SELKIRK RV (3” to 8”) Type B Gas Vent
GAS VENT DESIGNATIONS/TYPES OF APPLIANCES
Selkirk Canada Corporation Type B Gas Vent parts LISTED and produced under the
Factory Inspection and Follow-up program of Underwriters’ Laboratories, Inc.
carry the LISTING MARK illustrated here. Type B Gas Vent has been tested, and
listed using all of the supports, firestop, etc., described herein. Deletion
or modification of any of the required parts or materials may seriously impair
the safety of your installation, and void the certification and or warranty of
this vent. It is of the utmost importance that this vent be installed only in
accordance with these instructions.
Model RV is listed to CAN/ULC-S605, UL 641, available in diameters 3” to 8”.
Type B Gas Vent is designed for venting of listed (L.P. or natural) gas
appliances equipped with draft hoods and other listed gas appliances specified
for use with Type B gas vent producing flue gas temperatures not in excess of
245oC (470o F). DO NOT USE Type B Gas Vent for Category II, III or IV gas
appliances, or for any gas appliance which requires either a pressure-tight or
liquid-tight venting system.
All sizes of Selkirk Type B Gas Vent may be used in single and multistory
buildings. All Type B Gas Vents may be used for both individual and multiple
appliance venting.
Selkirk Type B Gas Vents are to be installed and used in accordance with the
Canadian Fuel Gas Installation Code CSA-B149.1-00, and/or applicable local/
regional codes.
CERTIFICATION LABELS
WARNING
Failure to follow the installation instructions could cause FIRE, CARBON
MONOXIDE POISONING, OR DEATH. If you are unsure of installation requirements,
call the Phone Number listed on the instructions,
1-888-735-5475 or visit
www.selkirkcorp.com.
GENERAL
Before beginning your installation be sure that the overall height and Gas
Vent size conform to building code requirements. Use Selkirk Gas Vent and
Chimney Sizing Handbook or the Fuel Gas Codes to select the correct Gas Vent
diameter. Avoid using a larger than necessary vent diameter. Situate the Gas
Vent in the structure so that it can be installed without cutting joists,
sills, plates or major load bearing partitions or members. It is also
important to locate the base of the Gas Vent as near as possible to the
heating appliance.
Selkirk Type B Gas Vent must be installed with 25mm (1”) minimum air space
clearance to combustibles. Where the Gas Vent extends through inhabited
spaces, it must be enclosed with 25mm (1”) clearance to avoid personal contact
and damage (see Fig. 2). These clearances are marked on all gas carrying items
and they apply whether they are horizontal or vertical, or pass through
floors, walls, roofs or framed spaces. The appropriate clearance should be
observed to joists, studs, subfloors, plywood, drywall, or plaster enclosures,
insulating sheathing, rafters, roofing, and any other materials classed as
combustible. Enclosure material should have a fire resistance rating at least
equal to that of adjacent floor or ceiling material. Keep electrical wires and
building insulation away and out of the required air space.
A NOTICE SHOULD BE POSTED near the point where the Gas Vent is connected to
the appliance, with the following wording: “Connect this Gas Vent only to gas
burning appliances, as indicated in the installation instructions and do not
connect to incinerators, or liquid or solid fuel burning appliances”. A
reminder also to homeowners to check the rain cap for icing during low ambient
temperatures.
GAS VENT JOINT METHOD
All joints in Selkirk Type B Gas Vent must be secured using the “Snap Lock”
feature. To use the Snap Lock feature, orient sections as shown in Fig.1 and
force adjacent piece together until a “SNAP” is heard, indicating full/proper
joint engagement. NOTE: Some local jurisdictions require a supplemental
screw(s) at joints to prevent disengagement of the joint. Although not
required under the terms of the UL Listing because of the integral couplers,
screws are permitted to be installed at the joints in RV Gas Vent. In such
case, the screws should be located aprox. 1/4” from overlapped edge and must
be maximum 1/4” in length so they do not pierce or deform the inner liner. A
new Lock-Tab® feature provides the equivalent of using a screw for this
purpose since, once engaged (with finger or thumb until it bends into the
groove in the top/ outlet end of the adjacent piece), it prevents the pipes
from being disengaged unless the tab is pried backout and dimples aligned
CAUTION: WEAR GLOVES WHILE HANDLING METAL PARTS TO AVOID PERSONAL INJURY. SHARP EDGES OR PROJECTIONS CAN CUT YOU.
Attic Insulation Shield
An Attic Insulation Shield must be installed where the vent passes into an
attic space. It is designed to keep insulation materials or debris from coming
into contact with the vent. It must accomodate the amount of insulation as
required by the National Building Code.
Where height restictions will not permit the use of the Attic Insulation
Shield, it is permissible to construct an enclosure with a 1″ air space
clearance to the outer pipe all the way to the underside of the roof deck. In
this application you would install a Firestop Spacer on the ceiling side.
For a proper installation, the opening must be fully framed at 1″ of clearance
to the outside casin of the pipe with framing material of the same dimension
as the ceiling or floor joist. Install the AIS from above and secure base with
nails or wood screws.
Seal the vapour barrier to the firestop or ceiling support assembly using an
appropriate caulking compound as per the requirement of local authorities.
AIR SUPPLY
Gas appliances must have an adequate air supply for combustion, vent operation, and ventilation. Special provisions for bringing in outside air may be necessary in tight buildings or when appliances are in small rooms. Consult the CSA-B149.1 Installation Code for gas and propane, and/ or local building codes for air supply requirements.
VENT CONNECTOR TYPE AND SIZE
Selkirk Gas Vent pipe meets all building codes and safety standards for use as
gas appliance vent connectors. Correct selection of connector and vent size is
detailed in the Selkirk Gas Vent and Chimney Sizing Handbook, the Installation
Gas Code CSA-B149.1-00, and/or local/regional codes.
Draft hood connectors must be attached to the appliance outlet with screws.
Single wall connectors, if used must be secured to the appliance, to the gas
vent, and at all joints with 3 sheet metal screws per joint. Attachment of
vent to non-metallic outlets should be per appliance manufacturer
recommendations.
VENT LOCATION AND ENCLOSURES
Selkirk Type B Gas Vents are recommended to be installed within the heated
portion of the structure wherever pssible to reduce heat loss which may in
turn lead to poor draft and/or condensation or/and ice problems. building can
cause reverse venting action when the appliance is off, or operating on its
pilot. In multi-family residential, high rise and many other types of
buildings, codes specify that vents must be located in firerated shafts or
chases. Building code requirements in such cases must be carefully followed
with respect to wall construction, access, clearance, support, initial
penetration of breaching, and method of termination.
If an exterior location is necessary, an exterior located Selkirk Type B Gas
Vent (as per Figure 4) must be:
- Enclosed by a chase spaced out 1” from the vent at least to the roof line.
- The enclosure should be caulked to prevent entry of moisture.
- It is also recmommended that his chase be insulated to a minimum of R-12 (RSI 2.1).
- Rigid type insulation is recommended. If a non rigid type is use, it must be restrained in such a manner so that the 1” air space clearance to combustible is respected.
- The bottom of the enclosure must be closed off.
- It is recommended to provide an access panel for future inspection and cleaning of the vent.
Appliances served by an exterior gas vent must have an air supply to the
appliance room adequate to balance indoor and outdoor pressures. Otherwise,
“stack action” of the heated building can cause reverse venting action when
the appliance is off, or operating on its pilot.
In multi-family residential, high rise and many other types of buildings,
codes specify that vents must be located in firerated shafts or chases.
Building code requirements in such cases must be carefully followed with
respect to wall construction, access, clearance, support, initial penetration
of breaching, and method of termination.
FIRE STOPPING
All Type B Gas Vents passing through floors, ceilings or walls must be firestopped using the Firestop Spacer as per Fig. 2, 4, 6, 7 and 9. The Firestop must close the area between the outer wall of the pipe and the opening in the structure. In areas such as attics with no floor, the Firestop should be placed on top of a properly framed opening. KEEP WIRES AND INSULATION OUT OF REQUIRED AIR SPACE AROUND GAS VENT. When venting is to be supported the Support Plate must be used as vent pipe supports. See Section 10. For gas vents within a shaft or chase, firestopping is provided by the vertical walls of the shaft. Any openings in the chase/shaft below the roof must be firestopped.
USE OF GAS VENT FITTINGS
(See Figs. 2, 3, 5 & 7.)
Do not cut gas vent pipe or fittings. Adjustable Lengths are telescoped over
fixed lengths, to accommodate odd distances between vent lengths or
connectors. An adjustable length suspended below a support serves as an
expansion joint between two fixed points of properly supported gas vent.
Ordinarily, the adjustable length must be secured, but for expansion joints it
should just maintain good contact and a minimum 1-1/2” overlap. DO NOT USE
adjustable lengths to suspend any weight of pipe below. Elbows are fully
adjustable. Selkirk tees, elbows, increasers, and short lengths are specially
designed to facilitate interconnections. Tees used to start vertical vents
must use a tee cap to prevent air leakage. All unused openings in a gas vent
must be sealed to prevent loss of effective vent action.
MINIMUM GAS VENT HEIGHT
A minimum gas vent height of 5 feet above the appliance draft hood is required (see Fig. 8). Where the vent has an offset, or serves multiple appliances, greater heights may be required for proper venting Special care must be taken with short gas vents on duct furnaces, unit heaters, and furnaces in attics to assure they have sufficient vent height to assure complete venting. Refer to appliance manufacturer instructions and local codes for required minimum heights.
SUPPORT – PRIMARY AND OFFSETS
Gas vent piping must be securely supported. Lateral runs are to be supported
at least every 5 feet. The Support Plate has been tested to support a maximum
of 35’ of Gas Vent; if additional height is required, use another Support
Plate on another floor level. Vertical runs fire stopped at 8 to 10 foot
intervals need only be supported near the bottom.
Cut away and frame a four sided opening in the floor from which the Gas Vent
shall be supported, to provide 25mm (1”) minimum clearance to combustibles.
Nail Support Plate securely to joist and framing members using 4 x 1-1/2” long
nails (1 nail at each corner).
Insert the first length from above through the clamp band and opening of the
support plate to proper elevation. Secure clamping band to the length with
tabs and 1/4” screws (provided) so weight of vent rests on plate. Room should
be left for the draft hood connector and adjustable length.
Additional Gas Vent Lengths above the Support are simply stacked on. See
joining section to secure lengths together.
Insure 1” minimum airspace is established and maintained. Tees used as vent inlets may be supported by sheet metal plates or brackets. Plumbers tape may be used to support both horizontal and vertical piping. Short vents with less than 6 feet of vertical pipe below the flashing may be suspended from the flashing. (The pipe may be supported by the storm collar resting on the top of the flashing.) Use 1/4 inch long sheet metal screws to attach the storm collar to the pipe at the appropriate place. Apply silicone sealant over the sheet metal screw head. Gas vents supported only by the flashing must be guyed above the roof to withstand snow and wind loads. All gas vents extending above the roof more than 5 feet must be securely guyed or braced.
FLASHING
The roof opening should be located and sized such that the vent is vertical
and has the required air space clearance. The Tall Cone Flashing is for flat
roofs only (see Fig. 10). It is nailed in place through all four sides of the
base flange. The Adjustable Roof Flashing (see Fig. 11) is positioned with the
lower portion of the base flange over roofing material and the upper portion
of the base flange under the roofing material. Nail through only the upper
portion and sides of the base flange. (DO NOT nail through lower flange.) Use
nails with a neoprene washer, or cover the nail heads with a silicone sealant.
Finish roofing around the flashing, covering the sides and upper areas of the
flange with roofing material.
VENT TERMINATION
Gas vent piping must extend through the flashing to a height above the roof
determined by Rules shown below. A storm collar is installed on the vent pipe
over the opening between pipe and flashing. Silicone sealant is used over the
joint between pipe and storm collar. The top is securely attached to the gas
vent as per section 13.
Rule I:
The top is suitable for installation on listed gas vents terminating a
sufficient distance from the roof so that no discharge opening is less than 2
feet horizontally from the roof surface, and the lowest discharge opening will
be no closer than the minimum height specified in Fig. 12-B. These minimum
heights may be used provided that the vent is not less than 8 feet from any
vertical wall.
Rule II – Tops for gas vent sizes 14” and larger. For installations other
than covered by the table (Fig. 12-B), or closer than 8 feet to any vertical
wall, the top shall be not less than 2 feet above the highest point where the
vent passes through the roof and at least 2 feet higher than any portion of a
building within 10 feet.
These rules were established on the basis of tests conducted in accordance
with American National Standard ANSI/UL 441.
RV ROUND TOP INSTALLATION
Selkirk Model RV Type B Gas Vent Round Top have a spring clip which engages
and locks automatically when the top is pushed into the upper end of the pipe.
To attach securely, bend a one inch length of the pipe upper end inward about
1/8”. The spring clip will lock under this bent edge. To remove the top from
any pipe, pull up evenly on opposite sides of the skirt of the top. If the gas
vent extending more than 1.25m (4’) above the roof additional lateral support
is required such as Selkirk Roof Brace Kit
CHECKING VENT OPERATION
Complete all gas piping, electrical, and vent connections. After adjusting the appliance and lighting the main burner, allow a couple of minutes for warmup. Hold a lighted match just under the rim of the draft hood relief opening (see Fig. 13). Proper venting will draw the flame toward or into the draft hood. Improper venting, indicated by escape or spillage of burned gas, will cause match to flicker or go out. Smoke from a cigarette will also be pulled into the draft hood if the vent is drawing properly and flow away if not. For fan assisted appliances, which have no draft hood, no such check is available. However, fan assisted appliances are designed to shut down if excessive pressure is detected at the outlet. If this occurs it may be an indication that the system is not venting properly.
PAINTING
Exterior above the roof line portions of the vent may be painted with high
temperature paint to prolong the life and appearance of the venting (and other
components) of Selkirk Gas Vents. Use proper painting procedure at time of
installation. Remove oil and dirt with a solvent and follow the paint
manufacturer instructions. Ordinary house paints applied directly to steel may
not adhere well and do not prevent underfilm corrosion which leads to paint
loosening and peeling
These instructions should be observed when installing Selkirk Gas Vents.
Engineering methods for design and sizing of all Selkirk Gas Vents are
provided in the “Selkirk Gas Vent and Chimney Sizing Handbook”. Following
these methods will assure safe and complete removal of combustion products