ENCELIUM Edge Standalone Wireless Light Management System Installation Guide

June 6, 2024
ENCELIUM

Edge Controller

PRODUCT SAFETY

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ THESE INSTRUCTIONS BEFORE USING THIS PRODUCT
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
The use of accessory equipment is not recommended by Encelium as it may cause an unsafe condition.
Do not use this equipment for anything other than the intended use.
****The Edge Controller must be installed in dry, indoor locations ONLY. Damp locations are defined as interior locations subject to moderate degrees of
moisture such as basements, barns, cold-storage warehouses, as well as partially protected locations under canopies, marquees, and open-roofed porches.

SAVE THESE INSTRUCTIONS.

GETTING STARTED

Overview
The Edge Controller configures and monitors the various components of the Encelium Edge standalone wireless lighting control system. For optimum performance, the Edge Controller may be installed onto a wall or ceiling surface. Installation into plenum-rated spaces is possible but NOT preferred.

EDGE CONTROLLER

Modular Installation
The Edge Controller must be connected to the supplied Encelium Edge Controller Power Supply Unit or an Ethernet PoE network switch using standard CAT-5 (or greater) Ethernet cabling. If a PoE network switch is not available, a PoE injector (active or passive) may be used. Ethernet PoE network switch or PoE injector connects to the PoE port pointed by POE-IN arrow.

  • The Edge Controller has been tested in accordance with UL2043 and is suitable to be used in plenum or “plenum rated” areas.
  • The Edge Controller may be installed into a drop-ceiling tile (preferred installation), directly onto a wall junction box, or onto a wall surface.

****Pay careful attention to the POE-IN and NC labels at the rear of the Edge Controller. The Ethernet cable from the Edge Controller Power Supply Unit or Ethernet PoE network switch or PoE injector connects to the PoE port pointed by the POE-IN arrow.

Ceiling Tile Installation

This is the preferred installation method for maximum antenna performance.

  1. Cut a hole in the ceiling using the supplied template (the cardboard cutout holding the ceiling mount bracket in place in the packaging).
  2. Assemble the Edge Controller and the ceiling mount bracket together. Push the ceiling mount bracket until the lock snaps into the groove.
  3. Push the assembled Edge Controller through the ceiling tile.
  4. Place the upper bracket onto the Edge Controller (above the ceiling tile from the plenum area) until it locks with the lower bracket.
  5. Connect the Ethernet cable to the PoE port using the POE-IN arrow point on the Edge Controller for alignment.

****GreenBus uses proprietary connectors and jacks for ease of installation only. GreenBus is a proprietary standard. Connect to Encelium X Lighting Control System only. Do not connect to other circuits.

Wall Junction Box Installation

  1. Connect the Ethernet cable to the PoE port using the POE-IN arrow point on the Edge Controller for alignment.
  2. Install the Edge Controller onto the box screws.

Wall Surface Installation

  1. Pre-drill two holes (3.28 inches or 83.3mm apart) on the wall using the supplied template.
  2. Install wall plugs and the supplied screws into the pre-drilled holes.
  3. Connect the Ethernet cable to the PoE port pointed by the POE-IN arrow on the Edge Controller.
  4. The Edge Controller must be mounted vertically.

EDGE CONTROLLER POWER SUPPLY

Top and Bottom Views

Junction Box Installation
Attach the Edge Controller Power Supply to a NEMA-approved Junction Box.

PoE Cable Installation
Attach PoE cable to the Edge Controller Power Supply.

Troubleshooting

There are no user-serviceable parts inside. For detailed information about how to set up, install, use, and maintain Encelium hardware and software, please visit: help.encelium.com

Regulatory Approval

Modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment under FCC rules.

This equipment has been tested and found to comply with Industry Canada ICES-003 Issue 5 (CAN ICES-3 (A)/NMB-3(A)).
Contains FCC ID: H79DFZM-E7210
Contains IC ID: 4259B-DFZM7210

Notes: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Copyright © 2021 Digital Lumens, Incorporated. All rights reserved. Digital Lumens, the Digital Lumens logo, We Generate Facility Wellness, SiteWorx, LightRules, Intelligence, Encelium, the Encelium logo, Polaris, GreenBus, and any other trademark, service mark, or tradename (collectively “the Marks”) are either trademarks or registered trademarks of Digital Lumens, Inc. in the United States and/or other countries, or remain the property of their respective owners that have granted Digital Lumens, Inc. the right and license to use such Marks and/or are used herein as nominative fair use. Due to continuous improvements and innovations, specifications may change without notice. DOC-000442-00 Rev A 11-21

INSTALLATION INSTRUCTIONS
Edge Controller Installation Instructions

https://encelium.com/

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ENCELIUM User Manuals

Related Manuals