings of the product as described in the manual.
- Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet or dusty environment.
- Ensure that there is always sufficient free space around the product for ventilation, and that ventilation openings are not blocked.
- Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts, curtains or other textiles, etc. in the immediate vicinity of the equipment.
- 1.3. Transport and storage
- During storage or transport of the product, ensure that the mains supply and battery cables are disconnected.
- No liability can be accepted for damage in transit if the equipment is not transported in its original packaging.
- Store the product in a dry environment; the storage temperature should range from 20°C to 60°C.
- Refer to the battery manufacturer’s manual for information on transport, storage, charging, recharging and disposal of the battery.
Installation and wiring
Installation
Find a dry and well-ventilated area to mount the Skylla-IP65 charger and
battery. Keep the cable length between the charger and the battery less than 6
meters.
The charger may be wall or floor mounted. Always make sure that air may flow
freely at the back side of the cabinet. This will improve cooling of the
charger and prolong lifetime.
Wall mounting
The unit can best be mounted vertical to a wall. See appendix for exact
positions of the mounting holes.
Wiring
The inlets for the mains cable, the battery cables, the remote functions and
the connection to attach the earth cable are located at the bottom of the
housing; see markings on the front panel.
For best protection against water and dust from entering the case, all
openings in the grey terminal block should be closed, either with a suitable
cable or, when no connection is used, a dummy piece of cable.
Connecting earth Connect the earth point to the installation earth.
Connections to earth have to be according to applicable safety standards. · On
a ship: connect to the earth plate or to the hull of the ship.
- On land: connect to the earth of the mains. The connection to the earth of the mains has to be according to applicable safety standards.
- Mobile applications (a vehicle, a car or a caravan): Connect to the frame of the vehicle.
The battery connections of the charger are fully floating with respect to this grounding point
Connecting the main battery
Before the main battery is connected to the charger, make sure the charger is
set to the correct battery type. Minimum cable cross section between main
battery and charger:
Skylla-IP65 type| cable length up to 1.5 m| cable length 1.5 m –
6 m
---|---|---
12/70| 10 mm2| 16 mm2
24/35| 6 mm2| 10 mm2
The largest possible cable lug that will fit through the battery cable glands is size S6-16. That cable lug will suit a maximum cable diameter of 16 mm2 and fit on an M6 bolt.
Main battery connection sequence
The Skylla-IP65 is NOT protected against reverse polarity of the main battery.
(“+” connected to “-” and “-” connected to “+”). Follow the installation
procedure. The warranty expires when the Skylla-IP65 becomes defective due to
reverse polarity.
Disconnect the mains supply before making or breaking connections to the main
battery.
- Disconnect the mains supply
- Disconnect battery cables from the battery.
- Remove the grey cover in the front panel of the charger, enabling access to the terminals.
- Connect battery cables to the charger: plus (red) to “+BAT1”; minus (black) to “-BAT”
- Connect battery cables to the battery: plus (red) to positive pole, minus (black) to negative pole.
- Connect the mains supply.
Main battery disconnection sequence
When disconnecting the battery cables, be very careful not to accidentally
short circuit the battery.
- Disconnect the mains supply.
- Disconnect battery cables from the battery.
- Remove the grey cover in the front panel of the charger, enabling access to the terminals.
- Disconnect the battery-cables from the charger.
- Disconnect all other cables like temperature sensor and/or voltage sensor used with this particular battery.
Connecting the starter battery
The Skylla-IP65 is NOT protected against reverse polarity of the starter
battery. (“+” connected to “-” and “-” connected to “+”). Follow the
installation procedure. The warranty expires when the Skylla-IP65 becomes
defective due to reverse polarity. Disconnect the mains supply before making
or breaking connections to the main battery. The starter battery has to be
connected using wire of at least 1.5 mm2 (max. 6 mm2 ). Connect the positive
(+) battery-pole to the “Starter battery plus” connector, see Figure 1. The
negative pole of the starter battery has to be connected to the “-BAT”
connection of the charger. The starter battery can draw current from the
battery connected to the main battery terminals in case the voltage of the
starter battery is lower than the voltage main battery. However, the main
battery cannot draw current from the starter battery even when the starter
battery is fully charged and the main battery is at minimum charge level.
VE.Can connection
The two VE.Can connectors provide access for parallel synchronised parallel
operation and remote control.
Synchronised parallel operation
Several charge controllers can be synchronized with the CAN interface to a
maximum of 10 chargers. This is achieved by simply interconnecting the
chargers with RJ45 UTP cables (bus terminators needed. The paralleled charge
controllers must have identical settings (e.g. charge algorithm). The CAN
communication ensures that the controllers will switch simultaneously from one
charge state to another (from bulk charge to absorption for example).The
output current of one charger may differ from another charger although
connected in parallel.In case of using remote sensors (voltage and/or
temperature), the remote sensor needs to be connected to one of the parallel
operating chargers. All other chargers will share the information via the CAN
interface. In case of synchronised parallel operation, the network icon will
blink every 3 seconds on all paralleled units.
Input/shore current limit
The AC input current limit of each charger is set to 10,5 A max and can be
adjusted with a CCGX device, NMEA 2000 or a Skylla-i-control GX remote panel.
See https://www.victronenergy.com/panel-systems-remote-monitoring/skylla-i
-control-gx The input power of one charger will never be more than 1050 W.
This means that at 100V AC in the input current is max 10,5 A, and at 230V AC
the maximum input current is 4,5 A. The input current limit of a parallel
charger group can be set with a CCGX device or with a Skylla-i-control GX
remote panel. The current limit as shown on the device is the shore current of
the group.
User relay, external sense and remote shut down
The wiring of these signals must be done with the mains disconnected from the
charger.
Figure 1 Connectors for external voltage/temperature sensing, Rem. Shut down, VE.Can bus and Starter battery.
External voltage sense
External voltage sensing may be used when accurate battery voltage sensing is
important, such as high charging currents in combination with long cables. To
connect the external voltage sensing option, proceed as follows: · connect a
red wire (0.75 mm2 ) between the positive battery terminal and connector “+
Volt. sense” · connect a black wire (0.75 mm2 ) between the negative battery
terminal and connector “- Volt. sense”
External temperature sense
The external temperature sensor, supplied with the charger, can be connected
to these terminals in order to perform temperature compensated charging of the
battery. The sensor is electrically isolated and must be connected to the
positive or negative pole of the battery. To connect the temperature sensor,
proceed as follows:
- connect the red wire to connector “+ Temp. sense”
- connect the black wire to connector “
- Temp. sense” – mount the temperature sensor on the positive or negative pole of the battery
- check in the menu for the actual temperature
Remote shut down
From factory the remote + and – are connected together with a jumper wire to
turn the charger on. In order to use the remote to shutdown the charger,
remove the jumper and connect a wire to “remote -” input. Switching the
“remote -” input to battery voltage causes the charger to turn on. This wire
can be used to connect to a BMS used for lithium batteries to control the
charger.
User relay connections
The user relay is triggered by a battery under-voltage situation (<11.8 V).
The function may be used for any desirable action: starting a generator,
sounding an alarm etc. The ratings of the relay can be found in the
specification.
Table 1. Relay modes
# | Description | Setup Menu # |
---|---|---|
0 | Skylla-i behaviour: on when charging (no error condition) and battery | |
voltage between low and high voltage settings | 12,13,14 and 15 | |
1 | Always off | |
2 | Temperature high > 85 ⁰C) | 12 and 13 |
3 | Battery voltage too low | |
4 | Equalization active | |
5 | Error condition present | |
6 | Temperature low (< -20 ⁰C) | |
7 | Battery voltage too high | 14 and 15 |
8 | Charger in float or storage |
ON OFF
: CM connected to NO
: CM connected to NC
Connecting the mains
- Check if the battery is connected to the charger.
- Remove the grey cover in the front panel of the charger, to access the AC input connector, see Figure 2.
- Connect the mains earth cable (green/yellow) to the AC input connector, terminal .
- Connect the mains neutral cable (blue) to the AC input connector terminal N.
- Connect the mains line cable (brown) to the AC input connector terminal L.
Control and Adjustment
When the charger is installed correctly, the charger should be set up to suit the battery connected. To set up the charger, apply mains power and enter the setup menu by pressing “SETUP” for three seconds. The charger will enter a standby mode (no power applied to the battery terminals) and the user can set up the unit accordingly. See the next table for all possible adjustments.
Monitor menu
The monitor menu is visible when power is applied to the charger.
The following table shows the consecutive lines when scrolling through the menu with the up/down keys:
- A valid temperature is shown. ” — ” means no sensor information or “Err” means invalid sensor data.
- The output channel number is shown in the first segment; only visible in a three output model.
- These items are only visible when relevant.
- After a short delay a scrolling text is shown with the error description.
- With the up/down keys the user can scroll through the monitor menu. Holding either up or down for three seconds will start the auto scrolling mode: all Monitor menu items will be shown for 5 seconds. The auto scroll mode can be exit by pressing up or down once.
Setup menu
The setup menu can be entered by pressing “SETUP” during three seconds.
After entering the setup menu, the user can scroll through the menu with the up/down keys. With select a menu item is entered and the present value is shown. With the up/down keys the user can scroll through the available modes or increase/decrease the value. By pressing select again the value/item is set. Pressing setup shortly will return to the setup menu. When setup is completed, exit the menu by pressing “SETUP” again three seconds.
Battery selection
The charge algorithm of the charger must fit the battery type connected to the
charger. The following table shows all the predefined battery types available
in the charge algorithm selection menu.
Power supply mode
The charger can be set to operate as a DC power supply. In this mode, the
charger functions as a constant voltage source: 1. an adjustable output
voltage of 8.0 to 15.9 V (12 V type) resp. 16.0 to 31.8 Volt (24 V type) 2. a
maximum output current of 60A (12 V type) resp. 30A (24 V type).
Temperature compensation (dV/dT)
The temperature sensor should be connected to the plus or negative pole of the
battery. The temperature compensation is a fixed setting, see table and fig.
4, and applies to all charge states. The temperature sensor must be installed
when:
- ambient temperature of the battery is expected to regularly be lower than 15 °C or to regularly exceed 30 °C
- charge current exceeds 15 A per 100 Ah battery capacity Temperature compensation is not required for Li-Ion batteries.
Power Control maximum use of limited shore current
A maximum mains current can be set in order to avoid interruption of an
external fuse in the mains supply.
Operation
Battery charging
After applying mains power and remote shut down is not active, the display
will show the following: All icons of the screen will be visible to check the
correct functioning of the display.
- The back lighting of the display is ON.
- Next the firmware version number will be displayed.
- Finally, the actual state is displayed on the screen:
- By using Voltage sensing, the actual battery voltage is shown.
When the mains plug is blinking, the mains voltage is below normal and the charger is reducing the maximum charge current. By using Voltage sensing, the actual battery voltage is shown.
Seven stage charge curve for lead-acid batteries
Figure 3 Voltage and current during different states in battery charging.
Bulk
Entered when the charger is started or when the battery voltage falls below
13.2 V / 26.4 V (due to a heavy load) during at least 1 minute. Constant
current is applied until gassing voltage is reached (14.4 V / 18.8 V).
Battery Safe
If absorption voltage is set higher than 14.4 V / 18.8 V, the rate of voltage
increase beyond 14.4 V / 18.8 V is limited to 7mV/14mV per minute, in order to
prevent excessive gassing.
Absorption
After the absorption voltage has been reached, the charger operates in
constant voltage mode. In case of adaptive charging, the absorption time is
dependent on the bulk time, see section 3.2.
Automatic equalization
If automatic equalization has been set to `on’, the absorption period is
followed by a second voltage limited constant current period: see section 3.3.
This feature will charge VRLA batteries to the full 100 %, and prevent
stratification of the electrolyte in flooded batteries. Alternatively, manual
equalization can be applied.
Float
After float charge the output voltage is reduced to storage level. This level
is not sufficient to compensate for slow self-discharge of the battery, but
will limit water loss and corrosion of the positive plates to a minimum when
the battery is not used.
Storage
After float charge the output voltage is reduced to storage level. This level
is not sufficient to compensate for slow self-discharge of the battery, but
will limit water loss and corrosion of the positive plates to a minimum when
the battery is not used.
Weekly battery `refresh’
Once a week the charger will enter Repeated Absorption-mode during one hour to
‘refresh’ (i. e. to fully charge) the battery
Four stage charge curve for Lithium Iron Phosphate (LiFePo4) batteries
Bulk
Entered when the charger is started, or when the battery voltage falls below
13,5 V / 27,0 V (due to a heavy load) during at least 1 minute. Constant
current is applied until absorption voltage is reached (14.2 V / 28.4 V).
Absorption
After the absorption voltage has been reached, the charger operates in
constant voltage mode. The recommended absorption time is 2 hours.
Storage
After absorption charge the output voltage is reduced to storage level. This
level is not sufficient to compensate for slow selfdischarge of the battery,
but will maximize service life.
Weekly battery `refresh’
Once a week the charger will enter Repeated Absorption-mode during one hour to
‘refresh’ (i. e. to fully charge) the battery.
Maintenance
This charger does not require any specific maintenance. However an annual check of the battery and mains connections is recommended. Keep the charger dry, clean and free of dust.
Troubleshooting
Problem | Possible cause | Solution |
---|---|---|
Charger does not function | The mains is not ok | Measure mains: 120 – 240 VAC |
Input or output fuses are defective | Return product to your dealer | |
The battery is not fully charged | A bad battery connection | Check battery |
connection
The wrong battery type has been selected in the menu.| Select correct battery
type in the menu.
Cable losses too high| Use cables with larger cross section.
Use external voltage sensing.
The battery is being overcharged| The wrong battery type has been selected in
the menu.| Select correct battery type in the menu.
A battery cell is defective.| Replace battery
Battery temperature too high| Overcharging or too fast charging| Connect
external temperature sensor
Error in display| See section 9| Check all charging equipment.
Check cables and connections.
Temperature Compensation
Specifications
Skylla-IP65 | 12/70 | 24/35 |
---|---|---|
Input voltage (VAC) | 120 – 240 | |
Input voltage range (VAC) (1) | 90 – 265 | |
Maximum AC input current | 12 | |
Frequency (Hz) | 45-65 | |
Power factor | 0,98 | |
Charge voltage ‘absorption’ (VDC) (2) | See table | See table |
Charge voltage ‘float’ (VDC) (2) | See table | See table |
Charge voltage ‘storage’ (VDC) (2) | See table | See table |
Charge current main batt. (A) (3) | 70 | 35 |
Charge current starter batt. (A) (4) | 3 | 4 |
Charge curve, lead-acid | 7 stage adaptive | |
Recommended battery capacity (Ah) | 350-700 | 150-350 |
Charge curve, Li-Ion | 2 stage, with on-off control or VE.Can bus control | |
Temperature sensor | Yes | |
Power supply function | Yes | |
Remote on-off port | Yes (can be connected to a Li-Ion BMS) | |
CAN bus communication port | Two RJ45 connectors, NMEA2000 protocol | |
Remote alarm relay | DPST AC rating: 240 VAC/4A DC rating: 4A up to 35 VDC, |
1 A up to 60 VDC
Forced cooling| Yes
Protection| Battery reverse polarity (fuse) Output short circuit Over
temperature
Operating temp. range| -20 to 60 °C (full output current up to 40 °C)
Humidity (non-condensing)| max 95 %
ENCLOSURE
Material & Colour| steel; blue, RAL 5012
Battery-connection| M6 bolts
Mains connection| screw-clamp 6 mm² (AWG 10)
Protection category| IP65
Weight kg (lbs)| 6 (14)
Dimensions hxwxd incl. glands in mm in inches| 401 x 265 x 151
(16 x 10.5 x 6)
STANDARDS
Safety| EN 60335-1, EN 60335-2-29
Emission| EN 55014-1, EN 61000-6-3, EN 61000-3-2
Immunity| EN 55014-2, EN 61000-6-1, EN 61000-6-2, EN 61000-3-3
-
Output current will gradually reduce below 110 3) Maximum current up to 40 °C (100 °F) ambient. Output current V to 50 % @ 100 V will reduce to 60 % at 50 °C, and to 40 % at 60 °C.
-
Depending upon battery type as selected in the 4) Depending upon state of charge of starter battery setup menu.
Skylla-IP65 Input voltage (VAC) Input voltage range (VAC) (1) Maximum AC input current Frequency (Hz) Power factor Charge voltage ‘absorption’ (VDC) (2) Charge voltage ‘float’ (VDC) (2) Charge voltage `storage’ (VDC) (2) Charge current main batt. (A) (3) Charge current starter batt. (A) (4) Charge curve, lead-acid Recommended battery capacity (Ah) Charge curve, Li-Ion Temperature sensor Power supply function Remote on-off port CAN bus communication port Remote alarm relay
Error Indicator
Error nr | Description | Possible cause | Solution |
---|---|---|---|
1 | battery temperature too high | Overcharging or fast charging | Check air flow |
near the battery Improve cooling of environment. The charger stops
automatically and will resume once the battery has cooled down
2| battery voltage too high| Wiring mistake, or another charger is over
charging| Check all charging equipment.
Check cables and connections
3, 4, 5| temp. sense error| Wiring mistake or temperature sensor broken| Check
the temperature sensor wiring and if that doesn’t help replace the temperature
sensor
6, 7, 8, 9| voltage sense error| Wiring mistake| Check the voltage sensor
wiring.
17| charger temperature too high| The heat generated by the charger cannot be
removed| Check air flow of the cabinet. Improve cooling of environment.
The charger stops automatically and will resume once the charger has cooled down.
18| Internal error| | Contact your dealer
20| charger bulk time expired| After 10 hours of bulk charging, the battery
voltage has still not reached the absorption voltage.| Possible cell failure
or higher charge current needed.
24| Fan failure| This error indicates that the fan is powered on but the
circuit does not measure any current draw by the fan. Most likely the fan is
either broken or obstructed.| Contact your dealer
34| Internal error| | Contact your dealer
37| No input voltage (only for the three output version)| Mains removed or ac-
input fuse blown| Check mains availability and fuse.
65| charger disappeared during operation| One of the other chargers with which
this charger was synchronizing has disappeared during operation| To clear the
error, switch the charger off and back on.
66| Incompatible device| The charger is being paralleled to another charger
that has different settings and/or a different charge algorithm| Make sure all
settings are the same and update firmware on all chargers to the latest
version.
67| BMS connection lost| Connection to the BMS lost| Check the VE.Can bus
cabling. When the charger needs to operate in standalone mode again, go to the
setup menu #31 (BMS Present) and set to N.
113, 114| Internal error| | Contact your dealer
115| | Communication error| Check wiring and terminators
116, 117,
118
| Internal error| | Contact your dealer
119| Settings invalid| | Restore defaults in the setup menu #62.