Type D40A
Compact Non-Contact Door Switch
INSTRUCTION MANUAL
Thank you for purchasing D40A Compact Non-contact Door Switch. Please read and understand this manual before using the products. Keep this manual ready to use whenever needed. An only a qualified person trained in professional electrical techniques should handle D40A. Please consult your OMRON representative if you have any questions or comments. Make sure that the information written in this document is delivered to the final user of the product.
EU Declaration of Conformity
OMRON declares that D40A is in conformity with the requirements of the
following EU Directives:
Machinery Directive 2006/42/EC
EMC Directive 2014/30/EU
Standards
D40A is designed and manufactured in accordance with the following standards:
ENISO13849-1:2015 Cat. 3 PL d (with G9SX-NS),
IEC/EN61508 SIL3 (with G9SX-NS),
IEC/EN60947-5-3 PDDB (with G9SX-NS),
IEC/EN61000-6-4, ISO14119 (Low level coded),
UL508, CAN/CSA C22.2 No.14
Safety Precautions
Meanings of Signal Words
The following signal words are used in this manual.
WARNING Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally, there may be significant property damage.
Meaning of Alert Symbols
The following alert symbols are used in this manual.
Indicates mandatory actions.
WARNING The machine may start operating and may result in serious injury
or death. Do not put the actuator close to the switch when the door is opened.
Also, make sure to install D40A to minimize defeat possibilities. For required
measures, refer to ISO14119 and other relevant standards and regulations.
Precautions for Safe Use
(1) Disconnect G9SX-NS from the power supply when wiring D40A. Devices
connected to G9SX-NS may operate unexpectedly.
(2) Do not operate the D40A with flammable or explosive gas.
(3) Incorrect wiring may lead to loss of safety function. Wire conductors
correctly and verify the operation of D40A before using the system in which
D40A is incorporated.
(4) Auxiliary monitoring output is NOT safety output. Do not use auxiliary
monitoring output as any safety output. Such incorrect use causes loss of
safety function of D40A and its relevant system.
(5) After installation of D40A, qualified personnel should confirm the
installation, and should conduct test operations and maintenance. The
qualified personnel should be qualified and authorized to secure the safety on
each phase of design, installation, running, maintenance, and disposal of the
system.
(6) A person in charge, who is familiar with the machine in which D40A is to
be installed, should conduct and verify the installation.
(7) Be sure to inspect D40A daily and every 6 months. Otherwise, serious
injury may possibly occur due to the system malfunction.
(8) Do not dismantle, repair, or modify D40A. Doing so may lead to the loss of
its safety functions.
(9) Use only appropriate components or devices complying with relevant safety
standards corresponding to the required level of safety category. Conformity
to requirements of the safety category is determined as an entire system. It
is recommended to consult a certification body regarding the assessment of
conformity to the required safety level.
Precautions for Correct Use
(1) D40A must be used with the designated actuator (D40A-1C or -A1) and
designated controller type G9SX-NS. Before using the D40A with any other OMRON
Safety Controller, check applicability in the Instruction Manual for the other
Controller.
(2) Handle with care Does not drop D40A to the ground or expose to excessive
vibration or mechanical shocks. D40A may be damaged and may not function
properly.
(3) Conditions of storage and usage Do not store or use the D40A under the
following conditions. D40A may be damaged and may not function properly.
- Indirect sunlight
- At ambient temperatures out of the range of –10 to 55°C
- At relative humidity out of the range of 25% to 85% or under such as temperature change that causes condensation.
- In corrosive or combustible gases
- With vibration or mechanical shocks out of the rated values.
- Under splashing of oil or chemicals
- In the atmosphere containing dust, saline, or metal powder.
- Where steel scrap or metal powder may fall directly to D40A.
(4) Use cables with a length less than 100m totally to connect multiple D40A switches. The supply voltage to D40A may decrease by the voltage drop depending on the cable or the wiring configuration. Check the power-supply voltage is in the rated range.
(5) Disconnect G9SX-NS from the power supply when replacing D40A. Devices
connected to G9SX-NS may operate unexpectedly.
(6) Adhesion of solvents such as alcohol, thinner, trichloroethane, or
gasoline on the product should be avoided. Such solvents make the marking on
D40A illegible and cause deterioration of parts.
(7) Do not use D40A in the magnetic field of 1.5mT or more. D40A may not
function properly.
(8) Do not use the D40A in the water or continuous water exposure environment.
Water may lead into the D40A.
(9) Do not use the switch or actuator as a stopper. Protect the switch and the
actuator by setting up the stopper. Separate the switch and the actuator to a
distance of 1mm or more.
(10) Install the D40A actuator and switch at an appropriate distance so that
it does not create a gap accessible to the hazard.
(11) Where two or more switches are mounted adjacent, they should be no closer than 25mm.
(12) Check that the machine is stopped whenever the interlocked guard door is open.
(13) Do not mount the switch and actuator on magnetic materials, otherwise, it may affect the operating distance. Refer to the chart below for the estimated influence.
Distance from magnetic materials | Operating distance |
---|---|
0 to 5mm | Approximately 90% of the original value |
5mm Min. | No influence |
(14) Tighten each screw with specified torque by using an M4 screw and washer for the installation of the switch and actuator. After installation and commissioning, the actuator and switch fixing screws should be coated with tamper-proof varnish or a similar compound. Using anaerobic locking compounds can have a detrimental effect on the plastic switch case if the compounds contact the switch case.
(15) Wiring
1. Use the following to wire to G9SX-NS
-Solid wire: 0.2 to 2.5mm2 AWG24 to AWG12
-Stranded wire: 0.2 to 2.5mm2 AW G22 to AW G12
2. When u cilia try output is not used, cut off the wiring and protect by
taping so that it does not contact other terminals.
3. When you use an additional cable of 20m or longer, use a multiconductor
cable to group the white, black, brown, and blue lines together.
(16) Handle cables with care:
- For bending cables, it is recommended to bend them with a radius of bend no less than six times the cable outer diameter.
- Do not apply a tensile strength of 50N or greater to the cables.
(17) This is a class A product. In residential areas, it may cause radio interference, in which case the user may be required to take adequate measures to reduce interference.
(18) If there is any machine that has a large surge current(e.g., a motor) near D40A, connect a surge absorber to D40A between the blue and the other lines (white, black, brown, and yellow), respectively.
The suggested surge absorber’s specification is as follows: (Per IEC61000-4-5(surge immunity)) -Breakdown voltage: 27-33V
Detection Ranges (Engineering data)
Note1. The operating distance is the distance between the switch and
actuator sensing surfaces.
Note2. The graph indicates shifting to X or Z direction from the
following condition that the switch and actuator target marks are on the same
axis and the sensing surfaces are exactly parallel condition. Dashed lines
indicate reference values for maximum and minimum operating distance at
ambient temperature +23°C. The solid line indicates reference values of the
maximum and minimum operating distances.
2 Switch and actuator operation
- Switch and Actuator Mounting Directions
- Switch and Actuator Operating Directions
- LED Display
LED color| Status
---|---
RED| The sensor does NOT detect actuator
YELLOW| Sensor detects actuator
Internal connection
Ratings and Specifications
Ratings
Item
|
D40A-1C□
---|---
Rated power consumption| 0.6W Max. (See Note1)
Auxiliary output| Load: 24VDC 10mA
(PNP open-collector output)
Specifications and Performance
Item
|
D40A-1C□
---|---
Assured operating and release distance| OFFON| 5mm min. (See Note2)
ON-OFF| 15mm max. (See Note2)
Differential travel| See “ 1 Detection ranges”
Temperature influence| See “ 1 Detection ranges”
Repeat accuracy (max.)| ±10% of operating distance at 23°C
Switching frequency| 1Hz with G9SX-NS□
Ambient temperature| -10 to +55°C
(No freezing or condensation)
Ambient humidity| 25 to 85%RH
Insulation resistance
(Between all conductive parts and switch case)
| 50Mohm Min. (by 500VDC megger)
Dielectric strength (Between all conductive parts and switch case)| 1000VAC
for 1min
Rated impulse withstand voltage| 1kV
Vibration resistance| Frequency: 10 to 55 to 10Hz, Amplitude: 0.75mm half
amplitude
Mechanical shock resistance| 300m/s2 Min.
Pollution degree| 3
Electromagnetic compatibility| As per IEC/EN 60947-5-3
Degree of protection| IP67
Material| Molded PBT
Mounting method| M4 screws
Terminal tightening torque| 1N•m
Relaiability data (ISO 13849-1)| MTTF = 100 year, DC = 60%
*This data does not include the values of a safety controller.
Note1. Power consumption of loads is not included.
Note2. Operating distance means the distance of sensing surfaces between
switch and actuator.
Connection Example
- Multiple switch connection Maximum 30 switches can be connected in series.
Dimensions
Switch
- D40A-1C015-F
- Single switch connection
- Wiring
Signal Name | Cable color | Pim number | Description of operation |
---|---|---|---|
Non-contact door switch power input | + | brown | 1 |
Connect to D3 terminal and D4 terminal on G9SX-NS□.
–| blue| 3
Non-contact door switch signal input|
white
|
2
| Input designated signal from G9SX-NS□.
To set non-contact door switch output in ON state, non-contact door switch
input must be in ON state.
Non-contact door switch output| black| 4| Output status depends on actuator
status and non-contact door switch input state.
Auxiliary monitoring output (PNP open corrector output)| yellow| 5| Output
when the sensor detects the actuator.
Troubleshooting
LED indicator Note1| Expected causes of the faults| Checking points and
measures to take
---|---|---
D40A| G9SX-NS□
Light off
|
NS Light off
| Failures involving the wiring of power supply input| Check that the brown
and the blue cable are correctly connected with G9SX-NS□’s D3 terminal and
terminal D4 respectively.
Failures of the parts of the circuits of D40A| Replace with a new D40A
Red Light on
|
NS Light off
| Installation on magnetic substance| Install the switch and actuator on a
non-magnetic material.
Installation in the vicinity of magnetic source| Install D40A separate from a
strong magnetic source.
Failures of the parts of the circuits of D40A| Replace with a new D40A
Yellow Light on
|
NS Light off or NS Blink
| Failures involving the wiring of D40A input| Check that the white cable is
correctly connected with G9SX-NS□’s D1 terminal.
Failures involving the wiring of D40A outputs| Check that the black cable is
correctly connected with G9SX-NS□’s D2 terminal.
Failures of the parts of the circuits of D40A| Replace with a new D40A
Performance Level / Safety Category
The D40A TOGETHER WITH g9sx-nsΟ can construct the condition conforming to PL=d
and Category 3 required by EN ISO 13849-1 European standard.
Refer to the following link for the Safety-related characteristic
data:http://www.fa.omron.co.jp/safety_6en/
This does NOT mean that D40A and G9SX-NS can always be used for the required
category under all similar conditions and situations.
UL does not provide UL certification for any functional safety rating or
aspects of the D40A device.
Conformity to the categories must be assessed as a whole system.
When using D40A and G9SX-NS for safety categories, make sure the conformity of
the whole system.
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards,
codes, or regulations which apply to the combination of the Product in the
Buyer’s application or use of the Product. At Buyer’s request, Omron will
provide applicable third-party certification documents identifying ratings and
limitations of use that apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product
in combination with the end product, machine, system, or other application or
use. Buyer shall be solely responsible for determining the appropriateness of
the particular Product with respect to Buyer’s application, product, or
system.
Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE
HAS BEEN DESIGNED TO ADDRESS THE RISKS AND THAT THE OMRON PRODUCT(S) IS
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
Inspection & Maintenance
• Daily inspection:
1. Check every guard door to see that the machine stops when the guard door
is opened.
• 6-month inspection:
1. Isolate all power.
2. Check the switch and actuator for proper alignment.
3. Check terminals for proper connections.
4. Check wiring for signs of damage.
5. Before resuming normal machine operation, check every guard door to see
that the machine stops when the guard door is opened.
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
Contact : www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1)
847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
Pudong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>