REGENCY B36XTE Medium Direct Vent Gas Fireplace Instruction Manual

June 7, 2024
Regency

REGENCY B36XTE Medium Direct Vent Gas Fireplace

REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-
PRODUCT

Product Specifications

  • Model: B36XTE Medium Direct Vent Gas Fireplace
  • Fuel Type: Natural Gas (B36XTE-NG11) / Propane (B36XTE-LP11)
  • Minimum Supply Pressure: 5 W.C./C.E. (1.25 kPa) for NG, 11 W.C./C.E. (2.74 kPa) for LP
  • Manifold Pressure – High: 3.5 W.C./C.E. (0.87 kPa) for NG, 10 W.C./C.E. (2.49 kPa) for LP
  • Manifold Pressure – Low: 1.6 W.C./C.E. (0.40 kPa) for NG, 6.4 W.C./C.E. (1.60 kPa) for LP
  • Orifice Size – Altitude 0-4500 ft.: #35 DMS for NG, #51 DMS for LP
  • Minimum Input Altitude 0-4500 ft.: 21,500 BTU/h (6.3 kW) for NG, 25,000 BTU/h (7.33 kW) for LP
  • Maximum Input Altitude 0-4500 ft.: 31,000 BTU/h (9.09 kW) for both NG and LP
  • CSA P.4.1 Fireplace Efficiency (FE): 65.90%
  • Approved Venting Systems: Flex Vent Systems: FPI AstroCapTM Flex Vent, Rigid Pipe Vent Systems: -5 x 8 approved, -4 x 6-5/8 approved

Product Usage Instructions

CLEARANCES

  • The clearances listed below are Minimum distances unless otherwise stated:
  • A major cause of chimney-related fires is failure to maintain required clearances (air space) to combustible materials.
  • It is of the greatest importance that this fireplace and vent system be installed only by these instructions.

Caution Requirements

  • The top, back, and sides of the fireplace are defined by standoffs.
  • The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING

  • Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to.
  • It is of the greatest importance that this fireplace and vent system be installed only by these instructions.

B36XTE Clearance Requirements

  • A: Mantel Height (min.) with Vignette +Vignette Trim (Stepped finish): 13″ (330mm)
  • B: Sidewall: 12″ (304mm) one side only
  • C: Ceiling: 36-3/4″ (933mm)
  • D: Mantel Depth (max.): 12″ (304mm)

Notes:

  • E: Alcove Width: 84″ (2134mm)
  • F: Alcove Depth: 36″ (914mm)

Minimum Vent Clearances to Combustibles

  • Horizontal Top: 2″ (51mm)
  • Horizontal Side: 1-1/2″ (38mm)
  • Horizontal Bottom: 1-1/2″ (38mm)
  • Vertical Vent: 1-1/2″ (38mm)

COMBUSTIBLE MANTEL CLEARANCES

  • Because of the extreme heat this fireplace emits, the mantel clearances are critical.

  • Combustible mantel clearances from the top of the unit are shown in the diagram below.

  • Note: Mantel starts at 1 deep and ends at 12 deep.

  • For Vignette with Vignette Finishing Trim flush finish, all materials (framing & finishing) below the mantel and the width of the Vignette finishing trim, (37-3/4) must be non-combustible if a lower mantel is desired.

  • The noncombustible mantle when installed at a lower overall height may not be lower than 6 inches from the top of the fireplace opening.

Frequently Asked Questions

Q: What are the fuel types supported by the B36XTE Gas Fireplace?

A: The B36XTE Gas Fireplace supports Natural Gas (B36XTE-NG11) and Propane (B36XTE-LP11).

Q: What is the minimum and maximum input altitude for this fireplace?

A: The minimum input altitude is 0-4500 ft. with a BTU range of 21,500 to 25,000, and the maximum input altitude is also 0-4500 ft with a BTU range of 31,000.

B36XTE Medium Direct

B36XTE Medium Direct Vent Gas Fireplace

Model B36XTE-NG11 B36XTE-LP11
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5” W.C./C.E. (1.25 kPa) 11” W.C./C.E. (2.74 kPa)
Manifold Pressure – High 3.5” W.C./C.E. (0.87 kPa) 10” W.C./C.E. (2.49 kPa)
Manifold Pressure – Low 1.6” W.C./C.E. (0.40 kPa) 6.4” W.C./C.E. (1.60 kPa)
Orifice Size – Altitude 0-4500 ft. #35 DMS #51 DMS
Minimum Input Altitude 0-4500 ft. (0-1372m) 21,500 BTU/h (6.3 kW) 25,000

BTU/h (7.33 kW)
Maximum Input

Altitude 0-4500 ft. (0-1372m)

| 31,000 BTU/h

(9.09 kW)

| 31,000 BTU/h

(9.09 kW)

CSA P.4.1 Fireplace Efficiency (FE)| 65.90%| 65.90%

REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-1

UNIT DIMENSIONS

UNIT DIMENSIONS WITH VIGNETTE & VIGNETTE FINISHING TRIMREGENCY-B36XTE-
Medium-Direct-Vent-Gas-Fireplace-FIG-2

UNIT DIMENSIONS WITH OPTIONAL FLUSH PANELS AND SAFETY SCREENREGENCY-
B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-3

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

  • A major cause of chimney-related fires is failure to maintain required clearances (air space) to combustible materials.
  • It is of the greatest importance that this fireplace and vent system be installed only per these instructions.

Caution Requirements

  • The top, back and sides of the fireplace are defined by standoffs.
  • The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING Fire hazard is an extreme risk

  • if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only per these instructions.

B36XTE Clearance Requirements

Clearance: Dimension Measured From:
A: Mantel Height (min.) with Vignette +Vignette Trim (Stepped finish)
13″ (330mm) Top of Fireplace Opening
A: Mantel Height (min.) with Flush Panels and Safety Screen 13″
(330mm) Top of Fireplace Opening
A: Mantel Height (min.) with Vignette + Vignette Trim Finished Flush
22″ (559mm) Top of Fireplace Opening
B: Sidewall 12″ (304mm) one side only Side of Fireplace Opening
C: Ceiling 36-3/4″ (933mm) Top of Fireplace Opening
D: Mantel Depth (max.) 12″ (304mm) (See Dimension A) from

Top of Fireplace Opening

E: Alcove Width| 84″ (2134mm)| Wall to Wall (Minimum)
F: Alcove Depth| 36″ (914mm)| Front to Back Wall (Maximum)
Notes:| 0″| No Hearth Required

Minimum Vent Clearances to Combustibles

Horizontal Top 2″ (51mm)
Horizontal Side 1-1/2 ” (38mm)
Horizontal Bottom 1-1/2″ (38mm)
Vertical Vent 1-1/2″ (38mm)

COMBUSTIBLE MANTEL CLEARANCES

  • Because of the extreme heat this fireplace emits, the mantel clearances are critical.
  • Combustible mantel clearances from the top of the unit are shown in the diagram below.
  • Note: Mantel starts at 1″ deep and ends at 12″ deep. **For Vignette with Vignette Finishing Trim flush finish, all materials (framing & finishing) below the mantel and the width of the Vignette finishing trim, (37-3/4″) must be non-combustible if a lower mantel is desired. The non-combustible mantle when installed at a lower overall height may not be lower than 6 inches from the top of the fireplace opening.
  • Note: Ensure the paint that is used on the mantel and the facing is “heat resistant” or the paint may discolour.

Mantel Clearance with Vignette + Vignette Trim (stepped finish) or Flush Panels and Safety Screen

Mantel Clearances B36XTE A B C D
From Top of the Fireplace Opening 32″ (813mm) 22″ (559mm) 17-1/2″ (445mm)

13″ (330mm)

Note: Ensure the paint that is used on the mantel and the facing is “High Quality” or the paint may discolour.

MANTEL LEG CLEARANCES

Mantel Clearance with Vignette and Vignette Finishing Trim (flush finish)

FRAMING

  • Determine the total thickness of the facing material (e.g. non-combustible plus ceramic tiles) to allow the finished surface to be flush with the front of the unit.
  • Total facing thickness can vary from 1/2″ (13mm) to 1-1/4″ (32mm) thick with Vignette only and Safety Screen and Flush Panels. When installing the Vignette + Vignette Finishing Trim Flush Finish the facing thickness is up to a maximum of 3-1/8″.

Vignette + Vignette Trim (Stepped Finish) or with Flush Panels and Safety Screen

  • Note: Secure the non-combustible board directly above the unit as shown.
  • Install a steel stud directly above the unit as shown to secure the non -combustible material.
  • Install Side Nailing Strips, Top Facing Support, and Top Standoffs before the unit is slipped into position. See the “Unit Assembly Before Installation” section for assembly details.

Vignette + Vignette Finishing Trim (Flush Finished)

  • For exterior walls, insulate the enclosure to the same degree as the rest of the house, and apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fireplace itself.)
  • The top of the fireplace opening must not be closer than 36-3/4″ (933mm) to the ceiling.

FRAMING WITH VIGNETTE + VIGNETTE TRIM (STEPPED FINISH) OR WITH FLUSH PANELS AND SAFETY SCREEN

Framing Dimensions Description B36XTE
M Framing Width 40-5/8″(1032mm)
N Framing Height 42″ (1067mm)
O (Rear Vent) Framing Depth – Rear Vent 20-3/4″ (527mm)
O (Top Vent) Framing Depth – Top Vent 20-1/2″ (521 mm)
P (Top Vent) Corner Facing Wall Width 48 – 5/8″ (1235mm)
P (Rear Vent) Corner Facing Wall Width 53″ (1346mm) AstroCapXL

61-1/2″ (1562mm) – other approved caps

Q (Top Vent)| Corner Facing Wall Width| 68-3/4″ (1746mm)
Q (Rear Vent)| Corner Facing Wall Width| 75″ (1905mm) AstroCapXL

87″ (2209mm) – other approved caps

R (Rear Vent)| Framed Chase Ceiling – Rear| 42″ (1067mm)
R (Top Vent)| Framed Chase Ceiling – Top| 50-1/2″ (1283mm)
S (Rear Vent)| Vent Centerline Height – Rear| 26-1/2″ (673mm)
S (Top Vent) (5″ x 8″)| Vent Centerline Height – Top| 42-1/8″ (1070mm)

Flex

| 44-1/4″ (1123mm) Rigid
S (Top Vent) (4″ x 6-5/8″)| Vent Centerline Height – Top| –| 49″ (1245mm) Rigid
T| Gas Connection Height| 1-1/2″ (38mm)
U| Gas Connection Inset| 4-1/8″ (105mm)
V| Gas Connection Width| 3-1/4″ (82mm)
W| Non-combustible Height| 8-3/4″ (222mm)

Important: Framing height requires consideration of the hearth depth. Dimension N = N + the thickness of the installed hearth.REGENCY-B36XTE-
Medium-Direct-Vent-Gas-Fireplace-FIG-11

FRAMING WITH VIGNETTE AND VIGNETTE TRIM (FLUSH FINISH)

Framing Dimensions Description B36XTE
M Framing Width 42-1/4″(1073mm)
N* Framing Height 42″ (1067mm)
O (Rear Vent) Framing Depth – Rear Vent 22-1/8″ (559mm)
O (Top Vent) Framing Depth – Top Vent 21-7/8″ (553 mm)
P (Top Vent) Corner Facing Wall Width 51 – 5/16″ (1303mm)
P (Rear Vent) Corner Facing Wall Width 55-11/16″ (1414mm) AstroCapXL

64-3/16″ (1630mm) – other approved caps

Q (Top Vent)| Corner Facing Wall Width| 72-1/2″ (1842mm)
Q (Rear Vent)| Corner Facing Wall Width| 78-3/4″ (2000mm) AstroCapXL

90-3/4″ (2305mm) – other approved caps

R (Rear Vent)| Framed Chase Ceiling – Rear| 42″ (1067mm)
R (Top Vent)| Framed Chase Ceiling – Top| 50-1/2″ (1283mm)
S (Rear Vent)| Vent Centerline Height – Rear| 26-1/2″ (673mm)
S (Top Vent) (5″ x 8″)| Vent Centerline Height – Top| 42-1/8″ (1070mm) Flex| 44-1/4″ (1123mm) Rigid
S (Top Vent) (4″ x 6-5/8″)| Vent Centerline Height – Top| –| 49″ (1245mm) Rigid
T| Gas Connection Height| 1-1/2″ (38mm)
U| Gas Connection Inset| 4-1/8″ (105mm)
V| Gas Connection Width| 3-1/4″ (82mm)
W| Non-combustible Height| 8-3/4″ (222mm)
*NOTE: When using the optional Vignette finishing trim, this can be installed as a 3-sided or 4-sided finish trim. If choosing to use this as a 4-sided finish trim the framing would need to be increased by 11/16″ inches minimum for this to fit. This must be to the finished floor. (Eg:42″ framing height + 11/16″ to bottom of 4-sided finishing trim +1/2 thick finished floor = 43 3/16

Important: Framing height requires consideration of the hearth depth. Dimension N = N + the thickness of the installed hearth.REGENCY-B36XTE-
Medium-Direct-Vent-Gas-Fireplace-FIG-12

NON- NON-COMBUSTIBLE REQUIREMENTS

Vignette +Vignette Trim (Stepped Finish) or with Flush Vignette + Vignette Finishing Trim (Flush Finish) Panels and Safety Screen

FINISHING

IMPORTANT FINISHING DETAIL NOTE: Before placing the unit into the final position – it is important to know the total thickness/height of the finished hearth (tile, carpet, etc.)
The base of the fireplace should be level or higher than the finished hearth height.

  • Note: All non-combustible facing material should butt up cleanly **** to the flanges around the firebox opening.
  • Rough edges will be visible from the front view with the flush louvres or flush panels – if not using the optional finishing trim.
  • To maintain a clean finished edge – it is recommended to install the non-combustible facing material with the finished edge against the fireplace/nailing strips.
  • Alternatively, you can use J Style Trim or Metal Corner Bead to cover the cut edges of the non-combustible facing material.
  • Important: Finishing materials such as tile, river rock, etc, must not protrude beyond the front-facing flanges at the sides and top of the firebox opening.

VENTING DIRECT VENT SYSTEM (FLEX)

HORIZONTAL TERMINATIONS ONLY

  • These venting systems, in combination with the B36XTE Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey.
  • The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the “Exterior Vent Termination Locations” section.
  • Regency Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the B36XTE with a maximum run of 4 feet.
1 6-7/8″ dia. flexible liner (4 ft. length)
2 4″ dia. flexible liner (4 ft. length)
3 spring spacers (4)
4 thimble (2)
5 AstroCap termination cap (1)
6 screws (12)
7 tube of Mill Pac (1)
8 plated screws (8)
9 screws #8 x 1-1/2″ Drill Point, Stainless

Steel (4)

If longer runs are needed, the Regency Direct Vent system (Flex) # 946-516 includes all the parts needed to install the B36XTE with a maximum 10′ run.

1 6-7/8″ dia. flexible liner (10 ft. length)
2 4″ dia. flexible liner (10 ft. length)
3 spring spacers (7)
4 thimble (2)
5 AstroCap termination cap (1)
6 screws (12)
7 tube of Mill Pac (1)
8 plated screws (8)
9 screws #8 x 1-1/2″ Drill Point, Stainless

Steel (4)

REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-17

Notes:

  1. Liner sections should be continuous without any joints or seams.
  2. Only Flex pipe purchased from Regency may be used for Flex installations.

HORIZONTAL TERMINATIONS

ASTROCAP XL & RIGID REAR VENT KIT FOR CORNER INSTALLATIONS

  • FOR CORNER INSTALLATION RIGID PIPE 5″ X 8″ – WHEN USING VIGNETTE FINISHING TRIM (SEE NEXT PAGE)
  • Designed for a minimum vent configuration when using a rear vent application with a horizontal termination in a corner installation.

Kit  946-612 Includes

1| AstroCap XL| 946-623/P
1| Rigid Pipe Adaptor| 770-994
1| Vinyl Siding Standoff (Optional)| 946-625
1| Wall Thimble| 58DVA-WT
1| 6″ galvanized rigid pipe| 58DVA-06
1| 8-1/2″ galvanized pipe extension| 58DVA-08A
1| 45º galvanized elbow| 58DVA-E45
1| 90 ml MillPac| 948-128

Placement of the unit into the corner

Back top corner of unit to the wall| 4″
Inside corner out along the wall| 53″
Across the face of the unit, wall-to-wall| 75″
Inside corner to front face of the unit| 37-1/2″

HORIZONTAL 5” X 8” RIGID REAR VENT KIT

  • ASTROCAP XL & RIGID REAR VENT KIT FOR CORNER INSTALLATIONS RIGID PIPE 5″ X 8″ – WHEN INSTALLED WITH VIGNETTE AND VIGNETTE FINISHING TRIM – FINISHED FLUSH
  • Designed for a minimum vent configuration when using a rear vent application with a horizontal termination in a corner installation.

Kit  946-612 Includes

1| AstroCap XL| 946-623/P
1| Rigid Pipe Adaptor| 770-994
1| Vinyl Siding Standoff (Optional)| 946-625
1| Wall Thimble| 58DVA-WT
1| 6″ galvanized rigid pipe| 58DVA-06
1| 8-1/2″ galvanized pipe extension| 58DVA-08A
1| 45º galvanized elbow| 58DVA-E45
1| 90 ml Mill Pac| 948-128

Placement of the unit into the corner

Back top corner of unit to the wall| 4″
Inside corner out along the wall| 55-11/16″
Across the face of the unit, wall-to-wall| 78-3/4″
Inside corner to the front face of the unit| 39-3/8″

VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS FLEX VENT OR RIGID PIPE 5″ X 8″

  • The Diagrams show all allowable combinations of vent runs with 5″ x 8″ venting using the Regency direct vent system or rigid vent system.
  • A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
  • For horizontal terminations, the Regency Direct Vent Flex System may be used for installations with a maximum continuous vent horizontal length of 3ft (0.9m).
  • Note: Must use an optional rigid pipe adaptor (Part # 770-994) when using Rigid Pipe vent systems.
  • Maintain clearance to combustibles.
  • The horizontal vent must be supported every 3 feet.
  • Firestops are required at each floor level and whenever passing through a wall.REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-24

HORIZONTAL TERMINATIONS Flex Vent 5″ x 8″

  • These venting systems, in combination with the B36XTE Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Intertek.
  • The location of the termination cap must conform to the requirements in the Vent Terminal Locations
  • The diagram is in the “Exterior Vent Termination Locations” section.
  • Regency® Direct Vent (Flex) System 4-foot Termination Kit (Part# 946-615) includes all the parts needed to install the B36XTE with either a top or rear vent.
  • Note: If top venting this unit, the 5″ x 8″ venting may only be used if venting to the minimum of 42-1/8″ to centerline.
  • No other application is approved.
FPI Kit # Length Contains:
#946-615 4 Feet 1)       8” flexible liner (Kit length)

2)       5” flexible liner (Kit length)

3)       spring spacers

4)       thimble

5)       AstroCap termination cap

6)       screws

7)       tube of Mill Pac

8)       plated screws

9)       S.S. screws #8 x 1-1/2” drill point

10)    vinyl siding standoff

REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-25

  1. 8″ dia. flexible liner (4 ft. length)
  2. 5″ dia. flexible liner (4 ft. length)
  3. spring spacers (4)
  4. thimble
  5. AstroCapXL termination cap (1)
  6. screws (12)
  7. tube of Mill Pac (1)
  8. plated screws (8)
  9. screws #8 x 1-1/2″ Drill Point, Stainless Steel (4)
  10. vinyl siding standoff

Notes:

  1. Liner sections should be continuous without any joints or seams.
  2. Only Flex pipe purchased from Regency may be used for Flex installations.
  3. Regency® Direct Vent System (Flex) is only approved for horizontal terminations.

HORIZONTAL TERMINATIONS Rigid Pipe 5″x 8REGENCY-B36XTE-Medium-Direct-
Vent-Gas-Fireplace-FIG-26

Horizontal Termination

A| Top Vent – No Vertical Rise

•     When venting with a 90° elbow directly off the unit, must use a 5″ X 8″ AstroCapXL™ Flex vent or approved Rigid Vent System

•     Max. 3 ft. horizontal run

B| Rear Vent w/ Horizontal Termination

•  Can only use 5″ x 8″ venting

•  Max. 3ft. horizontal run

VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS Rigid Pipe 4″ x 6-5/8″

  • must use Reducer Part # 946-606 & 770-994 Rigid Pipe Adaptor
  • The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o and two 45o elbows equal to one 90o elbow).REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-27
  • Maintain clearances to combustibles as listed in the “Clearances” section
  • The horizontal vent must be supported every 3 feet.
  • Firestops are required at each floor level and whenever passing through a wall.
  • A wall thimble is mandatory for all horizontal terminations due to high temperatures.

HORIZONTAL OR VERTICAL TERMINATIONS Rigid Pipe 4″ x 6-5/8″

  • must use Reducer Part # 946-606 & 770-994 Rigid Pipe Adaptor
  • The minimum components required for a basic horizontal termination using 4″ x 6-5/8″ are.
  • 1 Rigid Pipe Adaptor (770-994)
  • 1 Reducer (946-606)
  • 1 90o Elbow
  • 1 Wall Thimble
  • 1 Length of pipe to suit wall thickness
  • 1 Horizontal Termination Cap
  • Wall thickness is measured from the back standoffs to the inside mounting surface of the termination cap.
  • For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal.
  • The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
  • If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to an outside surface of the wall without siding and add 2 inches.REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-28

WARNING:

  • Do not combine venting components from different venting systems.
  • However, use of the the AstroCapTM and Regency Riser is acceptable with all systems.
  • This product has been evaluated by Intertek when using a rigid pipe adaptor and use of any of the specific chimney systems listed in this manual.
  • Use of these systems with the rigid pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of these components.
  • The Regency AstroCapTM and Regency Riser Vent terminal are certified for installations using Regency venting systems as well as any specific chimney systems listed in this manual. AstroCapTM is a proprietary trademark of Regency Fireplace Products.

HORIZONTAL TERMINATIONS Two (2) 90o Elbows (Rigid Pipe 4″ x 6 – 5/8″)

One 90o elbow = Two 45o elbows

Option| V| H + H1| With these options, the maximum total pipe length is 30 feet with a minimum of 6 feet total vertical and a maximum of 8 feet total horizontal.

Please note a minimum of 1 foot between 90 __**elbows is required.**

---|---|---|---
A)| 0′ Min.| 2′ Max.
B)| 1′ Min.| 3′ Max.
C)| 2′ Min.| 4′ Max.
D)| 3′ Min.| 5′ Max.
E)| 4′ Min.| 6′ Max.
F)| 5′ Min.| 7′ Max.
G)| 6′ Min.| 8′ Max
No Vent Restrictor Installed

  • Lengths do not include elbow indicated.
  • Must use reducer # 946-606 and rigid pipe adaptor #770-994.

HORIZONTAL TERMINATIONS Three (3) 90o Elbows (Rigid Pipe 4″ x 6 – 5/8 ″)REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-
FIG-31

One 90o elbow = Two 45o elbows

Option| V| H| V + V1| H + H1| With these options, max. total pipe length is 30 feet with min. of 12 feet total vertical and max. 9 feet total horizontal.

__**Please note min. 1 foot between 90 __**elbows is required.

---|---|---|---|---|---
A)| 0′ Min.| 1′ Max.| 1′ Min.| 2′ Max.
B)| 1′ Min.| 2′ Max.| 3′ Min.| 3′ Max.
C)| 2′ Min.| 2′ Max.| 5′ Min.| 4′ Max.
D)| 3′ Min.| 2′ Max.| 7′ Min.| 5′ Max.
E)| 4′ Min.| 3 Max.| 9′ Min.| 6′ Max.
F)| 5′ Min.| 4′ Max.| 10′ Min.| 7′ Max.
G)| 6′ Min.| 5′ Max.| 11′ Min.| 8′ Max.
H)| 7′ Min.| 6′ Max.| 12′ Min.| 9′ Max.
No Vent Restrictor Installed

  • Lengths do not include elbow indicated.
  • Must use reducer # 946-606 and rigid pipe adaptor #770-994.

VENTING ARRANGEMENTS FOR VERTICAL TERMINATIONS Rigid Pipe 4″ x 6-5/8″

  • must use Reducer Part # 946-606 & 770-994 Rigid Pipe Adaptor
  • The shaded area in the Diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90 elbows, with Rigid Pipe Venting Systems for Propane and Natural Gas.
  • Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed.REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-32
  • The vent must be supported at offsets.
  • Firestops are required at each floor level and whenever passing through a wall.
  • Maintain clearances to combustibles as listed in the “Clearances” section.
  • Refer to the “Vent Restrictor Position” section for details on how to change the vent restrictor from the factory setting to a 2-1/4″ opening,1-5/8″opening and 1-1/16″ opening.
  • Note: Must use an optional flue adapter when using Rigid Pipe (Part # 770-994).

VERTICAL TERMINATIONS

Three (3) 90o Elbows (Rigid Pipe 4″ x 6 – 5/8″)

One 90o elbow = Two 45o elbows

Option| V| H + H1| V + V1| With these options, max. total pipe length is 30 feet with min. of 10 feet total vertical and max. 8 feet total horizontal.

Please note min. 1 foot between 90 __**elbows is required.**

---|---|---|---|---
A)| 0′ Min.| 2′ Max.| 2′ Min.
B)| 1′ Min.| 2′ Max.| 3′ Min.
C)| 2′ Min.| 3′ Max.| 4′ Min.
D)| 3′ Min.| 4′ Max.| 6′ Min.
E)| 4′ Min.| 5′ Max.| 7′ Min.
F)| 5′ Min.| 6′ Max.| 8′ Min.
G)| 6′ Min.| 7′ Max.| 9′ Min.
H)| 7′ Min.| 8′ Max.| 10′ Min.
No Vent Restrictor Installed

  • Lengths do not include elbow indicated.
  • Must use reducer # 946-606 and rigid pipe adaptor #770-994

VENTING ARRANGEMENTS WITH CO-LINEAR FLEX SYSTEM

  • THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING A SEPARATE SOLID FUEL-BURNING APPLIANCE.
  • Masonry chimneys may take various contours which the flexible liner will accommodate. However, keep the flexible liner as straight as possible, to avoid unnecessary bending.
  • The Air Intake pipe must be attached to the inlet air collar of the termination cap.
  • This appliance is designed to be attached to two 3″ (76mm) co-linear aluminium flexes running the full length of the chimney. See the Venting Arrangements on next page for minimum and maximum heights.

Required Parts:

Part # Description

  • 946-529 Co-linear DV Vertical Termination Cap
  • 948-305 3″ Flex – 35 ft.
  • 946-563 Co-Axial to Co-Linear Adapter Kit which contains the following: Co-linear Flex Adapter Outer Pipe Inner Pipe Adapter
  • 770-994 Rigid Pipe Adaptor
  • 946-606 Vent Reducer

Alternate Approved Caps

  • 46dva-VC Vertical Termination Cap
  • 46dva-VCH High Wind Cap
  • 46dva-GK 3″ Co-linear Adapter with flashing
  • NOTE: See detailed venting arrangements, vertical terminations, co-linear flex system into masonry fireplaces in this manual.REGENCY-B36XTE-Medium-Direct-Vent-Gas-Fireplace-FIG-34

VERTICAL TERMINATIONS CO-LINEAR FLEX SYSTEM INTO MASONRY FIREPLACES

FOR BOTH RESIDENTIAL & MANUFACTURED HOMES REGENCY-B36XTE-Medium-Direct-Vent-
Gas-Fireplace-FIG-35

UNIT INSTALLATION

WITH HORIZONTAL TERMINATION 4″ X 6-5/8″ OR 5″ X 8″ VENTING

  • Rigid Vent Systems Minimum Vent Clearances to Combustibles
  • Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2″ (38mm).
Horizontal Top* 2″ (51mm)*
Horizontal Side 1-1/2 ” (38mm)
Horizontal Bottom 1-1/2″ (38mm)
Vertical Vent 1-1/2″ (38mm)

Below are the recommended framing dimensions (inside measurements) for the 4″ x 6-5/8″ and 5″ x 8″ rigid vent terminations – for use with a firestop or wall thimble.

Recommended Framed Opening Size

Vent Size| Framing Size
4″ x 6 – 5/8″| 10″ x 10″
5″ x 8″| 11″ x 11″

Install the vent system according to the manufacturer’s instructions included with the components.

  1. Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached.
    • If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.
  2. Direct Vent pipe and fittings are designed with special twist-lock connections to connect the venting system to the appliance flue outlet. A twist-lock appliance adaptor is required.
  3. In conjunction with the Approved Vent system, install the adaptor after the unit is set in its desired location. Put a bead of Mill-Pac inside the outer section of the adapter and a bead of on the inner collar. Slip the adapter over the existing inner and outer flue collar. Fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier).
  4. Level the fireplace and fasten it to the framing using nails or screws through the top and side nailing strips.
  5. Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
    • Note: For best results and optimum performance with each approved venting system, it is highly recommended to apply the “Mill-Pac” sealant (supplied) to every inner pipe connection.
    • Failure to do so may result in drafting or performance issues not covered under warranty. Horizontal runs of the vent must be supported every 3 feet (0.9 meters). Wall straps are available for this purpose.
  6. Mark the wall for a square hole.-see chart to left for size. The centre of the square hole should line up with the centre line of the horizontal pipe.
    • Cut and frame the square hole in the exterior wall where the vent will be terminated. See Diagram 2 for center-line requirements If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, an 8″ (203mm) diameter hole is acceptable.
    • Note:
    • a) The horizontal run of the vent must be level or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.
    • b) The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. See the “Exterior Vent Termination Locations” section for more details.
    • c) Snorkel Terminations:
    • For installations requiring a vertical rise on the exterior of the building, 14-inch and 36-inch tall snorkel terminations as shown in Diagram 2 are available, as well as the standard riser vent.
    • Follow the same installation procedures as used for standard horizontal termination. NEVER install the snorkel upside down.
    • Note: Riser vent is only for use in above-grade terminations.
    • NOTE: For snorkel terminations in ABOVE grade installations, follow national or local code requirements.
    • The vent riser is only available with 4″ x 6-5/8″ venting. With 5″ x 8″ venting, use an optional snorkel termination.
    • Below-Grade Snorkel Installation
    • If the snorkel termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the snorkel termination.
    • Do not attempt to enclose the snorkel within the wall or any other type of enclosure. See diagram 2c.
  7. Ensure that the pipe clearances to combustible materials are maintained (Diagram 5). Install the termination cap.
    • Note: If installing termination on a vinyl siding-covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
    • The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
  8. Before connecting the horizontal run of the vent pipe to the vent termination, slide the Wall Thimble over the vent pipe. The wall thimble is required for all horizontal terminations.
  9. Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. The vent pipe must extend into the vent cap sufficient distance to result in a minimum pipe overlap of 1-1/4 inches (32mm). Secure the connection between the vent pipe and the vent cap.
  10. Install a wall thimble in the centre of the framed hole and attach it with wood screws (Diagram 4).

UNIT INSTALLATION WITH HORIZONTAL TERMINATION 5″ X 8″ VENTING (Flex Vent Systems)

  • Minimum Vent Clearances to Combustibles
  • Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2″ (38mm).
Horizontal Top 2″ (51mm)
Horizontal Side 1-1/2 ” (38mm)
Horizontal Bottom 1-1/2″ (38mm)
Vertical Vent 1-1/2″ (38mm)

Below are the recommended framing dimensions (inside measurements) for the 5″ x 8″ flex vent terminations – for use with a firestop or wall thimble.

Recommended Framed Opening Size

Vent Size| Framing Size
5″ x 8″| 11″ x 11″

  1. Locate the unit in the framing, rough in the gas (preferably on the right side of the unit). Locate the centerline of the termination and mark the wall accordingly. Cut a square hole in the wall – see chart (inside dimension).
    • Note: If installing termination on a siding-covered wall, a vinyl siding standoff or vinyl furring strips must be used to ensure that the termination is not recessed into the siding.
  2. Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
  3. Assemble the vent assembly by applying Mill-Pac to the inner flue collar of the termination and slipping the inner flex liner over it at least 1-3/8″ (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill-Pac to the outer flex pipe and slip it over the outer flue collar of the vent terminal at least 1-3/8″(35mm) and fasten with the 3 screws.
    • NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meters). (Flame picture and performance will be affected by sags in the liner).
  4. Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls.
  5. Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with a proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
  6. Pull the centre inner and outer flex liner out enough to slip over the flue collars of the fireplace. (You may wish to cut the liner shorter to make it more workable.) Do not bend the liner more than 90o. The liners must slip over the collars a minimum of 1-3/8″.
  7. Apply Mill-Pac over the fireplace inner flue collar and slip the inner flex liner down over it and attach with 3 supplied screws.
  8. Do the same with the outer flue collar and outer flex liner.
  9. Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall to keep the water out.
  • IMPORTANT: Do not locate the termination hood where excessive snow or ice buildup may occur.
  • Be sure to check the vent termination area after snow falls, and clear to prevent accidental blockage of the venting system.
  • When using snow blowers, make sure snow is not directed towards the vent termination area.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Regency User Manuals

Related Manuals