DAIKIN 7.5 ton AC Standard Efficiency Light Commercial Condenser Units DX DZ Instructions

June 1, 2024
Daikin

DAIKIN 7.5 ton AC Standard Efficiency Light Commercial Condenser Units DX DZ

DAIKIN 7.5 ton AC Standard Efficiency Light Commercial Condenser Units DX
DZ

Standard Efficiency Light Commercial Condenser Units DX/DZ

MECHANICAL GUIDE SPECIFICATIONS FOR DX/DZ SERIES COMMERCIAL CONDENSER UNITS 7.5 AND 10 TON AC, AND HEAT PUMP.

RELATED SECTIONS (As Specified by the Construction Specification Institute)

  • Section 23 06 80 Schedules for Decentralized HVAC Equipment
    o 23 06 80.13 Decentralized Unitary HVAC Equipment Schedule:
    o Schedule is per the project specification requirements.

  • Section 23 07 16 HVAC equipment insulation
    o 23 07 16.13.A. Evaporator fan compartment

  • Section 23 09 13 Instrumentation and control devices for HVAC
    o 23 09 13.23 Sensors and Transmitters
    o 23 09 13.23.A. Thermostats

  • Section 23 09 33 Electric and Electronic Control System for HVAC
    o 23 09 33.13.A. General
    o 23 09 33.13.B. Safeties

  • Section 23 09 93 Sequence of Operations for HVAC Control
    o 23 09 93.13.A. INSERT SEQUENCE OF OPERATION

  • Section 23 40 13 Panel Air Filters
    o o 23 40 13.13.A. Standard filter section

  • Section 23 81 26 Large-Capacity Split-System Air-Conditioners

GENERAL

  • All units are charged with R-410A refrigerant and run-tested at the factory to check modes of operation and proper fan rotation.
  • Unit meets ASHRAE 90.1 minimum efficiency requirements.
  • Unit shall be designed to conform to ASHRAE 15.
  • All units are rated in accordance with AHRI Standards 340/360.
  • Units are ETL listed and certified under US and Canadian standards of safety requirements per UL 60335-2-40 4th Edition.
  • Units shall be designed in accordance with ISO 9001 and shall be manufactured in a facility registered by ISO 9001:2015.
  • Units shall be subjected to a completely automated run test on the assembly line. The data for each unit will be stored at the factory and must be available upon request.
  • Units shall be designed to prevent water intrusion into the control box.
  • Units are shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability.

VOLTAGES

  • All units are available in 208/240V 3-phase 60 Hz and 460V 3-phase 60 Hz.
  • Main power supply voltage, phase, and frequency must match those required by the manufacturer.

WARRANTY

• Units feature 5-year parts and compressor warranty.
• Complete warranty details are available from your local dealer/contractor or at www.daikinac.com.

CABINET

Unit cabinets are made with galvanized steel as follows, top panel 0.048” thick~19-gauge, access doors 0.034” ~21-gauge with a powder-paint finish on all the external surfaces. Service panels provide access to refrigeration and controls sections.

DX/DZ Mech Guide

www.DaikinAC.com

  • Cabinet finish panel is tested for 500 hours in a salt spray test in accordance with ASTM B117 standard for salt spray resistance.

ACCESS PANEL

  • All Cabinet panels are designed to be easily removable for servicing the Unit.

CONTROLS

  • Units are factory-wired with color-coded wires with low-voltage control circuit protected
    by a resettable circuit breaker on the 24-v transformer side. Transformer shall have 75VA capability.

  • Units have single-point power connections.

  • Unit to be provided with a terminal block for connection and control wiring.

  • Units come with a grounding lug as standard.

  • Units come standard with 5kA SCCR rating.

COMPRESSORS

  • Compressors are hermetically sealed scroll compressors and are factory mounted on rubber isolation grommets.
  • Compressors shall be internally protected from high discharge pressure by an internal pressure relief valve and externally protected via a high pressure switch in the discharge line.

COILS

  • Models utilize 7mm copper tube and aluminum fin condenser coils.
  • Coils are leak-tested to 575 psig and pressure-tested to 450 psig.
  • Heat Pump units have a TXV metering device.
  • Condenser coils are qualified to UL 60335-2-40 burst test. Units include high- and low-pressure switches, service ports, and factory-installed filter driers. All heat pump (DZ) units use a refrigerant accumulator.

HEAT PUMP HEATING

  • Condenser coil, compressors and refrigerant circuit are designed for heat pump operation.
    The refrigerant circuit contains a 4-way reversing valve to provide heat operation. Electric heating option is provided for auxiliary heating.

FANS

  • Fan motors are single phase, ECM direct-drive, multi-speed motors. All motors are thermally protected and use permanently lubricated bearings.
  • Outdoor condenser fans are direct-drive, permanently lubricated bearings, and contain overload protection.

COOLING/HEATING OPERATION RANGE OF OUTDOOR AMBIENT TEMPERATURE

  • The Cooling/Heating operating range is between 55°F (0°F with Low Ambient Kit) and 115°F outdoor ambient temperature.

STORAGE AND HANDLING

  • Unit to be stored and handled per manufacturer’s recommendations.
  • Unit to be stored in the upright position.

FIELD-INSTALLED OPTIONS

  • Anchor Bracket Kit
  • Low Ambient Kit
  • Outdoor Thermostat with Lockout Stat (Required for DZ heat pump applications where ambient temperatures fall below 0°F with 50% or higher relative humidity)

DX/DZ Mech Guide