DAIKIN FTXTM30R2V1B Room Air Conditioner Instruction Manual

June 6, 2024
Daikin

FTXTM30R2V1B Room Air Conditioner

Installation manual
Daikin room air conditioner

FTXTM30R2V1B FTXTM40R2V1B

Installation manual Daikin room air conditioner

English

Table of contents
Table of contents

1 About the documentation

2

1.1 About this document………………………………………………………… 2

2 Specific installer safety instructions

2

3 About the box

3

3.1 Indoor unit ……………………………………………………………………… 3

3.1.1 To remove the accessories from the indoor unit……… 3

4 About the unit

3

4.1 About the wireless LAN ……………………………………………………. 4

4.1.1 Precautions when using the wireless LAN……………… 4

4.1.2 Basic parameters ……………………………………………….. 4

5 Unit installation

4

5.1 Preparing the installation site ……………………………………………. 4

5.1.1 Installation site requirements of the indoor unit ………. 4

5.2 Mounting the indoor unit…………………………………………………… 4

5.2.1 To install the mounting plate ………………………………… 4

5.2.2 To drill a wall hole ………………………………………………. 5

5.2.3 To remove the pipe port cover ……………………………… 5

5.3 Connecting the drain piping………………………………………………. 6

5.3.1 To connect the piping on right side, right-back, or right- bottom……………………………………………………….. 6

5.3.2 To connect the piping on left side, left-back, or left-

bottom ………………………………………………………………. 6

5.3.3 To check for water leaks ……………………………………… 6

6 Piping installation

6

6.1 Preparing refrigerant piping………………………………………………. 6

6.1.1 Refrigerant piping requirements……………………………. 6

6.1.2 Refrigerant piping insulation ………………………………… 7

6.2 Connecting the refrigerant piping ………………………………………. 7

6.2.1 To connect the refrigerant piping to the indoor unit …. 7

7 Electrical installation

7

7.1 Specifications of standard wiring components …………………….. 7

7.2 To connect the electrical wiring to the indoor unit ………………… 8

8 Finishing the indoor unit installation

8

8.1 To insulate the drain piping, refrigerant piping and

interconnection cable ………………………………………………………. 8

8.2 To pass the pipes through the wall hole……………………………… 8

8.3 To fix the unit on the mounting plate ………………………………….. 9

9 Configuration

9

9.1 To set a different address…………………………………………………. 9

10 Commissioning

9

10.1 Checklist before commissioning………………………………………… 9

10.2 To perform a test run……………………………………………………….. 10

10.2.1 To perform a test run using the user interface ………… 10

11 Disposal

10

12 Technical data

10

12.1 Wiring diagram ……………………………………………………………….. 10

12.1.1 Unified wiring diagram legend………………………………. 10

1 About the documentation
1.1 About this document
INFORMATION Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
Installation manual
2

Target audience Authorised installers
INFORMATION This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.
WARNING Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
Documentation set This document is part of a documentation set. The complete set consists of: General safety precautions:
Safety instructions that you MUST read before installing Format: Paper (in the box of the indoor unit) Indoor unit installation manual: Installation instructions Format: Paper (in the box of the indoor unit) Installer reference guide: Preparation of the installation, good practices, reference data,… Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/ Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer. The original documentation is written in English. All other languages are translations.
Technical engineering data A subset of the latest technical data is available on the regional
Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
2 Specific installer safety instructions
Always observe the following safety instructions and regulations.
Unit installation (see “5 Unit installation” 4[ 4])
WARNING Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.
WARNING The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (e.g. open flames, an operating gas appliance, or an operating electric heater). The room size shall be as specified in the General safety precaution.
CAUTION For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Piping installation (see “6 Piping installation” 4[ 6])
CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units.
DANGER: RISK OF BURNING/SCALDING
CAUTION Use the flare nut fixed to the unit. To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use refrigeration oil for R32. Do NOT reuse joints.
CAUTION Do NOT use mineral oil on flared part. NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system.
CAUTION Incomplete flaring may cause refrigerant gas leakage. Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage. Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.
Electrical installation (see “7 Electrical installation” 4[ 7])
DANGER: RISK OF ELECTROCUTION
WARNING ALWAYS use multicore cable for power supply cables.
WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation. Make electrical connections to the fixed wiring. All components procured on-site and all electrical construction MUST comply with the applicable legislation.
WARNING If the power supply has a missing or wrong N-phase, equipment might break down. Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock. Install the required fuses or circuit breakers. Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side. Do NOT use taped wires, stranded conductor wires, extension cords, or connections from a star system. They can cause overheating, electrical shock or fire. Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

3 About the box
WARNING Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING Do NOT use locally purchased electrical parts inside the product. Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.
WARNING Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.

3 About the box

3.1 Indoor unit

3.1.1 To remove the accessories from the indoor unit

1 Remove:

the accessory bag located at the bottom of the package,

the mounting plate attached to the back of the indoor unit,

the spare SSID sticker located on the front grille.

a b c d e1 e2 f g h i

j

1× 1× 1× 1×

2× 1× 1×

a Installation manual b Operation manual c General safety precautions d Spare SSID sticker e1 Class 30: Silver particle filter (Ag-ion filter) (without
frame) e2 Class 40: Titanium apatite deodorising filter and silver
particle filter (Ag-ion filter) (with frame) f Indoor unit fixing screw (M4×12L). Refer to “8.3 To fix the
unit on the mounting plate” 4[ 9]. g Dry battery AAA.LR03 (alkaline) for user interface h User interface holder i User interface j Mounting plate
Spare SSID sticker. Do NOT throw away the spare sticker. Keep it in a safe place in case it is needed in future (e.g. in case the front grille was replaced attach it to the new front grille).
4 About the unit
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Installation manual
3

5 Unit installation
4.1 About the wireless LAN
For detailed specifications, installation instructions, setting methods, FAQ, declaration of conformity and the latest version of this manual, visit app.daikineurope.com.

INFORMATION
Daikin Industries Czech Republic s.r.o. declares that the radio equipment type inside of this unit is in compliance with Directive 2014/53/EU.
This unit is considered as combined equipment according to the definition of Directive 2014/53/EU.

4.1.1 Precautions when using the wireless LAN
Do NOT use near:
Medical equipment. E.g. persons using cardiac pacemakers or defibrillators. This product may cause electromagnetic interference.
Auto-control equipment. E.g. automatic doors or fire alarm equipment. This product may cause faulty behaviour of the equipment.
Microwave oven. It may affect wireless LAN communications.

4.1.2 Basic parameters

What Frequency range Radio protocol Radio frequency channel Output power Effective radiated power
Power supply

Value 2400 MHz~2483.5 MHz IEEE 802.11b/g/n 1~13 13 dBm 15 dBm (11b) / 14 dBm (11g) / 14 dBm (11n) DC 14 V / 100 mA

5 Unit installation
INFORMATION
If you are not sure how to open or close parts of the unit (front panel, electrical wiring box, front grille…) refer to the installer reference guide of the unit for opening and closing procedures.
WARNING
Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.

5.1 Preparing the installation site
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (e.g. open flames, an operating gas appliance, or an operating electric heater). The room size shall be as specified in the General safety precaution.
5.1.1 Installation site requirements of the indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
Air flow. Make sure nothing blocks the air flow.
Drainage. Make sure condensation water can be evacuated properly.
Wall insulation. When conditions in the wall exceed 30°C and a relative humidity of 80%, or when fresh air is inducted into the wall, then additional insulation is required (minimum 10 mm thickness, polyethylene foam).
Wall strength. Check whether the wall or the floor is strong enough to support the weight of the unit. If there is a risk, reinforce the wall or the floor before installing the unit.
Spacing. Install the unit at least 1.8 m from the floor and keep the following requirements in mind for distances from the walls and the ceiling:

30

50

50

(mm)

5.2 Mounting the indoor unit

5.2.1 To install the mounting plate

1 Install the mounting plate temporarily.

2 Level the mounting plate.

3 Mark the centres of the drilling points on the wall using a tape measure. Position the end of tape measure at symbol ” “.

4 Finish the installation by securing the mounting plate on the wall using M4×25L screws (field supply).

Class 30

Class 40

INFORMATION
The removed pipe port cover can be kept in the mounting plate pocket.

Installation manual
4

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

5 Unit installation

A

211

237

a

bc

a

c

a

120

120

295 44.5

44.5 52

d e
53

3
PIPING HOLE CENTER: 160mm TO THE LEFT

UNIT CENTER

a 160

f1 a 336

h

g

63

i

239

778

PIPING HOLE CENTER: 170mm TO THE RIGHT

a f2

a

170

336

d e
53 (mm)

B

a

b

c

a

c

a

120.5

130

299 52

UNIT CENTER

d

PIPING HOLE CENTER:170mm TO THE LEFT

PIPING HOLE CENTER:170 mm TO THE RIGHT

d

e

h

g

i

A

e

a

f1

70

53

170

197

446

998

f2 434

a 170

65 (mm)

A For class 30 B For class 40 a Recommended mounting plate fixing spots b Pocket for the pipe port cover c Tabs for placing a spirit level d Through- the-wall hole:
Class 30: Ø65 mm
Class 40: Ø80 mm

e Drain hose position f1 Measure point for piping hole center ” ” (to left) f2 Measure point for piping hole center ” ” (to right) g Gas pipe end h Liquid pipe end
i Center of the unit

5.2.2 To drill a wall hole

ab

CAUTION

For walls containing a metal frame or a metal board, use a

wall embedded pipe and wall cover in the feed-through

hole to prevent possible heat, electrical shock, or fire.

c

Ø65/80

NOTICE
Be sure to seal the gaps around the pipes with sealing material (field supply), in order to prevent water leakage.
1 Bore a 65 mm (for class 30) or 80 mm (for class 40) large feedthrough hole in the wall with a downward slope towards the outside.
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.

a Wall embedded pipe b Putty c Wall hole cover 4 After completing wiring, refrigerant piping and drain piping, do NOT forget to seal the gap with putty.
5.2.3 To remove the pipe port cover
INFORMATION To connect the piping on right-side, right-bottom, left-side or left-bottom, the pipe port cover MUST be removed.
1 Cut off the pipe port cover from inside the front grille using a coping saw.

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Installation manual
5

6 Piping installation
2 Remove any burrs along the cut section using a half round needle file.

NOTICE
Do NOT apply lubricating oil (refrigerant oil) to the drain plug when inserting it. The drain plug may deteriorate and cause drain leakage from the plug.
3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw; otherwise water leakage may occur.

NOTICE Do NOT use nippers to remove the pipe port cover, as this would damage the front grille.
5.3 Connecting the drain piping
5.3.1 To connect the piping on right side, rightback, or right-bottom
INFORMATION The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.
1 Attach the drain hose with adhesive vinyl tape to the bottom of the refrigerant pipes.
2 Wrap the drain hose and the refrigerant pipes together using insulation tape.

a

a

b

b

a Insulation fixing screw b Drain hose
4 Attach the drain hose to the refrigerant piping bottom side using adhesive vinyl tape.

a A

b

B

C

A Left-side piping B Left-back piping C Left-bottom piping a Remove the pipe port cover here for left-side piping b Remove the pipe port cover here for left-bottom piping

5.3.3 To check for water leaks
1 Remove the air filters. 2 Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

A
C abB
A Right-side piping B Right-bottom piping C Right-back piping a Remove the pipe port cover here for right side piping b Remove the pipe port cover here for right-bottom piping
5.3.2 To connect the piping on left side, leftback, or left-bottom
INFORMATION
The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.
1 Remove the insulation fixing screw on the right side and remove the drain hose.
2 Remove the drain plug on the left side and attach it to the right side.

6 Piping installation
6.1 Preparing refrigerant piping
6.1.1 Refrigerant piping requirements
CAUTION Piping and joints of a split system shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units.
NOTICE The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.

Installation manual
6

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Foreign materials inside pipes (including oils for fabrication) must be 30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Liquid piping Ø6.4 mm

Gas piping Ø9.5 mm

Refrigerant piping material

Piping material: Phosphoric acid deoxidised seamless copper.

Flare connections: Only use annealed material.

Piping temper grade and thickness:
Outer diameter Temper grade Thickness (t)(a) (Ø)
6.4 mm (1/4″) Annealed (O) 0.8 mm 9.5 mm (3/8″) Annealed (O)

Ø t

(a) Depending on the applicable legislation and the maximum working pressure of the unit (see “PS High” on the unit name plate), larger piping thickness might be required.

6.1.2 Refrigerant piping insulation

Use polyethylene foam as insulation material:

with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and 0.045 kcal/mh°C)

with a heat resistance of at least 120°C

Insulation thickness

Pipe outer diameter Insulation inner

(Øp)

diameter (Øi)

6.4 mm (1/4″)

8~10 mm

Insulation thickness (t)
10 mm

9.5 mm (3/8″)

10~14 mm

13 mm

Øi Øp
t

If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.
6.2 Connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
6.2.1 To connect the refrigerant piping to the indoor unit
WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable. Pipe length. Keep refrigerant piping as short as possible. 1 Connect refrigerant piping to the unit using flare connections. 2 Insulate the refrigerant piping, interconnection cable and drain hose on the indoor unit as follows:

7 Electrical installation
c

d

a

e

b

f

g

a Gas pipe b Gas pipe insulation c Interconnection cable d Liquid pipe e Liquid pipe insulation f Finishing tape g Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation.

7 Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING ALWAYS use multicore cable for power supply cables.
WARNING Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING Do NOT use locally purchased electrical parts inside the product. Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.
WARNING Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.

7.1 Specifications of standard wiring components

Component
Interconnection cable (indooroutdoor)

4-core cable 1.5 mm²~2.5 mm² and applicable for
220~240 V
H05RN-F (60245 IEC 57)

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Installation manual
7

8 Finishing the indoor unit installation
7.2 To connect the electrical wiring to the indoor unit
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice.
1 Set the indoor unit on the mounting plate hooks. Use the ” ” marks as a guide.

10 Shape the wires so that the service cover fits securely, then close the service cover.

a

b

d

c

a Mounting plate (accessory) b Piece of packing material c Interconnection cable d Wire guide
INFORMATION
Support the unit using a piece of packing material.

2 Open the front panel, and then the service cover. Refer to the Installer reference guide for opening procedure.
3 Pass the interconnection cable from the outdoor unit through the feed- through wall hole, through the back of the indoor unit and through the front side.
Note: In case the interconnection cable was stripped in advance, cover the ends with insulating tape.
4 Bend the end of the cable up.
NOTICE
Be sure to keep the power line and transmission line apart from each other. Transmission wiring and power supply wiring may cross, but may NOT run parallel.
In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.

8 Finishing the indoor unit installation
8.1 To insulate the drain piping, refrigerant piping and interconnection cable
1 After the drain piping, refrigerant piping and the electrical wiring are finished. Wrap refrigerant pipes, interconnection cable and drain hose together using insulation tape. Overlap at least half the width of the tape with each turn.
ab c
d

f

e

a Drain hose b Interconnection cable c Mounting plate (accessory) d Refrigerant piping e Indoor unit fixing screw M4×12L (accessory) f Bottom frame

8.2 To pass the pipes through the wall hole
1 Shape the refrigerant pipes along the pipe path marking on the mounting plate.

a b
c
a Terminal block b Electrical component block c Cable clamp 5 Strip the wire ends approximately 15 mm. 6 Match wire colours with terminal numbers on the indoor unit terminal blocks and firmly screw the wires to the corresponding terminals. 7 Connect the earth wire to the corresponding terminal. 8 Firmly fix the wires with the terminal screws. 9 Pull the wires to make sure that they are securely attached, then retain the wires with the wire retainer.

a b

c

cd

e

a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate (accessory)
NOTICE
Do NOT bend refrigerant pipes.
Do NOT push the refrigerant pipes onto the bottom frame or the front grille.

Installation manual
8

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

9 Configuration

NOTICE Be careful NOT to damage any of the surrounding parts when cutting the address jumper.
3 Turn the power supply on.

4 Press and

simultaneously.

5 Press , select and press

.

Result: The operation lamp will start to blink.

2 Pass the drain hose and refrigerant pipes through the wall hole.
8.3 To fix the unit on the mounting plate
1 Set the indoor unit on the mounting plate hooks. Use the ” ” marks as a guide.
2 Press the bottom frame of the unit with both hands to set it on the bottom hooks of the mounting plate. Make sure that the wires do NOT get squeezed anywhere.
Note: Take care that the interconnection cable does NOT get caught in the indoor unit.
3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks.
4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4×12L (accessory).
9 Configuration
9.1 To set a different address
In case 2 indoor units are installed in 1 room, different addresses for 2 user interfaces can be set.
1 Remove the cover and the batteries from the user interface. 2 Cut the address jumper J4.
a

a

ON/ OFF

b

a Operation lamp b Indoor unit ON/OFF switch

6 Press the indoor unit ON/OFF switch while the operation lamp is blinking.

Address jumper Factory setting

Address 1

After cutting with nippers 2

INFORMATION
If the setting could NOT be completed while the operation lamp was blinking, repeat the setting process from the beginning.

7 When the setting is complete, keep 5 seconds.

pressed for at least

Result: The user interface will return to the previous screen.

10 Commissioning
NOTICE General commissioning checklist. Next to the commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required).
The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during the commissioning and hand-over to the user.
NOTICE ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result.
10.1 Checklist before commissioning
After the installation of the unit, first check the items listed below. Once all checks are fulfilled, the unit must be closed. Power-up the unit after it is closed.
You read the complete installation instructions, as described in the installer reference guide. The indoor units are properly mounted.
The outdoor unit is properly mounted.

a Address jumper J4
FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Installation manual
9

11 Disposal
Air inlet/outlet Check that the air inlet and outlet of the unit is NOT obstructed by paper sheets, cardboard, or any other material. There are NO missing phases or reversed phases.
The refrigerant pipes (gas and liquid) are thermally insulated. Drainage Make sure drainage flows smoothly. Possible consequence: Condensate water might drip. The system is properly earthed and the earth terminals are tightened. The fuses or locally installed protection devices are installed according to this document, and have NOT been bypassed. The power supply voltage matches the voltage on the identification label of the unit. The specified wires are used for the interconnection cable. The indoor unit receives the signals of the user interface.
There are NO loose connections or damaged electrical components in the switch box. The insulation resistance of the compressor is OK.
There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units. There are NO refrigerant leaks.
The correct pipe size is installed and the pipes are properly insulated. The stop valves (gas and liquid) on the outdoor unit are fully open.

10.2 To perform a test run
Prerequisite: Power supply MUST be in the specified range. Prerequisite: Test run may be performed in cooling or heating mode.
Prerequisite: Test run should be performed in accordance with the operation manual of the indoor unit to make sure that all functions and parts are working properly.
1 In cooling mode, select the lowest programmable temperature. In heating mode, select the highest programmable temperature. Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3 minutes after the unit is turned OFF.
10.2.1 To perform a test run using the user interface
1 Press to switch the system on.

2 Press and

simultaneously.

3 Press , select and press

.

Result: Test run operation will stop automatically after about 30 minutes.

4 To stop operation sooner, press .

11 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.

12 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal (authentication required).

12.1 Wiring diagram
The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).

12.1.1 Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by “*” in the part code.

Symbol Meaning Circuit breaker

Symbol Meaning Protective earth

Connection , Connector
Earth Field wiring

Protective earth (screw)

A

Rectifier

Relay connector

Short-circuit connector

INDOOR OUTDOOR

Fuse Indoor unit
Outdoor unit
Residual current device

Terminal Terminal strip
Wire clamp

Symbol BLK BLU BRN GRN GRY

Colour Black Blue Brown Green Grey

Symbol ORG PNK PRP, PPL RED WHT YLW

Colour Orange Pink Purple Red White Yellow

Symbol AP BS
BZ, HO C

Meaning Printed circuit board Pushbutton ON/OFF, operation switch Buzzer Capacitor

Installation manual
10

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Symbol

Meaning

AC, CN, E, HA, HE, HL, Connection, connector HN, HR, MR_A, MRB, S, U, V, W, XA, K*R*, NE

D, VD

Diode

DB*

Diode bridge

DS*

DIP switch

E*H

Heater

FU, FU, (for characteristics, refer to PCB inside your unit)

Fuse

FG*

Connector (frame ground)

H*

Harness

HP, LED, V*L

Pilot lamp, light emitting diode

HAP

Light emitting diode (service monitor green)

HIGH VOLTAGE

High voltage

IES

Intelligent eye sensor

IPM*

Intelligent power module

KR, KCR, KFR, KHuR, KM

Magnetic relay

L

Live

L*

Coil

L*R

Reactor

M*

Stepper motor

M*C

Compressor motor

M*F

Fan motor

M*P

Drain pump motor

M*S

Swing motor

MR, MRCW, MRM, MRN

Magnetic relay

N

Neutral

n=, N=

Number of passes through ferrite core

PAM

Pulse-amplitude modulation

PCB*

Printed circuit board

PM*

Power module

PS

Switching power supply

PTC*

PTC thermistor

Q*

Insulated gate bipolar transistor

(IGBT)

Q*C

Circuit breaker

Q*DI, KLM

Earth leak circuit breaker

Q*L

Overload protector

Q*M

Thermo switch

Q*R

Residual current device

R*

Resistor

R*T

Thermistor

RC

Receiver

S*C

Limit switch

S*L

Float switch

S*NG

Refrigerant leak detector

S*NPH

Pressure sensor (high)

S*NPL

Pressure sensor (low)

SPH, HPS

Pressure switch (high)

S*PL

Pressure switch (low)

S*T

Thermostat

S*RH

Humidity sensor

SW, SW

Operation switch

SA*, F1S

Surge arrester

FTXTM30+40R2V1B Daikin room air conditioner 3P482320-13U ­ 2021.03

Symbol SR, WLU SS SHEET METAL TR TC, TRC V, RV VR
WRC X XM YE YR, YS ZC ZF, Z*F

12 Technical data
Meaning Signal receiver Selector switch Terminal strip fixed plate Transformer Transmitter Varistor Diode bridge, Insulated-gate bipolar transistor (IGBT) power module Wireless remote controller Terminal Terminal strip (block) Electronic expansion valve coil Reversing solenoid valve coil Ferrite core Noise filter
Installation manual
11

Verantwortung für Energie und Umwelt

3P482320-13U 2021.03

Copyright 2021 Daikin

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals