AccentPDIR ACS Series ACS-075-R Water Meters with Contact Output User Manual

June 6, 2024
AccentPDIR

AccentPDIR - Logo

ACS Series
Multi-jet Dry Type
Water Meters with Contact Output
ACS-075-R ·ACS-100-R
ACS-150-R ·ACS-200-R
USER MANUAL

AccentPDIR ACS Series ACS-075-R Water Meters - Cover

Multi-jet Dry Type
Water Meters with Contact Output
ACS-075R-200R

Main Technical Data

Nominal diameter| DN| 062-5/Tx
1/2″| 075-3/4″| 100-1″| 150-1 1/2″| 200-2″
---|---|---|---|---|---|---
Maximum flow rate US gpm| Qmax| 13.| 22| 31.| 88| 132
Nominal flow rate US gpm| Qn| 7.| 11| 15.| 44| 66
Transition flow rate US gpm| Qt| 0.53| 0.88| 1.| 4.| 5.
Minimum flow rate US gpm| Qmin| 0.133| 0.22| 0.31| 0.88| 1.
Minimum reading US gallon| 0.01| 0.01| 0.01| 0.1| 0.1
Minimum graduation US gallon| 0.005| 0.005| 0.005| 0.05| 0.05

* Maximum Permissible Error:
In the lower zone from Qmin inclusive up to but excluding Qt is ±5%.
In the upper zone from Qt inclusive up to and including Qmax is ±2%.

**Accuracy Curve

AccentPDIR ACS Series ACS-075-R Water Meters - Maximum Permissible
Error** Specifications

Temperature 105°F (40°C) max
Pressure 150 psi operating
Materials Body Cast bronze
Inter- Engineered thermoplastic
Magnet Alnico
Accuracy +1- 1.5% of reading
Sensor Reed switch
Maximum Current 20 mA
Maximum Voltage 24 Vdc or Vac
Cable Length 12′(4m) std (2000’max run)

General Information

ACS Series meters use the internationally-accepted multi-jet principle. A gear train drives the register totalizer dials. For pulse output, one of the pointers is replaced by a magnet arm, which is detected by a reed switch sensor attached to the outside of the lens. The reed switch provides dry contact closure and does not require power.

Pulse Output

Reed switch sensors respond to a magnet that rotates on the face of the meter under the lens. The sensor turns on and off once each time the magnet passes under it. Sensors are designed for electronic control loads, and should not be used to switch power loads or line voltages. See maximum current and voltage ratings, under specifications.

Inlet Strainer

Clean the strainer yearly, or as required, depending on water condition. Pull out the strainer or back-flush the meter to loosen trapped particulates.

Calibration

New meters are factory tested to meet AWWA C-708 Multi-Jet Meter accuracy specification.

Suggested Meter Installation

  • Thoroughly flush the service line upstream of the meter to remove dirt and debris.
  • Set the meter inline. Water meters are recommended to be installed horizontally with the register facing upwards.
  • Make sure the water flow follows the arrow cast on the meter body.
  • Slowly open any upstream valves to prevent damage to the meter.

Connection Diagrams

AccentPDIR ACS Series ACS-075-R Water Meters - Connection
Diagrams

Changing Pulse Rates

The pulse rate is determined by the dial on which the magnet pointer is located. To move the magnet pointer, 2″ remove meter top and lens, taking care not to lose the sealing ring. With fingers, lift the magnet pointer off its shaft and remove the plain pointer from the target dial. Reverse their positions and press them firmly into place. Securely seat the sealing ring and then replace the lens, matching the tab on the lens to the notch on the meter so as to align the sensor with the magnetic pointer dial. Thread the meter top on and tighten.

Meter Size| Pulse Rate| Drive Gear Position| Connection Diag.#
---|---|---|---
3/4″| 20 PIG| X0.01| 2
10 P/G| X0.01| 1
4 P/G| X0.1| l& magnet wheel
2 P/G| X0.1| 2
1 P/G| X0.1| 1
5 G/P| X1| 2
10 G/P| X1| 1
50 G/P| X10| 2
100 G/P| X10| 1
1″| 20 P/G| X0.01| 2
10 P/G| X0.01| 1
4 P/G| X0.1| l& magnet wheel
2 P/G| X0.1| 2
1 PIG| X0.1| 1
5 G/P| X1| 2
10 G/P| X1| 1
50 G/P| X10| 2
100 G/P| X10| 1
1-1/2″| 4 P/G| X0.1| l& magnet wheel
2 P/G| X0.1| 2
1 P/G| X0.1| 1
5 G/P| X1| 2
10 G/P| X1| 1
50 G/P| X10| 2
100 G/P| X10| 1
2″| 4 P/G| X0.1| 1& magnet wheel
2 P/G| X0.1| 2
1 P/G| X0.1| 1
5 G/P| X1| 2
10 G/P| X1| 1
50 GIP| X10| 2
100 G/P| X10| 1

Warranty

ACS water meters are warranted to perform to AWWA new meter accuracy standards and to be free from defects in materials and workmanship for a period of 12 months from date of shipment. If a meter does not perform as warranted, AccentPDIR will repair it free of charge subject to the terms of this warranty.
AccentPDIR liability under this performance warranty is expressly limited to the repair or replacement of the meter upon the customer’s returning the complete meter prepaid to:
AccentPDIR
Repair Department
2564 Industry Lane
Norristown, PA 19403
This performance guarantee shall not be applicable to meters which have been damaged by aggressive water conditions, foreign matter in media, mis- application, willful misconduct, negligence, vandalism, act of God, improper installation, frost/ freeze damage or using the meter outside of it’s specific operating parameters (especially temperature and flow ranges).
In no event shall AccentPDIR be liable for incidental or consequential damages of any kind, including but not limited to loss of profits or revenue, loss of use, cost of capital, cost of substitute equipment, facilities or services, downtime costs, delays and claims of customers of the customer or other third parties.

Internal Parts Replacement

All the internal parts of the meter lift out as a unit, after the top has been unscrewed. The lens can then be removed and the internal assembly lifted out. If necessary, turn the meter upside down and tap one end lightly on a countertop to loosen the internals. The assembly can be separated by hand.
AccentPDIR ACS Series ACS-075-R Water Meters -
Warranty

| Parts| 3/4″| 1″| 1 1/2″| 2″
---|---|---|---|---|---
1.| Lid/Hinge Assembly-Totalizer| A0323| A0324| A0325| A0326
1.| Lid/Hinge Assembly-Pulser| A0023| A0024| A0025| A0026
2.| Retaining Ring-Totalizer| A0328| A0329| A0330| A0331
2.| Retaining Ring-Pulser| A0128| A0129| A0130| A0131
3| Lens Gasket| A0004| A0005| A0006| A0006
4.| Lens-Totalizer| A0303| A0303| A0303| A0303
4.| Lens-Pulser| A0003| A0003| A0003| A0003
5| 0-Ring (clockwork seal)| A0044| A0044| A0044| A0044
6| Register Clockwork – Internal Assembly-includes: Register, central Gear, Magnetic Shield, Bushing, Register Chamber, Chamber Gasket, Impellar, Measuring Chamber, Internal Strainer| A0077| A0099| A0113| A0114
7| Strainer| A0120| A0121| A0122| A0123
8| Reed Switch Sensor w/cable, 1 ct.| A0001| A0001| A0001| A0001
8| Reed Switch Sensor w/cable, 2 ct.| A0002| A0002| A0002| A0002
9| Internal Strainer| A0015| A0017| A0019| A0021
10| Coupling Gasket, 2 ct./meter| A0028| A0030| A0032| A0034
11| Coupling Assembly| A0027| A0029| A0031| A0033

www.accentpdir.com · 2564 Industry Lane · Norristown, PA 19403 · 888-265-5632