BYD CBH-40A Battery-Box Premium HVS/HVM Combiner Box Instruction Manual
- June 6, 2024
- BYD
Table of Contents
CBH-40A Battery-Box Premium HVS/HVM Combiner Box
Battery-Box Premium HVS/HVM Combiner Box Installation Manual
Model: CBH-40A
V1.2
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
BYD Smart Device Hungary Kft.
Legal Provisions
All the information in this document is the property of BYD Smart Device
Hungary Kft. No part of this document could be reproduced in any way for
business use. Internal use is allowed.
BYD Smart Device Hungary Kft. makes no representations or warranties express
or implied, with respect to this document, including (with no limitation) any
implied warranties of utility, merchantability, or fitness for any particular
purpose. All such representations or warranties are expressly disclaimed.
Neither BYD Smart Device Hungary Kft. nor its distributors or dealers shall be
liable for any indirect, incidental, or consequential damages under any
circumstances.
The exclusion of implied warranties may not apply in all cases under some
statutes, and thus the above exclusion may not apply.
This document does not replace and is not intended to replace any local,
state, provincial, federal, or national laws, regulations, or codes applicable
to the installation, electrical safety, and use of the battery system. BYD
Smart Device Hungary Kft. assumes no responsibility for the compliance or
noncompliance with such laws or codes in connection with the installation of
the battery system.
Specifications are subject to change without notice. Every effort has been
made to make this document complete, accurate, and up-to-date. However, BYD
Smart Device Hungary Kft. may need to make some improvements under certain
circumstances without advance notice. BYD Smart Device Hungary Kft. shall not
be responsible for any loss caused by this document, including, but not
limited to, omissions errors, typographical errors, arithmetical errors, or
listing errors in this document. All trademarks are recognized.
BYD Smart Device Hungary Kft.
H-2071 Páty, Szent József út 4.
Installation Manual V1.2
2
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
Content
Legal Provisions…………………………………………………………………………………………………………………………………………….2 1.
Information on this Document …………………………………………………………………………………………………………….5
1.1. Validity ………………………………………………………………………………………………………………………………………..5 1.2.
Target Group………………………………………………………………………………………………………………………………5 1.3. Symbols
………………………………………………………………………………………………………………………………………5 2. Safety
……………………………………………………………………………………………………………………………………………………..6 2.1. Intended
Use………………………………………………………………………………………………………………………………6 2.2. Instructions and
Warnings…………………………………………………………………………………………………………6 2.3. Position and securing
………………………………………………………………………………………………………………..6 2.4. Safety Precautions
……………………………………………………………………………………………………………………..6 3. Scope of delivery
…………………………………………………………………………………………………………………………………..8 4. Product Description
………………………………………………………………………………………………………………………………9 4.1. Circuit
Diagram…………………………………………………………………………………………………………………………..9 4.2. Type
Label…………………………………………………………………………………………………………………………………..9 4.3. Symbols on the
Type Label …………………………………………………………………………………………………….. 10 5.
Assembly……………………………………………………………………………………………………………………………………………….11 5.1. Wall
Mounting …………………………………………………………………………………………………………………………..11
5.1.1. Selecting the Mounting Location………………………………………………………………………………….11
5.1.2. Mounting the Combiner Box ………………………………………………………………………………………..11 6.
Electrical Connection ………………………………………………………………………………………………………………………….. 13 6.1.
Connection Instructions ………………………………………………………………………………………………………….. 13 6.1.1.
Preliminary Checks ……………………………………………………………………………………………………….. 13 6.1.2. Safety
during Electrical Connection ……………………………………………………………………………. 14 6.2. Inserting
the Cables into the Switch Cabinet ………………………………………………………………………… 14 6.2.1.
Bottom view of Combiner Box with cable glands ……………………………………………………… 14 6.2.2.
Overview of the Connection Area ………………………………………………………………………………. 15 6.3.
Leading the Cables through the Cable Glands with sealing Gasket
……………………………………. 15 6.4. Connecting the DC Cables
……………………………………………………………………………………………………… 16 6.5. Connecting the Grounding Cable
………………………………………………………………………………………….. 17 7. Maintenance
……………………………………………………………………………………………………………………………………….. 18 7.1. Periodic
Maintenance ……………………………………………………………………………………………………………… 18 7.2. Extraordinary
Maintenance …………………………………………………………………………………………………….. 18
3
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
BYD Smart Device Hungary Kft.
8. Decommissioning……………………………………………………………………………………………………………………………….. 19
8.1. Disassembling the Combiner Box ………………………………………………………………………………………….. 19
8.2. Disposing of the Combiner Box……………………………………………………………………………………………… 19
9. Technical Data……………………………………………………………………………………………………………………………………. 20
Contact Information …………………………………………………………………………………………………………………… 22
Installation Manual V1.2
4
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
1. Information on this Document
1.1. Validity
This document is valid for the Battery-Box Premium HVS/HVM Combiner Box CBH-
40A.
1.2. Target Group
The instructions in this document may only be performed by qualified persons
who must have the following skills: · Knowledge of how batteries work and are
operated · Knowledge of how an inverter works and is operated · Knowledge of,
and adherence to the locally applicable connection requirements, standards,
and directives · Knowledge of, and adherence to this document and the
associated system documentation, including all safety instructions · Training
in dealing with the hazards associated with the installation and operation of
electrical equipment and batteries · Training in the installation and
commissioning of electrical equipment
Failure to do so will make any manufacturer’s warranty, guarantee or liability
null, and void unless you can prove that the damage was not due to non-
compliance.
1.3. Symbols
Symbol
Explanation Indicates a hazardous situation which, if not avoided, will result
in death or serious injury Indicates a hazardous situation which, if not
avoided, can result in death or serious injury Indicates a hazardous situation
which, if not avoided, can result in minor or moderate injury Indicates a
situation which, if not avoided, can result in property damage
Packaging instructions
5
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
2. Safety
BYD Smart Device Hungary Kft.
2.1. Intended Use
2.2. Instructions and Warnings
Failure to follow these instructions may have serious consequences, such as the destruction of the device, personal injury or death due to electric shock. Therefore, the following safety instructions must be read and understood prior to installation and use of the Combiner Box. For any clarifications or additional information, contact the BYD local service.
Symbol
Explanation
Once the product has been removed from its original packaging, visually inspect for damage that may have occurred during shipment. If damage is found, contact the distributor or manufacturer.
This product must only be used for the purpose for which it has been designed. Any other use is considered improper and therefore dangerous. The manufacturer is not liable for possible damage caused by improper, incorrect or unreasonable use
BYD holds itself responsible only for the product in its original configuration. BYD declines all responsibility for consequences deriving from non-original spare parts.
Any intervention that alters the structure or the operating cycle of the product must be carried out or authorized by BYD Smart Device Hungary Kft.
This manual is an integral and essential part of the product. Carefully read the recommendations contained in it since they provide important information on safe use and maintenance.
BYD may make technical changes in this manual and to the product at any time without notice. In case of typing errors or other types of errors, the corrections will be included in the new versions of the manual.
2.3. Position and securing
Failure to follow these instructions may have serious consequences, such as the destruction of the device, personal injury or death due to electric shock. Therefore, the following safety instructions must be read and understood prior to installation and use of the Combiner Box. For any clarifications or additional information, contact BYD local service.
Symbol
Explanation
If positioning in a closed environment, make sure the area is ventilated and allows regular recirculation of air. If installing in an open environment, position the enclosure in an area that is constantly shaded and protected from exposure to direct sunlight. These measures are important for preventing unnecessary and excessive overheating, which prolonged in time impairs the duration and operation of parts inserted inside.
Make sure the wall where the enclosure is to be mounted is suitable to support the weight. The weight is around 10 kg.
2.4. Safety Precautions
This section contains safety precautions that must be observed at all times when working on or with the product. To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and follow all safety precautions at all times.
Installation Manual V1.2
6
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
Danger to life from electric shock due to live voltage High voltages are
present in the live components of the Combiner Box. Touching live components
results in death or serious injury due to electric shock. · Wear personal
protective equipment when working on the Combiner Box. · Do not touch live
components. · Before performing any work, always disconnect the Combiner Box
from voltage sources unless supply voltage is absolutely necessary. · Ensure
that the device cannot be reconnected. · Ensure that no voltage is present. ·
Ground and short-circuit. · Cover or isolate any adjacent live components.
Protective covers must always be mounted. Danger to life from electric shock
due to live DC cables Touching live DC cables from batteries or an inverter
results in death or serious injury. · Prior to connecting the DC cables,
ensure that the DC cables are voltage-free. · Wear suitable personal
protective equipment when working on the Combiner Box.
Danger to life from electric shock if the Combiner Box is damaged
If the Combiner Box is damaged, dangerous situations may arise during
operation that results in death or serious injury from electric shock. · Only
use the Combiner Box when it is in a technically faultless condition and safe
to operate. · Regularly check the Combiner Box for visual damage. · Make sure
that all external safety equipment is freely accessible at all times. · Make
sure that all safety equipment is in good working order.
7
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
BYD Smart Device Hungary Kft.
3. Scope of delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your distributor if the scope of delivery is incomplete or damaged.
A
B
Figure 1 Component included in the scope of delivery
A
Battery-Box Premium HVS/HVM Combiner Box CBH-40A
B
Installation Manual
Installation Manual V1.2
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
4. Product Description
4.1. Circuit Diagram
The CBH-40A Combiner Box is a BYD battery system junction box to an inverter.
Up to three HVS/ HVM battery towers could be connected in parallel with this
Combiner Box.
Figure 2 Block circuit diagram of the CBH-40A Combiner Box
“1-B+”, “1-B-” and “PE 1” in the diagram above mean the positive power cable,
negative power cable, and grounding cable from the battery tower Number 1.
4.2. Type Label
There is one type label attached to the Combiner Box. The type label is
located on the left upside of the Combiner Box. You will find the following
information on the type label: · Manufacturer · Device type · Serial number ·
Device-specific characteristics · Production date
Production date: Year Month Day
You will require the information on the type label to use the product safely and when seeking customer support from the BYD local service. The type label must remain permanently attached to the product.
9
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
4.3. Symbols on the Type Label
Symbol
Explanation
BYD Smart Device Hungary Kft.
Beware of electrical voltage.
WEEE designation Do not dispose of the system together with the household
waste but in accordance with the disposal regulations for electronic waste
applicable at the installation site.
Indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
Installation Manual V1.2
10
BYD Smart Device Hungary Kft.
5. Assembly
5.1. Wall Mounting 5.1.1. Selecting the Mounting Location
Battery Box Premium HVS/HVM Combiner Box
Fire hazard due to wrong choice of mounting location Under fault conditions
electric arcs may occur in the Combiner Box. Electric arcs can cause fires if
the Combiner Box is mounted on flammable materials. · Do not mount the
Combiner Box on flammable construction materials. · Do not mount the Combiner
Box near highly flammable materials. · Do not mount the Combiner Box in
potentially explosive atmospheres.
Requirements for the mounting location: o The mounting location must not be in
a living or office area. o The mounting location must not block any escape
routes. o The mounting location must be freely and safely accessible at all
times without the necessity for any auxiliary equipment (such as scaffolding
or lifting platforms). Non-fulfillment of these criteria may restrict
servicing. o The mounting location must be suitable for the weight and
dimensions of the Combiner Box. o The mounting location must not be exposed to
direct solar irradiation. o The recommended height of the location is higher
than 1.6 meters from the ground. o Make sure that the Combiner Box enclosure
is not mounted in the path of rainwater.
Requirements for mounting:
o Mount the Combiner Box in such a way that the connection area is facing
downwards. o The recommended height of the wall box o Do not mount the
Combiner Box in an inclined position.
5.1.2. Mounting the Combiner Box
Danger of crushing if the Combiner Box is dropped
In·stWalhlaetinonmMouanntuinagl Vth1.e0 Combiner Box, take the weight of up to
9.7 kg into account. · Installer should use personal protective equipment.
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
BYD Smart Device Hungary Kft.
Damage to cable glands and plug connections due to improper transport and
installation
The cable glands and plug connections protrude from the enclosure.
·
Additionally required mounting material (not included in the scope of
delivery): · Four M5 screws. Take wall properties into account when choosing
the screw type. · Four washers. · If necessary, four screw anchors. Take wall
properties into account when choosing the screw anchor type.
Figure 3 Dimensions of the Combiner Box
Procedure:
1. Mark the position of the drill holes on the wall or stand. 2. Drill holes
at the marked positions. 3. If necessary, insert the screw anchors. 4. Fasten
the Combiner Box to the wall or stand using suitable screws and washers. 5.
Ensure that the Combiner Box is securely fixed.
Installation Manual V1.2
12
BYD Smart Device Hungary Kft.
6. Electrical Connection
6.1. Connection Instructions 6.1.1. Preliminary Checks
Battery Box Premium HVS/HVM Combiner Box
Before connecting the Combiner Box to the battery and inverter, make sure that: · The Combiner Box is in good condition and there was no damage during transport. · The Combiner Box is firmly anchored to walls and stable supports. · There are no remaining metallic parts, chips and derivatives from the installation activities.
After performing the checks listed in the points above, proceed to wire the
cables according to what is shown in the wiring diagram, making sure to use
suitable sizes and colors.
Make sure that the DC connections are properly secured inside the terminals in
order to prevent possible overheating that may lead to dangerous situations.
13
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
6.1.2. Safety during Electrical Connection
BYD Smart Device Hungary Kft.
Danger to life due to electric shock
High voltages are present in the live components of the Combiner Box.
Therefore, work on the Combiner Box is only allowed if the power is
disconnected and the guidelines that apply at the installation location are
strictly followed. · Disconnect from voltage sources: · Ensure that the device
cannot be reconnected. · Ensure that no voltage is present. · Ground and
short-circuit. · Cover or isolate any adjacent live components. Protective
covers must always be mounted.
6.2. Inserting the Cables into the Switch Cabinet 6.2.1. Bottom view of
Combiner Box with cable glands
A
D C
E B
Figure 4 Bottom view of Combiner Box with cable glands
Position A B C D E
Description Cable entry for connecting positive power cables from battery towers Cable entry for connecting negative power cables from battery towers Grounding cables input from battery towers Output DC cable glands to an inverter Grounding cable output gland to a common ground point
Installation Manual V1.2
14
BYD Smart Device Hungary Kft.
6.2.2. Overview of the Connection Area B
Battery Box Premium HVS/HVM Combiner Box
A D
C E
Figure 5 Overview of the connection area
Position A B C D E
Description Positive input cable blocks Negative input cable blocks Grounding posts for input grounding cables Output DC cable blocks Grounding post for output grounding cable
6.3. Leading the Cables through the Cable Glands with sealing Gasket
Procedure: 1. Release the cable gland. 2. Lead the cable through the swivel
nut of the cable gland. Ensure that the thread of the swivel nut is facing
upwards. 3. Lead the cable through the seal insert. 4. Insert the seal insert
into the cable gland together with the cable.
15
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
BYD Smart Device Hungary Kft.
5. Cut the cable to length.
6.4. Connecting the DC Cables
BYD recommends using bootlace ferrules for connecting the DC cables to the blocks.
Damage to the Combiner Box due to moisture penetration · Moisture can
penetrate the Combiner Box through unsealed cable glands.
Cable requirements: The diameter of the DC cables: 5 mm to 12.5 mm. Cross
section: 6 mm2 to 16 mm2 Procedure: 1. Attach the cables to an external cable
support rail.
2. Cut the cables to length and strip 25 mm off the insulation.
3. If you are using bootlace ferrules, mount the bootlace ferrules and crimp
gas-tight.
4. Lead the cables to the blocks.
5. Insert a flat-head screwdriver into the switch of the connector.(
recommended screwdriver type, S3.5×100)
6. Hold the cables, and push up the screwdriver to make the switch go to the end.
Installation Manual V1.2
16
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
7. Make sure the switch is well fixed at the end of the sink. 8. Remove the screwdriver from the connector.
6.5. Connecting the Grounding Cable
Cable requirement · Conductor cross-section: 10 -16 mm2
· Outer diameter: 5 mm to 12.5 mm
· With a ring terminal Procedure: 1. Loose the original nut and washer on the
ground post. 2. Put the grounding cable in the ground post. 3. Tighten the nut
and washer. (torque: 5.5 Nm). 4. Ensure that the grounding cable is securely
fixed.
17
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
BYD Smart Device Hungary Kft.
7. Maintenance
7.1. Periodic Maintenance
It is recommended to periodically inspect the panel and check the following points: · There are no evident signs of rust or corrosion which may impair functioning and safety.
(Yearly – Visual inspection) · There are no water infiltrations and excessive dust infiltration. (Yearly – Visual inspection) · The mass grounding and drains are efficient.
(Yearly – Visual inspection) · There is insulation between the electrical circuits and masses.
(5 Year – Insulation test) · All the DC connections are correctly tightened.
(Yearly – Dynamometric torque tool) · There are no burn marks on the
terminals.
(Yearly – Visual inspection) · The door panel of the enclosure is firmly
closed at the end of all the checks and after any maintenance.
(Yearly – Visual inspection)
7.2. Extraordinary Maintenance
If damaged components need to be replaced only use materials identical to those originally supplied.
If the electrical connections are damaged due to mechanical or electrical causes or due to rodents, immediately disconnect the system or at least the damaged part. After verifying that no failures were caused to the equipment, proceed with the replacement of the wires using similar materials.
All the maintenance operations must be performed by taking into account all safety instructions, checking beforehand that the components are not powered.
Installation Manual V1.2
18
BYD Smart Device Hungary Kft.
8. Decommissioning
8.1. Disassembling the Combiner Box
Battery Box Premium HVS/HVM Combiner Box
Danger to life due to electric shock when touching live components of the
Combiner Box
· Observe the following safety rules when disconnecting: Disconnect from
voltage sources. Ensure that the device cannot be reconnected. Check that
no voltage or current is present. Ground and short-circuit. Cover or
isolate any adjacent live components.
Risk of burns from touching hot components
· Wear personal safety equipment when working on the device.
Requirement: The Combiner Box must be disconnected from voltage sources.
Procedure: 1. Open the doors of the Combiner Box. 2. Disconnect the input
cables from the blocks. 3. Disconnect the output cables. 4. Disconnect the
grounding cables. 5. Release the cable glands. 6. Pull all cables out of cable
glands and isolate them. 7. Disassemble the Combiner Box.
8.2. Disposing of the Combiner Box
Dispose of the Combiner Box in accordance with the applicable disposal
regulations for electronic waste.
19
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
9. Technical Data
General Data Maximum Operating Voltage (Un) Rated Insulation Voltage (Ui)
Rated Impulse Voltage (Uimp) Maximum input current per battery tower Maximum
output current Rated Current of the ASSEMBLY (InA): Rated short-time withstand
current (Icw) Pollution degree Fuse holder Fuse type
BYD Smart Device Hungary Kft.
1000V DC 1000V DC 6kV 35 A 40A 40A 10kA 3 Rail Mounting -1,500 VDC 40A 22×58 –
1,500 VDC – gPV
MECHANICAL DATA Enclosure Length/ Width/ Height Weight Degree of Protection
Type of electrical connection Form of separation
Installation Manual V1.2
SGCC (Galvanized Cold Rolled Steel) 540×350×120mm 9.7kg IP55 FFF fixed
connection Form1 (no internal separation)
20
BYD Smart Device Hungary Kft.
Battery Box Premium HVS/HVM Combiner Box
ENVIRONMENT DATA Ambient temperature during normal operation Ambient temperature during storage Humidity Altitude
-10~+50 (Note 1) -10~+50 0 % to 95 % non-condensing up to 4,000 m (Note 2)
DC INPUT DATA Maximum number of battery towers Input cable glands entry Input connection DC conductor cross-section Ground cable cross-section
3 9 M20×1.5 with 1 input each Directly on terminal blocks 6 mm2 to 16 mm2 10 mm2 to 16 mm2
DC OUTPUT DATA
Output cable glands entry
3 M20×1.5 with 1 input each
Input connection
Directly on terminal blocks
DC conductor cross-section
6 mm2 to 16 mm2
Ground cable cross-section
10 mm2 to 16 mm2
(Note 1): Derating of 0.5%/K of max. current from 40°C to 50°C.
(Note 2): Derating of maximum voltage versus altitude. 1.5 % per 100 m from 2,001 m to 3,000 m.
1.0% per 100 m from 3,001 m to 4,000m.
21
Installation Manual V1.2
Battery Box Premium HVS/HVM Combiner Box
10. Contact Information
BYD Smart Device Hungary Kft.
BYD Global Service bboxservice@byd.com Telephone: +86 755 89888888-47175 Address:No.3009,BYD Road, Pingshan,Shenzhen,518118,P.R.China www.bydbatterybox.com
Social media link https://www.facebook.com/BatteryBoxBYD/ https://twitter.com/BYD_BatteryBox https://www.linkedin.com/company/byd- battery-box
Australia
South Africa
Alps Power Pty Ltd
service @alpspower.com.au
Telephone: +61 2 8005 6688 Address: 14/47-51 Lorraine St Peakhurst NSW 221
www.alpspower.com.au
Europe
AFRIPLUS ENERGY GROUP (PTY) LTD USA
Support@afriplusenergy.co.za Telephone: +27 21 140 3594 Address: The Pavilion,
Corner of Dock & Portswood Road, V&A WATERFRONT, 8001, CAPE TOWN
EFT-Systems GmbH service@eft-systems.de Telephone +49 9352 8523999
+44 (0) 2037695998(UK) +34 91 060 22 67(ES) +39 02 873683(IT) Address:
Bruchtannenstraße 28, 63801 Kleinostheim, Germany www.eft-systems.de BYD US
service
bboxusservice@byd.com Telephone: +1(833) 338-8721
Installation Manual V1.2
22
References
- 📧bboxservice@byd.com
- ALPS POWER PTY LTD – BYD Battery-Box Australia Authorized Partner
- BYD Battery-Box – BYD Battery-Box
- BYD Battery-Box – BYD Battery-Box
- Eft-Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>