NetGuard 1500VA PowerShield Gladiator PSGL1500 User Manual
- June 6, 2024
- NetGuard
Table of Contents
PSGL1500
1500VA GLADIATOR
Line Interactive Pure Sine Wave UPS
Software
Download the latest PowerShield NetGuard
UPS Monitoring Software:
www.powershield.com.au/downloads
Default password : administrator
Australian Designed Power Protection Solution
SAFETY INSTRUCTION
Thank you for purchasing this PowerShield power protection product. Please comply with all warnings and operating instructions in this manual. Save this manual and carefully read the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
Transportation
- Please transport the UPS system only in the original package to protect against shock and impact.
Preparation
-
Do not dismantle the UPS system.
-
Do not plug the UPS input into its own output.
-
Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.
-
Condensation may occur if the UPS system is moved directly from a cold to a warm environment.
The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment. -
Do not install the UPS system near water or in moist environments.
-
Do not install the UPS system where it would be exposed to direct sunlight or near a heater.
-
Do not block ventilation holes in the UPS housing.
Installation
-
This unit is intended for installation in a controlled environment (temperature-controlled, indoor area free of conductive contaminants).
Avoid installing the UPS in locations where there is standing or running water, or excessive humidity. -
Caution – Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Operation
- Prevent fluids or other foreign objects from entering the UPS system.
- Do not connect appliances or devices to the UPS output sockets which would overload the UPS system.
- Place cables in such a way that no one can step on or trip over them.
- Do not connect domestic appliances such as hair dryers to UPS output sockets.
- Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
Maintenance, service, and faults
- The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
- Caution – the risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous. Do not open the unit.
- Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capacity BUScapacitors.
Storage & Maintenance
The UPS system contains no user-serviceable parts. If the battery service life (3-5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a
cool, dry location.
During storage, recharge the battery in accordance with the following table:
Storage Temperature | Recharge Frequency | Charging Duration |
---|---|---|
0 – 40°C | Every 3 months | 1-2 hours |
Introduction
This PowerShield product is an intelligent line interactive pure sinewave UPS (Uninterruptible Power Supply) which is designed to protect your personal computer or sensitive electronic equipment from all forms of power interference, including complete power failure.
Package Contents
NOTE: Before installation, please inspect the unit. Be sure that nothing
inside the package is damaged. Please keep the original package in a safe
place for future use. You should have received the following items inside of
the package:
1. UPS unit 2. User manual 3. USB cable
Product Overview
- LCD display (Please check LCD section for the details)
- Up/down button
- Mute button
- ON / OFF button
- USB charger ports (5V 3A, type A/type C) for device charging
- USB communication port for UPS monitoring and control
- Input circuit breaker
- Battery backup outlets
- AC input for connecting to utility power
Installation
Before installing the UPS, please read below to select a proper location to
install the UPS.
If this up has been idle for a minimum of 6 months the batteries will require
recharging before use.
It is recommended to recharge the batteries by simply plugging it in for a
period of around 5 hours.
- UPS should be placed on a flat and clean surface. Place it in an area away from vibration, dust, humidity, high temperature, flammable liquids and gases, corrosive and conductive contaminants. Install the UPS indoors in a clean environment, where it is away from windows and doors.
- The maximum altitude is 1000m to keep the UPS in normal operation at full load. If it’s used in higher altitude areas, please reduce the connected load. Altitude derating power with connected loads for UPS normal operation is listed as below:
Altitude (m)| Derating factor1)
---|---
1000
1500
2000
2500
3000
3500
4000
4500
5000| 1.0
0.95
0.91
0.86
0.82
0.78
0.74
0.7
0.67
Based on the density of dry air =1.225 kg/m3 at sea level, +15ºC
(1) Since fans lose efficiency with altitude, force air-cooled equipment will have a smaller derating. - Place UPS: This PowerShield up is equipped with a fan for cooling. Therefore, place the UPS in a well-ventilated area. Maintain a minimum clearance of 100mm in the front of the UPS and 300mm in the back and sides of the UPS for heat dissipation and easy maintenance.
Step 1: UPS Input Connection
Plug the UPS into a two-pole, three-wire, grounded receptacle. Avoid using
extension cords. For the best results, charge the battery at least 5 hours
before initial use. The unit charges its battery while connecting to the
utility.
Note: Do not expect full battery run capability during this initial
charge period.
Step 2: UPS Output Connection
Connect the computer and monitor to the outlets. These outlets provide battery
backup, EMI filtering, line conditioning, and surge protection. Battery power
is automatically provided in case of power failure.
CAUTION: NEVER connect a laser printer or scanner to the UPS. The
equipment may draw significant power to overload the UPS.
Step 3: Connect Communication Port and Install Software
Connect one end of the USB cable to PC and the other to the USB port at the
rear of the UPS.
Download the latest version of NetGuard® Software from
https://powershield.com.au/supportmenu/download-area/netguard-software-
downloads to your hard drive. Follow on-screen instructions to complete the
software installation.
To monitor CPU speed, temperature, and percentage (%) CPU resources please download and install the CPU Monitor file. Once installed, the user can configure the CPU Monitor to autorun on Windows Startup and send CPU Information to the UPS directly. Note: CPU Monitor is only available for= Windows.
The CPU Monitor file can be downloaded from https://powershield.com.au/supportmenu/download-area/netguard-software- downloads/
HID Function
This PowerShield UPS is equipped with HID function. You may simply connect one
computer with the installed OS via USB port to execute safe shutdown during
power failure even though there is no monitoring software installed.
Step 4: Turn On the UPS
Before using the UPS, be sure to remove this label from the LCD remote panel
module.
To turn on the UPS, simply press the ON/OFF button on the front panel for 2 seconds. UPS will beep once and LED bars will light up with different colors in order of light blue, orange, yellow, green, blue, purple, and scroll from bottom to top in 6 secs. Then, LCD will light on.
Remote panel operation
The LCD panel can be removed from the base and placed close to you when playing a PC game. Follow the illustrations below to remove the remote panel. The distance between the remote panel and base should not be more than 6m.
There is a NiMH battery installed on the back of remote panel. Once the remote panel is installed on the base unit, it will automatically charge the battery. When the battery capacity is low level, the icon will flash to remind users to charge the remote panel.
Battery Replacement
Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries. Typical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short-duration discharges have a negative impact on battery life.
-
WARNING! This PowerShield UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure.
-
This UPS contains no user-serviceable parts. Repairs and battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
-
Caution – Do not dispose of batteries in a fire. The batteries may explode.
-
Caution – Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
-
Caution – A battery can present a risk of electrical shock and a high short-circuit current. Contact with any part of a grounded battery can result in electrical shock. The following precautions should be observed when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source and load prior to installing or servicing the battery.
f) Remove battery grounds during installation and maintenance to reduce the likelihood of shock.
Remove the connection from the ground if any part of the battery is determined to be grounded. -
Caution – the risk of electric shock. The battery circuit is not isolated from the input voltage.
Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present. -
Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
-
Caution – Replace batteries with the same number and type as originally installed in the UPS.
These batteries have pressure-operated vents. These UPSs contain sealed non- spillable maintenance-free lead-acid batteries.
Please follow the steps below to replace the batteries if necessary.
Step 1: Turn off the equipment that is plugged into the output of the UPS.
Step 2: Turn off the UPS.
Step 3: Remove the AC input plug of the UPS from the AC wall outlet.
Step 4: Remove all equipment from the output sockets of the UPS.
Step 5: Remove the battery cover by loosening two screws located on the bottom
of the UPS and slide the battery cover downward, then outward. Set it aside.
Step 6: Disconnect the battery wires (BAT+ and BAT-). Then, slide out the
existing battery pack from the UPS by grasping the battery tape.
Caution – Do not short the positive wire and negative wire of battery.
Caution – DO NOT pull the battery pack out by pulling the battery wires.
Step 7: Slide the new battery pack into the UPS.
Step 8: Verify proper polarity. Re-connect the battery connectors together.
NOTE- Some sparking might occur and this is normal when reconnecting
batteries.
Step 9: Re-install the battery cover onto the UPS. Now, the UPS is ready for
normal operation.
NOTICE: Properly dispose of the old batteries at an appropriate recycling
facility or return them to the supplier in the packing material for the new
batteries.
Operation
Button Function
Button|
Function
---|---
ON/OFF| • Press and hold 2 seconds to turn on or off the UPS.
• Hold “on/off” button for 10 seconds to reset the unit in case of
communication failure between the remote panel and UPS.
• Quick press 5 times to reset pairing when a wireless transmission fails.
MUTE| Press and hold 2 seconds to enable or disable the mute function.
UP/DOWN| • Press and hold 0.5 seconds to switch display information.
• Press and hold 2 seconds to enter the setting menu.
LCD Panel
Display|
Function
---|---
Configuration and fault information
| Indicates the fault or warning codes.
Mute operation
| Indicates that the UPS alarm is disabled.
Input, Battery, Backup time, Output & Load information
| Indicate the input voltage, input frequency, battery voltage, battery
capacity, backup time, output voltage, output frequency, load capacity, load
percentage, NiMH battery, PC CPU speed, PC CPU temperature and PC CPU load
percentage.
K: kilo, W: watt, V: voltage, A: ampere, %: percent, ℃: centigrade degree,
Hz: frequency, min: minute.
Load information
| Indicates the
load level by 0-24%, 25-49%, 50-74% and 75- 100%, or overload alarm.
Mode operation information
| UPS operates on the Line mode.
| UPS operates on the AVR mode.
| UPS operates on the Battery mode.
| The setting of LED bars.
| Indicates PC’s CPU temperature (°C)
Setting the temperature alarm level.
| Indicates PC’s CPU speed (Mhz)
| Indicates PC’s CPU Load
| Indicates wireless connection matched.
| This indicates the remote panel is connected to the docking base.
Battery information
| Indicates the UPS
battery level by 0-24%, 25-49%, 50-74%, and 75-100%.
Once the battery is at a low level, “LOW BATT” icon will display.
| Indicates the NiMH battery level of the remote panel.
*Except UPS fault condition, LCD backlight automatically shuts off if no action for 1 minute (30 seconds when panel is removed from base).
Audible Alarm
Overload | Sounding every 0.5 seconds |
---|---|
Low battery | Sounding every second |
Overcharge | Sounding every 1.5 seconds |
Battery replacement | Sounding every 2 seconds |
Battery mode | Sounding every 10 seconds |
Fault | Continuously sounding |
Warning Indicator
Display| Warning| Flashing/on|
Alarm
---|---|---|---
| Over-current on output| Flashing every 0.5 secs| Sounding every 0.5 secs
| Overload| Flashing every 0.5 secs| Sounding every 0.5 secs
| Low battery| Flashing every 0.5 secs| Sounding every 1 sec
| Battery replacement or battery is not connected.| On| Sounding every 2
secs
| Abnormal NiMH battery charging| Flashing every 0.5 secs| N/A
LCD Setting
After pressing and holding the “UP/DOWN” button for 2 seconds, the unit will enter setting mode. Press the “UP/DOWN” button to select setting programs. Press the “ON/OFF” button on the selectable option page. Press the “ON/OFF” button again to access selectable options. Press the “UP/DOWN” button to switch different options. Once the option is selected, press the “ON/OFF” button to confirm or the “MUTE” button to exit.
Setting Programs:
Display Setting
The LCD display information will be switched in turns by pressing the “UP/DOWN” button. The selectable information is switched as below order: input voltage, input frequency, battery voltage, battery capacity, estimated backup time, output voltage, output frequency, output in kW, output load percentage, NiMH battery voltage, PC CPU frequency, PC CPU temperature, CPU utilization, panel board firmware version, Baseboard firmware version, and UPS control board firmware version.
Trouble Shooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Problem/Fault code
| Possible Cause/Fault Event|
Solutions
---|---|---
UPS will not turn on after pressing On/Off button.| Hold the On/Off button too
short.| Press and hold the On/Off button for at least 2 seconds and then
release.
The main supply is normal, but the UPS is operating in battery mode.| Power
cord is loose.| Re-connect AC input power cord.
Circuit breaker is tripped.| Reset the input circuit breaker. If the input
circuit breaker trips after UPS restarts, remove excessive loads from the UPS.
The AC normal icon is illuminated, but there is no output.| The UPS has an
internal fault.| Restart the UPS and press the On button. If the UPS works
normally, the software has control of the UPS.
Battery backup time is shorter than the nominal value.| Batteries are not
fully charged.| Charge the batteries for at least 5 hours and then check
capacity. If the problem still persists, consult your dealer.
Battery defect.| Contact your dealer to replace the battery.
Fault code E12 and is on. icon| The output voltage is too high on battery
mode.| Contact your dealer.
Fault code: E13 and icon are on.| The output voltage is too low on battery
mode| Contact your dealer.
Warning code E32 and icon are flashing.| Communication lost between UPS and
Base.| Contact your dealer.
Warning code E32 and icon flashes.| The distance between the remote panel and
the docking base is out of wireless transmission range.| Keep the distance of
the remote panel and the docking base closer.
Error occurs in the process of paring passwords.| Quick press the “ON/OFF”
button 5 times to reset the pairing. At this time, the remote panel is
required to connect to the docking base.
Fault code E14 and is on. icon| Output is short-circuited.| Check if connected
devices are in short circuit status. Disconnect short-circuited loads and
restart the UPS again.
Fault code E15 and is on. icon| Overcurrent on output.| Reduce the connected
load by switching off some equipment.
Fault code E20 and is on. icon| Fan lock fault.| Contact your dealer.
Fault code E21| Overcharge voltage| Contact your dealer.
Fault code E28 and icon are on.| Low battery voltage.| Please replace the
battery. If the fault still occurs after the battery is replaced, contact your
dealer.
Fault code E43 and icon are on.| Overload fault| Contact your dealer.
icon is illuminated and a constant alarm.| The UPS has an internal problem.|
Contact your dealer.
Specifications
POWERSHIELD GLADIATOR GAMING UPS
MODEL| GLADIATOR GAMING UPS
Model Number| PSGL1500
Capacity| 1500VA / 900W
INPUT
Voltage| 240 VAC
Voltage Range| 170~280VAC
OUTPUT
Voltage| 240 VAC
AC Voltage Regulation (Batt. Mode)| ±10%
Frequency Range (Batt. Mode)| 50/60 Hz ±1 Hz
Harmonic Distortion| 3% THD (Linear Load), ; 5 % THD (Non-linear Load)
Transfer Time| 6ms typical, 10ms max
Waveform (Batt. Mode)| Pure Sine Wave
Outlets| 6 x Australian Outlets with surge and battery backup
USB Charger| USB-A and USB-C 5V / 3 Amp
BATTERY
Battery Type and Number| 12 V/9 Ah x 2
Typical Recharge Time| 6~8 hours recover to 90% capacity
PROTECTION
Surge Protection| 1140 Joules / 30,000 Amps
INDICATORS
LCD Display| Input/output voltage, input/output frequency, load in VA/Watts,
battery capacity, estimated remaining runtime, site wiring fault indications.
PHYSICAL
Dimension, (D x W x H) mm Tower| 430 x 99 x 280
Weight (kg)| 13.3
OPERATING ENVIRONMENT
Humidity| 50-90 % RH @ 0- 40°C (non-condensing)
Noise Level| Less than 45dB
COMMUNICATIONS AND MANAGEMENT
Interface| USB
Software Support| PowerShield® NetGuard® software – supports Windows, Linux,
Unix, and Mac-based operating systems*
COMPLIANCE
Compliance & Standards| CE (Class B ), EN 62040-1:2008/A1:2013, IEC
62040-1:2008/A1:2013
RoHS| Directive 2001 /65 / EU
Product specifications are subject to change without prior notice. *CPU monitoring software available only for Windows OS.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>